Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Upload: morris-young

Post on 21-Dec-2015

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

Phase Angle Alarming in ROSE for Steady-State Stability Analysis

Marianna Vaiman V&R Energy

JSIS MeetingSalt Lake City, UT

March 5, 2015

1Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 2: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

V&R’s Approaches to Phase Angle Limit Computation

Phase angle limit should be determined in real time, and not based on historical dataPhase angle limit is a physical limit:– Depends on system topology and conditions;– Depends on how the system is stressed;– The limit changes with system conditions.

Voltage and thermal limits are operating limits:– Depend on the equipment/hardware.

Three types of different phase angle limits:– 1. Based on user-defined scenario-based stressing;– 2. Based on optimal scenario-based stressing;– 3. Based on “natural” direction of system stressing.

Phase angle limit can be computed using different data sets:– State Estimator data; combination of State Estimator and PMU

data; PMU data 2

Phase angle limit should be determined in real time, and not based on historical dataPhase angle limit is a physical limit:– Depends on system topology and conditions;– Depends on how the system is stressed;– The limit changes with system conditions.

Voltage and thermal limits are operating limits:– Depend on the equipment/hardware.

Three types of different phase angle limits:– 1. Based on user-defined scenario-based stressing;– 2. Based on optimal scenario-based stressing;– 3. Based on “natural” direction of system stressing.

Phase angle limit can be computed using different data sets:– State Estimator data; combination of State Estimator and PMU data; PMU data

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 3: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

Approach 1. User-DefinedScenario-based Stressing

3

Approach 1. User-defined sources/sinks:– “Traditional”, but not optimal (maximum stressing)

Maximum transfer capability may be reached due to exhausting resources before reaching voltage/thermal/stead-state stability violation.

POM computes the most critical (sensitive) phase angle differences to each stressing:– Both in real-time and off-line.

In addition, can monitor user-defined phase angle differences.Phase angle limit is computed based on State Estimator (SE) data.Alarming is done based on both SE and PMU data.

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 4: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

Computing Limits and Alarming in ROSEThe key computation in ROSE:– ROSE computes both the limit and the current state, and

can issue an alarm based on these two parameters;– Since the limits are computed in real-time, these limits

are “dynamic” (changing).

There are two types of alarms in ROSE:– SE-based (model-based) alarming;– PMU-based alarming.

Both types of alarms may be expressed in terms of MW on the interfaces or phase angles.

4Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 5: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

5

SE-Based Alarming

Two types of alarming are available:– Flow on the interface in MW;– Phase angle difference between two PMU locations in Degrees:

PMU locations are user-defined as an input.

Limit is computed both in MW and degrees.If the difference between the limit in MW and base case MW flow is less than MW alarming threshold, a MW alarm is issued.If the difference between the limit in degrees and base case phase angle difference in degrees is less than Phase Angle alarming threshold, a Phase Angle alarm is issued.

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 6: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

6

PMU-Based AlarmingTwo types of alarming are available:– Flow on the interface in MW;– Phase angle difference between two PMU locations in Degrees:

PMU locations are user-defined as an input

Limit is computed both in MW and degrees.If the difference between the limit in MW and the current MW flow obtained from PMU data is less than MW alarming threshold, a MW alarm is issued.If the difference between the limit in degrees and current phase angle difference obtained from the PMU stream in degrees is less than Phase Angle alarming threshold, a Phase Angle alarm is issued.

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 7: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

7

Both 1-D or 2-D ROSE boundaries are computed; – Each point on the boundary corresponds to thermal

overload, flowgate constraint, voltage violation, or voltage collapse.

Alarms are issued for 1-D scenarios:– Visualization includes trending of results in Real Time

and Historical Trend.

ROSE Analysis

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 8: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

8

ROSE Client at ISO NE

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 9: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

9

2-D Limits in MW and Degrees

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 10: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

Approach 2. Optimal Scenario-based Stressing

Approach 2. Optimal sources/sinks determine by the software:– Such that interface/path flow is maximized;– Can be a pre-selected list of potential source/sink locations

(such as several control areas);– This is maximum phase angle limit for the given interface/path.

POM computes the most critical (sensitive) phase angle differences to each path/interface:– Both in real-time and off-line.– In addition, can monitor user-defined phase angle differences.

Phase angle limit is computed based on State Estimator (SE) data.Alarming is done based on both SE and PMU data.V&R has a planning tool to determine maximum interface flow and phase angle limit.

10Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 11: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

Approach 3. “Natural” Direction of Stressing

PMU data is used to determine the “natural” direction of stressing.Phase angle limit is computed based on both SE and PMU data:– PMU data is used to determine the change in system

conditions, and thus direction in which the system is stressed;

– SE data is used to determine the limit for the “natural” stressing direction;

– Stressing in the traditional sense is not performed.– This is not a commercial tool yet:

Technology/algorithms have been developed.

11Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 12: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

Only PMU-Based AnalysisPhase angle limit is computed based on PMU data.PMU data is used to:– Create a measurement-based real-time case;– Determine phase angle limit using stressing.

Two ways to use measurement-based real-time case:– Run the analysis when State Estimator (SE) case is

not available or the system approaches stability limits between the two SE cases.

– Run the analysis continuously without interruption all the time:

Case is created and computations are performed with approx. the sampling PMU rate;Stressing can be performed using any of the three approaches described in the previous slides.

– This is not a commercial tool yet:Technology/algorithms have been developed. 12

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.

Page 13: Phase Angle Alarming in ROSE for Steady-State Stability Analysis Marianna Vaiman V&R Energy JSIS Meeting Salt Lake City, UT March 5, 2015 1 Copyright ©

13

V&R has developed different approaches to compute phase angle limits.Different types of phase angle limit computation are discussed.Computations are based on SE and PMU data.

Conclusion

Copyright © 1997-2015 V&R Energy Systems Research, Inc. All rights reserved.