notifier am2000n specification

2
D-197.1-AM2000N-ENG Rev. A.4 06/2011 ANALOGUE CONTROL PANEL AM2000 DESCRIPTION AM2000N is a microprocessor analog control panel for fire alarm systems management, developed in compliance with EN-54.2 and EN-54.4 regulations. This control panel has 2 analog loops that can manage 99 detectors and 99 modules each, for a total of 198 detectors and 198 i/o modules. The control panel is also programmable through PK2000 pc software, that allows: configuration, storing and printing. Available, on request, with MODBUS protocol. MAIN FEATURES Microprocessor-based system 2 analogue communication loops Each line can manage 99 detectors + 99 input/output modules Graphic backlit LCD display 8 lines, 40 columns (240X64 dots). 2 serial interfaces in standard version: - 1 RS-485 interface to connect up to 16 repeaters LCD6000N/T and LCD6000A; - 1 RS-232 interface predisposed for PK software. 4 access levels designed according to EN-54.2 and EN.54.4 standards. 3 password levels (Operator - Maintenance - Configuration). Configurable descriptions: 32 characters for point; 32 characters for zone description. 150 physical zones and 400 logic groups. User-programmable CBE (Control-by-event) equations to program actions to be performed, using logic operators (And-Or-Xor-Delay-etc.). History log 999 events in non volatile memory. Real time watch. Self loop configuration with self device recognition. Software functions configurations for in field devices. Auto-recognition of points with the same address. Alarm and fault management. Programmable detectors alarm threshold. Detector clean alarm signalling. Low sensitivity detector signalling. Automatic night/day mode. WalkTest function for each zone. Keyboard with specific function keys: evacuation, delay reset, buzzer mute, sounder silence/restore, reset. Alphanumeric keys for in field configuration. OUTPUTS Supervised sounders output. Voltage free contacts relay output: - general alarm; - general fault. POWER SUPPLY Control panel is powered by mains and in mains fault condition it will continue normal operation, thanks to batteries. Mains requirements: Voltage: 230 Vac single-phase -15% ÷ +10%. Frequency: 50 / 60Hz. Current: 0,5 A. Power supply 24Vcc (27.6Vdc -10% ÷ +2% ripple max. 100mVpp) 2,1A tot, (panel’s power, user output, power supply for analog devices on loop). User output for auxiliary loads; in example: bells, sounders, etc. Battery charger: - Output voltage: 27,6Vdc - Output current: 1A - ripple max 100m Vpp (with temperature compensation) - Batteries: 2 x 12V 18 Ah max. - Signalling: Low batteries, charger fault, battery fault. ENVIRONMENTAL FEATURES Temperature range: - 5° C + 40° C. Humidity: 10 93 % (without condense). Stock temperature: - 10° C + 50° C. MECHANICAL FEATURES Weight: 6 Kg. Dimensions: 267 x 483 x 111 mm.

Upload: deena-mcgee

Post on 27-Dec-2015

213 views

Category:

Documents


3 download

DESCRIPTION

Notifier AM2000N Brochure and Technical SpecificationEnglish languageRemote panels list

TRANSCRIPT

Page 1: Notifier AM2000N Specification

D-197.1-AM2000N-ENG Rev. A.4 06/2011

ANALOGUE CONTROL PANEL

AM2000

DESCRIPTION AM2000N is a microprocessor analog control panel for fire alarm systems management, developed in compliance with EN-54.2 and EN-54.4 regulations. This control panel has 2 analog loops that can manage 99 detectors and 99 modules each, for a total of 198 detectors and 198 i/o modules. The control panel is also programmable through PK2000 pc software, that allows: configuration, storing and printing. Available, on request, with MODBUS protocol. MAIN FEATURES ■ Microprocessor-based system ■ 2 analogue communication loops ■ Each line can manage 99 detectors + 99

input/output modules ■ Graphic backlit LCD display 8 lines, 40 columns

(240X64 dots). ■ 2 serial interfaces in standard version:

- 1 RS-485 interface to connect up to 16 repeaters LCD6000N/T and LCD6000A; - 1 RS-232 interface predisposed for PK software.

■ 4 access levels designed according to EN-54.2 and EN.54.4 standards.

■ 3 password levels (Operator - Maintenance - Configuration).

■ Configurable descriptions: 32 characters for point; 32 characters for zone description.

■ 150 physical zones and 400 logic groups. ■ User-programmable CBE (Control-by-event)

equations to program actions to be performed, using logic operators (And-Or-Xor-Delay-etc.).

■ History log 999 events in non volatile memory. ■ Real time watch. ■ Self loop configuration with self device

recognition. ■ Software functions configurations for in field

devices. ■ Auto-recognition of points with the same address. ■ Alarm and fault management. ■ Programmable detectors alarm threshold. ■ Detector clean alarm signalling. ■ Low sensitivity detector signalling. ■ Automatic night/day mode. ■ WalkTest function for each zone. ■ Keyboard with specific function keys: evacuation,

delay reset, buzzer mute, sounder silence/restore, reset.

■ Alphanumeric keys for in field configuration.

OUTPUTS ■ Supervised sounders output. ■ Voltage free contacts relay output:

- general alarm; - general fault.

POWER SUPPLY Control panel is powered by mains and in mains fault condition it will continue normal operation, thanks to batteries. Mains requirements: ■ Voltage: 230 Vac single-phase -15% ÷ +10%. ■ Frequency: 50 / 60Hz. ■ Current: 0,5 A. ■ Power supply 24Vcc (27.6Vdc -10% ÷ +2%

ripple max. 100mVpp) 2,1A tot, (panel’s power, user output, power supply for analog devices on loop).

■ User output for auxiliary loads; in example: bells, sounders, etc.

■ Battery charger: - Output voltage: 27,6Vdc - Output current: 1A - ripple max 100m Vpp

(with temperature compensation) - Batteries: 2 x 12V 18 Ah max. - Signalling: Low batteries, charger fault,

battery fault. ENVIRONMENTAL FEATURES ■ Temperature range: - 5° C + 40° C. ■ Humidity: 10 93 % (without condense). ■ Stock temperature: - 10° C + 50° C. MECHANICAL FEATURES ■ Weight: 6 Kg. ■ Dimensions: 267 x 483 x 111 mm.

Page 2: Notifier AM2000N Specification

D-197.1-AM2000N-ENG Rev. A. 4 06/2011

ANALOGUE CONTROL PANEL

AM2000

SISTEMA GESTIONE QUALITÀ E AMBIENTE

CERTIFICATI UNI EN ISO 9001:2008

UNI EN ISO 14001:2004

NOTIFIER ITALIA S.r.l. - A socio unico - 20097 San Donato Milanese (Ml) - Via Grandi, 22 - Tel.: 02/518971 - Fax: 02/5189730 - E-mail: [email protected] Capitale Sociale € 2.700.000,00 i.v. - C.C.A.A. 1456164 - Trib. Milano Reg. Soc. 348608 - Vol. 8549 Fasc. 8 - Partita IVA IT 11319700156 (informativa privacy art. 3 Digs 196/03) - Ufficl Regionali: 10143 Torino – Corso Potenza, 6 - Tel.: 011/0650611 - Fax: 011/4531183 - E-mail: [email protected] - 35010 Limena (PD) Via IV Novembre, 6/c Int. 9 - Tel.: 049/7663511 - Fax: 049/7663550 - E-mail: [email protected] - 40050 Funo di Argelato (BO) - Asta Servizi, Bl. 3B, Gall. B n. 85, Centergross - Tel.: 051/864855 - Fax: 051/6647638 - E-mail: [email protected] - 50136 Firenze –Via Aretina, 167/M Tel/Fax: 055/289177 - 00118 Roma - Via Del Casale Santarelli, 51 - Tel.: 06/7988021 - Fax: 06/79880250 - E-mail: [email protected] - 80143 Napoli - Palazzo Prof. Studi - Centro Direzionale, Isola E2, Scala B, Piano 5° - Tel.: 081/7879398 - Fax: 081/7879159- E-mail: [email protected] - 70125 Bari - Via Delia Costituente, 29 - Tel.: 080/5013247 - Fax: 080/5648114 - E-mail: [email protected] - 95128 Catania - Viale Alcide De Gasperi, 187 - Tel.: 095/7128993 - Fax: 095/7120753 - E-mail: [email protected]

www.notifier.it

Tutti i dati sono soggetti a cambiamento senza preavviso. Tutti i diritti di questa pubblicazione sono riservati.

PK2000 PK2000 is a PC software for AM2000N control panel, and allows to: ■ Transfer and show control panel’s configurations on

PC. ■ Transfer programs from PC to control panel. ■ Create and manage a file-archive with

configurations, editable in any moment and transferable to the control panel

The programming functions that can be realized by using this software are the same the user can carry out working on the control panel. PK software is Windows XP compatible. The communication between control panel and PC is realized through RS232 serial port. OPTIONAL BOARDS SIB600W: Microprocessor-based communication board for new concentration system. SIB600W is equipped with Ethernet port (LAN TCP/IP) and USB port for PC and printer. SIB600W is linkable with all compatible external devices. SIB600OEM: Microprocessor-based communication board, endowed with an RS232/485 output for connection with NOTI-FIRE-NET-2000N with CEIABI protocol or MODBUS on request (only for fire system).

LCD PANELS REPEATER Remote panels with LCD display for NOTIFIER AM Series remote management. Panels and annunciator are endowed with backlit graphic LCD display 320x240 dots. Repeaters are characterized by high brightness and contrast that assure clear view in any light environment condition. The connection with panels is performed by RS-485 connection. LCD-6000-N Fire repeater. LCD-6000-N is endowed with seven keys that allow navigation through different menus and execution of system management functions: silent, reset, disablement and lamp test. LCD-6000-A Zone programmable repeater.

LCD-6000-A shows active panel events with relative devices or zones. The zone displayed are configured by PC with PK software.

LCD-6000-T Technologic alarm repeater and Gas detection. Specific to display gas detection related events and 420mA technologic events. LCD-6000-T is equipped with 3 additional LEDs for pre-alarm and alarm levels.