me96nsr power meter
TRANSCRIPT
-
8/13/2019 ME96NSR Power Meter
1/11
MITSUBISHIELECTRONIC MULTI-MEASURING INSTRUMENT
ME96NSR
Small & Flexible
-
8/13/2019 ME96NSR Power Meter
2/11
1. Lineup
Model Name Transmission
ME96NSR
ME96NSR-MB ModBus Communication
Model NameAnalog
Output
Pulse
Output
Contact
Input
Contact
Output
Transmission
Function
ME-4201-NS96 4 2 - 1 -
ME-0040C-NS96 - - 4 - CC-Link
ME-0052-NS96 - - 5 2 -
Basic Device
Optional Plug-in Module
-
8/13/2019 ME96NSR Power Meter
3/11
2. FeaturesVariety of Measuring Items
3P4W/3P3W Common Use
Variety of Display Functions
VT, CT Set Freely
A,DA,V,W,var,VA,PF,Hz,Wh,varh,HI,HV
96m
m
96 mm
DIN 9696mm Size
Large Bar Graph + Tri-level Digital Display
Option Module Plug-in Add-on Type
No need to specify phase-wire when ordering
Instrument Rated Current 5A/1A Common Use
Remote Input/Output Function
-
8/13/2019 ME96NSR Power Meter
4/11
Variety of Display Functions
All PhaseSimultaneous Display
4 Measuring ElementsSimultaneous Display
3. Functions
Average Voltage
Voltage
Current
Power
Factor
Electricity
-
8/13/2019 ME96NSR Power Meter
5/11
Special Display Pattern
Functions Available
Keep the display unchanged
Keep the display unchanged when even when the DISPLAYbutton is pushed
Please set only 1 display
Use ME96NSR instead of electric energy meter by displaying
electric power
UpperSelect from A,V,W,var,VA,PF,Hz
MiddleSelect from A,V,W,var,VA,PF,Hz
LowerSelect from A,V,W,var,VA,PF,Hz,Wh,varh
Maximum of 4 displays are settable
-
8/13/2019 ME96NSR Power Meter
6/11
Maximum/Minimum
Value Display
Alarm Indicator
Displays Alarm Indicator in bar graph
Enable to grasp the percentage against
the Alarm Indicator instantly
Cyclic DisplayAutomatically changes display every 5 seconds
Cyclic Display continues even after the power
is turned ON/OFFMin. Value
Max. Value
Current Value
Min. Value
Max. Value
Alarm Indicator
-
8/13/2019 ME96NSR Power Meter
7/11
Remote Input/Output Function
ME-0040C-NS96
Contact Input: 4 points
Test Function
Even during a setup of a facility, where no input current/voltage is found,
analog output, pulse output, alarm output, and communication data is replied.
This allows for easy checking of systems wiring and monitoring program.
ME-0052-NS96
Contact Input: 5 points
Contact Output: 2 points
Latch Function (Over 30ms)
-
8/13/2019 ME96NSR Power Meter
8/11
4. SpecificationsMeasuring Items 3P4W 3P3W
Current (A) A1,A2,A3,AN,AAVG A1,A2,A3,AAVG
Current Demand (DA) DA1,DA2,DA3,DAN,DAAVG DA1,DA2,DA3,DAAVG
Voltage (V)V12,V23,V31,VLLAVG or
V1N,V2N,V3N,VLNAVGV12,V23,V31,VLLAVG
Active Power (W) W,W1,W2,W3 W
Reactive Power (var) var,var1,var2,var3 var
Apparent Power (VA) VA,VA1,VA2,VA3
Frequency (Hz) Hz
Power Factor (PF) PF,PF1,PF2,PF3 PF
Active Energy (Wh) Imported, Exported
Reactive Energy (varh) Imported Lead, Imported Lag, Exported Lead, Exported Lag
Harmonics Current (HI)HI1,HI2,HI3,HIN HI1,HI2,HI3
THD, h1, h13 RMS Value and Distortion Ratio
Harmonics Voltage (HV)
HV1N,HV2N,HV3N HV12,HV23
THD, h1, h13 RMS Value and Distortion Ratio
-
8/13/2019 ME96NSR Power Meter
9/11
Measuring ItemsDisplay Analog Output, Pulse Output
AC5A AC1A AC5A AC1A
Current (A)
0.5 1.0 0.5 1.0
Current Demand (DA)
Voltage (V)
Active Power (W)
Reactive Power (var)
Apparent Power (VA)
Frequency (Hz)
Power Factor (PF) 2.0 3.0 2.0 3.0
Active Energy (Wh) 1.0 2.0 1.0 2.0
Reactive Energy (varh) 2.0 2.0 2.0 2.0
Harmonics Current (HI) 2.52.5
(RMS Value, 0Rating60)
Harmonics Voltage (HV) 2.5
2.5
(Total Distortion Ratio, 020)
Measuring Accuracy
-
8/13/2019 ME96NSR Power Meter
10/11
-
8/13/2019 ME96NSR Power Meter
11/11
ENDEND