Objectives

• Discuss Project Topics

• Learn to design VAV and DOAS System

3D model – Biomedical Engineering (BME) Building

3D model – Biomedical Engineering (BME) Building

3D model – Biomedical Engineering (BME) Building

3D model – Biomedical Engineering (BME) Building

VAV Example

http://www.trane.com/commercial/library/vol242/v24b6.asp

-One system

-Multiple Spaces/Zones

- VAV box for each space/zone

VAV System Terms & Equations(you can find them in ASHRAE Standard 62)

• Fraction of minimum outdoor air in space/zone supply airXi = VOAi / VSAi

• Critical space

Space with maximum Xi , Z=max(Xi)

• Fraction of outdoor air in system supply air

X = sum(VOA ) / sum(VSA)

• Required Fraction of outdoor air:

Y=X/(1+X-Z)

Example Solution

Space1 Space 2 Space 3 Space 4

VSA

VOA

Xi

X

Z

Y

Other Issues Related to VAV

• Fan control

• Minimum supply air

• Occupancy sensors

DOAS System

• http://doas.psu.edu/

Enthalpy wheel

Desiccant wheel

Figure 3 – A desiccant-based cooling system combined with regenerative heat exchanger, vapor compression cooling, and evaporative humidifier (hybrid system).

HVAC ControlExample 1:

Economizer (fresh air volume flow rate control)

mixing

damper

fresh air

T & RH sensors

recirc. air

Controlled device is damper

- Damper for the air - Valve for the liquids

Economizer Fresh air volume flow rate control

mixing

damper

Fresh(outdoor) air

T & RH sensors

Recirc. air

% fresh air

Minimum for ventilation

100%

TOA (hOA)

enthalpy

Economizer – cooling regime

How to control the fresh air volume flow rate?

% fresh air

Minimum for ventilation

100%

If TOA < Tset-point → Supply more fresh air than the minimum required

The question is how much?

Open the damper for the fresh air

and compare the Troom with the Tset-point .

Open till you get the Troom = Tset-point

If you have 100% fresh air and your still need cooling use cooling coil.

What are the priorities: - Control the dampers and then the cooling coils or - Control the valves of cooling coil and then the dampers ?

Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer

Economizer – cooling regime

Example of SEQUENCE OF OERATIONS:

If TOA < Tset-point open the fresh air damper the maximum position

Then, if Tindoor air < Tset-point start closing the cooling coil valve

If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-point Other variations are possible

HVAC ControlExample 2:

Dew point control (Relative Humidity control)filter

fancooling coil

heating coil

filter

mixing

damper fresh air

T & RH sensors

We either measure Dew Point directly or T & RH sensors substitute dew point sensor

Humidity generationHeat gains

We should supply air with lower humidity ratio (w) and lower temperature

Relative humidity control by cooling coil

TDP

Mixture

Cooling Coil

RoomSupply

Heating coil

Relative humidity control by cooling coil (CC)• Cooling coil is controlled by TDP set-point

if TDP measured > TDP set-point → send the signal to open more the CC valve

if TDP measured < TDP set-point → send the signal to close more the CC valve

cooling coil

heating coil

mixing

Fresh air

Tair & TDP sensors

Control valves

• Heating coil is controlled by Tair set-point

if Tair < Tair set-point → send the signal to open more the heating coil valve

if Tair > Tair set-point → send the signal to close more the heating coil valve

Sequence of operation(ECJ research facility)

Control logic:

Mixture in zone 1: IF (( TM<TSP) & (DPTM<DPTSP) ) heating and humidifying Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heatingHumidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA)

decrease humid.

Mixture in zone 2: IF ((TM>TSP) & (DPTM<DPTSP) ) cooling and humidifying Cool. coil cont.: IF (TSP<TSA) increase cooling or IF (TSP>TSA) decrease

coolingHumidifier: IF (DPTSP>DPTSA) increase humidifying or IF (DPTSP<DPTSA)

decrease hum.

Mixture in zone 3: IF ((DPTM>DPTSP) ) cooling/dehumidifying and reheatinCool. coil cont.: IF (DPTSP>DPTSA) increase cooling or IF (DPTSP<DPTSA)

decrease cooling Heater control: IF (TSP>TSA) increase heating or IF (TSP<TSA) decrease heating

Set Point (SP)

Mixture 2

Mixture 3

Mixture 1

DBTSP

DPTSP