MID Energy Meter and Measurement System
Smart Energy &Power Quality Solutions
Electronic DIN-rail energy meterECSEM series
Area of applicationElectronic energy meters are primarily used for the recording of effective and reactive energy. Their area of application is in the field of energy management or cost centre analysis. Various communication options are available for this in order to avoid the time consuming process of manually reading at site. As a transducer the effective pulses can be sent to a control system, e.g. BMS, PLC, SCADA or the ProData® datalogger including visualisation software GridVis.
The M-Bus and Modbus RTU protocols are available via the integrated communications interface for the field of building control technology. With the corresponding selections these interfaces enable the additional values of voltage, current, power, power factor and frequency on the bus, alongside effective power and reactive power. For consumption data the energy meters ECSEM can be used for sub-metering in combination with the measurement instruments UMG 96RM-E, UMG 604, UMG 605, UMG 508 and UMG 511 via Modbus RTU.
ApplicationsThe ECSEM series electronic energy meter is suitable for the measurement of effective and reactive energy consumption. The measurement is designed for 1-phase and 3-phase systems with a voltage of L-N 230 VAC ±20 %. The current inputs are designed for either direct connection or measurement via a current transformer. The installation is via DIN-rails, where special value is placed on the extraordinarily compact construction. All ECSEM series meters can be lead-sealed. Effective and reactive power are available in one tariff or two tariffs and in four quadrants. The accuracy of the meter is class 1 for effective energy and class 2 for reactive energy.
Capture and recordingAll meters save the energy readings to non-volatile memory. The meter reading cannot be reset in the MID version.
Main features• Communication: Modbus, M-Bus, S0 pulse outputs• Direct measurement up to 80 A or via current transformer• 1 or 2 Tariffs• With MID approval• Terminal cover can be sealed• 4 quadrant measurement• Measured values: Effective energy, reactive energy,
effective power, reactive power• Class 1 for effective energy
ECSEM series
2
Load profile
Energy reports
Ethernet (TCP/IP)
ProData II data logger Gateway for Modbus meters plus15 pulse inputs for pulse meters
Grid Visualisation SoftwareGridVis
Cold store Refrigerated display Lighting Escalator
Network
Remote read-out with a PC and central data logging on a data server
Remote read-out with a PC and central data logging on a data server
Fig.: Remote read-out with a PC via the Ethernet Modbus Gateway of ProData® data logger
3
Versions and technical data
Overview of devices
Single-phase energy meter Three-phase energy meter (two S0 pulse output)
Types ECSEM88MID ECSEM119MID ECSEM121MID ECSEM123MID ECSEM129MID ECSEM66MID ECSEM74MID
1 S0 pulse output
2 S0 pulse output
2 S0 pulse output
2 S0 pulse output
2 S0 pulse output
Pulse value 1000 Imp/kWh, length 90 ms
Pulse value 500 Imp/kWh/kvarh,length 30 ... 50 ms
Pulse value 100-10-1 Imp/kWh/kvarh, depending converters length 30 ... 100 ms
Pulse value 100-10-1 Imp/kWh/kvarh, depending converters length 30 ± 2 ms
Pulse value 500 Imp/kWh/kvarh, length 30 ± 2 ms
Item number 14.01.335 14.01.341 14.01.336 14.01.337 14.01.338 14.01.339 14.01.340
Communication module to extend the energy meter via IR-interface**
EIB-KNX* - - -
* Item number: 14.01.412 Baud rate: 9600Baud; Applicable parameters: Wh, kvarh, V, A, Hz, cos-phi, kW, kvar
** The EIB-KNX communication module has a lateral optical IR-interface. The energy meters ECSEM88MID, ECSEM119MID, ECSEM121MID and ECSEM123MI can be extended to an EIB-KNX interface by a simple click-on mounting.
General technical data
Connection 32 ADirect measurement
80 ADirect measurement
80 ADirect measurement
80 ADirect measurement
... 1/A Current transformer
... 5/A Current transformer
80 ADirect measurement
Dimensions (H x W x D mm)
90 x 18 x 70 90 x 54 x 70 90 x 54 x 70 90 x 54 x 70 90 x 72 x 70 90 x 72 x 70 90 x 72 x 70
Units wide 1 3 3 3 4 4 4
Power consumption 8 VA 1.6 VA 1.6 VA 1.6 VA 2.1 VA 2.1 VA 2.1 VA
Max. burden on current terminals (IMax)
0.9 VA 4.0 VA 4.0 VA 4.0 VA0.07 VA per phase
0.45 VA per phase
0.8 VAper phase
Working temperature (°C) -25 … +55 -25 … +55 -25 … +55 -25 … +55 -25 … +55 -25 … +55 -25 … +55
Storage temperature (°C) -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70
Protection type (front/terminals) IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20
Max. connectible wires(mm2)
Measurement: 16 Measurement: 50Input tariff: 1.5
Measurement: 50Input tariff: 1.5
Measurement: 50Input tariff: 1.5
Measurement: 4Input tariff: 1.5
Measurement: 4Input tariff: 1.5
Measurement: 35Input tariff: 1.5
Supply voltage Self-supplied Self-supplied Self-supplied Self-supplied Self-supplied Self-supplied Self-supplied
Measurement range
Voltage range (V; AC) 230 V AC ±20 % 230 V AC ±20 % 230 V AC ±20 % 230 V AC ±20 %230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
Current range (A) 0.02 ... 32 0.02 ... 80 0.02 ... 80 0.02 ... 80 0.001 ... 1.2 0.003 ... 6 0.015 ... 80
Operation frequency, mains (Hz)
50 50 50 50 50 50 50
Measurement 1-phase 1-phase 1-phase 1-phase3-phase(4 wires)
3-phase(4 wires)
3-phase(4 wires)
* MID only in 50 Hz.
4
Versions and technical data
Measured values
Types ECSEM88MID(S0 pulse)
ECSEM119MID(2x S0 pulse)
ECSEM121MID(Modbus)
ECSEM123MID (M-Bus)
ECSEM129MID(S0 pulse)
ECSEM66MID(S0 pulse)
ECSEM74MID (S0 pulse)
Effective energy measurement accuracy Class B Class B Class B Class B Class B Class B Class B
Messgenauigkeit Blindenergie Class 2 Class 2 Class 2 Class 2 Class 2 Class 2 Class 2
Tariffs 1 2 2 2 2 2 2
VoltageL1, L2, L3 - - - - -
L1-2, L2-3, L3-1 - - - - - - -
CurrentL1, L2, L3 - - - - -
N - - - - - - -
Power factorL1, L2, L3 - - - - -
∑L - - - - - - -
Frequency - - - - -
Effective powerL1, L2, L3 - - -
∑L - - - - - - -
Reactive powerL1, L2, L3 - - - -
∑L - - - - - - -
Apparent powerL1, L2, L3 - - - - -
∑L - - - - - - -
Effective energy (consumption)
L1, L2, L3, ∑L
Tariffs 1 and 2
Effective energy (delivery)
L1, L2, L3, ∑L
Tariffs 1 and 2
Reactive energy (consumption)
L1, L2, L3, ∑L - - - -
Tariffs 1 and 2 - - - -
Reactive energy (delivery)
L1, L2, L3, ∑L - - - -
Tariffs 1 and 2 - - - -
Effective energy (partial consumption)
∑L - - - - - - -
Tariffs 1 and 2 - - - - - - -
Display Remote read-out *1 only L1 *2 only tariff 1
*1
*1
*2
*1
*2
*1 *1
*1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1
*1
*1
*1 *1
*1 *1
*1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1 *1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1 *1
5
64
45
6
90
44
L1 NL1
1 2 3 4 65
54
5-230 V AC5-300 V DC
230 V AC (LOAD)LN
L1 L1
ProData
Tari�
Shield
L1 L1 N
230 VAC
L1
N
80A
61 5432
230 VAC
Modbus RTU
RTD-
D+
120 Ω
ECSEM118 - ECSEM119MID
64
45
6
90
44
L1 NL1
1 2 3 4 65
54
L1 L1 N
230 VAC
L1
N
80A
61 5432
230 VAC
Tari�
M-Bus
M1M2
M1M2
In out
6321
~/+~/+
~/-~/-
kWh kvarh
S0S0
L1 L1 N
230 VAC
L1
N
80A
ECSE
M11
8 - E
CSE
M11
9MID
65
230 VAC
Tari�
ECSEM118 - ECSEM119MID
64
45
6
90
44
L1 NL1
1 2 3 4 65
54
ECSEM series
Meter groupECSEM88MID(pulse output)
Meter groupECSEM121MID(Modbus)
Meter groupECSEM123MID(M-Bus)
Dimensional drawing
Dimensional drawing
Dimensional drawing
Dimensional drawing
Circuit diagram
Circuit diagram
Circuit diagram
Meter groupECSEM119MID(pulse output)
Circuit diagram
6
1 542
230 V a.c.
Tari�
3
~
kWh kWh
1 542
230 V a.c.
Tari�
3
~
230/400 V a.c.
230/400 V a.c.
5-230 V AC5-300 V DC
5-230 V AC5-300 V DC
76
76
kWh kWh
1 542
230 V a.c.
Tari�
3
~
kWh kWh
1 542
230 V a.c.
Tari�
3
~
230/400 V a.c.
230/400 V a.c.
5-230 V AC5-300 V DC
5-230 V AC5-300 V DC
76
76
kWh kWh
64
45
6
90
4472
1 542
230 V AC
Tari�
3
~
1 542
230 V AC
Tari�
3
~1 542
230 V AC
Tari�
3
~
230/400 V AC
230/400 V AC230/400 V AC
5-230 V AC5-300 V DC
5-230 V AC5-300 V DC
5-230 V AC5-300 V DC
7676
76
kWh kWh
kWh kWh
kWh kWh
230/400VAC
k1 l1 k2
L1L2L3N
N
k l k l k l
l2 k3 I3 L1 L2 L3
K L K L K L
~
5-230 V AC5-300 V DC
kWh kvarh
5432
230 VAC
6 7
Tari�
1
~
5-230 V AC5-300 V DC
kWh kvarh
5432
230 VAC
6 7
Tari�
1
230/400 VAC
k1 l1 k2
L1L2L3N
N
k l k l k l
l2 k3 I3 L1 L2 L3
K L K L K L
230/400VAC
k1 l1 k2
L1L2L3N
N
k l k l k l
l2 k3 I3 L1 L2 L3
K L K L K L
~
5-230 V AC5-300 V DC
kWh kvarh
5432
230 VAC
6 7
Tari�
1
~
5-230 V AC5-300 V DC
kWh kvarh
5432
230 VAC
6 7
Tari�
1
230/400 VAC
k1 l1 k2
L1L2L3N
N
k l k l k l
l2 k3 I3 L1 L2 L3
K L K L K L
1 542
230 V AC
Tari�
3
~
1 542
230 V AC
Tari�
3
~1 542
230 V AC
Tari�
3
~
230/400 V AC
230/400 V AC230/400 V AC
5-230 V AC5-300 V DC
5-230 V AC5-300 V DC
5-230 V AC5-300 V DC
7676
76
kWh kWh
kWh kWh
kWh kWh
45
6
90
4472 64
45
6
90
4472
45
6
90
4472 64
45
6
90
4472
Meter groupECSEM129MID(pulse output, current transformer x/1 A)
Meter groupECSEM66MID(pulse output, current transformer x/5 A)
Meter groupECSEM74MID(pulse output, 80 A direct measurement)
Circuit diagram
ECSEM series
Circuit diagram
Circuit diagram
Dimensional drawing
Dimensional drawing
Dimensional drawing
Neutral wire connection to the meter is mandatory.
Neutral wire connection to the meter is mandatory. Earthing of secondary winding of external CTs is required by law in many countries. Please check the regional requirements (TCC) before installation.
Neutral wire connection to the meter is mandatory. Earthing of secondary winding of external CTs is required by law in many countries. Please check the regional requirements (TCC) before installation.
7
Overview of devices
Three-phase energy meters with integrated communication interface
TypesECSEM155MID(Modbus)
ECSEM157MID(M-Bus)
ECSEM68MID (Modbus)
ECSEM67MID(M-Bus)
ECSEM76MID(Modbus)
ECSEM75MID (M-Bus)
Item number 14.01.323 14.01.325 14.01.313 14.01.317 14.01.315 14.01.319
* Note: Due to the integrated interface this energy meters are delivered without IR-interface.
General technical data
Connection... 1/A Current transformer
... 1/A Current transformer
... 5/A Current transformer
... 5/A Current transformer
80 A Direct measurement
80 A Direct measurement
Dimensions (H x W x D mm)
90 x 72 x 70 90 x 72 x 70 90 x 72 x 70 90 x 72 x 70 90 x 72 x 70 90 x 72 x 70
Units wide 4 4 4 4 4 4
Power consumption 2.1 VA 2.1 VA 2.1 VA 2.1 VA 2.1 VA 2.1 VA
Max. burden on current terminals (IMax)
0.07 VA per phase
0.07 VA per phase
0.45 VA per phase
0.45 VA per phase
0.8 VA per phase
0.8 VA per phase
Working temperature (°C) -25 … +55 -25 … +55 -25 … +55 -25 … +55 -25 … +55 -25 … +55
Storage temperature (°C) -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70 -25 … +70
Protection type (front/terminals)
IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20 IP51 / IP20
Max. connectible wires(mm2)
Measurement: 4Input tariff: 1.5
Measurement: 4Input tariff: 1.5
Measurement: 4Input tariff: 1.5
Measurement: 4Input tariff: 1.5
Measurement: 35Input tariff: 1.5
Measurement: 35Input tariff: 1.5
Supply voltage Self-supplied Self-supplied Self-supplied Self-supplied Self-supplied Self-supplied
Measurement range
Voltage range (V; AC)230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
230 / 400 V AC ±20 %
Current range (A) 0.001 ... 1.2 0.001 ... 1.2 0.003 ... 6 0.003 ... 6 0.015 ... 80 0.015 ... 80
Operation frequency, mains (Hz)
50 50 50 50 50 50
Measurement3-phase(4 wires)
3-phase(4 wires)
3-phase(4 wires)
3-phase(4 wires)
3-phase(4 wires)
3-phase(4 wires)
Versions and technical data
* MID only in 50 Hz.
8
Measured values
TypesECSEM155MID(Modbus)
ECSEM157MID(M-Bus)
ECSEM68MID (Modbus)
ECSEM67MID(M-Bus)
ECSEM76MID(Modbus)
ECSEM75MID (M-Bus)
Effective energy measurement accuracy Class B Class B Class B Class B Class B Class B
Reactive energy measurement accuracy Class 2 Class 2 Class 2 Class 2 Class 2 Class 2
Tariffs 2 2 2 2 2 2
VoltageL1, L2, L3
L1-2, L2-3, L3-1
Current L1, L2, L3, N
Power factor L1, L2, L3, ∑L
Frequency
Effective power L1, L2, L3, ∑L
Reactive power L1, L2, L3, ∑L
Apparent power L1, L2, L3, ∑L
Effective energy (consumption)
L1, L2, L3, ∑L
Tariffs 1 and 2
Effective energy (delivery)
L1, L2, L3, ∑L
Tariffs 1 and 2
Reactive energy (consumption)
L1, L2, L3, ∑L
Tariffs 1 and 2
Reactive energy (delivery)
L1, L2, L3, ∑L
Tariffs 1 and 2
Effective energy (partial consumption)
∑L - - -
Tariffs 1 and 2
Versions and technical data
Measured values
Display Remote read-out
9
Shield
Shield Shield
Shield
Shield Shield
Meter groupECSEM157MID(M-Bus, current transformer x/1 A)
Dimensional drawing
ECSEM157MID circuit diagram(M-Bus)
Meter groupECSEM155MID(Modbus, current transformer x/1 A)
Dimensional drawing
ECSEM155MID circuit diagram(Modbus)
ECSEM series
Neutral wire connection to the meter is mandatory. Earthing of secondary winding of external CTs is required by law in many countries. Please check the regional requirements (TCC) before installation.
Neutral wire connection to the meter is mandatory. Earthing of secondary winding of external CTs is required by law in many countries. Please check the regional requirements (TCC) before installation.
10
230/400 V a.c.
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
N
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
230/400 V a.c.
N
71 6542
230 V a.c.
Tarif
M-Bus
3
M1 M2M1 M2
71 6542
230 V a.c.
Tarif
M-Bus
3
M1 M2M1 M2
230/400 V a.c.
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
N
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
230/400 V a.c.
N
71 6542
230 V a.c.
Tarif
M-Bus
3
M1 M2M1 M2
71 6542
230 V a.c.
Tarif
M-Bus
3
M1 M2M1 M2
230/400 V a.c.
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
N 71 6542
230 V a.c.
Tarif
Modbus RTU
3
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
230/400 V a.c.
N 71 6542
Tarif
3
RT D- D+Shield
230 V a.c. Modbus RTU
RT D- D+Shield
230/400 V a.c.
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
N 71 6542
230 V a.c.
Tarif
Modbus RTU
3
L1L2L3N
L1 L1 L2 L2 L3 L3
3 x 80 A
230/400 V a.c.
N 71 6542
Tarif
3
RT D- D+Shield
230 V a.c. Modbus RTU
RT D- D+Shield
Meter groupECSEM75MID / ECSEM76MID(80 A direct measurement)
Meter groupECSEM68MID / ECSEM67MID(current transformer x/5 A)
Dimensional drawing
Dimensional drawing
ECSEM75MID circuit diagram(M-Bus)
ECSEM76MID circuit diagram(Modbus)
ECSEM series
ECSEM68MID circuit diagram(Modbus)
ECSEM67MID circuit diagram(M-Bus)
Neutral wire connection to the meter is mandatory. Earthing of secondary winding of external CTs is required by law in many countries. Please check the regional requirements (TCC) before installation.