novigo - eu.bt-pip.com€¦ · public address and voice evacuation system • modern digital system...

16
siemens.com/buildingtechnologies Novigo Advanced Public Address and Voice Evacuation System Creating Perfect Places

Upload: others

Post on 20-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

siemens.com/buildingtechnologies

NovigoAdvanced Public Address and Voice Evacuation System

Creating Perfect Places

Page 2: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

2

An essential element of ensuring safety of lives is the ability to manage a phased and orderly evacuation in the event of an emergency.

The Novigo voice alarm system from Siemens not only offers full compliance with the relevant legal standards across multi-level, multi-occupancy estates, but also operates as an advanced public address system.

Novigo delivers high performance in automated and live messaging

Time as a key factor for evacuation

Page 3: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

3

Modular Architecture

The Novigo platform is a sophisticated audio streaming voice system, suitable for the most challenging voice applications.

Novigo is highly scalable and tested in accordance with European standard EN 54-16 and meets relevant local codes of practice for installation. The solution is fully configurable with the capacity to extend to 4,000 network nodes; it can be split into zones to ensure appropriate messaging across particular areas and is fully capable of integration to third party systems.

During an emergency people are immediately notified about the nature of the incident and the appropriate action they need to take. These live or recorded messages reduce the potential for panic or confusion when an alarm is sounded, as the messaging is clear, informative and controlled.

Importantly, sound quality is excellent for both automatic and live messaging, as well as for any selected background music.

Public Address and Voice Evacuation System

• Modern digital system for managing alarm situations to immediately alert personnel

• Enables controlled emergency evacuation

• Choice of live and recorded messaging

• Multiple channels of digital audio offering studio sound quality

• Up to 4,000 devices on the network and 16,000 loud-speaker lines

• Remote access via cRSP enabling cost effective remote maintenance and remote operation

• Multiple interfaces to fire detection and security systems

• Redundant configuration means no single point of failure and continuous monitoring of all relevant components

• Controlled via intuitive, configurable touch screen GUI

• Operation via smart phone application, e.g. adjustment of volume levels and audio sources

• Decentralized audio system with no single point of failure

• Significant storage capacity for messaging and music files

• No latency for live applications

Page 4: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

4

Novigo is an Ethernet-based digital audio network.

Signals from audio frequency (AF) sources are digitized and fed into the network. Conversely, digital audio streams can be taken at any point from the network, and prepared for analog processing.

Technical Overview

4

Novigo: Network

The Novigo system consists of multiple components including audio network modules, intercoms, keypads and amplifiers. Loudspeaker lines can be connected at each audio network module.

The individual system units are interconnected via a 100 MBit copper or fiber network via a switch (such as PN2001) and different topologies are possible within the network.

Audio and control signals are transmitted via the same network connection, with a capacity of up to 4,000 devices.

Novigo allows up to 64 audio streams in studio quality (48 kHz/24-bit with a constant latency of 1.3 ms at all exits) via the Ethernet-based network. Other settings for more channels at lower audio quality are also available.

Novigo: Technical Features

• For intuitive operation networkable keypads (station, panel PC, remote control unit etc.) are available.

• Utilizes certified network switches, power supplies and real-time configuration software.

• Comprehensive Digital Signal Processing (DSP).

• Integration of pro-sound applications, standard speakers available.

• PC-based real-time operation and configuration.

• Real-time configuration via the system software.

Page 5: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

55

Novigo™ Control Systems

Audio source

Novigo™ Network

Management Systems

4 AF inputs

4 AF outputs

8 I/O contacts 4 supervised loudspeaker lines

8 analog inputs 0 – 10 V2 Ethernet 100Base-TX connections

Fire service call stationsand desk stations

2 AF inputs 2 supervised audio outputs 4 digital in- and 6 digital outputs1 Micro-SD slot for text messages 2 Ethernet 100Base-TX connections

Novigo™ AC-Net Module (4/4)

4 AF inputs

4 AF outputs

16 supervised loudspeaker lines 8 I/O contacts

8 analog inputs 0 – 10 V2 Ethernet 100Base-TX connections

Novigo™ AC-Net Matrix (16)

Novigo™ Amplifier

Novigo™ Amplifier

4 AF outputs

4 supervised loudspeaker linesDSP per audio output 8 I/O contacts8 analog inputs 0 – 10 V2 Ethernet 100Base-TX connections

Novigo™ AC-Net Module(0/4)

Sinteso™ FC20

EOLEOL

EOLEOL

EOLEOL

EOLEOL

EOLEOL

EOLEOL

Sta

ndar

d I/F

——! —

Emergency Mode

Novigo can be used as an automatic or manual evacuation system.

Studies reveal that many people do not react to conven-tional alarms such as bells or sirens. Many assume that it is a test or false alarm; others are confused and unsure of what action to take.

In the event of a fire or major alert, rapid and orderly evacuation is the highest priority. Novigo communicates clear messages about the nature of the incident and the next course of action using clear language, minimizing the potential for panic or confusion.

• Fire announcements

• Evacuation instructions

• Warnings

Standard Mode

Novigo can be used as a simple public address system for instant transmission of information as well as for background music.

• Live broadcasts for delivering information on organizational activities and relevant announcements

• Pre-recorded communications such as advertising and marketing campaigns, including messaging in different languages

• Continuous music to create a certain environment that can be interspersed with live broadcasts

Page 6: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

6

Corporate Offices

Airports

Railway Stations

Shopping Centers

Hospitals

University Campuses

Hotels

Manufacturing Plants

Event Venues

Stadiums

6

Novigo combines the highest safety standards with advanced audio and the latest networking technologies. All audio network modules and control points, as well as the common network, have been designed in accordance with EN 54-16 approval requirements. Novigo can be scaled from a standalone to a wide area system.

Page 7: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

77

System Components

Station types PC2001 PC2002 PC2003

Product image

Housing type Dimensions (H x W x D mm)

19", 1HE 482 x 44 x 180

19", 1HE 482 x 44 x 180

19", 1HE 482 x 44 x 357

Weight 3.1 kg 3.0 kg 8.5 kg

AF inputs 0 dB 4 0 4

AF inputs 100 V 4 4 4

AF outputs 0 dB (amplifier/ external)

4 4 4

AF outputs 100 V (supervised loudspeaker lines)

4 4 16

Analog measurement inputs 0..10 V 8 8 0

Digital inputs 8 8 8

Digital outputs 8 8 8

Fault relay Potential-free contact, max. 48V AC/DC / 500 mA

Serial interfaces 1 x RS232 / RS485 1 x RS232 / RS485 1 x RS232 / RS485

Ethernet port 100Base-TX 2 x RJ45 2 x RJ45 2 x RJ45

LC Display Yes Yes No

Power supply 24 VDC 24 VDC 24 VDC

Current consumption 0.3...0.37 A 0.3...0.37 A 0.5...5 A

Audio features 64 audio channels, sample rate 48 or 96 kHz, resolution 16 / 24 / 32 Bit, fixed latency of 0.6 / 1.3 / 2.6 ms, frequency 20 Hz - 20 kHz, dynamic > 100 dB

Audio processing on inputs (DSP) Leveler, compressor, limiter, equalizer –

Leveler, compressor, limiter

Audio processing on each audio output

Leveler, compressor, limiter, equalizer, automatic volume control, delay up to 24.5 seconds

Automatic volume control 4 4 4

Voice memory Optional 2 GB Micro SD card (for example for alarm messages of up to three hours)

Network Switched Ethernet IEEE802.3u100 MBit/s full duplex OSI Layer 2; OSI Layer 3 (UDP/IP) in preparation

Comparative Overview of the Audio Network Modules

The audio network modules represent a central feature of Novigo. A comparison of the technical characteristics of these components can be seen in the table below.

Page 8: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

88

Individual Components at a Glance

Digital Audio Modules

PC2001

PC2001 AC-Net Module (4/4)

Ethernet-based multi-channel audio system for alarming applications. It has the following functions:

• 4 AF inputs (line/mic), 4 AF outputs• 4 AF inputs (100 V), 4 AF outputs (100 V)• 8 Digital control I/Os, 8 analog inputs• Ethernet interface (TCP/IP), serial ports (RS232, RS485) etc. to control the systems, and for

remote maintenance and remote monitoring• Real-time audio transmission and integrated real-time recorder for delayed announcements• Integrated Micro-SD Card reader/writer for a memory card of max. 2 GB• Line monitoring by the EOL module PCA2004• Status display on the front for the most important system states

PC2002

PC2002 AC-Net Module (0/4)

Ethernet-based multi-channel audio system for alarming applications. It has the following functions:

• 4 AF outputs • 4 AF inputs (100 V), 4 AF outputs (100 V)• 8 Digital control I/Os, 8 analog inputs• Ethernet interface (TCP/IP), serial ports (RS232, RS485) are available connectivity options

to control the systems, and for remote maintenance and remote monitoring• Real-time audio transmission and integrated real-time recorder for delayed announcements• Integrated Micro-SD Card reader/writer for a memory card of max. 2 GB• Line monitoring by the EOL module PCA2004• Status display on the front for the most important system states

PC2003

PC2003 Novigo AC-Net Matrix (16)

Ethernet-based multi-channel audio system for alarming applications. It has the following functions:

• 4 AF inputs (line/mic), 4 AF outputs• 4 AF inputs (100 V), 16 AF outputs (100 V)• 8 Digital control I/Os, 8 analog inputs• Ethernet interface (TCP/IP), serial ports (RS232, RS485) are available connectivity options

to control the systems, and for remote maintenance and remote monitoring• Real-time audio transmission and integrated real-time recorder for delayed announcements• Integrated Micro-SD Card reader/writer for a memory card of max. 2 GB• Line monitoring by the EOL module PCA2004• Status LEDs on the front for the most important system states

Page 9: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

99

Individual Components at a Glance

Switches

PN2001

PN2001 AC-Net Switch (2x4/2)

Ethernet switch used to connect the individual components in the network.

• 2 x 4 x 10/100 Mbps Fast Ethernet Port (RJ45)• 2 x 100Base-FX Port (802.3u 100Base-FX-compliant fiber multimode interface)• LED status lights on the front panel

PN2002

PN2002 AC-Net Switch (1x8/2)

• Switch for data transmission• 8 ports for 10/100/1000Base-T RJ45 connections, 2 ports for 100/1000Base-SX SFP fiber

optic interface• Connections for redundant power supply with reverse polarity protection• LED status lights• Temperature range: -40 ... + 75 °C

PN2003

PN2003 AC-Net Switch FOI SM

• Interface for data transmission via fiber optic cable• For distances up to 10,000 meters • Protocol: IEEE 802.3z• Single mode• SFP Port

PN2004

PN2004 AC-Net Switch FOI MM

• Interface for data transmission via fiber optic cable• For distances up to 550 meters • Protocol: IEEE 802.3z• Multimode• SFP Port

Page 10: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

1010

Individual Components at a Glance

Stations

PT2001

PT2001 AC-Net desk station

The desk mounted microphone is used to control and monitor the system, and includes the following features:

• 19 freely configurable keys (for individual labeling)• Monitored microphone• Built-in speaker• 1 additional AF input (Line / Mic), 1 additional AF output• 4 digital inputs, 6 digital outputs• 2-line text display• Real-time audio transmission and integrated real-time recorder for delayed announcements• Integrated Micro-SD Card reader/writer for a memory card of max. 2 GB• Ethernet (TCP/IP) interface for connection to a superior management system

PTO2001

PTO2001 AC-Net desk station button extension (24 buttons)

PTO2001 is an extension of the PT2001 desk station with 24 programmable buttons. With a maximum of four extensions, the desk station can be expanded to a total of 115 keys.

PTO2002

PTO2002 AC-Net desk station extension (key switch)

Available in some European countries as an extension of PT2001. In the UK and Switzerland, the key switch 'Kaba' (FTO2005 - C1) is used, and in Denmark, Norway, Sweden and Finland, the 'Nordic' key switch (FTO2006 - B1) is used. The key switch allows for a release of all keys, which can be used to trigger or stop an alarm (enable "operating level 2").

PT2002

PT2002 Fire service call stations (AT), Austrian local code of practice

The fire service interface PT2002 (in compliance with ÖNorm F 3033) offers the possibility of playing stored alarms and evacuation messages.The fire service has the highest priority. Once the alarm or intercom button has been pressed, all other signals are interrupted in the building. Live announcements are possible using the integrated hand-held microphone.

• Steel case (lockable, red)• Dynamic handheld microphone with talk button• Built-in speaker• Integrated Micro-SD Card reader/writer• Alarm message keys• Displays for alarm, operation and fault

Page 11: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

1111

Individual Components at a Glance

Control Panels

PT2004

PT2004 System Status Indicator (19")

Status messages of the system are highlighted visually and acoustically on the system status display. At the front, the color-coded visual indicators display the operational status, including fault and voice alarms. If a fault occurs, an acoustic warning tone plays – this can be acknowledged via a button. The system status indicator is mounted in the network cabinet.

PT2005

PT2005 Alarm Panel (19")

The alarm panel is used to manually trigger a voice alarm. It has various buttons and LEDs at the front, which have the following functions:

• 'Initiate' manually triggers a voice alarm, with built-in LED (red light)• 'Reset' manually resets a voice alarm• 'Silence' mutes a voice alarm, with built-in LED (green light)• 'Fault Indication Reset' acknowledges an alarm message

The alarm control panel is mounted in the control cabinet.

PT2006

PT2006 Remote Control Panel

PT2006 is a control panel for program selection, output zone selection and volume control. The panel has a mounting frame and can be mounted in a flush-mounted socket. Over the RS-485 interface, up to 16 panels can be connected to the audio network modules PC2001, PC2002 or PC2003. A 4-pin wiring is required (power supply is carried).

PT2007

PT2007 System Status Indicator

The system status indicator PT2004 is available in a smaller design for panel mounting.

Status messages of the system are highlighted visually and acoustically on the system status display. At the front, the color-coded visual indicators display the operational status, including fault and voice alarms. If a fault occurs, an acoustic warning tone plays – this can be acknowledged via a button.

Page 12: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

12

Power Amplifiers

PA2001

PA2001 Power Amplifier (2x250 W)

The power amplifier PA2001 enhances audio signals in the network and is installed in the control cabinet. The control LEDs are located on the front and the volume controls are located on the back. The power amplifier has a maintenance-free cooling system without fans. In addition, the device is equipped with protection circuits against open circuit, short circuit, over temperature and over current.

• 2 AF inputs• 2 x 250 watts (1 x 500 watts in bridge mode) output power• 230 V AC and 24 V DC power supply

PA2003

PA2003 Power Amplifier (4x150 W)

The power amplifier PA2003 enhances audio signals in the network and is installed in the control cabinet. The control LEDs are located on the front and the volume controls are located on the back. The power amplifier has a maintenance-free cooling system without fans. In addition, the device is equipped with protection circuits against open circuit, short circuit, over temperature and over current.

• 4 AF inputs• 4 x 150 watts (2 x 300 watts in bridge mode) output power• 230 V AC and 24 V DC power supply

PA2007

PA2007 Power Amplifier (1x250 W)

The power amplifier PA2007 enhances audio signals in the network and is installed in the control cabinet. The control LEDs are located on the front and the volume controls are located on the back. The power amplifier has a maintenance-free cooling system without fans. In addition, the device is equipped with protection circuits against open circuits, short circuits, over temperatures and over currents.

• 1 AF input• 1 x 250 watts output power• 230 V AC and 24 V DC power supply

Power Supply

PP2001

PP2001 Power Supply (19", 288 / 3.600 W)

The PP2001 power supply provides enough power for the connected 24 V consumers in the system. This power supply allows simultaneous charging and monitoring of two lead-acid batteries up to 220 Ah (including protection against discharge).

Individual Components at a Glance

Page 13: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

13

Individual Components at a Glance

Extras

PCA2001

PCA2001 Ground Fault Monitoring Module (24 V)

The PCA2001 is a component for remote ground fault monitoring, safety-relevant components such as fire and security stations as well as control panels.

PCA2002

PCA2002 Micro SD-Card (industrial)

The 2 GB Micro-SD memory card serves as a voice storage for alarm messages. It has a capacity to store a duration of approximately 3 hours of audio.

The card meets the high quality standards for industrial use.

PCA2004

PCA2004 End-of-Line Module EOL3 (active)

The PCA2004 end-of -line module allows for flexible speaker line configuration. Several branched speaker lines can be monitored and can be used to achieve cable monitoring up to an individual speaker.

PCA2007

PCA2007 AVC Microphone

The PCA2007 is a microphone designed specifically for use with the audio network modules PC2001, PC2002 or PC2003. It is used for automatic volume control of background music and announcements, and takes the prevailing ambient sound into account. The PCA2007 provides a great solution for ambient noise sensing and compensation controller (ANS) applications.

Page 14: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

14

Extras

PCA2008

PCA2008 AVC Monitor

The PCA2008 is a surveillance component which monitors the performance (short circuit and interruption) of up to four microphones. Furthermore, the summation of up to four microphone signals is possible, so that, for example, the sum can be used in four spatially distributed microphones as a measure of the volume control.

PCA2009

PCA2009 Power Supply 24 V / 5 A

The 230 V AC power supply with an output voltage of 24 V DC is used as an optional power supply of AC-Net modules PC2001, PC2002 and PC2003.

PCA2010

PCA2010 Power Supply 230 V / 24 V / 30 W

The 230 V AC power supply with an output voltage of 24 V DC is used as an optional power supply of AC-Net desk station PT2001.

PCA2011

PCA2011 DC / DC Converter

Accessory for various special applications.

PCI2001

PCI2001 Output Module (8x)

The PCI2001 allows an extension of the existing digital outputs by 8 relay outputs. The maximum permissible switching current is 7 A / 24 V per relay.

Individual Components at a Glance

Page 15: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

15

Individual Components at a Glance

19“ Network Cabinet

Rittal TS8

Rittal TS8 (42HE)

• Dimensions (H x W x D): 2000 mm x 800 mm x 800 mm• Protection per IEC 60529: IP55• Basic cabinet weight: 100 kg • Fully assembled weight: up to 200 kg• Smaller cabinet sizes are also possible (i.e. custom height x 600 mm x 600 mm)

Page 16: Novigo - eu.bt-pip.com€¦ · Public Address and Voice Evacuation System • Modern digital system for managing alarm situations to immediately alert personnel • Enables controlled

June 2017

Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested performance features are binding only when they are expressly agreed upon in the concluded contract.

© Siemens Switzerland Ltd, 2017

Published by Siemens Switzerland Ltd 2016

Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel +41 41 724 24 24

When building technology creates perfect places – that’s Ingenuity for life.

Never too cold. Never too warm. Always safe. Always secure.

With our knowledge and technology, our products, our solutions and our services, we turn places into perfect places.

We create perfect places for their users’ needs – for every stage of life. #CreatingPerfectPlaces www.siemens.com/perfect-places