nhp safety reference guide...safety rating: cat. 4, ple to iso 13849-1: 2008 topic page important...

20
NHP SAFETY REFERENCE GUIDE Actuator Subsystems - Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off Products: GuardLogix Controller, PowerFlex 527 Drive Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 SAFETY FUNCTION DOCUMENTS GuardLogix

Upload: others

Post on 07-Jul-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

NHP S

AFET

Y REF

EREN

CE G

UIDE

Actuator Subsystems - Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-offProducts: GuardLogix Controller, PowerFlex 527 DriveSafety Rating: CAT. 4, PLe to ISO 13849-1: 2008

SAFETY FUNCTION DOCUMENTS

GuardLogix

Page 2: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Table of Contents:

Important User Information 6-260

General Safety Information 6-262

Introduction 6-262

Safety Function Realization: Risk Assessment 6-263

Stop Safety Function 6-263

Safety Function Requirements 6-263

Functional Safety Description 6-263

Integrated Safety 6-264

Bill of Material 6-264

Setup and Wiring 6-264

Configuration 6-265

Programming 6-269

Calculation of the Performance Level 6-175

Verification and Validation Plan 6-273

Additional Resources 6-277

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Application Technique

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-offProducts: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Topic Page

Important User Information 2

General Safety Information 3

Introduction 3

Safety Function Realization: Risk Assessment 4

Stop Safety Function 4

Safety Function Requirements 4

Functional Safety Description 5

Bill of Material 6

Setup and Wiring 6

Configuration 7

Calculation of the Performance Level 12

Verification and Validation Plan 15

Additional Resources 17

6A-260NHP Safety Reference Guide > Safety Function Documents: GL

Page 3: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Important User InformationRead this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,nand standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for PPE

6A-261NHP Safety Reference Guide > Safety Function Documents: GL

Page 4: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

IntroductionThis application technique explains how to program the logic (GuardLogix® controller) and configure the actuator (PowerFlex® 527 drive with integrated safe torque-off ) subsystems of a safety function. In this application technique, the GuardLogix controller de-energizes the final control devices, in this case, the integrated safe torque-off (STO) inputs on the PowerFlex 527 drive. The final control element is de-energized immediately for a category 0 stop, and a delay (or monitoring that the hazard is stopped or in a safe state) is introduced before de-energizing for a category 1 stop. This example uses a 1756-L73S GuardLogix controller, but is applicable to any GuardLogix 5570 controller (1756-L7xS) using the Studio 5000 Logix Designer® application, version 24 or later.

Use this application technique in conjunction with the sensor subsystems from any other GuardLogix safety function application technique. For example, you can use sensor subsystems 1 and 2 from GuardLogix: Safety Gate Application with SensaGuard™ Switch Safety Application Example, publication SAFETY-AT029, along with the actuator subsystems from this application technique, to create the following overall safety function.

This application example is for advanced users and assumes that you are trained and experienced in safety system requirements.

ATTENTION: Perform a risk assessment to make sure all task and hazard combinations have been identified and addressed. The risk assessment can require additional circuitry to reduce the risk to a tolerable level. Safety circuits must take into consideration safety distance calculations, which are not part of the scope of this document.

General Safety InformationContact Rockwell Automation to find out more about our safety risk assessment services.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

You must add the PFH values for each subsystem together to create a PFH for the overall safety function. Depending on the sensor subsys-tems and devices you choose, the overall safety rating of your system could be reduced. The results of an example calculation for a complete safety function are shown in the section titled Calculation of the Performance Level on page 12.

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 3

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

General Safety Information

Contact Rockwell Automation to find out more about our safety risk assessment services.

Introduction

This application technique explains how to program the logic (GuardLogix® controller) and configure the actuator (PowerFlex® 527 drive with integrated safe torque-off ) subsystems of a safety function. In this application technique, the GuardLogix controller de-energizes the final control devices, in this case, the integrated safe torque-off (STO) inputs on the PowerFlex 527 drive. The final control element is de-energized immediately for a category 0 stop, and a delay (or monitoring that the hazard is stopped or in a safe state) is introduced before de-energizing for a category 1 stop. This example uses a 1756-L73S GuardLogix controller, but is applicable to any GuardLogix 5570 controller (1756-L7xS) using the Studio 5000 Logix Designer® application, version 24 or later.

Use this application technique in conjunction with the sensor subsystems from any other GuardLogix safety function application technique. For example, you can use sensor subsystems 1 and 2 from GuardLogix: Safety Gate Application with SensaGuard™ Switch Safety Application Example, publication SAFETY-AT029, along with the actuator subsystems from this application technique, to create the following overall safety function.

IMPORTANT This application example is for advanced users and assumes that you are trained and experienced in safety system requirements.

ATTENTION: Perform a risk assessment to make sure all task and hazard combinations have been identified and addressed. The risk assessment can require additional circuitry to reduce the risk to a tolerable level. Safety circuits must take into consideration safety distance calculations, which are not part of the scope of this document.

IMPORTANT You must add the PFH values for each subsystem together to create a PFH for the overall safety function. Depending on the sensor subsystems and devices you choose, the overall safety rating of your system could be reduced. The results of an example calculation for a complete safety function are shown in the section titled Calculation of the Performance Level on page 12.

SensaGuard Switch 1734-IB8S 1756-L7xS

PowerFlex 527 Drive

Subsystem 1 Subsystem 2 Subsystem 3 Subsystem 4

Input Logic Output

6A-262NHP Safety Reference Guide > Safety Function Documents: GL

Page 5: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Safety Function Realization: Risk AssessmentThe required performance level is the result of a risk assessment and refers to the amount of the risk reduction to be carried out by the safety-related parts of the control system. Part of the risk reduction process is to determine the safety functions of the machine. In this application, the performance level required (PLr) by the risk assessment is Category 3, Performance Level d (CAT. 3, PLd), for each safety function. A safety system that achieves CAT. 3, PLd, or higher, can be considered control reliable. Each safety product has its own rating and can be combined to create a safety function that meets or exceeds the PLr.

Stop Safety FunctionThis application technique includes one partial safety function. The safety function is the stopping of a motor when the safety system detects that one or more sensor subsystems have placed a demand on the safety function. The stopping of the motor removes the hazard. The stop category is category 0, which is an uncontrolled coasting of the motor. If the risk assessment determines that coasting is dangerous, then a category 1 stop should be implemented.

Safety Function RequirementsPlacing a demand on the sensor subsystem generates a stop command that prevents hazardous motion. Once the stop command is reset, a secondary action (pressing the Start button) lets hazardous motion resume. Faults within these complex subsystems are unknown and must be detected at a rate that enables the overall safety function to meet the requirements for Performance Level d (PLd), per ISO 13849-1. The vendor must provide Probability of Dangerous Failure per Hour (PFHd) values for these subsystems.

The safety functions in this application technique each meet or exceed the requirements for Category 3, Performance Level d (CAT. 3, PLd), per ISO 13849-1 and control reliable operation per ANSI B11.19.

Functional Safety DescriptionThe GuardLogix controller and PowerFlex 527 drive with integrated safe torque-off (STO) both use 1oo2 architectures to achieve the PFHd value that is used in the PL calculation section of this document. The GuardLogix controller PFHd was generated with a 20-year Proof Test Interval (PTI), and the PowerFlex 527 drive PFHd was generated with a 10-year PTI.

The PowerFlex 527 drive integrated STO feature is used to stop and prevent hazardous motion. PowerFlex 527 drives have a single, module-defined, integrated STO safety tag that is controlled within the safety task of the GuardLogix controller.

The PowerFlex 527 drive is connected via CIP Safety over an EtherNet/IP™ network to the GuardLogix safety controller.

The PowerFlex 527 drive integrated STO uses the CIP Safety protocol. The CIP Safety™ protocol inserts the data into the CIP Safety packet twice. One piece of data is normal and the other is inverted. CIP Safety packets are also timestamped by the producer so that the consumer can determine the age of the packet when it arrives. If a good packet does not arrive before the Connection Reaction Time Limit (CRTL) expires, then the STO feature within the PowerFlex 527 drive goes to the safe state: OFF.

CIP Safety protocol supports a direct connection between the PowerFlex drive and the GuardLogix controller, making the EtherNet/IP hardware between these two end devices a black channel. Therefore, the EtherNet/IP hardware does not have to be included in the PL calculation. The Probability of Failure per Hour (PFH) of the CIP Safety protocol has already been included in the controller PFH value.

The STO feature forces the drive output power transistors to a disabled state when the STO command from the GuardLogix controller is de-energized, which results in a condition where the drive is coasting. This feature does not provide electrical power isolation. For safe distance calculations and reaction time calculations, the response time of the STO feature is less than 12 ms from the time the STO command is de-energized in the PowerFlex 527 drive.

When all safety input interlocks are satisfied, no faults are detected, and a proper reset occurs, the STO tags within the GuardLogix controller are set to high (1). In summary, when a demand is placed on the safety function, the STO tag is de-energized and the motor coasts to a stop for a category 0 stop. If a category 1 stop is being used, then the demand on the safety function drives the speed to zero (using a STOP command issued from the Logix controller to the PowerFlex 527 drive), and after a pre-determined delay, the STO tag is de-energized. When the safety interlocks are returned to the active state (closed), and a proper reset function occurs, the PowerFlex drive STO is enabled.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

4 Safety Function: Door Monitoring

Safety Function Realization: Risk AssessmentThe required performance level is the result of a risk assessment and refers to the amount of the risk reduction to be carried out by the safety-related parts of the control system. Part of the risk reduction process is to determine the safety functions of the machine. In this application, the performance level required (PLr) by the risk assessment is Category 3, Performance Level d (CAT. 3, PLd), for each safety function. A safety system that achieves CAT. 3, PLd, or higher, can be considered control reliable. Each safety product has its own rating and can be combined to create a safety function that meets or exceeds the PLr.

Door Monitoring Safety FunctionPart of the risk reduction process is to determine the safety functions included in the safety project. This safety project has two safety functions:

• Removal of power from the motor when the E-stop is pressed

• Removal of power from the motor when the gate is opened

Safety Function RequirementsPressing the E-stop or opening the guard gate stops hazardous motion by removal of power to the motor. When the E-stop is released and the guard gate is closed, power to the motor and hazardous motion does not resume until the safety system is reset and a secondary action (Start button is pressed and released) occurs. Faults at the E-stop, gate interlock switch, wiring terminals, or safety controller are detected before the next safety demand.

The PowerFlex 525 drive monitors itself for input, internal, and output faults. When the PowerFlex 525 drive detects a fault, it turns off its output, removing power to the motor. The fault must be corrected and power to the drive cycled before the drive can be restarted. Faults at the safe torque-off (STO) inputs on the PowerFlex 525 drive can go undetected.

From: Risk Assessment (ISO 12100)

1. Identification of safety functions

2. Specification of characteristics of each function

3. Determination of required PL (PLr) for each safety function

To: Realization and PL Evaluation

Rockwell Automation Publication SAFETY-AT126A-EN-P – January 2014

6A-263NHP Safety Reference Guide > Safety Function Documents: GL

Page 6: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Integrated Safety: Safe Torque-off Considerations for a Stop Category 1In the event of a malfunction, the most likely stop category is category 0. When designing the machine application, timing and distance must be considered for a coast to stop, as well as the possibility of the loss of control of a vertical load. These malfunctions include a transition (programmatic or keyswitch) from Run to Program mode, or any loss of communication that drops out the STO networked tags. Use additional protective measures if this occurrence might introduce unacceptable risks to personnel.

Bill of MaterialThe output subsystems in this application technique use these products.

Setup and WiringFor detailed information on installing and wiring, refer to the publications listed in the Additional Resources on the back cover

System Overview

The final control device is the PowerFlex 527 drive with integrated safe torque-off (STO). Because this drive features integrated STO inputs, rather than hard-wired inputs, there is no need for a safety output module in this safety function.

The GuardLogix controller and the PowerFlex 527 drive are both connected on an EtherNet/IP network. CIP Safety protocol requires a direct connection between the PowerFlex drive and the GuardLogix controller. This makes the EtherNet/IP hardware between these two end devices a black channel. Any EtherNet/IP hardware can be used with no effect on the PL calculation.

The overall safety function must have individual reset buttons for resetting faults and for resetting safety outputs. These reset buttons can be wired to any input module (safety or standard) in your system. The safety rating of the reset button must not diminish the rating of the relevant safety function. This is accomplished by the trailing edge or falling edge of the button generating the reset command, thus tolerating faults in the reset circuit..

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Cat. No. Description Qty

25C-V2P5N104 PowerFlex 527 drive, 120VAC, 2.5A, Frame A 1

1756-L73SGuardLogix processor, 8.0 MB standard memory, 4.0 MB safety memory

1

1756-EN2T ControlLogix® EtherNet/IP bridge 3

1756-A4 4-slot ControlLogix chassis 1

1756-PA72Power supply, 120/240V AC input, 3.5 A @ 24V DC

1

800FM-G611MX10800F reset push button - metal, guarded, blue, R, metal latch mount, 1 N.O. contact, standard

2

6A-264NHP Safety Reference Guide > Safety Function Documents: GL

Page 7: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Electrical SchematicA schematic for this actuator subsystem is not needed, because the PowerFlex 527 drive and the GuardLogix controller are connected on an EtherNet/IP network.

The following I/O configuration shows the GuardLogix controller and the EtherNet/IP module in the local chassis, connected to the PowerFlex 527 drive over an EtherNet/IP network.

ConfigurationThe GuardLogix controller is configured by using the Studio 5000 Logix Designer application, version 24 or later. You must create a new project and add the PowerFlex 527 drive. A detailed description of each step is beyond the scope of this document. Knowledge of the Logix Designer application is assumed.

Create a Project with a GuardLogix Controller and a PowerFlex 527 Drive1. In the Logix Designer application, create a new project with a GuardLogix controller.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

The Logix Designer application, version 24 or later, is required to support PowerFlex 527 drives with integrated STO.

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 7

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Electrical Schematic

A schematic for this actuator subsystem is not needed, because the PowerFlex 527 drive and the GuardLogix controller are connected on an EtherNet/IP network.

The following I/O configuration shows the GuardLogix controller and the EtherNet/IP module in the local chassis, connected to the PowerFlex 527 drive over an EtherNet/IP network.

Configuration

The GuardLogix controller is configured by using the Studio 5000 Logix Designer application, version 24 or later. You must create a new project and add the PowerFlex 527 drive. A detailed description of each step is beyond the scope of this document. Knowledge of the Logix Designer application is assumed.

Create a Project with a GuardLogix Controller and a PowerFlex 527 Drive

1. In the Logix Designer application, create a new project with a GuardLogix controller. fif

IMPORTANT The Logix Designer application, version 24 or later, is required to support PowerFlex 527 drives with integrated STO.

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 7

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Electrical Schematic

A schematic for this actuator subsystem is not needed, because the PowerFlex 527 drive and the GuardLogix controller are connected on an EtherNet/IP network.

The following I/O configuration shows the GuardLogix controller and the EtherNet/IP module in the local chassis, connected to the PowerFlex 527 drive over an EtherNet/IP network.

Configuration

The GuardLogix controller is configured by using the Studio 5000 Logix Designer application, version 24 or later. You must create a new project and add the PowerFlex 527 drive. A detailed description of each step is beyond the scope of this document. Knowledge of the Logix Designer application is assumed.

Create a Project with a GuardLogix Controller and a PowerFlex 527 Drive

1. In the Logix Designer application, create a new project with a GuardLogix controller. fif

IMPORTANT The Logix Designer application, version 24 or later, is required to support PowerFlex 527 drives with integrated STO.

6A-265NHP Safety Reference Guide > Safety Function Documents: GL

Page 8: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

2. Enable Time Synchronization for the GuardLogix controller.

3. In the Controller Organizer, add the 1756-EN2T module to the 1756 Backplane.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

8 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

2. Enable Time Synchronization for the GuardLogix controller.

3. In the Controller Organizer, add the 1756-EN2T module to the 1756 Backplane.

8 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

2. Enable Time Synchronization for the GuardLogix controller.

3. In the Controller Organizer, add the 1756-EN2T module to the 1756 Backplane.

6A-266NHP Safety Reference Guide > Safety Function Documents: GL

Page 9: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

4. On the 1756-EN2T General tab, do the following:

a. Name the 1756-EN2T module.

b. Type an IP address for the 1756-EN2T module (your address may differ from the one shown in the image).

c. Change the Time Sync Connection to Time Sync and Motion.

d. Click OK.

5. Add the PowerFlex 527 drive under the 1756-EN2T module.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 9

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

4. On the 1756-EN2T General tab, do the following:a. Name the 1756-EN2T module.b. Type an IP address for the 1756-EN2T module (your address may differ from the one shown in the image).c. Change the Time Sync Connection to Time Sync and Motion.d. Click OK.

5. Add the PowerFlex 527 drive under the 1756-EN2T module.

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 9

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

4. On the 1756-EN2T General tab, do the following:a. Name the 1756-EN2T module.b. Type an IP address for the 1756-EN2T module (your address may differ from the one shown in the image).c. Change the Time Sync Connection to Time Sync and Motion.d. Click OK.

5. Add the PowerFlex 527 drive under the 1756-EN2T module.

6A-267NHP Safety Reference Guide > Safety Function Documents: GL

Page 10: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

6. In the PowerFlex 527 New Module dialog box, do the following:

a. Change the name.

b. Set the IP address (your address may differ from the one shown in the image).

c. Change the Connection to Motion and Safety to indicate that both motion and safety are being managed by the GuardLogix controller.

d. Select the proper Power Structure.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

10 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

6. In the PowerFlex 527 New Module dialog box, do the following:a. Change the name.b. Set the IP address (your address may differ from the one shown in the image).c. Change the Connection to Motion and Safety to indicate that both motion and safety are being managed by the

GuardLogix controller.d. Select the proper Power Structure.

6A-268NHP Safety Reference Guide > Safety Function Documents: GL

Page 11: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Program the LogicThe accumulated ‘safety interlocks OK’ tag is used in the seal-in rung to drive the STO tag. If the safety interlock tag drops out, so does the safe torque-off (STO) feature, and it remains off until a manual reset action is carried out. The STO output is energized if the safety interlocks are satisfied, there are no faults, there is a valid connection, and there is a falling edge on the reset button.

The following code is an example for a category 0 stop. When a demand is placed on safety interlocks, and ‘Safety_Interlocks_OK’ goes to low (0), then the PowerFlex 527 drive STO output immediately goes to low (0) as well.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 11

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Program the Logic

The accumulated 'safety interlocks OK' tag is used in the seal-in rung to drive the STO tag. If the safety interlock tag drops out, so does the safe torque-off (STO) feature, and it remains off until a manual reset action is carried out. The STO output is energized if the safety interlocks are satisfied, there are no faults, there is a valid connection, and there is a falling edge on the reset button.

The following code is an example for a category 0 stop. When a demand is placed on safety interlocks, and 'Safety_Interlocks_OK' goes to low (0), then the PowerFlex 527 drive STO output immediately goes to low (0) as well.

6A-269NHP Safety Reference Guide > Safety Function Documents: GL

Page 12: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

The following code is an example for a category 1 stop. When a demand is placed on the safety interlocks, then the PowerFlex 527 drive STO output goes to low (0) after a three-second delay. The length of the delay is determined by the risk assessment. During the three-second delay, the ‘Motion_Axis_Stop’ tag can be used to stop the axis. For example, this could control a Motion Axis Stop command.

Falling Edge Reset

ISO 13849-1 stipulates that instruction reset functions must occur on falling edge signals. To comply with this requirement, a One Shot Falling (OSF) instruction is used on the reset rung. Then, the OSF instruction Output Bit tag is used as the reset bit for the STO output or enable rungs.

Calculation of the Performance LevelWhen properly implemented, the PowerFlex 527 drive with integrated safe torque-off (STO) subsystem can be used in a safety function that achieves a safety rating of CAT. 4, Performance Level e (PLe), according to ISO 13849-1: 2008, as calculated by using the Safety Integrity Software Tool for the Evaluation of Machine Applications (SISTEMA).

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

To calculate the PL of your entire safety function, you must include the sensor subsystems along with the logic and actuator subsystems shown here. Depending on the sensor subsystems and devices you choose, the overall safety rating of your system could be reduced. An example that describes how to calculate the safety rating for a complete safety function appears in the section titled Complete Safety Function PL Calculation Example on page 13.

12 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

The following code is an example for a category 1 stop. When a demand is placed on the safety interlocks, then the PowerFlex 527 drive STO output goes to low (0) after a three-second delay. The length of the delay is determined by the risk assessment. During the three-second delay, the 'Motion_Axis_Stop' tag can be used to stop the axis. For example, this could control a Motion Axis Stop command.

Falling Edge Reset

ISO 13849-1 stipulates that instruction reset functions must occur on falling edge signals. To comply with this requirement, a One Shot Falling (OSF) instruction is used on the reset rung. Then, the OSF instruction Output Bit tag is used as the reset bit for the STO output or enable rungs.

Calculation of the Performance Level

When properly implemented, the PowerFlex 527 drive with integrated safe torque-off (STO) subsystem can be used in a safety function that achieves a safety rating of CAT. 4, Performance Level e (PLe), according to ISO 13849-1: 2008, as calculated by using the Safety Integrity Software Tool for the Evaluation of Machine Applications (SISTEMA).

IMPORTANT To calculate the PL of your entire safety function, you must include the sensor subsystems along with the logic and actuator subsystems shown here. Depending on the sensor subsystems and devices you choose, the overall safety rating of your system could be reduced. An example that describes how to calculate the safety rating for a complete safety function appears in the section titled Complete Safety Function PL Calculation Example on page 13.

6A-270NHP Safety Reference Guide > Safety Function Documents: GL

Page 13: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Logic and Actuator Subsystem CalculationThe (logic) GuardLogix controller subsystem uses 1.20% of PLe bandwidth. The (actuator) PowerFlex 527 integrated STO subsystem uses 2.10% of PLe bandwidth. The PFH of the PowerFlex 527 drive was generated with a Proof Test Interval (PTI) of 10 years, which generates the yellow warning shown below. The GuardLogix controller and other subsystems used in this safety function example have a PTI of 20 years or higher.

The logic and actuator subsystems can be modeled as follows.

Complete Safety Function PL Calculation ExampleThis example takes the actuator subsystems from this document and combines them with the sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, to illustrate how any sensor subsystems can be added to the output subsystems within this publication.

Here are the actuator subsystems described in this publication.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 13

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Logic and Actuator Subsystem Calculation

The (logic) GuardLogix controller subsystem uses 1.20% of PLe bandwidth. The (actuator) PowerFlex 527 integrated STO subsystem uses 2.10% of PLe bandwidth. The PFH of the PowerFlex 527 drive was generated with a Proof Test Interval (PTI) of 10 years, which generates the yellow warning shown below. The GuardLogix controller and other subsystems used in this safety function example have a PTI of 20 years or higher.

The logic and actuator subsystems can be modeled as follows.

Complete Safety Function PL Calculation Example

This example takes the actuator subsystems from this document and combines them with the sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, to illustrate how any sensor subsystems can be added to the output subsystems within this publication.

Here are the actuator subsystems described in this publication.

Subsystem 1 Subsystem 2 Subsystem 3

Determined by the sensor

subsystems you choose

PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 13

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Logic and Actuator Subsystem Calculation

The (logic) GuardLogix controller subsystem uses 1.20% of PLe bandwidth. The (actuator) PowerFlex 527 integrated STO subsystem uses 2.10% of PLe bandwidth. The PFH of the PowerFlex 527 drive was generated with a Proof Test Interval (PTI) of 10 years, which generates the yellow warning shown below. The GuardLogix controller and other subsystems used in this safety function example have a PTI of 20 years or higher.

The logic and actuator subsystems can be modeled as follows.

Complete Safety Function PL Calculation Example

This example takes the actuator subsystems from this document and combines them with the sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, to illustrate how any sensor subsystems can be added to the output subsystems within this publication.

Here are the actuator subsystems described in this publication.

Subsystem 1 Subsystem 2 Subsystem 3

Determined by the sensor

subsystems you choose

PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015 13

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Logic and Actuator Subsystem Calculation

The (logic) GuardLogix controller subsystem uses 1.20% of PLe bandwidth. The (actuator) PowerFlex 527 integrated STO subsystem uses 2.10% of PLe bandwidth. The PFH of the PowerFlex 527 drive was generated with a Proof Test Interval (PTI) of 10 years, which generates the yellow warning shown below. The GuardLogix controller and other subsystems used in this safety function example have a PTI of 20 years or higher.

The logic and actuator subsystems can be modeled as follows.

Complete Safety Function PL Calculation Example

This example takes the actuator subsystems from this document and combines them with the sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, to illustrate how any sensor subsystems can be added to the output subsystems within this publication.

Here are the actuator subsystems described in this publication.

Subsystem 1 Subsystem 2 Subsystem 3

Determined by the sensor

subsystems you choose

PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

6A-271NHP Safety Reference Guide > Safety Function Documents: GL

Page 14: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Here are the subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029: sensor, logic, and actuator.

The sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, are the SensaGuard Interlock Switch and the 1734-IB8S POINT Guard I/O™ input module. The overall safety function is shown here, combining those sensor subsystems from publication SAFETY-AT029, and the logic and actuator subsystems from this document.

The PFH values for each subsystem in the safety function modeled above are taken from their respective publications and combined.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

14 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Here are the subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029: sensor, logic, and actuator.

The sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, are the SensaGuard Interlock Switch and the 1734-IB8S POINT Guard I/O™ input module. The overall safety function is shown here, combining those sensor subsystems from publication SAFETY-AT029, and the logic and actuator subsystems from this document.

The PFH values for each subsystem in the safety function modeled above are taken from their respective publications and combined.

IMPORTANT The PFH for this complete safety function, with the sensor, logic, and actuator subsystems, is 4.93E-09, which consumes 4.93% of the PLe bandwidth. The PL for the complete safety function is PLe.

Subsystem 1 Subsystem 2 Subsystem 3 Subsystem 4

SensaGuard Switch

1734-IB8S PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

14 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Here are the subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029: sensor, logic, and actuator.

The sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, are the SensaGuard Interlock Switch and the 1734-IB8S POINT Guard I/O™ input module. The overall safety function is shown here, combining those sensor subsystems from publication SAFETY-AT029, and the logic and actuator subsystems from this document.

The PFH values for each subsystem in the safety function modeled above are taken from their respective publications and combined.

IMPORTANT The PFH for this complete safety function, with the sensor, logic, and actuator subsystems, is 4.93E-09, which consumes 4.93% of the PLe bandwidth. The PL for the complete safety function is PLe.

Subsystem 1 Subsystem 2 Subsystem 3 Subsystem 4

SensaGuard Switch

1734-IB8S PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

14 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Here are the subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029: sensor, logic, and actuator.

The sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, are the SensaGuard Interlock Switch and the 1734-IB8S POINT Guard I/O™ input module. The overall safety function is shown here, combining those sensor subsystems from publication SAFETY-AT029, and the logic and actuator subsystems from this document.

The PFH values for each subsystem in the safety function modeled above are taken from their respective publications and combined.

IMPORTANT The PFH for this complete safety function, with the sensor, logic, and actuator subsystems, is 4.93E-09, which consumes 4.93% of the PLe bandwidth. The PL for the complete safety function is PLe.

Subsystem 1 Subsystem 2 Subsystem 3 Subsystem 4

SensaGuard Switch

1734-IB8S PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

6A-272NHP Safety Reference Guide > Safety Function Documents: GL

Page 15: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

14 Rockwell Automation Publication SAFETY-AT141A-EN-P - May 2015

Safety Function: Actuator Subsystems – Category 0 or Category 1 Stop via a PowerFlex 527 Drive with Integrated Safe Torque-off

Here are the subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029: sensor, logic, and actuator.

The sensor subsystems from GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029, are the SensaGuard Interlock Switch and the 1734-IB8S POINT Guard I/O™ input module. The overall safety function is shown here, combining those sensor subsystems from publication SAFETY-AT029, and the logic and actuator subsystems from this document.

The PFH values for each subsystem in the safety function modeled above are taken from their respective publications and combined.

IMPORTANT The PFH for this complete safety function, with the sensor, logic, and actuator subsystems, is 4.93E-09, which consumes 4.93% of the PLe bandwidth. The PL for the complete safety function is PLe.

Subsystem 1 Subsystem 2 Subsystem 3 Subsystem 4

SensaGuard Switch

1734-IB8S PowerFlex 527 Drive

GuardLogix Controller

Input Logic Output

The PFH for this complete safety function, with the sensor, logic, and actuator subsystems, is 4.93E-09, which consumes 4.93% of the PLe bandwidth. The PL for the complete safety function is PLe.

Verification and Validation PlanVerification and validation play important roles in the avoidance of faults throughout the safety system design and development process. ISO 13849-2 sets the requirements for verification and validation. The standard calls for a documented plan to confirm that all of the safety functional requirements have been met.

Verification is an analysis of the resulting safety control system. The Performance Level (PL) of the safety control system is calculated to confirm that the system meets the required Performance Level (PLr) specified. The SISTEMA software is typically used to perform the calculations and assist with satisfying the requirements of ISO 13849-1.

Validation is a functional test of the safety control system to demonstrate that the system meets the specified requirements of the safety function. The safety control system is tested to confirm that all of the safety-related outputs respond appropriately to their corresponding safety-related inputs. The functional test includes normal operating conditions in addition to potential fault injection of failure modes. A checklist is typically used to document the validation of the safety control system.

The following plan assumes a category 0 stop is being used. You must make appropriate adaptations to the plan if your safety function requires a category 1 stop.

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

6A-273NHP Safety Reference Guide > Safety Function Documents: GL

Page 16: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

General Machinery Information

Machine Name/ModelNumber

Machine Serial Number

Customer Name

Test Date

Tester Name(s)

Schematic Drawing Number

Controller Name

Safety Signature ID

Safety Network Number(s)

Logix Designer Application

Safety Control System Modules GuardLogix Modules Firmware Version

GuardLogix Safety Controller 1768-L73S V24 or later

Logix Ethernet Bridge 1756-EN2T

GuardLogix Safety System Configuration and Wiring Verification

Test Step Verification Pass/Fail Changes/Modifications

1Verify that the safety system has been designed in accordance with the GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099.

2Verify that the safety application program has been designed in accordance with the GuardLogix Application Instruction Safety Reference Manual, publication 1756-RM095.

3Visually inspect the safety system network and verify that the I/O is wired as documented in the schematics.

4Visually inspect the Logix Designer application program to verify that the safety system network and I/O module configuration is configured as documented.

Verification and Validation Checklist

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

6A-274NHP Safety Reference Guide > Safety Function Documents: GL

Page 17: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

GuardLogix Safety System Configuration and Wiring Verification cont.

Test Step Verification Pass/Fail Changes/Modifications

5

Visually inspect the Logix Designer application program to verify that suitable safetycertified instructions are utilized. The logic must be readable, understandable, and testable with the aid of clear comments.

6All input devices are qualified by cycling their respective actuators. Monitor the status in the Controller Tags window of the Logix Designer application.

7All output devices are qualified by cycling their respective actuators. Monitor the status in the Controller Tags window of the Logix Designer application.

Normal Operation Verification - The GuardLogix safety system properly responds to all normal Start, Stop, and Reset commands.

Test Step Verification Pass/Fail Changes/Modifications

1

Initiate a Start command. The PowerFlex 527 drive safe torque-off (STO) feature should energize for a normal machine run condition. Verify proper machine status indication and safety application program indication.

2

Initiate a Stop command. The PowerFlex 527 drive STO feature should de-energize for a normal machine stop condition. Verify proper machine status indication and safety application program indication.

3

While the system is running, place a demand on the sensor subsystem. The PowerFlex 527 drive STO feature should de-energize for a normal safe condition. Verify proper machine status indication and safety application program indication. Repeat for all sensor subsystems.

4

While the system is stopped with the sensor subsystems in a safe state, initiate a Start command. The PowerFlex 527 drive STO feature should remain de-energized for a normal safe condition. Verify proper machine status indication and safety application program indication.

5

While the system is stopped with the sensor subsystems in a safe state, initiate a Reset command. The PowerFlex 527 drive STO feature should remain de-energized. Verify proper machine status indication and safety application program indication

Verification and Validation Checklist

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

6A-275NHP Safety Reference Guide > Safety Function Documents: GL

Page 18: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

GuardLogix Controller and Network Tests

Test Step Validation Pass/Fail Changes/Modifications

1

While the system is running, remove the EtherNet/IP network connection between the PowerFlex 527 drive and the controller. The PowerFlex 527 drive STO feature should deenergize. Verify proper machine status indication and I /O connection status in the safety application program.

2Restore the EtherNet/IP connection and allow time to reestablish communication. Verify that the PowerFlex 527 drive STO feature does not automatically energize.

3

While the system is running, switch the controller out of Run mode. The PowerFlex 527 drive should de-energize. Return the controller to Run mode. The PowerFlex 527 drive STO feature should remain de-energized. Verify proper machine status indication and safety application program indication.

Safety Output Tests

Test Step Validation Pass/Fail Changes/Modifications

1

Initiate a Safety Reset command. The PowerFlex 527 drive STO feature should energize for a normal machine run condition. Verify proper machine status indication and safety application program indication.

Verification and Validation Checklist

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

In addition to the verification and validation steps provided here, consult the application technique for your input subsystem for the steps required to validate the input device. For the input subsystem example used in this safety function application technique, we reference GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029.

6A-276NHP Safety Reference Guide > Safety Function Documents: GL

Page 19: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

Document Description

GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099

Describes the GuardLogix 5570 controller system. Provides instructions on how to develop, operate, or maintain a GuardLogix 5570 controller-based safety system that uses the Studio 5000 Logix Designer application, version 21 or later.

GuardLogix Application Instruction Safety Reference Manual, publication 1756-RM095

Describes the Rockwell Automation GuardLogix Safety Application Instruction Set. Provides instructions on how to design, program, or troubleshoot safety applications that use GuardLogix controllers.

GuardLogix: Safety Gate Application with SensaGuard Switch Safety Application Example, publication SAFETY-AT029

Provides instructions on how to wire, configure, and program a Compact GuardLogix® controller and POINT Guard I/O module to monitor a SensaGuard switch mounted on a door.

PowerFlex 527 Adjustable Frequency AC Drive User Manual, publication 520-UM002

Provides detailed information on how to install, configure, operate, and maintain a PowerFlex 527 adjustable frequency AC drive.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines on how to install a Rockwell Automation® industrial system.

Safety Products Catalog, publication S117-CA001 website http://www.rockwellautomation.com/rockwellautomation/catalogs/overview.page

Provides information about Rockwell Automation safety products.

Product Certifications website, available from the Product Certifications link on http://www.ab.com

Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley® distributor or Rockwell Automation sales representative.

Additional Resources

These publications contain additional information concerning related products from Rockwell Automation

Safety Function Documents: GuardLogixSafety Function: Actuator Subsystems Products: GuardLogix Controller, PowerFlex 527 Drive

Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008

6A-277NHP Safety Reference Guide > Safety Function Documents: GL

Page 20: NHP SAFETY REFERENCE GUIDE...Safety Rating: CAT. 4, PLe to ISO 13849-1: 2008 Topic Page Important User Information 2 General Safety Information 3 Introduction 3 Safety Function Realization:

The information contained in this and any related publications is intended as a guide only. Every care has been taken to ensure that the information given is accurate at time of publication.

Neither NHP nor any of the manufacturers portrayed in this and any related publications accept responsibility for any errors or omissions contained therein nor any misapplications resulting from such errors or omissions.

Risk assessments should be conducted by authorized persons. The purchaser and installer are responsible for ensuring the safety system(s) incorporating these products complies with all current regulations and applicable standards.

Products are subject to change without notice and may differ from any illustration(s) provided. All products offered for sale are subject to NHP standard Conditions of Sale, a copy of which is available on application.

Safety Function Document

Disclaimer

6A-278NHP Safety Reference Guide > Safety Function Documents: GL