phd 300- honeywell training course

121
PHD R300 Training By Dr. Amr Arafa

Upload: dr-eng-amr-arafa-

Post on 08-Aug-2015

1.363 views

Category:

Engineering


244 download

TRANSCRIPT

Page 1: PHD 300- honeywell training course

PHD R300 Training

By

Dr. Amr Arafa

Page 2: PHD 300- honeywell training course

2 File Number

Process History Database

Introduction

Page 3: PHD 300- honeywell training course

3 File Number

The Role of PHD

• The role of PHD is to:

- Integrate all real-time process and process-related data.

- Provide a consistent and common base of process and process-related information to applications.

- Manage the archiving of process data.

- Provide a single controlled interface to DCS and SCADA systems.

- Provide process calculation and trending capabilities.

Page 4: PHD 300- honeywell training course

4 File Number

PHD System computers Supported Operating Systems: - Server (SQL Server 2008 & PHD Server)

Windows 2003 (x86) Windows 2003 (x64)

Windows 2003 R2 (x86) Windows 2003 R2 (x64)

Windows 2008 (x86) Windows 2008 (x64)

Including both Standard and Enterprise versions - Client (PHD Configuration Tool, Uniformance System Console and the R300 .NET API) Windows XP Professional (x86) Windows Vista Business (x86 & x64) Windows 2003 (x86) Windows 2003 (x64)

Windows 2003 R2 (x86) Windows 2003 R2 (x64)

Windows 2008 (x86) Windows 2008 (x64)

Including both Standard and Enterprise versions

Page 5: PHD 300- honeywell training course

5 File Number

Basic PHD Components

• PHD collects, integrates and maintains a history of real-time continuous and discrete production data, process performance data, and process-related data.

Page 6: PHD 300- honeywell training course

6 File Number

Basic PHD Components

Page 7: PHD 300- honeywell training course

7 File Number

System Components and Data Flow

Page 8: PHD 300- honeywell training course

8 File Number

Data Processing : Confidence Factor

Page 9: PHD 300- honeywell training course

9 File Number

Intelligent Data Retrieval

• PHD provides application programs with built-in data manipulations and calculations, thus simplifying application development and maintenance.

- Data Reduction Calculations

- Automatic Missing Data Interpolation and Extrapolation

- Automatic Engineering Unit Conversions

Page 10: PHD 300- honeywell training course

10 File Number

Intelligent Data Retrieval : Automatic Engineering Unit Conversions

• When an application program requests data from PHD, it is possible to specify the units it requires.

• PHD converts the units from those stored with the tag into the requested units, eliminating having to build conversion functions into the various user tools and applications.

• A tag can be defined with any unit code, but is convertible by PHD only if it makes use of PHD base units (standard or user-configured).

Page 11: PHD 300- honeywell training course

11 File Number

USC •Built as a Microsoft Management Console add-in. •Makes connection to the PHDStart service which then transfers the communication over to the other PHD services in review. •The functionality provides access to any PHD component system in the environment using either trusted or non-trusted access connections. When trusted the account the user is logged in with to the computer is passed over to the PHD service for connection authentication. When non-trusted the user must enter a user account that can be validated by the remote PHD system.

Page 12: PHD 300- honeywell training course

12 File Number

PCT •While it is based upon Honeywell‟s Common Desktop Framework the tool accesses the SQL Server databases PHDCFG and PHDAPP for storage of any configuration performed. •When installed the default expectation is the person utilizing the tool will be logged on to the local computer with an account that can be authenticated as a member of the Product Administrators or Local Engineers upon the computer where the SQL Server databases are hosted.

Page 13: PHD 300- honeywell training course

13 File Number

Uniformance PHD Client Component

• Process Studio

Page 14: PHD 300- honeywell training course

14 File Number

Uniformance PHD Client Component

• IE Plugin

Page 15: PHD 300- honeywell training course

15 File Number

PHD Server Follow up steps

During installation the following Local Account groups are created: Local Operators, Local Engineers, Product Administrators.

25 HONEYWELL - CONFIDENTIAL PHD R300.x

Page 16: PHD 300- honeywell training course

16 File Number

Lesson Topic - PHD Server now installed

These icons appear on the desktop for every server where

PHD Server services are

installed.

Further customization is configured in the PHD Configuration Tool and Uniformance System Console.

32 HONEYWELL - CONFIDENTIAL PHD R300.x

Page 17: PHD 300- honeywell training course

17 File Number

Process History Database

Real-Time Data Interface Management

Page 18: PHD 300- honeywell training course

18 File Number

RDI Configuration Overview

• The three major steps for configuration of an RDI are:

- Enter configuration data into the Interfaces in PCT.

- Run the configuration utility and execute its Save RDI/Link Configuration command.

- Cold start PHD.

Page 19: PHD 300- honeywell training course

19 File Number

RDI Configuration Overview

• Interfaces (RDI‟ and Links) form is used to configure RDI‟s

Page 20: PHD 300- honeywell training course

20 File Number

RDI Configuration Overview – Experion Link

Page 21: PHD 300- honeywell training course

21 File Number

RDI Configuration Overview - Shadow RDI

Page 22: PHD 300- honeywell training course

22 File Number

RDI Configuration utility

• From the Start menu, open the PHD RDI Configuration utility (RDISetup.exe).

Page 23: PHD 300- honeywell training course

23 File Number

PHD RDI Configuration utility, continued

• Configure the Miscellaneous parameters as necessary, then select File>Save RDI/Link Configuration.

Adds to PHD

Page 24: PHD 300- honeywell training course

24 File Number

PHD RDI Configuration utility – Save configuration

•Save RDI Configuration form

Page 25: PHD 300- honeywell training course

25 File Number

Start PHD Cold

• Cold Start PHD using following command.

- PHDCTL Start Cold

Page 26: PHD 300- honeywell training course

26 File Number

RDM

2 HONEYWELL - CONFIDENTIAL File Number

•Redirection Manager (RDM) is required on the PHD Server if the PHD Experion Link is

to connect to a redundant pair of Experion Servers.

•In such a case, the PHD Experion Link is configured to connect to Redirection

Manager instead of the Experion OPC HDA server.

•RDM forwards requests to the active Experion Server of a configured redundant pair.

Redirection occurs whenever a failure is detected in the active Experion Server.

•RDM blocks all OPC calls until after the failover completes or after a user-configured

timeout.

Page 27: PHD 300- honeywell training course

27 File Number

Process History Database

Tag Configuration

Page 28: PHD 300- honeywell training course

28 File Number

PHD Terminology

• Tag

- Point. parameter

- TIC100.PV, TIC100.SP

• Attribute

- Parameter in Source System

• Parent Tag (template)

- Point Class

- Used for simplification of initial configuration and ongoing maintenance through dynamic inheritance.

Page 29: PHD 300- honeywell training course

29 File Number

PHD Tag Definitions

• All PHD Data is referenced by tag name. Tag Ids (numbers) are used internally. Tag Ids cannot be reused.

• History is associated with the Tag Id. (When a tag is deleted from Sql Server, the Tag Id will not be reused.)

• Tag names can be the same as those used on the source system, or they can be different.

• Tag names can include a prefix and/or suffix - Ex. BB.F131.PV

Page 30: PHD 300- honeywell training course

30 File Number

PHD Tag Definitions

• Tags are classified into 5 groups:

- Parent Tags – templates which can be used when creating one of the other four classes of tags.

- Collected Tags – tags which store data collected from PHD interfaces.

- Manual Input Tags – tags which store data that is manually entered by a user.

- Virtual Tags – tags which provide data that is calculated based on collected tag values, manual input tag values and/or other virtual tag values.

- Stored Virtual Tags – tags which provide calculated data based on collected tag values, manual input tag values and/or other virtual tag values. This calculated data is then stored in the history archive.

Page 31: PHD 300- honeywell training course

31 File Number

Class Tags and Inheritance (templates)

• In general terms, class tags should be defined for each set of tags having similar data processing requirements. Many children per parent. No software limit to the number of levels, but Honeywell recommends no more than three; otherwise, it gets too complicated.

Page 32: PHD 300- honeywell training course

32 File Number

Class Tags and Inheritance

• Each tag's definition specifies what tag attributes are inherited from its

parent. The parent class-tag must be specifically defined for a tag.

• A class-tag may in turn inherit values from another class-tag.

• If a class-tag attribute is modified, any tags that inherit the attribute dynamically inherit the change. This permits the system to be configured with a set of intelligent default tag attributes.

• Initial tag definition as well as ongoing tag maintenance is simplified, as behavior of entire classes of tags can be altered by modification of the parent class-tag.

• On a per tag basis, users can override inherited tag definitions for tags that may have unique requirements within a class.

• You can identify Class tags any way you want. Class tags can identify tag types such as temperatures, orifice flows, set points, or tag usage such as optimization tags.

• If the active flag on a parent tag is enabled, it has no impact other than causing the parent tag to be displayed in Tag Explorer under the Parents folder.

Page 33: PHD 300- honeywell training course

33 File Number

Tag Configuration Form

• Following options are available to create various new tags.

Page 34: PHD 300- honeywell training course

34 File Number

Tag Configuration Form

• The Tag Configuration form allows you to enter new tags or modify existing tag configuration information.

Page 35: PHD 300- honeywell training course

35 File Number

Tag Configuration Form

• Tags can be searched using wild Character „*‟ or using options available in advanced search.

Page 36: PHD 300- honeywell training course

36 File Number

Tag Configuration Form

• Enable Flag Pane will provide various following options

Allow Data Store - This enables data

storage to Archive files.

Allow Data Edit – This enables to

modify historied data for the tag.

Page 37: PHD 300- honeywell training course

37 File Number

Tag Configuration Form

• Collection Pane provides various options related to RDI‟s & source tags.

RDI/Link Collector – Name of

RDI which is collection values

Source System – This will

provide the name of source

system.

Source Tag Name – The name

of tag in source system

Page 38: PHD 300- honeywell training course

38 File Number

Tag Configuration Form

• The Storage Pane allows to optimize data storing function using Compression/Quantum

Page 39: PHD 300- honeywell training course

39 File Number

Tag Configuration Form

• The Advanced Configuration is for specifying ways to optimizes data storing functions of PHD.

Data Elimination Compression

Storage Format Compression

Page 40: PHD 300- honeywell training course

40 File Number

Tag Configuration Form

• After creating new tags or modifying the existing tags, click on “Send Tag Def to PHD” button to upload the changes to PHD Server.

Page 41: PHD 300- honeywell training course

41 File Number

Process History Database

Uniformance System Console

Page 42: PHD 300- honeywell training course

42 File Number

What is USC ?

• This tool is a graphic replacement for PHDMAN – however far greater functionality than was available through PHDMAN is provided in USC.

• The tool provides access to all PHD Server services, their settings and ability to control the system remotely from the physical computer.

• Appropriate access privileges are required to control system and alter configuration settings.

• USC provides the ability to connect via the PHDStart service upon every computer where PHD Services are installed.

• Connections can utilize both trusted (automatically validating the user account logged in with) and untrusted (when the user passes a valid user account that can be validated) connections.

Page 43: PHD 300- honeywell training course

43 File Number

How to set it up ?

• When first started USC has no information of any systems in the environment.

Page 44: PHD 300- honeywell training course

44 File Number

How to set it up ?

• To create a connection either right click upon the Uniformance System Console menu or just selecting Define Server.

Page 45: PHD 300- honeywell training course

45 File Number

How to set it up

• And the ability to enter the desired computer name hosting the PHD Services is opened.

Page 46: PHD 300- honeywell training course

46 File Number

How to set it up

• Once hostname is entered click upon OK

Page 47: PHD 300- honeywell training course

47 File Number

How to set it up

• With the computer upon the local domain and being a member of “Product Administrators” or “Local Engineers” select trusted connection

Page 48: PHD 300- honeywell training course

48 File Number

Services & Access

• And now one can see the beginning of the listed information that can be viewed in USC.

• The ability to remotely start and stop PHD completely or any of the individual services.

• With appropriate privileges using “Task List” the opportunity exists to actually kill a service – caution must be taken as operating system services can be chosen here as well.

Page 49: PHD 300- honeywell training course

49 File Number

Services & Access

• Starting at the top the DCOM Setting for OPC components can be seen.

Page 50: PHD 300- honeywell training course

50 File Number

Services & Access

• Ability to chose Event Logs to view.

Page 51: PHD 300- honeywell training course

51 File Number

Services & Access

• Viewing the data in these as well

Page 52: PHD 300- honeywell training course

52 File Number

Services & Access

• Even registry settings can be remotely viewed.

Page 53: PHD 300- honeywell training course

53 File Number

Services & Access

• The ability to configure Uniformance System Monitoring is managed under USC.

Page 54: PHD 300- honeywell training course

54 File Number

Services & Access

• Ability to view and control PHD upon the remote computer is provided.

Page 55: PHD 300- honeywell training course

55 File Number

Services & Access

• Interfaces running under RDIServer can be managed

Page 56: PHD 300- honeywell training course

56 File Number

Services & Access

• Ability to see how RDC is working

Page 57: PHD 300- honeywell training course

57 File Number

Services & Access

• When right clicking upon one of the PHD Server services and selecting properties.

Page 58: PHD 300- honeywell training course

58 File Number

Services & Access

• Access to the settings for the selected service are provided

Page 59: PHD 300- honeywell training course

59 File Number

Process History Database

IE Plugin

Page 60: PHD 300- honeywell training course

60 File Number

IE Toolbar

• Need to enable the IE toolbar

- right-click on IE toolbar, and select “Uniformance PHD”

- requires IE6 or later

Page 61: PHD 300- honeywell training course

61 File Number

IE Toolbar

• IE Toolbar

Page 62: PHD 300- honeywell training course

62 File Number

IE Toolbar - Options Dialog

• The Options menu enables you to connect to the PHD Server and specify the format for the output files.

Page 63: PHD 300- honeywell training course

63 File Number

IE Toolbar - Get Data Dialog

• The Get Data option is used for conducting data query.

Page 64: PHD 300- honeywell training course

64 File Number

IE Toolbar - Get Data Dialog

• The result of Get Data is as below :

Page 65: PHD 300- honeywell training course

65 File Number

IE Toolbar - Tag List Dialog

• The Tag List option is used for viewing the list of Tags.

Page 66: PHD 300- honeywell training course

66 File Number

IE Toolbar - Tag List Dialog

• The result of Tag List is as below.

Page 67: PHD 300- honeywell training course

67 File Number

IE Toolbar - Other Useful Commands

• List of RDIs: phd://localhost/RDIList?

• List of Links: phd://localhost/LinkList?

• List of Parent Tags phd://localhost/ParentTagList?

• See help information for more details

Page 68: PHD 300- honeywell training course

68 File Number

Process History Database

Excel Companion

Page 69: PHD 300- honeywell training course

69 File Number

Purpose of Excel Companion

• The Excel Companion is an add-in for retrieving PHD data in

Excel Files.

• The add-in provides a drop-down menu and an optional tool

bar from which you can call a dialog box. You use the

dialog box to create a function in a cell that retrieves data.

The dialog box makes building the function call very user

friendly.

Page 70: PHD 300- honeywell training course

70 File Number

The Excel Companion adds a „Uniformance‟ menu to standard Excel. Using this menu, PHD data, Event data, and LIMS data can be retrieved and placed on a worksheet. Once the data is on the worksheet, Excel functions can be used to analyze the data.

Note:

Visual PHD must be installed to use the Excel Companion.

Page 71: PHD 300- honeywell training course

71 File Number

Basic Steps: 1. Enter the tagnames for the

history call. (The Tag Explorer can be used to add one or more tagnames to the dialog box.)

2. Use the arrow button to move

the tagnames entry to the Selected Tags list.

3. Select the items you want to be

shown in the results. 4. Select one or more aggregates. 5. Specify an absolute or relative-

based start/end time. 6. Specify the Interval. 7. Select OK.

Use a dialog box to create the history function call in a cell.

1.

3. 2.

4.

5.

6.

Page 72: PHD 300- honeywell training course

72 File Number

„Get PHD Data‟ Dialog Box

• Use a dialog box to create the history function in a cell.

- Enter the tagnames for the history call.

Page 73: PHD 300- honeywell training course

73 File Number

„Get PHD Data‟ Dialog Box

• Use the arrow button to move the tagnames entry to the

Selected Tags list.

Page 74: PHD 300- honeywell training course

74 File Number

„Get PHD Data‟ Dialog Box

• Select the items you want to be shown in the results.

Page 75: PHD 300- honeywell training course

75 File Number

„Get PHD Data‟ Dialog Box

• Select one or more aggregates.

Page 76: PHD 300- honeywell training course

76 File Number

„Get PHD Data‟ Dialog Box

• Specify an absolute or relative-based start/end time & interval.

Page 77: PHD 300- honeywell training course

77 File Number

„Get PHD Data‟ Dialog Box

• Select “OK” to get data in excel

Page 78: PHD 300- honeywell training course

78 File Number

„Get PHD Data‟ Dialog Box

• The “Advanced” portion of the dialog box allows you to

specify - the output starting cell (contains the function call),

- the output presentation format, and other options.

Page 79: PHD 300- honeywell training course

79 File Number

Process History Database

PHD Backup Strategy

Page 80: PHD 300- honeywell training course

80 File Number

Uniformance Backup Overview

• Types of backups:

- PHD Archives

- Sql Server Database

Page 81: PHD 300- honeywell training course

81 File Number

Backup of PHD Archives

- Shut Down PHD using PHDCTL Stop command

Page 82: PHD 300- honeywell training course

82 File Number

Backup of PHD Archives

- Take a current backup of [drive:]\program files\Honeywell\Uniformance\ PHDServer directory and its subdirectories (with the exception of the GBLSECT directory) on backup media

Page 83: PHD 300- honeywell training course

83 File Number

Backup of PHD Archives

- Restart PHD using PHDCTL start cold command.

Page 84: PHD 300- honeywell training course

84 File Number

Sql Server Database Backups

• There are 2 databases of PHD in Sql Server : PHDAPP & PHDCFG

Page 85: PHD 300- honeywell training course

85 File Number

Sql Server Database Backups

• Right Click on Database : PHDCFG & go to Tasks & Backup.

Page 86: PHD 300- honeywell training course

86 File Number

Sql Server Database Backups

• In the Back Up Database details, give the location of backup.

Page 87: PHD 300- honeywell training course

87 File Number

Sql Server Database Backups

• Once backup is finished, following message appears.

Page 88: PHD 300- honeywell training course

88 File Number

Sql Server Database Backups

• Repeat the above procedure to backup “PHDAPP” Database.

Page 89: PHD 300- honeywell training course

89 File Number

Testing of Backup

• Honeywell recommends that backups be tested on a regular basis, by restoring the backup onto an offline system to test the validity of the backup.

Page 90: PHD 300- honeywell training course

90 File Number

Process History Database

Uniformance Process Studio

Page 91: PHD 300- honeywell training course

91 File Number

How to organize your favourite tags

• One of the features of Uniformance Process Studio is a workspace in which you can organize all of your tags/items for quick and easy access.

Page 92: PHD 300- honeywell training course

92 File Number

How to organize your favourite tags

• Create folders.

Page 93: PHD 300- honeywell training course

93 File Number

How to organize your favourite tags

• Find your tags/items

Page 94: PHD 300- honeywell training course

94 File Number

How to organize your favourite tags

• Drag/drop tags/items to the workspace/folder

Page 95: PHD 300- honeywell training course

95 File Number

Trend

• Click Trend to start a new trend window.

Page 96: PHD 300- honeywell training course

96 File Number

Trend

• Drag/drop tags from a workspace, folder or from the tag/item Browser

• You can add up to 32 tags/items per trend.

Workspace

Page 97: PHD 300- honeywell training course

97 File Number

Trend

• Hairlines allow you to see the data at specific times. To turn Hairlines on and off, use checkboxes on the menu or use right-click> Display.

Click the checkboxes to

turn on both Hairlines.

Page 98: PHD 300- honeywell training course

98 File Number

Trend options to support analysis

• Zoom

Drag the mouse to draw a box

where you want to zoom in.

To undo the zoom,

right-click and choose Reset

Zoom.

Page 99: PHD 300- honeywell training course

99 File Number

Trend options to support analysis

• You can add or eliminate columns from the trend properties table.

Right-click on the table and

select Columns.

Then select the columns

that you want from the list.

Page 100: PHD 300- honeywell training course

100 File Number

Trend options to support analysis

• You can arrange your windows to suit your needs.

• For this example, open three Trend windows and follow the instructions.

Right-click on a tab and select New

Horizontal Tab Group Right-click on a different tab and

select New Vertical Tab Group

Page 101: PHD 300- honeywell training course

101 File Number

Trend options to support analysis

• When you initially create a trend, it has a single Y axis. There are several other trend types to choose from.

To switch to a different

trend type, select Type

you want from the menu

Page 102: PHD 300- honeywell training course

102 File Number

Trend options to support analysis

• Trends: - Single Y, Multiple Y & Strip Chart

Page 103: PHD 300- honeywell training course

103 File Number

Trend options to support analysis

• Try the following advanced options that are available through the trend‟s right-click menu:

- Offset the time axis – useful to compare two different batch uns.

Page 104: PHD 300- honeywell training course

104 File Number

Trend options to support analysis

• First, use the right-click menu to configure the Secondary X Axis.

• Then, to show the X axis with the offset, right-click the Trend Properties table, add the Xaxis column, and set a tag/item‟s Xaxis property to Top.)

Page 105: PHD 300- honeywell training course

105 File Number

Multi-trend

• In addition to Trends, you can build a Multi-trend window to easily view numerous small plots (up to 25).

Page 106: PHD 300- honeywell training course

106 File Number

Multi-trend

• Click MultiTrend to start a new Multi-trend window.

From the Home tab – click MultiTrend

to launch a new window.

Page 107: PHD 300- honeywell training course

107 File Number

Multi-trend

•Notice that this top section changes to match whatever you have selected down here.

Page 108: PHD 300- honeywell training course

108 File Number

Multi-trend

• Click Layout and then select the layout you want.

Page 109: PHD 300- honeywell training course

109 File Number

Multi-trend

• Drag/drop tags/items onto each plot. Use the same drag/drop method as the full Trend.

Page 110: PHD 300- honeywell training course

110 File Number

Multi-trend

• Hairlines are available for the Multi-trend.

Turn on Hairlines.

The boxes display the data

values at the Hairline

location.

Drag a Hairline to a new

time and view the data

values in the boxes.

You can also use the slider

on the time control to move

Hairlines.

Page 111: PHD 300- honeywell training course

111 File Number

Multi-trend

• Use the time control to change the time settings for all of the plots.

• Double-click on any small plot to quickly navigate to a full Trend.

Page 112: PHD 300- honeywell training course

112 File Number

Table

• The Table in Uniformance Process Studio provides a quick, simple data display.

• It also supports manual data entry/edit through the right-click menu.

Page 113: PHD 300- honeywell training course

113 File Number

Table

• Click Table to start a new table window.

Page 114: PHD 300- honeywell training course

114 File Number

Table

• Drag/drop several tags/items onto the table. Use the same drag/drop method as the Trend and multiTrend.

From the Home tab – click Table to launch

a new window.

NOTE: Always return Home to open a

new window.

Page 115: PHD 300- honeywell training course

115 File Number

Table

• The Standard table type has optional filters on each column.

Select (Custom) to display this

dialog box where you can enter

your own custom filter.

Page 116: PHD 300- honeywell training course

116 File Number

Table

• You can export values or PHD tag/item configuration to excel.

Page 117: PHD 300- honeywell training course

117 File Number

Time Control

• The Time Control can be used with Trends, MultiTrends, Tables, and Graphics.

• The Time Control allows you to set time related properties and to automatically play or step through data.

• You can use the time control in relative or absolute time format.

Page 118: PHD 300- honeywell training course

118 File Number

Workspace

•You can save Trends, MultiTrends, Tables and various other items to a workspace for reuse: - Trends

- Multi-Trends

- Tables

- Tags/Items

- Time Ranges

- Graphics

- External documents

- Web pages

Page 119: PHD 300- honeywell training course

119 File Number

Workspace

• To save to a workspace

- Close a Table window.

- If you made changes, it asks if you want to save them. Click Yes to save to the workspace.

- Enter a name for the table.

- Result:

Page 120: PHD 300- honeywell training course

120 File Number

Workspace

• In addition, you can use direct entry, drag/drop, or copy/paste to save to a workspace.

To save to a workspace through direct

entry, right-click on a workspace

folder, choose Add, and then select

what you want to add.

To add to a workspace through drag/drop,

move your mouse in the area below the

tab until a gray border appears. Drag the

gray border to a folder in the workspace.

Page 121: PHD 300- honeywell training course

121 File Number

Workspace

• Each workspace is saved as an .xml file that can be imported.

• You can email the file or save it to a shared location.

• To save the workspace to a shared location, select Send Workspace To> My Computer and then browse to a local or network share.

• Your colleague can then select Import Workspace and browse to the .xml file in the shared location.

You can have multiple

workspaces available.