(24) AC-1-V1-GF-Livi/Dining Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM Hourly Analysis Program v4.61 Page 1 of 16 1. General Details: Air System Name ............................................... (24) AC-1-V1-GF-Livi/Dining Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1 2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm Central Cooling Data: Supply Air Temperature ............................................................................ 52.0 °F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 % Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 % 3. Zone Components: Space Assignments: Zone 1: Zone 1 V1M-GF-Livi/Dining x1 Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 °F Cooling T-stat: Unocc. .............................................................................. 80.0 °F Heating T-stat: Occ. .................................................................................. 70.0 °F Heating T-stat: Unocc. .............................................................................. 65.0 °F T-stat Throttling Range ............................................................................. 1.50 °F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

Upload: jomon

Post on 31-Aug-2015

16 views

Category:

Documents


0 download

DESCRIPTION

hlc

TRANSCRIPT

  • (24) AC-1-V1-GF-Livi/Dining Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 1 of 16

    1. General Details: Air System Name ............................................... (24) AC-1-V1-GF-Livi/Dining Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 52.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-GF-Livi/Dining x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (24) AC-1-V1-GF-Livi/Dining Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 2 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 52.0 F Supply Fan Airflow .................................................................................. 850.5 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 850.5 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 22.9 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (25) AC-2-V1-GF-Kitchen Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 3 of 16

    1. General Details: Air System Name .................................................... (25) AC-2-V1-GF-Kitchen Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 52.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-GF-Kitchen x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 75.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (25) AC-2-V1-GF-Kitchen Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 4 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 52.0 F Supply Fan Airflow .................................................................................. 469.4 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 469.4 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 18.0 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (26) AC-3-V1-GF-Majlis+corr Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 5 of 16

    1. General Details: Air System Name .............................................. (26) AC-3-V1-GF-Majlis+corr Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 55.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-GF-Majlis+corr x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (26) AC-3-V1-GF-Majlis+corr Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 6 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 55.0 F Supply Fan Airflow .................................................................................. 601.1 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 601.1 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 16.8 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (27)AC-4-V1-GF-Maids rm+guest r Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 7 of 16

    1. General Details: Air System Name .................................... (27)AC-4-V1-GF-Maids rm+guest r Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 55.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-GF-Maids rm+guest rm x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (27)AC-4-V1-GF-Maids rm+guest r Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 8 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 55.0 F Supply Fan Airflow .................................................................................. 638.6 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 638.6 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 17.9 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (28) AC-5-V1-FF-Master bed rm Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 9 of 16

    1. General Details: Air System Name ......................................... (28) AC-5-V1-FF-Master bed rm Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 55.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-FF-Master bed rm x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (28) AC-5-V1-FF-Master bed rm Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 10 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 55.0 F Supply Fan Airflow .................................................................................. 586.3 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 586.3 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 15.9 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (29) AC-6-V1-FF-Bed rm 1 Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 11 of 16

    1. General Details: Air System Name .................................................. (29) AC-6-V1-FF-Bed rm 1 Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 53.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-FF-Bed rm 1 x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (29) AC-6-V1-FF-Bed rm 1 Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 12 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 53.0 F Supply Fan Airflow .................................................................................. 370.1 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 370.1 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 11.7 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (30) AC-7-V1-FF-Bed rm 2 Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 13 of 16

    1. General Details: Air System Name .................................................. (30) AC-7-V1-FF-Bed rm 2 Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 55.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-FF-Bed rm 2 x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (30) AC-7-V1-FF-Bed rm 2 Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 14 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 55.0 F Supply Fan Airflow .................................................................................. 415.8 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 415.8 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load .......................................................................... 9.1 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • (31)AC-8-V1-FF-Bed rm 3+Fam liv Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 15 of 16

    1. General Details: Air System Name ..................................... (31)AC-8-V1-FF-Bed rm 3+Fam liv Equipment Type ............................................................................. Split AHU Air System Type ................................................................. Single Zone CAV Number of zones ........................................................................................... 1

    2. System Components: Ventilation Air Data: Airflow Control .................................................. Constant Ventilation Airflow Ventilation Sizing Method ................................... Sum of Space OA Airflows Unocc. Damper Position ...................................................................... Closed Damper Leak Rate ........................................................................................ 0 % Outdoor Air CO2 Level .............................................................................. 400 ppm

    Central Cooling Data: Supply Air Temperature ............................................................................ 55.0 F Coil Bypass Factor ................................................................................. 0.100 Cooling Source ........................................................................ Air-Cooled DX Schedule ............................................................................ JFMAMJJASOND Capacity Control .................................. Cycled or Staged Capacity - Fan On

    Supply Fan Data: Fan Type .............................................................................. Forward Curved Configuration .................................................................................. Draw-thru Fan Performance ...................................................................................... 0.00 in wg Overall Efficiency ......................................................................................... 54 % Fan Control ............................................... 1-speed fan, cooling and heating

    Duct System Data: Supply Duct Data: Duct Heat Gain .............................................................................................. 0 % Duct Leakage ................................................................................................ 0 %

    Return Duct or Plenum Data: Return Air Via ................................................................... Return Air Plenum Wall Heat Gain to Plenum ............................................................................. 0 % Roof Heat Gain to Plenum ........................................................................... 70 % Lighting Heat Gain to Plenum ...................................................................... 30 %

    3. Zone Components: Space Assignments:

    Zone 1: Zone 1

    V1M-FF-Bed rm 3+Liv+corr x1

    Thermostats and Zone Data: Zone ........................................................................................................... All Cooling T-stat: Occ. .................................................................................. 74.0 F Cooling T-stat: Unocc. .............................................................................. 80.0 F Heating T-stat: Occ. .................................................................................. 70.0 F Heating T-stat: Unocc. .............................................................................. 65.0 F T-stat Throttling Range ............................................................................. 1.50 F Diversity Factor ......................................................................................... 100 % Direct Exhaust Airflow ................................................................................. 0.0 CFM Direct Exhaust Fan kW ............................................................................... 0.0 kW

    Thermostat Schedule ................................................................................... th Unoccupied Cooling is ..................................................................... Available

    Supply Terminals Data: Zone ........................................................................................................... All Terminal Type ................................................................................... Diffuser Minimum Airflow ....................................................................................... 0.00 CFM/person

    Zone Heating Units: Zone ........................................................................................................... All Zone Heating Unit Type .......................................................................... None

    Zone Unit Heat Source ................................................... Electric Resistance Zone Heating Unit Schedule ............................................... JFMAMJJASOND

  • (31)AC-8-V1-FF-Bed rm 3+Fam liv Input Data Project Name: AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 Prepared by: reyami 09:02AM

    Hourly Analysis Program v4.61 Page 16 of 16

    4. Sizing Data (Computer-Generated): System Sizing Data: Cooling Supply Temperature .................................................................... 55.0 F Supply Fan Airflow ................................................................................ 1156.3 CFM Ventilation Airflow ....................................................................................... 0.0 CFM

    Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................... 10.0 F Hot Water Delta-T ..................................................................................... 20.0 F

    Safety Factors: Cooling Sensible .......................................................................................... 10 % Cooling Latent ............................................................................................... 5 % Heating .......................................................................................................... 0 %

    Zone Sizing Data: Zone Airflow Sizing Method ................................ Sum of space airflow rates Space Airflow Sizing Method ............................ Individual peak space loads

    Zone Supply Airflow Zone Htg Unit Reheat Coil -

    (CFM) (MBH) (MBH) (CFM) 1 1156.3 - -

    5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load ........................................................................ 28.4 MBH Design OAT ............................................................................................ 115.0 F Equipment Sizing .......................................................................... Auto-Sized Capacity Oversizing Factor ............................................................................ 0 % ARI Performance Rating ....................................................................... 11.000 EER DX System Configuration ............................. 1-stage compression, 1 circuit Conventional Cutoff OAT .......................................................................... 55.0 F Low Temperature Operation ................................................................... Used Low Temperature Cutoff OAT ..................................................................... 0.0 F

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 1 of 12

    V1M-FF-Bed rm 1

    1. General Details: Floor Area .......................................................... 192.0 ft Avg. Ceiling Height ............................................... 10.2 ft Building Weight .................................................... 70.0 lb/ft 1.1. OA Ventilation Requirements: Space Usage ......................................... User-Defined OA Requirement 1 ................................................. 0.0 CFM OA Requirement 2 ................................................ 0.00 CFM/ft Space Usage Defaults .......... ASHRAE Std 62.1-2007

    2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Unvented) Wattage ................................................................ 1.20 W/ft Ballast Multiplier ................................................... 1.25 Schedule ............................................................. Villa

    2.4. People: Occupancy ............................................................. 3.0 People Activity Level ........................................... Office Work Sensible ............................................................. 245.0 BTU/hr/person Latent ................................................................. 205.0 BTU/hr/person Schedule .............................................................. Villa

    2.2. Task Lighting: Wattage ................................................................ 0.00 W/ft Schedule ............................................................ None

    2.5. Miscellaneous Loads: Sensible .................................................................... 0 BTU/hr Schedule ............................................................ None Latent ........................................................................ 0 BTU/hr Schedule ............................................................ None

    2.3. Electrical Equipment: Wattage .............................................................. 150.0 Watts Schedule ............................................................. Villa

    3. Walls, Windows, Doors:

    Exp. Wall Gross Area (ft) Window 1 Qty. Window 2 Qty. Door 1 Qty. NW 150.0 47 0 0

    3.1. Construction Types for Exposure NW Wall Type ................................................................. U=0.15 1st Window Type ..................................................... U - 0.37

    4. Roofs, Skylights:

    Exp. Roof Gross Area (ft) Roof Slope (deg.) Skylight Qty. H 192.0 0 0

    4.1. Construction Types for Exposure H Roof Type .......................................................... Roof ( TYP)

    5. Infiltration: Design Cooling ................................................... 52.00 CFM Design Heating ..................................................... 0.00 CFM Energy Analysis .................................................... 0.00 CFM Infiltration occurs at all hours.

    6. Floors: Type ......................................... Slab Floor On Grade Floor Area .......................................................... 192.0 ft Total Floor U-Value ............................................ 0.100 BTU/(hr-ft-F) Exposed Perimeter ................................................ 0.0 ft Edge Insulation R-Value ....................................... 0.00 (hr-ft-F)/BTU

    7. Partitions: 7.1. 1st Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 129.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F) Uncondit. Space Max Temp .................................. 95.0 F Ambient at Space Max Temp .............................. 115.0 F Uncondit. Space Min Temp ................................... 75.0 F Ambient at Space Min Temp ................................. 55.0 F

    7.2. 2nd Partition Details: (No partition data).

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 2 of 12

    V1M-FF-Bed rm 2

    1. General Details: Floor Area .......................................................... 188.0 ft Avg. Ceiling Height ............................................... 10.2 ft Building Weight .................................................... 70.0 lb/ft 1.1. OA Ventilation Requirements: Space Usage ......................................... User-Defined OA Requirement 1 ................................................. 0.0 CFM OA Requirement 2 ................................................ 0.00 CFM/ft Space Usage Defaults .......... ASHRAE Std 62.1-2007

    2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Unvented) Wattage ................................................................ 1.20 W/ft Ballast Multiplier ................................................... 1.10 Schedule ............................................................. Villa

    2.4. People: Occupancy ............................................................. 2.0 People Activity Level ........................................... Office Work Sensible ............................................................. 245.0 BTU/hr/person Latent ................................................................. 205.0 BTU/hr/person Schedule .............................................................. Villa

    2.2. Task Lighting: Wattage ................................................................ 0.00 W/ft Schedule ............................................................ None

    2.5. Miscellaneous Loads: Sensible .................................................................... 0 BTU/hr Schedule ............................................................ None Latent ........................................................................ 0 BTU/hr Schedule ............................................................ None

    2.3. Electrical Equipment: Wattage .............................................................. 150.0 Watts Schedule ............................................................. Villa

    3. Walls, Windows, Doors:

    Exp. Wall Gross Area (ft) Window 1 Qty. Window 2 Qty. Door 1 Qty. SE 106.0 75 0 0 SE 60.0 0 0 0

    3.1. Construction Types for Exposure SE Wall Type ................................................................. U=0.22 1st Window Type ..................................................... U - 0.37

    3.2. Construction Types for Exposure SE Wall Type ............................................................... U=0.096

    4. Roofs, Skylights:

    Exp. Roof Gross Area (ft) Roof Slope (deg.) Skylight Qty. H 188.0 0 0

    4.1. Construction Types for Exposure H Roof Type .......................................................... Roof ( TYP)

    5. Infiltration: Design Cooling ..................................................... 0.00 CFM Design Heating ..................................................... 0.00 CFM Energy Analysis .................................................... 0.00 CFM Infiltration occurs at all hours.

    6. Floors: Type ...................... Floor Above Conditioned Space (No additional input required for this floor type).

    7. Partitions: 7.1. 1st Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 106.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F) Uncondit. Space Max Temp .................................. 95.0 F Ambient at Space Max Temp .............................. 115.0 F Uncondit. Space Min Temp ................................... 75.0 F Ambient at Space Min Temp ................................. 55.0 F

    7.2. 2nd Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 327.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F) Uncondit. Space Max Temp ................................. 95.0 F Ambient at Space Max Temp ............................. 115.0 F Uncondit. Space Min Temp .................................. 75.0 F Ambient at Space Min Temp ................................ 55.0 F

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 3 of 12

    V1M-FF-Bed rm 3+Liv+corr

    1. General Details: Floor Area .......................................................... 555.0 ft Avg. Ceiling Height ............................................... 10.2 ft Building Weight .................................................... 70.0 lb/ft 1.1. OA Ventilation Requirements: Space Usage ......................................... User-Defined OA Requirement 1 ................................................. 0.0 CFM OA Requirement 2 ................................................ 0.00 CFM/ft Space Usage Defaults .......... ASHRAE Std 62.1-2007

    2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Unvented) Wattage ................................................................ 1.20 W/ft Ballast Multiplier ................................................... 1.25 Schedule ............................................................. Villa

    2.4. People: Occupancy ............................................................. 6.0 People Activity Level ........................................... Office Work Sensible ............................................................. 245.0 BTU/hr/person Latent ................................................................. 205.0 BTU/hr/person Schedule .............................................................. Villa

    2.2. Task Lighting: Wattage ................................................................ 0.00 W/ft Schedule ............................................................ None

    2.5. Miscellaneous Loads: Sensible .................................................................... 0 BTU/hr Schedule ............................................................ None Latent ........................................................................ 0 BTU/hr Schedule ............................................................ None

    2.3. Electrical Equipment: Wattage .............................................................. 300.0 Watts Schedule ............................................................. Villa

    3. Walls, Windows, Doors:

    Exp. Wall Gross Area (ft) Window 1 Qty. Window 2 Qty. Door 1 Qty. NW 170.0 0 0 0 SE 163.0 0 0 0 SW 166.0 152 0 0 SW 130.0 0 0 0 SW 40.0 0 0 0 SW 50.0 0 0 0

    3.1. Construction Types for Exposure NW Wall Type ............................................................... U=0.093

    3.2. Construction Types for Exposure SE Wall Type ............................................................... U=0.093

    3.3. Construction Types for Exposure SW Wall Type ................................................................. U=0.15 1st Window Type ..................................................... U - 0.37

    3.4. Construction Types for Exposure SW Wall Type ............................................................... U=0.112

    3.5. Construction Types for Exposure SW Wall Type ............................................................... U=0.104

    3.6. Construction Types for Exposure SW Wall Type ................................................................. U=0.12

    4. Roofs, Skylights:

    Exp. Roof Gross Area (ft) Roof Slope (deg.) Skylight Qty. H 555.0 0 0

    4.1. Construction Types for Exposure H Roof Type .......................................................... Roof ( TYP)

    5. Infiltration: Design Cooling ................................................... 52.00 CFM

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 4 of 12

    Design Heating ..................................................... 0.00 CFM Energy Analysis .................................................... 0.00 CFM Infiltration occurs at all hours.

    6. Floors: Type ...................... Floor Above Conditioned Space (No additional input required for this floor type).

    7. Partitions: 7.1. 1st Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 846.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F) Uncondit. Space Max Temp .................................. 95.0 F Ambient at Space Max Temp .............................. 115.0 F Uncondit. Space Min Temp ................................... 75.0 F Ambient at Space Min Temp ................................. 55.0 F

    7.2. 2nd Partition Details: (No partition data).

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 5 of 12

    V1M-FF-Master bed rm

    1. General Details: Floor Area .......................................................... 352.0 ft Avg. Ceiling Height ............................................... 10.2 ft Building Weight .................................................... 70.0 lb/ft 1.1. OA Ventilation Requirements: Space Usage ......................................... User-Defined OA Requirement 1 ................................................. 0.0 CFM OA Requirement 2 ................................................ 0.00 CFM/ft Space Usage Defaults .......... ASHRAE Std 62.1-2007

    2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Unvented) Wattage ................................................................ 1.20 W/ft Ballast Multiplier ................................................... 1.25 Schedule ............................................................. Villa

    2.4. People: Occupancy ............................................................. 3.0 People Activity Level ........................................... Office Work Sensible ............................................................. 245.0 BTU/hr/person Latent ................................................................. 205.0 BTU/hr/person Schedule .............................................................. Villa

    2.2. Task Lighting: Wattage ................................................................ 0.00 W/ft Schedule ............................................................ None

    2.5. Miscellaneous Loads: Sensible .................................................................... 0 BTU/hr Schedule ............................................................ None Latent ........................................................................ 0 BTU/hr Schedule ............................................................ None

    2.3. Electrical Equipment: Wattage .............................................................. 150.0 Watts Schedule ............................................................. Villa

    3. Walls, Windows, Doors:

    Exp. Wall Gross Area (ft) Window 1 Qty. Window 2 Qty. Door 1 Qty. NE 117.0 70 0 0 SE 167.0 0 0 0 NE 127.0 0 0 0

    3.1. Construction Types for Exposure NE Wall Type ................................................................. U=0.58 1st Window Type ..................................................... U - 0.37

    3.2. Construction Types for Exposure SE Wall Type ............................................................... U=0.093

    3.3. Construction Types for Exposure NE Wall Type ............................................................... U=0.096

    4. Roofs, Skylights:

    Exp. Roof Gross Area (ft) Roof Slope (deg.) Skylight Qty. H 352.0 0 0

    4.1. Construction Types for Exposure H Roof Type .......................................................... Roof ( TYP)

    5. Infiltration: Design Cooling ................................................... 52.00 CFM Design Heating ..................................................... 0.00 CFM Energy Analysis .................................................... 0.00 CFM Infiltration occurs at all hours.

    6. Floors: Type ...................... Floor Above Conditioned Space (No additional input required for this floor type).

    7. Partitions: 7.1. 1st Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 200.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F)

    Uncondit. Space Max Temp ................................. 95.0 F Ambient at Space Max Temp ............................. 115.0 F Uncondit. Space Min Temp .................................. 75.0 F Ambient at Space Min Temp ................................ 55.0 F

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 6 of 12

    7.2. 2nd Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 120.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F)

    Uncondit. Space Max Temp ................................. 95.0 F Ambient at Space Max Temp ............................. 115.0 F Uncondit. Space Min Temp .................................. 75.0 F Ambient at Space Min Temp ................................ 55.0 F

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 7 of 12

    V1M-GF-Kitchen

    1. General Details: Floor Area .......................................................... 182.0 ft Avg. Ceiling Height ............................................... 10.2 ft Building Weight .................................................... 70.0 lb/ft 1.1. OA Ventilation Requirements: Space Usage ......................................... User-Defined OA Requirement 1 ................................................. 0.0 CFM OA Requirement 2 ................................................ 0.00 CFM/ft Space Usage Defaults .......... ASHRAE Std 62.1-2007

    2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Unvented) Wattage ................................................................ 1.50 W/ft Ballast Multiplier ................................................... 1.25 Schedule ............................................................. Villa

    2.4. People: Occupancy ............................................................. 2.0 People Activity Level ........................................ Medium Work Sensible ............................................................. 295.0 BTU/hr/person Latent ................................................................. 455.0 BTU/hr/person Schedule .............................................................. Villa

    2.2. Task Lighting: Wattage ................................................................ 0.00 W/ft Schedule ............................................................ None

    2.5. Miscellaneous Loads: Sensible .................................................................... 0 BTU/hr Schedule ............................................................ None Latent ........................................................................ 0 BTU/hr Schedule ............................................................ None

    2.3. Electrical Equipment: Wattage .............................................................. 300.0 Watts Schedule ............................................................. Villa

    3. Walls, Windows, Doors:

    Exp. Wall Gross Area (ft) Window 1 Qty. Window 2 Qty. Door 1 Qty. NW 128.0 46 0 0

    3.1. Construction Types for Exposure NW Wall Type ............................................................... U=0.104 1st Window Type ..................................................... U - 0.37

    4. Roofs, Skylights: (No Roof or Skylight data).

    5. Infiltration: Design Cooling ................................................. 127.00 CFM Design Heating ..................................................... 0.00 CFM Energy Analysis .................................................... 0.00 CFM Infiltration occurs at all hours.

    6. Floors: Type ......................................... Slab Floor On Grade Floor Area .......................................................... 182.0 ft Total Floor U-Value ............................................ 0.100 BTU/(hr-ft-F) Exposed Perimeter ................................................ 0.0 ft Edge Insulation R-Value ....................................... 0.00 (hr-ft-F)/BTU

    7. Partitions: 7.1. 1st Partition Details: Partition Type ....................................... Wall Partition Area ................................................................... 126.0 ft U-Value .............................................................. 0.400 BTU/(hr-ft-F) Uncondit. Space Max Temp .................................. 95.0 F Ambient at Space Max Temp .............................. 115.0 F Uncondit. Space Min Temp ................................... 75.0 F Ambient at Space Min Temp ................................. 55.0 F

    7.2. 2nd Partition Details: (No partition data).

  • Space Input Data AL ZAHIA VILLA-EDITED U VALUE -(05-08-15) 08/05/2015 reyami 09:02AM

    Hourly Analysis Program v4.61 Page 8 of 12

    V1M-GF-Livi/Dining

    1. General Details: Floor Area .......................................................... 430.0 ft Avg. Ceiling Height ............................................... 10.2 ft Building Weight .................................................... 70.0 lb/ft 1.1. OA Ventilation Requirements: Space Usage ......................................... User-Defined OA Requirement 1 ................................................. 0.0 CFM OA Requirement 2 ................................................ 0.00 CFM/ft Space Usage Defaults .......... ASHRAE Std 62.1-2007

    2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Unvented) Wattage ................................................................ 2.00 W/ft Ballast Multiplier ................................................... 1.25 Schedule ............................................................. Villa

    2.4. People: Occupancy ............................................................. 8.0 People Activity Level .................................... Sedentary Work Sensible ............................................................. 280.0 BTU/hr/person Latent ................................................................. 270.0 BTU/hr/person Schedule .