Prepared By: A.RAFEEK, TESTING ENGINEER Page 1 PROCEDURE FOR TAPCON260

Upload: others

Post on 06-Apr-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 1

PROCEDURE FOR

TAPCON260

Page 2: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 2

Table of contents

Chapter 1

Getting started

Establishing connection with the Tapcon260

Downloading the Settings from the Tapcon260

Chapter 2

Setting Values in the Tapcon260

Sending the setting values to the Tapcon260

Chapter 3

Tapcon 260 testing

Bandwith Test

Voltage Test

Current Test

Page 3: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 3

CHAPTER 1

GETTING STARTED

Page 4: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 4

Open the MR TAPCON-trol SYSTEM.

Click on Establish connect to device.

Page 5: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 5

Click on Connect.

Downloading the settings

Page 6: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 6

Select the Device group, Device name & Name.

This Device identcode is last four digits from the relay serial number.

Then click finish.

Page 7: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 7

Here we have the settings of TAPCON 260. Right click on the AVR

Page 8: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 8

CHAPTER 2

SETTING VALUES

Page 9: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 9

Set the desired value 1 as 100 V.Set the bandwidth value as 5%.

Set the overcurrent settings 110%

Page 10: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 10

Set the Over Voltage & undervoltage stting 110% & 90% respectively.

Page 11: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 11

Set the primary current & Voltage

Page 12: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 12

Here you can check your all settings

Page 13: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 13

CHAPTER 3

TAPCON260 TESTING

Page 14: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 14

Bandwith Check

Connect the voltage and current leads as per given schemes

You have to inject the secondary voltage as per your setting

Ramp from 100 V to 94 V it will start raising the pulse when it reaches 95 V.

Page 15: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 15

Ramp from 100 V to 106 V it will start raising the pulse when it reaches 105 V.

Page 16: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 16

Undervoltage & Overvoltage Test

To test the undervoltage ramp from 100 V to 85V it will give you trip at less than 90 V

Page 17: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 17

To test the undervoltage ramp from 100 V to 115V it will give you trip at more than 110 V

Page 18: PROCEDURE FOR TAPCON260 - My Protection Guide...Chapter 2 Setting Values in the Tapcon260 Bandwith Check Connect the voltage and current leads as per given schemes You have to inject

Prepared By: A.RAFEEK, TESTING ENGINEER Page 18

Overcurrent Test

To test the Overcurrent ramp secondary current 1A TO 1.2 A ,it will give you trip at 1320 A as primary in AVR front screen.