manual medidor de energia ma400

Upload: jpineda55

Post on 30-Oct-2015

125 views

Category:

Documents


4 download

TRANSCRIPT

  • INTERFACE

    UM EN EEM-MA400Order No.:

    User manual

  • Designation:

    Revision:

    Order No.:

    This user manual is valid for:

    2011-06-08

    INTERFACE

    104414_en_00 PHOENIX CONTACT

    Energy meter for single, two, and three-phase networks

    UM EN EEM-MA400

    00

    Designation Revision Order No.EEM-MA400 2901364

    User manual

  • EEM-MA400

    PHOENIX CONTACT

    Please observe the following notesIn order to ensure the safe use of the product described, you have to read and understand this manual. The following notes provide information on how to use this user manual.

    User group of this manualThe use of products described in this manual is oriented exclusively to Phoenix Contact accepts no liability for erroneous handling or damage to products from Phoenix Contact or third-party products resulting from disregard of information contained in this user manual.

    Explanation of symbols used and signal words This is the safety alert symbol. It is used to alert you to potential personal injury 104414_en_00

    The following types of messages provide information about possible property damage and general information concerning proper operation and ease-of-use.

    hazards. Obey all safety measures that follow this symbol to avoid possible injury or death.

    DANGERThis indicates a hazardous situation which, if not avoided, will result in death or serious injury.

    WARNINGThis indicates a hazardous situation which, if not avoided, could result in death or serious injury.

    CAUTIONThis indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

    NOTEThis symbol and the accompanying text alert the reader to a situation which may cause damage or malfunction to the device, hardware or software, or surrounding property.

    This symbol and the accompanying text provide the reader with additional information, such as tips and advice on the efficient use of hardware and on software optimization. It is also used as a reference to other sources of information (user manuals, data sheets).

  • 104414_en_00

    General terms and conditions of use for technical documentationPhoenix Contact reserves the right to alter, correct, and/or improve the technical documentation and the products described in the technical documentation at its own discretion and without giving prior notice, insofar as this is reasonable for the user. The same applies to any technical changes that serve the purpose of technical progress.The receipt of technical documentation (in particular data sheets, installation instructions, user manuals, etc.) does not constitute any further duty on the part of Phoenix Contact to furnish information on alterations to products and/or technical documentation. Any other agreement shall only apply if expressly confirmed in writing by Phoenix Contact. Please note that the supplied documentation is product-specific documentation only and that you are responsible for checking the suitability and intended use of the products in your specific application, in particular with regard to observing the applicable standards and regulations. Although Phoenix Contact makes every effort to ensure that the information and content are accurate, up-to-date, and state-of-the-art, technical inaccuracies and/or printing errors in the information cannot be ruled out. Phoenix Contact does not offer any guarantees as to the reliability, accuracy, or completeness of the information. All information made available PHOENIX CONTACT

    in the technical data is supplied without any accompanying guarantee, whether expressly mentioned, implied or tacitly assumed. This information does not include any guarantees regarding quality, does not describe any fair marketable quality, and does not make any claims as to quality guarantees or guarantees regarding the suitability for a special purpose.Phoenix Contact accepts no liability or responsibility for errors or omissions in the content of the technical documentation (in particular data sheets, installation instructions, user manuals, etc.).The aforementioned limitations of liability and exemptions from liability do not apply, in so far as liability must be assumed, e.g., according to product liability law, in cases of premeditation, gross negligence, on account of loss of life, physical injury or damage to health or on account of the violation of important contractual obligations. Claims for damages for the violation of important contractual obligations are, however, limited to contract-typical, predictable damages, provided there is no premeditation or gross negligence, or that liability is assumed on account of loss of life, physical injury, or damage to health. This ruling does not imply a change in the burden of proof to the detriment of the user.

  • EEM-MA400

    PHOENIX CONTACT

    Statement of legal authorityThis manual, including all illustrations contained herein, is copyright protected. Use of this manual by any third party is forbidden. Reproduction, translation, and public disclosure, as well as electronic and photographic archiving and modification, require written consent by Phoenix Contact. Violators are liable for damages.Phoenix Contact reserves all rights in the case of patent award or listing of a registered design. Third-party products are always named without reference to patent rights. The existence of such rights shall not be excluded.

    How to contact us

    Internet Up-to-date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at:www.phoenixcontact.com

    Make sure you always use the latest documentation.

    Subsidiaries

    Published by104414_en_00

    It can be downloaded at:www.phoenixcontact.net/catalog

    If there are any problems that cannot be solved using the documentation, please contact your Phoenix Contact subsidiary. Subsidiary contact information is available at www.phoenixcontact.com.

    Should you have any suggestions or recommendations for improvement of the contents and layout of our manuals, please send your comments to:[email protected]

    PHOENIX CONTACT GmbH & Co. KGFlachsmarktstrae 832825 BlombergDEUTSCHLANDTelefon +49 - (0) 52 35 - 3-00Telefax +49 - (0) 52 35 - 3-4 12 00

  • 104414_en_00

    Table of contents1 Safety notes ............................................................................................................................1-1

    2 Device description ..................................................................................................................2-12.1 Displaying measured values...............................................................................2-22.2 Characteristics....................................................................................................2-32.3 Communication module......................................................................................2-4

    3 Operating and indication elements .........................................................................................3-1

    4 Mounting and installation ........................................................................................................4-14.1 Cutout dimensions..............................................................................................4-14.2 Mounting ............................................................................................................4-24.3 Pin assignment ...................................................................................................4-3

    5 Configuration .......

    6 Operation DisplayPHOENIX CONTACT i

    4.4 Installation ..........................................................................................................4-44.4.1 External current transformers ..............................................................4-44.4.2 Three-phase network with asymmetrical load (4NBL) .........................4-44.4.3 Three-phase network with asymmetrical load (3NBL) .........................4-54.4.4 Three-phase network with symmetrical load (3BL/4BL) ......................4-74.4.5 Two-phase network (2BL) ...................................................................4-84.4.6 Single-phase network (1BL) ................................................................4-8

    4.5 Mounting the communication module.................................................................4-9

    ...................................................................................................................5-15.1 Configuration mode (PROG) COdE 100 ..........................................................5-35.2 Example: Configuring the device for a

    three-phase network with asymmetrical load......................................................5-45.3 Current transformers ..........................................................................................5-55.4 Current measuring time ......................................................................................5-65.5 Power measuring time ........................................................................................5-75.6 Reset ..................................................................................................................5-85.7 Configuring the LCD ...........................................................................................5-95.8 Operating hours counter...................................................................................5-105.9 Displaying the software version and serial number..................................................5-125.10 Exiting configuration mode ...............................................................................5-12

    ing measured values ................................................................................6-16.1 Displaying currents and the total

    harmonic distortion (THD) ..................................................................................6-26.2 Displaying voltages, frequency, and the

    total harmonic distortion (THD)...........................................................................6-56.3 Displaying the power and power factors .............................................................6-8

  • EEM-MA400

    ii PHOENIX CONTACT

    6.4 Displaying the energy .......................................................................................6-11

    7 Function test ...........................................................................................................................7-17.1 Calling the function test ......................................................................................7-2

    7.1.1 Automatic correction of current connections .......................................7-37.2 Repeat function test (started manually) ..............................................................7-4

    8 Troubleshooting ......................................................................................................................8-1

    9 Communication module ..........................................................................................................9-19.1 MODBUS basics ................................................................................................9-19.2 Connecting and installing the

    EEM-RS485-MA400 communication module .....................................................9-2

    10 MODBUS register t

    11 Technical data .....

    A Abbreviations........104414_en_00

    9.3 Configuring the EEM-RS485-MA400 communication module ............................9-39.3.1 Setting the MODBUS address ............................................................9-49.3.2 Setting the transmission speed ...........................................................9-59.3.3 Setting the parity .................................................................................9-69.3.4 Setting the stop bits ............................................................................9-6

    9.4 MODBUS/JBUS register tables ..........................................................................9-79.5 Reading/writing MODBUS RTU registers ...........................................................9-7

    9.5.1 Settings ...............................................................................................9-89.5.2 Access to MODBUS registers .............................................................9-9

    ables .......................................................................................................10-1

    .................................................................................................................11-1

    .................................................................................................................. A-1

  • Safety notes

    104414_en_00 PHOENIX CONTACT 1-1

    1 Safety notes

    DANGER: Risk of electric shocks, burns or explosions The "attention symbol" on the device label means:

    Read the installation note in its entirety. Follow the installation note to avoid impairing the intended protection.

    Only qualified specialist personnel may install, start up, and operate the device. Observe the national safety and accident prevention regulations.

    When working on the device, always disconnect it from the power supply. Short circuit the secondary side of each current transformer.

    Use an appropriate voltage measuring device to ensure that no voltage is present. Mount all equipment, doors, and covers before switching on the device again. Installation should be carried out following the instructions provided in the operating

    instructions. Access to circuits within the device is not permitted. The device does not require maintenance. Repairs may only be carried out by the

    manufacturer.Non-compliance with these safety precautions can result in serious injury.

    NOTE: Risk of damage to the device Provide a switch/circuit breaker close to a device, which is labeled as the

    disconnecting device for this device. Provide overcurrent protection (I 16 A) in the installation. Observe the maximum permissible values for the device supply (400 V AC/

    350 V DC), mains frequency (50/60 Hz), maximum voltage at connection terminal blocks (500 V AC phase/phase or 289 V AC phase/neutral conductor).

  • EEM-MA400

    2-1 PHOENIX CONTACT

    2 Device descriptionThe EEM-MA400 is a highly accurate energy meter for measuring electrical parameters in low-voltage systems up to 500 V. It is designed for front-panel installation and supports the measurement, counting, and display of all electrical parameters in single, two, and three-phase networks with and without neutral conductor (symmetrical and asymmetrical).The buttons located on the front of the device allow fast, direct access to the required parameters as well as device configuration. The device can be extended with a communication module.

    The following parameters can be measured or monitored:

    Current Actual values I1, I2, I3, IN Maximum values I1, I2, I3, IN Total harmonic distortion of currents (THD I1, THD I2, THD I3)

    Voltages/frequency

    Real, reactive, and apparent power

    Power factor

    Energy (power meter)104414_en_00

    Actual phase/phase value (U12, U23, U31) Actual phase/N value (V1, V2, V3) Frequency (F) Total harmonic distortion of phase/phase conductor voltages (THD U12, THD U23,

    THD U31) Total harmonic distortion of phase/N conductor voltages (THD V1, THD V2, THD V3)

    Actual value for each phase (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3) Sum of actual values (P, Q, S) Maximum values (P, Q, S)

    Actual value for each phase (PF1, PF2, PF3) Total actual value (PF)

    Positive real energy (EA+) Positive reactive energy (ER+)

  • Device description

    104414_en_00

    2.1 Displaying measured values

    I button Currents (I1, I2, I3., IN) Maximum current value (I1, I2, I3) Total harmonic distortion of currents (THD I1, THD I2, THD I3)

    U/F button Conductor voltages (U12, U23, U31) Conductor voltages to N (V1, V2, V3) Frequency (F) Total harmonic distortion of phase/phase conductor voltages (THD U12, THD U23,

    THD U31) Total harmonic distortion of phase/N conductor voltages (THD V1, THD V2, THD V3)

    P/PF button

    E button

    To switch over to the next measured values within a menu, the corresponding button must be pressed once again.PHOENIX CONTACT 2-2

    Total real power (P), total reactive power (Q), total apparent power (S) Real power per phase (P1, P2, P3), reactive power per phase (Q1, Q2, Q3), apparent

    power per phase (S1, S2, S3) Maximum value of real power (P), reactive power (Q), apparent power (S) Total power factor (PF) Power factor per phase (PF1, PF2, PF3)

    Positive real energy (EA+) Positive reactive energy (ER+) Operating hours

  • EEM-MA400

    2-3 PHOENIX CONTACT

    2.2 CharacteristicsCurrent measurement (TRMS)

    Primary current transformer 9999 ASecondary current transformer 5 AMinimum measured current 5 mADisplay 0 ... 9999 A Intrinsic consumption < 0.6 VAMeasured value update 1 sAccuracy 0.2% (10 ... 110% IN)Continuous overload 6 AShort-term overload 10 x IN for 1 s

    Voltage measurement (TRMS)

    Direct phase/phase 50 ... 500 V ACDirect phase/N 28 ... 289 V ACMeasured value update 1 s

    Power measurement

    Power factor measurement

    Frequency measurement

    Measurement of energy amount104414_en_00

    Accuracy 0.2% (50 ... 600 V AC)

    Display 0 ... 9999 kW/kvar/kVAMeasured value update 1 sAccuracy 0.5% (-90 ... +90)

    Measured value update 1 sAccuracy 0.5% (0.5 < PF < 1)

    Measuring range 45 ... 65 HzMeasured value update 1 sAccuracy 0.1% (45 ... 65 Hz)

    Real energy (IEC 62053-22) Class 0.5 SReactive energy (IEC 62053-23) Class 2

  • Device description

    104414_en_00

    2.3 Communication moduleThe device can be extended with the following communication module: JBUS/MODBUS communication (EEM-RS 485-MA400, Order No. 2901365):

    Serial RS-485 JBUS/MODBUS connection in RTU mode with a speed of up to 38,400 baud

    The communication module is plugged into the back of the device and also secured in place with screws. For a description of the maximum number of communication modules and the slots to be used, please refer to "Mounting the communication module" on page 4-9.For information about the configuration of the communication module, please refer to "Communication module" on page 9-1.PHOENIX CONTACT 2-4

  • EEM-MA400

    3-1 PHOENIX CONTACT 104414_en_00

    3 Operating and indication elements

    Figure 3-1 Operating and indication elements

    1. Pushbuttons with dual functionality: Normal mode: Display measured valuesProgramming mode: Change configuration

    2. Backlit LCD3. Display measured values in relevant conductor4. Measured value5. Unit6. Display for recording the real energy (flashes for every kWh)7. Display active communication (if optional communication module is installed)

    1

    2

    3

    4

    5

    67

  • Mounting and installation

    104414_en_00

    4 Mounting and installation

    4.1 Cutout dimensions

    Avoid being in close proximity to systems that can generate electromagnetic interference.In addition, avoid mechanical vibrations with acceleration rates greater than 1g (9.81 m/s2) at frequencies below 60 Hz.

    92+ 0,8-

    0,0PHOENIX CONTACT 4-1

    Figure 4-1 Cutout dimensions

    92+ 0,8-

    0,0

    96

    96 EMpro

    U

    6080

    45

  • EEM-MA400

    4-2 PHOENIX CONTACT

    4.2 Mounting104414_en_00

    Figure 4-2 Mounting

    To ensure that the device is securely placed on the front panel, the device must be pressed into the mounting slot from the front and then secured from behind using the four clamps provided.

    To mount the device, proceed as follows:1. Press the device into the mounting slot from the front and hold it in this position.2. Secure the device from behind with the four clamps, as shown in Figure 4-2.3. Push the clamps as far as they will go onto the latch, until the device is securely

    positioned and the clamps snap into place.

  • Mounting and installation

    104414_en_00

    4.3 Pin assignment

    s2 s1 s2 s1 s2s1

    I2 I3I1

    V1 V2 V3 VN AUXPHOENIX CONTACT 4-3

    Figure 4-3 Pin assignment

    1 Supply voltage range (AUX): 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CCI1, I2, I3 Connection of measured currents:

    S1 (input)S2 (output)

    V1, V2, V3, VN Connection of measured voltage

    Maximum tightening torque for the relevant screws: 0.4 Nm.

    DANGER: Risk of electric shockIf the device is disconnected, the secondary sides of the relevant current transformers must be short circuited. A URTK6 transformer disconnect terminal block (Order No. 3026272) can be used for this.

    1

    2

  • EEM-MA400

    4-4 PHOENIX CONTACT

    4.4 InstallationThe device is designed for connection to various network types in two, three or four-wire networks with even or uneven load.

    4.4.1 External current transformersWhen selecting the current transformer, the secondary nominal current must be 5 A. The primary nominal current is determined by the current consumption of the load. Appropriate PACT current transformers can be found in the Phoenix Contact INTERFACE catalog.

    When measuring by means of current transformers, the accuracy is greatly influenced by the quality of the transformers used.Operation using voltage transducers is not supported.104414_en_00

    4.4.2 Three-phase network with asymmetrical load (4NBL)

    Figure 4-4 Three-phase network with asymmetrical load (4NBL)

    DANGER: Risk of electric shockOnly install current transformers and corresponding measuring devices when the power supply is disconnected.Observe the order in which the current transformers are connected when wiring them (direction of current flow). Primary circuit: K-P1 L-P2; secondary circuit: k-S1 I-S2When the current transformer is operated with an open secondary circuit, hazardous voltages may occur at the secondary terminal blocks.Do not ground the secondary side of a current transformer in an IT network.

    1 Supply voltage range: 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CC

  • Mounting and installation

    104414_en_00

    4.4.3 Three-phase network with asymmetrical load (3NBL)PHOENIX CONTACT 4-5

    Figure 4-5 Measurement via 3 current transformers

    Figure 4-6 Measurement via 2 current transformers

    1 Supply voltage range: 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CC

  • EEM-MA400

    4-6 PHOENIX CONTACT 104414_en_00

    Figure 4-7 Measurement via 2 current transformers

    1 Supply voltage range: 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CC

    The solution with two current transformers reduces the degree of accuracy of phases by 0.5%, whereby their current is calculated vectorially (without current transformer).

  • Mounting and installation

    104414_en_00

    4.4.4 Three-phase network with symmetrical load (3BL/4BL)PHOENIX CONTACT 4-7

    Figure 4-8 Three-phase network with symmetrical load (3BL/4BL)

    1 Supply voltage range: 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CC

    The solution with one current transformer reduces the accuracy of phases by 0.5%, whereby their current is calculated vectorially (without current transformer).

  • EEM-MA400

    4-8 PHOENIX CONTACT

    4.4.5 Two-phase network (2BL)104414_en_00

    Figure 4-9 Two-phase network (2BL)

    4.4.6 Single-phase network (1BL)

    Figure 4-10 Single-phase network (1BL)

    1 Supply voltage range: 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CC

    1 Supply voltage range: 110 400 V AC 10% at 50/60 Hz120 350 V DC 20%

    2 Fuse: 0.5 A gG/BS 88 2A gG/0.5 A class CC

  • Mounting and installation

    104414_en_00

    4.5 Mounting the communication moduleThe communication module is plugged into the back of the device and also secured in place with screws.PHOENIX CONTACT 4-9

    Figure 4-11 Mounting the communication module

    For information about the configuration of the communication module, please refer to "Communication module" on page 9-1.

    Table 4-1 Installation overviewDesignation Order No. Max.

    numberSpace requirements

    Slot No.

    EEM-RS485-MA400 2901365 1 1 slot 1 ... 2

    12

  • EEM-MA400

    5-1 PHOENIX CONTACT

    5 ConfigurationThe device can be configured via pushbuttons. The configuration is shown in the following subsections.

    To configure the EEM-MA400, press the gray buttons consecutively, as described in the relevant example.The corresponding configuration menu is displayed for the communication module used. For the required configuration settings, please refer to "Communication module" on page 9-1.

    Button DescriptionPROG Open configuration mode (press and hold for 3 seconds)104414_en_00

    Select the next menu item Open edit mode In edit mode: Select parameters/values to be changed In edit mode: Change parameters/valuesOK Confirm setting

  • Configuration

    104414_en_00

    100Configuration mode:

    4NBL, 3NBL, 4BL, 3BL, 2BL , 1BLMains types:

    Set primary currentCurrent transformer:

    20' min; 30' min; 60' min; 2' sec; 5' min; 8' min; 10' min; 15' minMeasuring time for currents tocalculate MAX values:

    20' min; 30' min; 60' min; 2' sec; 5' min; 8' min; 10' min; 15' minMeasuring time for real power tocalculateMAX values:

    Serial number:

    Software version:

    Reset measured valu

    Operating hours cou

    LCD display:

    see extension moPHOENIX CONTACT 5-2

    Figure 5-1 Flowchart

    Pressserial number is displayed

    until you reach menu item Ser l :

    Press until you reach menu item SOFt:software version is displayed

    es / times: I: Maximal value of the currentsP: Maximal real power valueEA: active energy (+kWh)ER: reactive power (+kVArh)HOUR: operating hours counter

    Yes; No

    AUX: activated, if supply voltage is availableI: activated, if threshold value is set (input current)U: activated, if threshold value is set (input voltage)

    nter:

    Set valueThreshold value: I / U

    AUX: illuminated, if supply voltage is availableI: illuminated, if current is being measuredU: illuminated, if voltage is being measuredfor AUX: Illumination goes out automatically after 2 minutes.The display is illuminated again after pressing any key.

    dule

  • EEM-MA400

    5-3 PHOENIX CONTACT

    5.1 Configuration mode (PROG) COdE 100

    Once the appropriate setting has been made and confirmed by pressing "OK", the next menu item is called automatically. To switch to configuration mode, press and hold down the "PROG" button for at least

    3 seconds. Follow the instructions and enter "Code 100". Confirm with "OK".

    In configuration mode, the labeling below the pushbuttons applies.

    U104414_en_00

    Figure 5-2 Switching to configuration mode

    U

    U

    U

    1 x3 seconds

    1 x

    1 x

    1 xConfirm

  • Configuration

    104414_en_00

    5.2 Example: Configuring the device for a three-phase network with asymmetrical load

    NET = 3NBL

    U

    1 xPHOENIX CONTACT 5-4

    Figure 5-3 Setting a three-phase network with asymmetrical load (3NBL)

    U

    U

    1 x 1BL2 x 2BL3 x 3BL4 x 3NBL5 x 4BL6 x 4NBL

    1 xConfirm

  • EEM-MA400

    5-5 PHOENIX CONTACT

    5.3 Current transformersEnter the ratio of the current transformers used as shown in the following example.

    Example: Transformer ratio CT = 1200/5A

    U

    1 x104414_en_00

    Figure 5-4 Setting transformer ratio CT = 1200/5A

    The current transformer output for the secondary side is always 5 A and cannot be changed.

    U

    U

    1 x

    1 x

    U

    U

    1 x

    1 xConfirm

  • Configuration

    104414_en_00

    5.4 Current measuring timeThis value specifies over which period the currents are to be measured for determining the maximum values.

    Example: Measuring time of 20 minutes tIME I = 20

    U

    1 x

    UPHOENIX CONTACT 5-6

    Figure 5-5 Setting the current measuring time

    U

    1 xConfirm

    1 x 20 min.2 x 30 min.3 x 60 min.4 x 2 sec.5 x 5 min.6 x 8 min.7 x 10 min.8 x 15 min.

  • EEM-MA400

    5-7 PHOENIX CONTACT

    5.5 Power measuring timeThis value specifies over which period the power is to be measured for determining the maximum values.

    Example: Measuring time of 20 minutes tIME P = 20

    U

    1 x104414_en_00

    Figure 5-6 Setting the power measuring time

    U

    1 xConfirm

    U

    1 x 20 min.2 x 30 min.3 x 60 min.4 x 2 sec.5 x 5 min.6 x 8 min.7 x 10 min.8 x 15 min.

  • Configuration

    104414_en_00

    5.6 ResetExample: rSET = EA

    U

    U

    1 xPHOENIX CONTACT 5-8

    Figure 5-7 Resetting with rSET = EA

    U

    U

    1 x

    1 xConfirm

    0 x MAX I, maximum current value1 x MAX P, maximum real power value2 x EA, real energy (+kWh)3 x ER, reactive energy (+kVArh)4 x HOUR, operating hours counter

    U

    1 x

  • EEM-MA400

    5-9 PHOENIX CONTACT

    5.7 Configuring the LCDThe LCD lighting can be configured in various ways.

    Configuration options The display is illuminated when: Supply voltage is present (AUX) Current is being measured (I) Voltage is being measured (U)In the case of the AUX setting (supply voltage is present), the display automatically goes out after 2 minutes. The display is illuminated again when a button is pressed.

    Example: The display is illuminated when voltage is being measuredbACLIT = U104414_en_00

    Figure 5-8 Configuring the LCD

    U

    U

    1 x

    1 xConfirm

    U

    1 x AUX, supply voltage is present2 x I, current is being measured3 x U, voltage is being measured

  • Configuration

    104414_en_00

    5.8 Operating hours counterExample: Operating hours counter depending on the current flow. The counter is

    activated if the current is greater than 1000 A.

    U

    U

    1 xPHOENIX CONTACT 5-10

    Figure 5-9 Setting a current-dependent operating hours counter - part 1

    U

    U

    U

    1 x

    1 x

    1 xConfirm

    0 x AUX, supply voltage1 x I, input current2 x U, input voltage

  • EEM-MA400

    5-11 PHOENIX CONTACT

    U

    1 xConfirm

    U

    1 x104414_en_00

    Figure 5-10 Setting a current-dependent operating hours counter - part 2

  • Configuration

    104414_en_00

    5.9 Displaying the software version and serial numberSwitch to programming mode.

    Example: SOFt = U302

    U

    1 x SOFt2 x EPHOENIX CONTACT 5-12

    Example: E = 23210280097

    Figure 5-11 Displaying the software version and serial number

    5.10 Exiting configuration modeTo exit configuration mode, press and hold down the "PROG" button for at least 3 seconds.

    Figure 5-12 Exiting configuration mode

    U

    1 x3 seconds

  • EEM-MA400

    6-1 PHOENIX CONTACT

    6 Operation Displaying measured valuesThe measured values are accessed via pushbuttons. In operational mode, the labeling above the pushbuttons applies.

    Table 6-1 Pushbutton functions in operational modePushbutton Displays...

    Currents, total harmonic distortion (THD) of currents

    U104414_en_00

    By pressing the appropriate pushbutton several times, further measured values can be displayed within the selected menu (see also "Displaying measured values" on page 2-2).

    Voltages, frequency, total harmonic distortion (THD) of voltages

    Power, power factor (PF)

    Energy

  • Operation Displaying measured values

    104414_en_00

    6.1 Displaying currents and the total harmonic distortion (THD)

    Press button:1 x

    Currents in conductors (I1, I2, I3)EMpro

    U F P PF EIPHOENIX CONTACT 6-2

    2 x Current in neutral conductor (IN)

    3 x Maximum current value (I1, I2, I3)

    EMpro

    U F P PF EI

    EMpro

    U F P PF EI

  • EEM-MA400

    6-3 PHOENIX CONTACT

    4 x Maximum neutral conductor

    current value (IN)

    5 x

    EMpro

    U F P PF EI

    EMpro104414_en_00

    Total harmonic distortion of current THD I1 (%)

    6 x Total harmonic distortion of current

    THD I2 (%)

    U F P PF EI

    EMpro

    U F P PF EI

  • Operation Displaying measured values

    104414_en_00

    7 x Total harmonic distortion of current

    THD I3 (%)

    EMpro

    U F P PF EIPHOENIX CONTACT 6-4

  • EEM-MA400

    6-5 PHOENIX CONTACT

    6.2 Displaying voltages, frequency, and the total harmonic distortion (THD)

    Press button:U 1 x

    Phase/N conductor voltages (V1, V2, V3)

    EMpro

    U F P PF EI104414_en_00

    2 x Phase/phase conductor voltages

    (U12, U23, U31)

    3 x Frequency (F)

    EMpro

    U F P PF EI

    EMpro

    U F P PF EI

  • Operation Displaying measured values

    104414_en_00

    4 x Total harmonic distortion of

    phase/phase conductor voltage THD U12 (%)

    5 x

    EMpro

    U F P PF EI

    EMproPHOENIX CONTACT 6-6

    Total harmonic distortion of phase/phase conductor voltage THD U23 (%)

    6 x Total harmonic distortion of

    phase/phase conductor voltage THD U31 (%)

    U F P PF EI

    EMpro

    U F P PF EI

  • EEM-MA400

    6-7 PHOENIX CONTACT

    7 x Total harmonic distortion of phase/N

    conductor voltage THD V1 (%)

    8 x

    EMpro

    U F P PF EI

    EMpro104414_en_00

    Total harmonic distortion of phase/N conductor voltage THD V2 (%)

    9 x Total harmonic distortion of phase/N

    conductor voltage THD V3 (%)

    U F P PF EI

    EMpro

    U F P PF EI

  • Operation Displaying measured values

    104414_en_00

    6.3 Displaying the power and power factorsPress button:

    1 x Total real power (P) Total reactive power (Q) Total apparent power (S)

    EMpro

    U F P PF EIPHOENIX CONTACT 6-8

    2 x Real power per phase (P1, P2, P3)

    3 x Reactive power per phase

    (Q1, Q2, Q3)

    EMpro

    U F P PF EI

    EMpro

    U F P PF EI

  • EEM-MA400

    6-9 PHOENIX CONTACT

    4 x Apparent power per phase (S1, S2, S3)

    5 x

    EMpro

    U F P PF EI

    EMpro104414_en_00

    Maximum real power value (P) Maximum reactive power value (Q) Maximum apparent power value (S)

    6 x Total power factor (PF) + inductive

    U F P PF EI

    EMpro

    U F P PF EI

  • Operation Displaying measured values

    104414_en_00

    7 x Power factor per phase

    (PF1, PF2, PF3) + inductive

    EMpro

    U F P PF EIPHOENIX CONTACT 6-10

  • EEM-MA400

    6-11 PHOENIX CONTACT

    6.4 Displaying the energyPress button:

    1 x Absorbed (positive) real energy (EA+)

    EMpro

    U F P PF EI104414_en_00

    2 x Absorbed (positive) reactive energy

    (ER+)

    3 x Operating hours

    EMpro

    U F P PF EI

    EMpro

    U F P PF EI

  • Function test

    104414_en_00

    7 Function test

    The following errors are displayed by the EEM-MA400:

    To perform the function test, the device must be connected and ready for operation. The power factor (PF) of the system must be between 0.6 > PF < 1. If the power factor

    is not within this range, this function cannot be used. The connections (without neutral conductors) are checked using the

    4BL/3BL/2BL/1BL setting. All connections (with neutral conductors) are checked using the 4NBL and 3NBL

    setting.

    Error DescriptionPHOENIX CONTACT 7-1

    To eliminate Err 1, Err 2, and Err 3, change the order of the current connections. To eliminate Err 4, Err 5, and Err 6, change the order of the voltage connections of the measuring transducer.

    Err 0 No errorErr 1/2/3 Current transformer connection phase 1/phase 2/phase 3Err 4 Voltage between V1/V2Err 5 Voltage between V2/V3Err 6 Voltage between V3/V1

  • EEM-MA400

    7-2 PHOENIX CONTACT

    7.1 Calling the function testPress button: The test menu is opened when the "test button" is pressed and held down for at least three

    seconds.

    The function test is started automatically if a test has not yet been performed.

    EMpro104414_en_00

    Figure 7-1 Calling the function test

    Hold down the "test button" for at least three seconds.The test starts automatically. No errors were found in the following example.

    Figure 7-2 Call function test

    Press and hold down the "test button" again for at least three seconds; the device switches to display mode again.

    Figure 7-3 Exit function test

    U

    1 x3 seconds

    U

    1 x3 seconds

    U

    1 x3 seconds

  • Function test

    104414_en_00

    7.1.1 Automatic correction of current connections

    Example: Err 1 Current transformer connection phase 1

    If the direction of current flow is mixed up due to the connection order being incorrect, the measurement signals can be corrected automatically. It is not necessary to rewire connection terminal blocks S1 (input) and S2 (output).

    Call function test

    Select correction

    Activate correction

    Confirm entry

    Exit function test, display mode

    U

    1 x3 secondsPHOENIX CONTACT 7-3

    Figure 7-4 Automatic correction of current connections

    U

    1 x3 seconds

    U

    1 x

    U

    1 x

    U

    1 x

  • EEM-MA400

    7-4 PHOENIX CONTACT

    7.2 Repeat function test (started manually)

    It is possible to perform an entirely new test, as shown below.

    This menu is only displayed if the device has already been tested.

    Call function test

    Select repeat function test

    Activate repeat function test

    Confirm your entry with "OK"

    U

    1 x3 seconds104414_en_00

    Figure 7-5 Performing a repeat function test

    U

    1 x

    U

    1 x

    U

    1 x

  • Troubleshooting

    104414_en_00

    8 TroubleshootingThis section contains a list of possible problems that may occur when working with the device. The action to be taken and the way in which the user must respond in order to solve the issue are described for each individual problem.

    Error/fault RemedyDevice not ready for operation Check the power supplyBacklighting goes out Check the configuration of the backlighting

    (see Page 5-9)Voltages = 0 Check the voltage inputCurrents = 0 or faulty Check the current input

    Check the configuration of the current transformer ratios

    Incorrect display of power, pNo display of phasesPHOENIX CONTACT 8-1

    ower factor, and energy Start the function test Check the configuration of the device (see Page 5-4)

  • EEM-MA400

    8-2 PHOENIX CONTACT 104414_en_00

  • Communication module

    104414_en_00

    9 Communication module

    9.1 MODBUS basicsThe data is transmitted using the MODBUS RTU (remote terminal unit) protocol. Communication takes place according to the master/slave access method. Communication begins when requested by the master (PLC). Each slave (EEM-MA400) has a unique address (valid range 1 ... 247). If a slave detects that its address has been addressed by the master, the slave always sends a response. The slaves never communicate with each other. They are not able to initiate communication with the master. Connected extension modules write the analog/digital input and output values to an internal register, for example.The MODBUS master (PLC) can read the individual registers using the PLC address.The data to be transmitted is always in a fixed frame and is defined as follows:

    Table 9-1 Example: ReaSlave address

    Function

    05 03 C

    Table 9-2 Example: ResSlave address

    Function

    05 03PHOENIX CONTACT 9-1

    Frame DescriptionSlave address Here, the slave address is specified (valid range 1 ... 247)Function code Here, it is established whether parameters are to be read or written.Address Register addressData - E.g., from the master: Which parameters are requested?

    - E.g., from the slave: Content of the requested parametersCRC (Cyclic Re-dundancy Check)

    The cyclic redundancy check: test value for data in order to detect errors in data transmission.

    The maximum waiting time (timeout) is 250 ms.Each bus device must have a unique address. Slave address 0 is reserved for a broadcast.

    d device parameters (initiated by the master)High address Low

    addressNo. of high words No. of low

    words CRC 16

    6 5C 00 02 3915

    ponse from a slave (initiated by slave)Number of bytes Low

    register valueHigh register value

    CRC 16

    04 0011 IDDD 2FAF

  • EEM-MA400

    9-2 PHOENIX CONTACT

    Function codes in MODBUSSeveral function codes are defined in MODBUS. They are as follows:

    Table 9-3 Example: Write device parametersSlave address

    Function High address Low address

    High register value

    Low register value

    CRC 16

    05 06 E0 00 00 05 7F8D

    Each bus device must have a unique address. Slave address 0 is reserved for a broadcast.

    Function code Name Abbrevia- Description

    03 hex Read ho06 hex16 hex

    Write sinWrite m104414_en_00

    9.2 Connecting and installing the EEM-RS485-MA400 communication module

    tionld register R Read device parametersgle register

    ultiple registersW Write individual device parameters word-by-word,

    write several device parameters word-by-word

    Other function codes exist, but they are not supported.

    For information about connecting and installing the EEM-RS485-MA400 communication module, please refer to the corresponding package slip at www.phoenixcontact.net/catalog.

  • Communication module

    104414_en_00

    9.3 Configuring the EEM-RS485-MA400 communication module

    The module can be configured using the pushbuttons on the front of the measuring device. The configuration is shown in the following subsections.

    Button DescriptionPROG Open configuration mode (press and hold for 3 seconds) Select the next menu item Open edit mode In edit mode: Select parameters/values to be changed In edit mode: Change parameters/valuesOK Confirm settingPHOENIX CONTACT 9-3

    Figure 9-1 Flowchart

    2,4 kBit/s; 4,8 kBit/s; 9,6 kBit/s;19,2 kBit/s; 38,4 kBit/s

    0 ... 254EEM-RS485-M400

    Odd; Even; nO

    1; 2Stop bits:

    Parity:

    Transmission speed:

    MODBUS address:

  • EEM-MA400

    9-4 PHOENIX CONTACT

    9.3.1 Setting the MODBUS addressSet the MODBUS address as shown in the following example.

    Example: COM ADR = 7

    U

    3 x

    U104414_en_00

    Figure 9-2 Setting the MODBUS address

    U

    1 xConfirm

    2 x

  • Communication module

    104414_en_00

    9.3.2 Setting the transmission speedSet the transmission speed as shown in the following example.

    Example: COM BDS = 19200 BDS (baud)

    All MODBUS devices must be set to the same transmission speed.

    U

    1 xPHOENIX CONTACT 9-5

    Figure 9-3 Setting the transmission speed

    U

    1 xConfirm

    U

    1 x 2.4 kbps2 x 4.8 kbps3 x 9.6 kbps4 x 19.2 kbps5 x 38.4 kbps

  • EEM-MA400

    9-6 PHOENIX CONTACT

    9.3.3 Setting the paritySet the parity as shown in the following example.

    Example: COM PAR = Even

    U

    1 x

    U104414_en_00

    Figure 9-4 Setting the parity

    9.3.4 Setting the stop bitsSet the stop bits as shown in the following example.

    Example: COM STOP = 2

    Figure 9-5 Setting the stop bits

    1 x Odd2 x Even3 x No

    U

    1 x

    U

    1 x 2 bits2 x 1 bit

    U

    1 xConfirm

  • Communication module

    104414_en_00

    9.4 MODBUS/JBUS register tablesFor the MODBUS/JBUS register tables, please refer to "MODBUS register tables" on page 10-1.

    9.5 Reading/writing MODBUS RTU registersIn the following example, some points for testing the MODBUS structure with the "Modbus Poll" simulation software are described. The simulation software is a freeware tool and can be downloaded at http://www.modbustools.com/.PHOENIX CONTACT 9-7

  • EEM-MA400

    9-8 PHOENIX CONTACT

    9.5.1 Settings1. Open the interface settings via "Connection, Connect". 104414_en_00

    2. Choose "Connection, Serial Port" as shown in the following example.

  • Communication module

    104414_en_00

    3. Set the desired serial interface parameters in the fields below. Set "Mode" to RTU. PHOENIX CONTACT 9-9

    4. Confirm the settings with "OK".

    9.5.2 Access to MODBUS registers1. Open the MODBUS register access settings as follows: "Setup, Read/Write

    Definition".2. Set the desired "Slave ID". 3. Under "Function," you can choose the register access type (read "03" or write

    "06"/"16"). 4. Under "Address", set the start address for the desired register. 5. Under "Quantity", set the register length.

  • EEM-MA400

    9-10 PHOENIX CONTACT

    Example: "Read" functionRead main measured values based on current transformer (see "C550 hex: Display current main measured values based on current transformer (taking into consideration transformation ratios)" on page 10-1):

    1. After entering the "Slave ID", choose the "03 Read Holding Registers" under "Function". 2. Enter start address 50512 under "Address". 3. Under "Quantity", enter 4 as the number of data words.

    Operating hours counter Data word/decimal address 50512/50513Conductor voltage U12 Data word/decimal address 50514/50515104414_en_00

    4. Confirm with "OK".The contents of register 50512 50515 are displayed.

    So that the contents of the register can be used again, they must be converted into the corresponding units (see "C550 hex: Display current main measured values based on current transformer (taking into consideration transformation ratios)" on page 10-1).

  • Communication module

    104414_en_00

    Content of register 50513 (operating hours counter) = 4703247032 : 100 = 470.32 hContent of register 50515 (conductor voltage U12) = 3565535655 : 100 = 356.57 V

    Example: "Write" functionConfiguration of the measurement duration for determining the average/maximum current value (see "8E00 hex: Configuration of measuring device" on page 10-9):1. After entering the "Slave ID", choose "16 Write Multiple Registers" under "Function". 2. Enter start address 36352 under "Address". 3. Under "Quantity", enter 8 as the number of data words. PHOENIX CONTACT 9-11

    4. Confirm with "OK".5. As shown below, enter the desired measurement duration in row 6 (2 s, 5 min, 8 min,

    10 min, 15 min, 20 min, 30 min, 60 min), e.g., 10 for 10 min.

  • EEM-MA400

    9-12 PHOENIX CONTACT 104414_en_00

  • MODBUS register tables

    104414_en_00

    10 MODBUS register tablesIn this section, you will find the following registers.

    Table 10-1 Register overviewStart address

    Description On page...

    C550 hex Display current main measured values based on current transformer (taking into consideration transformation ratios)

    Table 10-2 on page 10-1

    C650 hex Display energy values Table 10-3 on page 10-2

    C750 hex Display average values based on current transformer over the set measurement duration (taking into consideration transformation ratios)

    Table 10-4 on page 10-3

    C850 hex Display current main measured values not based on current transformer (without taking into considerat

    Table 10-5 on

    C950 hex Display harmo

    E000 hex Connection co

    E200 hex Save configura

    400 hex Reset measure

    8D00 hex Information ab

    8E00 hex Configuration o

    Table 10-2 C550 hex: Distransformatio

    Decimal address

    Hexa-decimal address

    50512 C55050514 C55250516 C55450518 C55650520 C55850522 C55A50524 C55C50526 C55E50528 C560PHOENIX CONTACT 10-1

    ion transformation ratios) page 10-4nic distortion and harmonics Table 10-6 on

    page 10-6nfiguration of measuring device Table 10-7 on

    page 10-6tion and restart measuring device Table 10-9 on

    page 10-7d values Table 10-11 on

    page 10-8out the connected extension module Table 10-12 on

    page 10-8f measuring device Table 10-13 on

    page 10-9

    play current main measured values based on current transformer (taking into consideration n ratios)

    Number of data words

    Designation Unit Register access

    2 Hour: Operating hours counter h/100 R2 U12: Conductor voltage (1-2) V/100 R2 U23: Conductor voltage (2-3) V/100 R2 U31: Conductor voltage (3-1) V/100 R2 V1: Conductor voltage to N V/100 R2 V2: Conductor voltage to N V/100 R2 V3: Conductor voltage to N V/100 R2 F: Frequency Hz/100 R2 I1: Current mA R

  • EEM-MA400

    10-2 PHOENIX CONTACT

    50530 C562 2 I2: Current mA R50532 C564 2 I3: Current mA R50534 C566 2 In: Neutral conductor current mA R50536 C568 2 P: Total real power +/- kW/100 R50538 C56A 2 Q: Total reactive power +/- kvar/100 R50540 C56C 2 S: Total apparent power kVA/100 R50542 C56E 2 PF: Total power factor

    -: Capacitive, +: Inductive0.001 R

    50544 C570 2 P1: Real power phase 1 +/- kW/100 R50546 C57250548 C57450550 C57650552 C57850554 C57A50556 C57C50558 C57E50560 C58050562 C582

    50564 C584

    50566 C586

    50568 C58850570 C58A50572 C58CRange: 62 words (decimal) o

    Table 10-2 C550 hex: Display current main measured values based on current transformer (taking into consideration transformation ratios) [...]

    Decimal address

    Hexa-decimal address

    Number of data words

    Designation Unit Register access

    Table 10-3 C650 hex: DisDecimal address

    Hexadeaddress

    50768 C65050770 50778 C652 ...50780 C65C104414_en_00

    2 P2: Real power phase 2 +/- kW/100 R2 P3: Real power phase 3 +/- kW/100 R2 Q1: Reactive power phase 1 +/- kvar/100 R2 Q2: Reactive power phase 2 +/- kvar/100 R2 Q3: Reactive power phase 3 +/- kvar/100 R2 S1: Apparent power phase 1 kVA/100 R2 S2: Apparent power phase 2 kVA/100 R2 S3: Apparent power phase 3 kVA/100 R2 PF1: Power factor phase 1

    -: Capacitive, +: Inductive0.001 R

    2 PF2: Power factor phase 2-: Capacitive, +: Inductive

    0.001 R

    2 PF3: Power factor phase 3-: Capacitive, +: Inductive

    0.001 R

    2 Not available - R2 Not available - R2 Not available - R

    r 3E words (hexadecimal)

    play energy values cimal Number

    of data words

    Designation Unit Register access

    2 Hour: Operating hours counter h/100 RC65A 10 Not available -

    2 EA+: Current positive real energy kWh R

  • MODBUS register tables

    104414_en_00

    50782 C65E 2 ER+: Current positive reactive energy kvarh R50784 ... 50826 C660 ... C68A 44 Not available -50828 C68C 1 Not available -50829 C68D 1 Not available -50830 C68E 1 Not available -50831 C68F 1 Not available -50832 C690 1 Not available -Range: 65 words (decimal) or 41 words (hexadecimal)

    Table 10-3 C650 hex: Display energy values [...]Decimal address

    Hexadecimal address

    Number of data words

    Designation Unit Register access

    Slave address Function

    05 03

    Slave address Function

    05 03

    Table 10-4 C750 hex: Disinto considera

    Decimal address

    Hexadeciaddress

    51024 ... 51068 C750 ... C51070 C77E51072 C78051074 C78251076 C78451078 C786PHOENIX CONTACT 10-3

    Example:In order to read the positive real energy from address C65C, the following data sequence must be sent:

    Response from the EEM-MA400: The register contents correspond to a positive real energy of 177,645 kWh.

    High address

    Low address

    No. of high words

    No. of low words

    CRC 16

    C6 5C 00 02 3915

    Number of bytes Low register value

    High register value

    CRC 16

    04 0011 IDDD 2FAF17 7645

    play average values based on current transformer over the set measurement duration (taking tion transformation ratios)

    mal Number of data words

    Designation Unit Register access

    77C 46 Not available - R2 max I1: Maximum current value mA R2 max I2: Maximum current value mA R2 max I3: Maximum current value mA R2 max In: Maximum current value mA R2 max P+: Maximum value of total positive real

    powerkW/100 R

  • EEM-MA400

    10-4 PHOENIX CONTACT

    51080 C788 2 Not available -51082 C78A 2 max Q+: Maximum value of total positive reactive

    powerkvar/100 R

    51084 C78C 2 Not available -51086 C78E 2 max S+: Maximum value of total positive apparent

    powerkVA/100 R

    51088 ... 51093 C790 ... C795 6 Not available - RRange: 70 words (decimal) or 46 words (hexadecimal)

    Table 10-4 C750 hex: Display average values based on current transformer over the set measurement duration (taking into consideration transformation ratios) [...]

    Decimal address

    Hexadecimal address

    Number of data words

    Designation Unit Register access

    Table 10-5 C850 hex: Disconsideration

    Decimal address

    Hexa-decimal address

    51280 C85051281 C85151282 C85251283 C85351284 C85451285 C85551286 C85651287 C85751288 C85851289 C85951290 C85A51291 C85B51292 C85C51293 C85D51294 C85E51295 C85F

    51296 C860104414_en_00

    When you use this table, you must multiply the values by the transformation ratios for the converters used.

    play current main measured values not based on current transformer (without taking into transformation ratios) Number of data words

    Designation Unit Register access

    1 Hour: Operating hours counter h R1 U12: Conductor voltage V/100 R1 U23: Conductor voltage V/100 R1 U31: Conductor voltage V/100 R1 V1: Conductor voltage to N V/100 R1 V2: Conductor voltage to N V/100 R1 V3: Conductor voltage to N V/100 R1 F: Frequency Hz/100 R1 I1: Current mA R1 I2: Current mA R1 I3: Current mA R1 In: Neutral conductor current mA R1 P: Total real power +/- kW/100 R1 Q: Total reactive power +/- kvar/100 R1 S: Total apparent power kVA/100 R1 PF: Total power factor

    -: Capacitive, +: Inductive0.001 R

    1 P1: Real power phase 1 +/- kW/100 R

  • MODBUS register tables

    104414_en_00

    51297 C861 1 P2: Real power phase 2 +/- kW/100 R51298 C862 1 P3: Real power phase 3 +/- kW/100 R51299 C863 1 Q1: Reactive power phase 1 +/- kvar/100 R51300 C864 1 Q2: Reactive power phase 2 +/- kvar/100 R51301 C865 1 Q3: Reactive power phase 3 +/- kvar/100 R51302 C866 1 S1: Apparent power phase 1 kVA/100 R51303 C867 1 S2: Apparent power phase 2 kVA/100 R51304 C868 1 S3: Apparent power phase 3 kVA/100 R51305 C869

    51306 C86A

    51307 C86B

    51308 C86C51309 C86D51310 C86E51311 C86F

    51312 C87051313 C871

    51314 C872Range: 35 words (decimal) o

    Table 10-5 C850 hex: Display current main measured values not based on current transformer (without taking into consideration transformation ratios) [...]

    Decimal address

    Hexa-decimal address

    Number of data words

    Designation Unit Register access

    Slave address

    Function Ha

    05 03 CPHOENIX CONTACT 10-5

    Example:In order to display all the values in Table C850 with a length of 35 words with a single request, the following data sequence must be sent:

    1 PF1: Power factor phase 1-: Capacitive, +: Inductive

    0.001 R

    1 PF2: Power factor phase 2-: Capacitive, +: Inductive

    0.001 R

    1 PF3: Power factor phase 3-: Capacitive, +: Inductive

    0.001 R

    1 Not available R1 Not available R1 Not available R1 EA+: Total positive real energy since startup

    (cannot be reset)MWh R

    1 Not available R1 EA-: Total negative real energy since startup

    (cannot be reset)MWh R

    1 Not available Rr 23 words (hexadecimal)

    igh ddress

    Low address

    No. of high words

    No. of low words

    CRC 16

    8 50 00 35 BA28

  • EEM-MA400

    10-6 PHOENIX CONTACT

    Table 10-6 C950 hex: Display harmonic distortion and harmonics Decimal address

    Hexadecimal address

    Number of data words

    Designation Unit Register access

    Total harmonic distortion THD51536 C950 1 THD U12: Total harmonic distortion of

    conductor voltage0.10% R

    51537 C951 1 THD U23: Total harmonic distortion of conductor voltage

    0.10% R

    51538 C952 1 THD U31: Total harmonic distortion of conductor voltage

    0.10% R

    51539 C953 1 THD V1: Total harmonic distortion of conductor voltage to N

    0.10% R

    51540 C954

    51541 C955

    51542 C95651543 C95751544 C95851545 C959

    Range: 10 words (decimal) o

    Table 10-7 E000 hex: CoDecimal address

    Hexa-decimal address

    57344 E000

    57345 E001

    57346 E00257347 E00357348 E00457349 E005104414_en_00

    1 THD V2: Total harmonic distortion of conductor voltage to N

    0.10% R

    1 THD V3: Total harmonic distortion of conductor voltage to N

    0.10% R

    1 THD I1: Total harmonic distortion of current 0.10% R1 THD I2: Total harmonic distortion of current 0.10% R1 THD I3: Total harmonic distortion of current 0.10% R1 THD In: Total harmonic distortion of neutral

    conductor current0.10% R

    r A words (hexadecimal)

    nnection configuration of measuring deviceNumber of data words

    Designation Unit Register access

    1 Network type: 0: 1BL 1: 2BL 2: 3BL 3: 3NBL 4: 4BL 5: 4NBL

    R/W

    1 Current transformer secondary side:5: 5 A

    A R/W

    1 Current transformer primary side A R/W1 Not available 1 Not available 1 Not available

  • MODBUS register tables

    104414_en_00

    Example:

    57350 E006 1 Not available 57351 E007 1 Not available 57352 E008 2 Not available 57354 E00A 1 Not available 57355 E00B 1 Not available Range: 12 words (decimal) or C words (hexadecimal)

    Table 10-7 E000 hex: Connection configuration of measuring device [...]Decimal address

    Hexa-decimal address

    Number of data words

    Designation Unit Register access

    Table 10-8 ConfigurationSlave address

    Function

    05 06

    Table 10-9 E200 hex: SaDecimal address

    Hexa-decimal address

    57856 E200

    Range: 1 word (decimal) or 1

    Table 10-10 After changinSlave address

    Function

    05 06PHOENIX CONTACT 10-7

    The response from the EEM-MA400 is identical to the message sent.

    Example:

    The response from the EEM-MA400 is identical to the message sent.

    of a 4-wire network with asymmetrical load (4NBL) for the EEM-MA400High address

    Low address

    No. of high words

    No. of low words

    CRC 16

    E0 00 00 05 7F8D

    ve configuration and restart measuring deviceNumber of data words

    Designation Unit Register access

    1 Action:0xA1: Save settings in EEPROM0xB2: Restart measuring device

    W

    word (hexadecimal)

    g the configuration parameters, the following command can be used to save themHigh address

    Low address

    High register value

    Low register value

    CRC 16

    E2 00 00 A1 7F8E

  • EEM-MA400

    10-8 PHOENIX CONTACT

    Table 10-11 400 hex: Reset measured valuesDecimal address

    Hexa-decimal address

    Number of data words

    Designation Unit Register access

    1024 400 1 Reset: max I1,I2,I3: Maximum current value (I1, I2, I3): 0x1P+, Q+, S: 0x2EA+: Current positive real energy kWh+: 0x80ER+: Current positive reactive energy kvarh+: 0x100All parameters: 0 x 1000

    / W

    Range: 1 word (decimal) or 1 word (hexadecimal)

    Slave address

    Function

    05 06

    Table 10-12 8D00 hex: InfDecimal address

    Hexa-decimal address

    Nda

    36096 8D00 136097 8D01 136098 8D02 1

    36099 8D03 1

    Range: 4 words (decimal) or104414_en_00

    Example:The following data sequence can be used to reset all saved values:

    The response from the EEM-MA400 is identical to the message sent.

    If you want to reset several parameters simultaneously, you must add the numbers to the "Designation" column, e.g., to reset P+ and ER+:2 + 100 = 102 (hex)

    High address

    Low address

    High register value

    Low register value

    CRC 16

    04 00 10 00 84BE

    ormation about the connected extension moduleumber of ta words

    Designation Unit Register access

    Not available -Not available -Slot 1 0xFF: No module connected0x1: JBUS/MODBUS EEM-RS485-MA400

    - R

    Slot 2 0xFF: No module connected0x1: JBUS/MODBUS EEM-RS485-MA400

    - R

    4 words (hexadecimal)

  • MODBUS register tables

    104414_en_00

    Table 10-13 8E00 hex: Configuration of measuring deviceDecimal address

    Hexa-decimal address

    Number of data words

    Designation Unit Register access

    36352 8E00 1 Network type: 0: 1BL 1: 2BL 2: 3BL 3: 3NBL 4: 4BL 5: 4NBL

    / R/W

    36353 8E01 1 Current transformer secondary side:5: 5 A

    A R/W

    36354 8E02 1 Current transformer primary side A R/W36355 8E0336356 8E04

    36357 8E05

    36358 ... 36360 8E06 ... 8E36361 8E09

    36362 8E0A

    36363 ... 36368 8E0B ... 8E10

    Range: 17 words (decimal) oPHOENIX CONTACT 10-9

    1 Not available1 Measurement duration for determining the

    maximum current value: (2 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min)

    / R/W

    1 Measurement duration for determining the maximum value of power P,Q,S: (2 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min)

    / R/W

    08 3 Not available 1 Operating hours counter:

    1: AUX: Activated when supply voltage is present2: I: Activated when threshold value is set (input current)3: U: Activated when threshold value is set (input voltage)

    R/W

    1 Operating hours counter threshold value (current/voltage)

    A/V R/W

    6 Not available

    r 11 words (hexadecimal).

  • EEM-MA400

    11-1 PHOENIX CONTACT

    11 Technical data

    Input dataMeasuring principle True r.m.s. value measurement (TRMS) up to 51st harmonic Measured value AC sine (45 Hz ... 65 Hz)

    Voltage measurement V1, V2, V3Input voltage range

    Phase/phasePhase/neutral conductor

    50 . 500 V AC 28 . 289 V AC

    Accuracy 0.2%

    Current measurement I1, I2, I3Input current (via external transformers)

    Overload capacityOperate threshold of the nominal meAccuracy

    Power measurementMeasuring rangeAccuracyReal energy (IEC 62053-22)Reactive energy (IEC 62053-23)

    Output dataOptional for communication module

    SupplySupply voltage range

    Nominal power consumption

    DisplayTypeRefresh

    General dataDimensions W/H/DInstallation depth without extension mInstallation depth with extension modDegree of protection

    Weight104414_en_00

    PrimarySecondary

    9999 A5 A6 A (continuous)

    asuring range value 5 mA0.2%

    0 ... 9999 kW/kvar/kVA0.5%Class 0.5SClass 2

    110 400 V AC 10% 120 ... 350 V DC 20%< 5 VA (without extension modules)< 10 VA (with extension modules)

    Backlit LCD1 s

    96 x 96 x 82 mmodule 60 mmule 80 mm

    FrontBack

    IP51 IP20400 g

  • Technical data

    104414_en_00

    Electrical isolationRated insulation voltage < 300 V AC (L/N) surge voltage category III

    300 V AC ... 600 V AC surge voltage category IIMeasuring device voltage input/measuring device supply (measuring device U-IN/measuring device POW)

    Safe isolation (EN 61010-1)

    Measuring device voltage input/measuring device current input (measuring device U-IN/measuring device I-IN)

    Safe isolation (EN 61010-1)

    Measuring device current input/measuring device supply (measuring device I-IN/measuring device POW)

    Basic insulation (EN 61010-1)

    Measuring device voltage input/extension module(measuring device U-IN/extension module)

    See extension module

    Measuring device current input/extension module(measuring device I-IN/extension module)

    See extension module

    Measuring device supply/extension module(measuring device POW/extension module)

    See extension module

    Test voltage 3.5 kV AC (50 Hz, 1 min.) safe isolationTest voltagePollution degree

    Connection dataConductor cross section (current)Conductor cross section (voltage anConnection methodTightening torque

    Ambient conditionsAmbient temperature (operation)Ambient temperature (storage/transpPermissible humidity (operation)

    Conformance/approvalsConformanceConformance with EMC DImmunity to electrostatic discharge aImmunity to high-frequency electromImmunity to electrical fast transients/Immunity to surge voltages accordinImmunity to power frequency magneImmunity to voltage dips, short interrConducted and radiated noise emissConformance with Low VoElectrical safety for electrical equipmregulation, and laboratory usePHOENIX CONTACT 11-2

    1.4 kV AC (50 Hz, 1 min.) basic insulation2

    0.5 mm ... 6 mm d other) 0.5 mm ... 2.5 mm

    Screw connection0.4 Nm

    -10C ... 55C (14F ... 131F) ort) -20C ... +85C (-4F ... 185F)

    95%

    CE-compliantirective 2004/108/ECccording to IEC 61000-4-2agnetic fields according to IEC 61000-4-3burst according to IEC 61000-4-4g to IEC 61000-4-5tic fields according to IEC 61000-4-8uptions, and voltage variations IEC 61000-4-11ion according to EN 55011 Class Altage Directive 2006/95/ECent for measurement, control, EN 61010-1

  • 104414_en_00 PHOENIX CONTACT A-1

    A Abbreviations1BL Single-phase network, 2-wire with 1 current transformer

    2BL Two-phase network, 2-wire with 1 current transformer

    3BL Three-phase network with symmetrical load, 3-wire with 1 current transformer

    3NBL Three-phase network with asymmetrical load, 3-wire with 2 or 3 current transformers

    4BL Three-phase network with symmetrical load, 4-wire with 1 current transformer

    4NBL Three-phase network with asymmetrical load, 4-wire with 3 current transformers

    AUX Supply voltage

    bACLIt Backlighting

    Ct Current transformer

    Ct In Current transformer for neutral conductor

    EA Real energy (kWh)

    HOUr Operating hours counter

    MAX Maximum values within the set measuring time

    nEt Network type

    PF Power factor

    rSET Reset

    SErI Serial number

    SOFt Software version

    THD Total harmonic distortion

    tIME 4I Measuring time to determine the maximum current values

    tIME P Measuring time to determine the maximum power values

    Operating hours counter

    1 Safety notes2 Device description2.1 Displaying measured values2.2 Characteristics2.3 Communication module

    3 Operating and indication elements4 Mounting and installation4.1 Cutout dimensions4.2 Mounting4.3 Pin assignment4.4 Installation4.4.1 External current transformers4.4.2 Three-phase network with asymmetrical load (4NBL)4.4.3 Three-phase network with asymmetrical load (3NBL)4.4.4 Three-phase network with symmetrical load (3BL/4BL)4.4.5 Two-phase network (2BL)4.4.6 Single-phase network (1BL)

    4.5 Mounting the communication module

    5 Configuration5.1 Configuration mode (PROG) COdE 1005.2 Example: Configuring the device for a three-phase network with asymmetrical load5.3 Current transformers5.4 Current measuring time5.5 Power measuring time5.6 Reset5.7 Configuring the LCD5.8 Operating hours counter5.9 Displaying the software version and serial number5.10 Exiting configuration mode

    6 Operation Displaying measured values6.1 Displaying currents and the total harmonic distortion (THD)6.2 Displaying voltages, frequency, and the total harmonic distortion (THD)6.3 Displaying the power and power factors6.4 Displaying the energy

    7 Function test7.1 Calling the function test7.1.1 Automatic correction of current connections

    7.2 Repeat function test (started manually)

    8 Troubleshooting9 Communication module9.1 MODBUS basics9.2 Connecting and installing the EEM-RS485-MA400 communication module9.3 Configuring the EEM-RS485-MA400 communication module9.3.1 Setting the MODBUS address9.3.2 Setting the transmission speed9.3.3 Setting the parity9.3.4 Setting the stop bits

    9.4 MODBUS/JBUS register tables9.5 Reading/writing MODBUS RTU registers9.5.1 Settings9.5.2 Access to MODBUS registers

    10 MODBUS register tables11 Technical dataA Abbreviations