okoguard-okolon@ ts-cpe type rhh or rhw-2 or use-2, vw … data sheet.pdfokoguard-okolon ts-cpe 600...
TRANSCRIPT
A--_-lIu
B --=----I~I
A Uncoated. Copper ConductorB Composite Okoguard/Okolon
TS-CPE Insulation
Product DataSection 3: Sheet 1
Okoguard-Okolon@ TS-CPE Type RHHor RHW-2 or USE-2, VW-1, FT-4, CSA RW-90600V Power and Control Iij:\ ~Copper Conductor/90°C Wet or Dry ~ ~For Cable Tray Use-Sunlight Resistant-For Direct Burial
Composite InsulationOkoguard-Okolon TS-CPE is Okonite's tradename for its composite insulation systemconsisting of a layer of EPR and coveredwith a chlorinated polyethylene (CPE)thermoset compound.
The advantages of Okoguard EPR, with aproven track record of over 40 years as amedium voltage insulation, are now offeredin low voltage cables, Okolon TS-CPE isOkonite's trade name for its chlorinated poly-ethylene (CPE) thermoset compound.
ApplicationsOkoguard-Okolon TS-CPE 600 Volt Powerand Control Cables are recommended foruse in all low voltage circuits where continu-ity of service is the prime consideration.These cables may be installed in wet or drylocations, indoors or outdoors, in raceways,underground ducts, directly buried in theearth, or lashed to a messenger for aerial in-stallation, These cables may also be in-stalled in cable tray (size 1/0 AWG and largerper NEC 392.2).
SpecificationsConductor: Uncoated soft copper per ASTMB-3. Solid per ASTM B-3. Sizes smaller than#8 are compress stranded per ASTM B-8.Sizes #8 and larger are compact strandedper ASTM B-496.
Insulation: Meets or exceeds all require-ments of ICEA S-95-658, NEMA WC-70 andUL Standards 44 and 854.
Listed by Underwriters Laboratories, Inc. asType RHH or RHW-2 or USE-2, VW-1. Sizes1/0 AWG and larger are also marked sunlightresistant, for use in cable tray.
Listed by CSA as RW-90, -40C, FT1 (1/0and larger: FT4) , sunlight resistant.
Product Features• Sizes 1/0 AWG and larger pass the Ver-tical Tray Flame Test requirements of UL1581 for use in cable tray.
• Passes the IEEE 383 Vertical TrayFlame Test. (sizes #6 AWG and larger)
• Passes the IEEE 1202 Vertical TrayFlame Test. (sizes 1/0 AWG & larger)
• Extreme heat resistance;90°C continuous rating, wet or dry130°C emergency overload rating250°C short circuit rating
• Exceptional resistance to deformationat high temperature.
• Stable electrical properties.
• Low SIC and power factor.
• Low moisture absorption,
• Mechanically rugged.
• Resistant to weather, most oils, acidsand alkalies.
• More flexible, easier to install and termi-natE;·than XLPE insulation.
• UL and CSA Listed.
Composite InsulationThickness (mils)
Conductor Okolon(AWG/kcmil) Okoguard TS-CPE
14-9 30 15
8 45 15
6-2 45 30
1-4/0 55 45
250-500 65 65
750-1000 80 65
Okoguard-Okolon TS-CPE Type RHH or Pr~duct DataRHW-2 or USE-2, VW-1, FT-4, CSA RW-90 Section 3: Sheet 1600V Power and ControlCopper Conductor/90°C Wet or Dry ® 1ftFor Cable Tray Use - Sunlight Resistant - For Direct Burial .L ~
112-24-2061.•. 112-24-2071
112-24-2091
.•. 112-24-2101112-24-2121
.•. 112-24-2131
112-24-2171.•. 112-24-2191.•. 112-24-2221
.•. 112-24-2251
.•. 112-24-2311112-24-2331
.•. 112-24-2351
.•. 112-24-2371112-24-2391
.•. 112-24-2411
.•. 112-24-2431
.•. 112-24-2471
f21
3.303.683.68
0.160.170.18
0.190.200.21
0.230.270.33
0.380.430.52
0.560.600.64
0.700.800.89
4.064.574.57
4.835.085.33
5.846.868.38
5875
119
232532
344649
63 3082 55
130 75
184 95280 130372 150
28 1530 1537 20
39 2051 3054 30
15 2415 2420 30
20 3030 4230 42
30 4850 5565 75
85 97115 130130 156
446 170 150 179539 195 175 204654 225 200 242
805 260 230993 290 255
1320 350 310
278317384
---I,•...••.•.112-24-2531.•. 112-24-2591.•. 112-24-2651
14 114 712 1
45 1.1445 1.1445 1.14
1.011.211.36
9.7511.0013.16
173257340
1827 430 3802690 535 4753568 615 545
Visit Okonite's web site, www.okonite.com, for the most up to date dimensions.
12 710 110 7
45 1.1445 1.1445 1.14
.• Authorized stock item. Available from our Customer Service Centers.
9 198 76 7
45 1.1460 1.5275 1.91
To order a color other than black. change the last digit of thecatalog number as follows:
White 2 Orange 5
Red 3 Blue 6
Green 4 Yellow 7
Example: To order #14/Sol - Red, the catalog number would be112-24-2063.
Bllll00301
77
19
7575
100
1.911.912.54
14.1015.1416.33
414507622
477,598689
(1) Ampacities are based on Table 310.16 of the National Electrical Code forthese 90°C rated conductors at an ambient temperature of 30°C. The 75°Cwet column is provided for additional information.
The ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger. Deratingfor more than three current carrying conductors within a raceway is in accor-dance with NEC Sectiion 310.15.B.2.
(2) Based on three (3) conductors in a single enclosed or exposed conduit. Ca-paci~ies based on 40°C air ambient using ICEA methods. For 30°C ambientmultiply values by 1.10; for 50°C multiply by .90. For other ambients or installa-tion conditions refer to Engineering Data Book EHB.
For ampacities in cable tray, see NEC Section 392.11.B.
If6\\THE OKONITE COMPANY~ Ramsey, New .Jersey 07446
1/0 19 100 2.542/0 19 100 2.543/0 19 100 2_54
4/0250350
193737
100130130
2.543.303.30
500750
1000
376161
130145145
17.6820.3222.61
766938
1265
25.6530.7334.54
175025903391