mm ztk 1a zoc saf dwg 5002 rev b2_in

4

Upload: jazz9971

Post on 18-Jan-2016

28 views

Category:

Documents


0 download

DESCRIPTION

lng

TRANSCRIPT

Page 1: Mm Ztk 1a Zoc Saf Dwg 5002 Rev b2_in
miaojinniu
remark
According to API 505 (figure 104), the radius of source is 7.5m when gas pressure is above 1900kPa and the road must not be encroached. Unfortunately, there is no enough space to remove road according to radius of source rated 7.5m. Thus the radius of source we adopted is 3m which indicated in ITB document then there will be enough space to remove road.
Page 2: Mm Ztk 1a Zoc Saf Dwg 5002 Rev b2_in
Page 3: Mm Ztk 1a Zoc Saf Dwg 5002 Rev b2_in
miaojinniu
remark
When get the detailed information, the accurate classification will be added.
Page 4: Mm Ztk 1a Zoc Saf Dwg 5002 Rev b2_in