product catalogue - logitron · programmable analog inputs 1 2 1 1 see pl300 digital input 1 2 1...

76
Product Catalogue 2013

Upload: others

Post on 27-Jan-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Product Catalogue

    2013

  • A manufacturing company

    & a registered trademark

    Pixsys stands for twenty years of experience in designing and manufacturing of instrumentation for process control and industrial automation.Starting with hardware and software design, up to product assembly, we complete the entire manufacturing cycle at our factory in Italy. Product concept relies on extremely flexible hardware and software structures allowing reduced order codes, and on user-friendly interfaces and programming tools which simplify start-up and after-sales service. Browse the web site www.pixsys.net for detailed information.

  • Sharing and interconnecting,

    just a few clicks away

    DOWNLOADManuals, Software tools and Application Notes available for download within each product page. VIDEO-MANUALSShort video-manuals provide descriptions and examples about programming options by keyboard or by Memory Cards, as well as demos of software tools. FORUM & FAQA dedicated area for all your questions related to set-up, configuration and operating modes for Pixsys devices, including FAQ area for round-the-clock answers to the most frequent questions.

    TRAINING SESSIONSSpecial attention is reserved to technical training about the programmable systems (PLCs, HMIs) and also parametric devices if required. Arranged upon request, they can be focused on a specific project, as an opportunity to combine theory and practice. Contact our Sales dept for details.

    EXTENSIVE SALES NETWORKBecome a PIXSYS partner!Are you a Systems Integrator with a background in PLCs and HMIs programming? Or a distributor/reseller of industrial electronic devices with a focus on solutions rather than on single components? Contact our Export dept to discuss cooperation and become a partner of our expanding sales network. NEWSLETTERSign-up on our website to receive regular updates about products, special promotions, events and tradeshows. BLOGAn interactive space to communicate and to share case-histories, ideas, hints and suggestions about Pixsys devices and upcoming projects. Open to your contribution.

    ApplicationNotes

    ApplicationNotes

  • 4 Summary - Parametric devices

    Controllers / Indicators

    Click on page no. for product details p. 17 p. 19 p. 20 p. 21 p. 22 p. 23 p. 24 p. 25 p. 26 p. 34 p. 35MAIN FEATURES ATR121 / ATR141 ATR142 ATR171 ATR236 ATR243 ATR401 DRR245 DRR450 STR550 ATR131 DDR132DIMENSIONS (mm) 32 x 74 (front) x 53 32 x 74 (front) x 53 72 x 72 (front) x 99 48 x 48 (front) x 107 48 x 48 (front) x 125 48 x 96 (front) x 123 DIN 43880 (EN50022) (EN50022) 96 x 48 (front) x 48 32 x 74 (front) x 53 DIN 43880 (EN50022)

    POWER SUPPLY 24 - 230 - 115 Vac 12..24 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24 V dc 24..230 Vac/dc 24 - 230 - 115 Vac 230 Vac

    PROGRAMMABLE ANALOGUE INPUTS 1 1 1 / 2 (23 ABC-T) 1 (Only temperature) 1 2 1 1 (TC K, J, T, E) 1 1 / 2 (NTC only) 3 (NTC / PTC)

    DIGITAL INPUT 2 2CURRENT TRANSFORMER INPUT (Optional)RELAY OUTPUTS 2 2 1..4 1 2 / 3 2..4 2 2 1 / 3 4 (1 x 30A)SSR CONTROL OUTPUT 2ANALOGUE OUTPUTS (mA/Volt) (Optional) (Optional) 2RS 485 / MODBUS (Optional) (Optional) (Optional) (Optional) (Optional)

    SOFTwARE FEATURESPID / AUTOTUNINGPROG. HEATING / COOLING ACTIONOPEN / CLOSE LOGIC (valves)RETRANSMISSION PV/SPVREMOTE SETPOINTRAMP / SOFT STARTPRE-PROGRAMMED CYCLE (3 steps)DUAL PID HEATING / COOLINGLIMIT CONTROLLER (manual reset)DEFROST FUNCTIONEASY-UP CODESMEMORY CARDLABSOFTVIEW (programming software)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    AppLIcATIONSFOOD INDUSTRYCOLD CHAIN EQUIPMENTSHVACPACKAGINGPLASTICS / RUBBER INDUSTRYFOOTWEAR / LEATHER MACHINERYTEXTILE INDUSTRYLABORATORY EQUIPMENTSOVENS / FURNACESBURNERS / BOILERS

  • 5Summary - Parametric devices

    Click on page no. for product details p. 17 p. 19 p. 20 p. 21 p. 22 p. 23 p. 24 p. 25 p. 26 p. 34 p. 35MAIN FEATURES ATR121 / ATR141 ATR142 ATR171 ATR236 ATR243 ATR401 DRR245 DRR450 STR550 ATR131 DDR132DIMENSIONS (mm) 32 x 74 (front) x 53 32 x 74 (front) x 53 72 x 72 (front) x 99 48 x 48 (front) x 107 48 x 48 (front) x 125 48 x 96 (front) x 123 DIN 43880 (EN50022) (EN50022) 96 x 48 (front) x 48 32 x 74 (front) x 53 DIN 43880 (EN50022)

    POWER SUPPLY 24 - 230 - 115 Vac 12..24 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24..230 Vac/dc 24 V dc 24..230 Vac/dc 24 - 230 - 115 Vac 230 Vac

    PROGRAMMABLE ANALOGUE INPUTS 1 1 1 / 2 (23 ABC-T) 1 (Only temperature) 1 2 1 1 (TC K, J, T, E) 1 1 / 2 (NTC only) 3 (NTC / PTC)

    DIGITAL INPUT 2 2CURRENT TRANSFORMER INPUT (Optional)RELAY OUTPUTS 2 2 1..4 1 2 / 3 2..4 2 2 1 / 3 4 (1 x 30A)SSR CONTROL OUTPUT 2ANALOGUE OUTPUTS (mA/Volt) (Optional) (Optional) 2RS 485 / MODBUS (Optional) (Optional) (Optional) (Optional) (Optional)

    SOFTwARE FEATURESPID / AUTOTUNINGPROG. HEATING / COOLING ACTIONOPEN / CLOSE LOGIC (valves)RETRANSMISSION PV/SPVREMOTE SETPOINTRAMP / SOFT STARTPRE-PROGRAMMED CYCLE (3 steps)DUAL PID HEATING / COOLINGLIMIT CONTROLLER (manual reset)DEFROST FUNCTIONEASY-UP CODESMEMORY CARDLABSOFTVIEW (programming software)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    AppLIcATIONSFOOD INDUSTRYCOLD CHAIN EQUIPMENTSHVACPACKAGINGPLASTICS / RUBBER INDUSTRYFOOTWEAR / LEATHER MACHINERYTEXTILE INDUSTRYLABORATORY EQUIPMENTSOVENS / FURNACESBURNERS / BOILERS

  • Process Controllers / Programmers

    Click on page no. for product details p. 27 p. 28 p. 29 p. 30 p. 31MAIN FEATURES ATR 421 ATR 620 ATR 621 ATR 902 ATR 313DIMENSIONS (mm) 48 x 96 (front) x 123 72 x 72 (front) x 99 72 x 72 (front) x 99 120 x 65 (front) x 65 251 x 146 (front) x 66

    POWER SUPPLY 24..230 Vac / dc 24 / 110 / 230 Vac 24..230 Vac / dc 230 Vac 12..24 Vac / dc

    PROGRAMMABLE ANALOG INPUTS 1 2 1 1 See PL300DIGITAL INPUT 1 2 1 See PL300RELAY OUTPUTS 2..4 2..3 2..4 2 See PL300SSR CONTROL OUTPUT See PL300ANALOGUE OUTPUTS (mA/Volt)RS 485 / MODBUS (Optional) (Optional)POTENTIOMETER IMP. / FEEDBACK SIGNAL (module PL250)

    SOFTWARE FEATURESPID / AUTOTUNINGOPEN / CLOSE LOGIC (Valves)RETRANSMISSION PV/SPVREMOTE SETPOINTCYCLE RECOVERYWAITING FUNCTIONDELAYED STARTGAS KILN OPTIONSMULTILOOP APPLICATIONSCYCLES / PROGRAMS 15 15 15 15 20STEPS / SEGMENTS 45 20 45 18 30MEMORY CARDLABSOFTVIEW (programming software)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    APPLICATIONSGLASS / CERAMICS KILNSENVIRONMENTAL CHAMBERSDRYERSHEAT TREATMENT PLANTSLABORATORY EQUIPMENTINDUSTRIAL FURMACES HOBBY KILNS (pottery, metal clay, glassware)METAL WORKINGFOOD INDUSTRY

    6 Summary - Parametric devices

  • Timers / Counters

    Click on page no. for product details p. 27 p. 28 p. 29 p. 30 p. 31MAIN FEATURES ATR 421 ATR 620 ATR 621 ATR 902 ATR 313DIMENSIONS (mm) 48 x 96 (front) x 123 72 x 72 (front) x 99 72 x 72 (front) x 99 120 x 65 (front) x 65 251 x 146 (front) x 66

    POWER SUPPLY 24..230 Vac / dc 24 / 110 / 230 Vac 24..230 Vac / dc 230 Vac 12..24 Vac / dc

    PROGRAMMABLE ANALOG INPUTS 1 2 1 1 See PL300DIGITAL INPUT 1 2 1 See PL300RELAY OUTPUTS 2..4 2..3 2..4 2 See PL300SSR CONTROL OUTPUT See PL300ANALOGUE OUTPUTS (mA/Volt)RS 485 / MODBUS (Optional) (Optional)POTENTIOMETER IMP. / FEEDBACK SIGNAL (module PL250)

    SOFTWARE FEATURESPID / AUTOTUNINGOPEN / CLOSE LOGIC (Valves)RETRANSMISSION PV/SPVREMOTE SETPOINTCYCLE RECOVERYWAITING FUNCTIONDELAYED STARTGAS KILN OPTIONSMULTILOOP APPLICATIONSCYCLES / PROGRAMS 15 15 15 15 20STEPS / SEGMENTS 45 20 45 18 30MEMORY CARDLABSOFTVIEW (programming software)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    APPLICATIONSGLASS / CERAMICS KILNSENVIRONMENTAL CHAMBERSDRYERSHEAT TREATMENT PLANTSLABORATORY EQUIPMENTINDUSTRIAL FURMACES HOBBY KILNS (pottery, metal clay, glassware)METAL WORKINGFOOD INDUSTRY

    Click on page no. for product details p. 32 p. 33MAIN FEATURES TcT101 TcT201DIMENSIONS (mm) 32 x 74 (front) x 53 48 x 48 (front) x 107

    POWER SUPPLY 24..230 Vac / dc 24..230 Vac / dc

    DIGITAL INPUTS (NPN / PNP / TTL) 3 3RELAY OUTPUTS 2 / 1 (4ABC-T) 2ANALOGUE INTPUT (potentiometer)RS485 / MODBUS (4ABC-T)

    SOFTwARE FEATURESTIMER (on-off / pause-work / oscillator / pwm) (1ABC) (1ABC)PROGRAMMABLE TIME BASIS (1ABC) (1ABC)

    COUNTER MODE (up / down / lock / hold) (2ABC) (2ABC)

    COUNTING FREQUENCY (up to 100 khz) (2ABC) (2ABC)TACHOMETER (up to 100 khz) (3ABC) (3ABC)START / STOP / HOLD BY DIGITAL INPUTBACK-UP BATTERYMEMORY CARDLABSOFTVIEW (programming software)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    AppLIcATIONSCONTROL PANELSPRODUCTION QUANTITY MANAGEMENTPRE-SET COUNTINGSFOOD INDUSTRYWATER TREATMENTENCODER READING FLOWMETER OPTION

    7Summary - Parametric devices

  • PLCs - I/O Modules

    Click on page no. for product details p. 38 p. 39 p. 40 p. 41 p. 42 p. 43 p. 46

    MAIN FEATURES EpL101 - pLc pL110 - pLc pL250 - pLc pL260 - pLc pL300 - I/O MOD. McM260 - I/O MOD. ETD884 Exp.MOD.DIMENSIONS (mm) 151 x 80 x max 33 108 x 890 x 64 160 x 90 x 58 160 x 90 x 58 160 x 90 x 58 90 x 71 x 58 92 x 87 x 17POWER SUPPLY 24 / 230 Vac 24 Vac / Vdc 12..24 Vac / Vdc 12..24 Vdc 12..24 Vac / Vdc 12..24 Vac / Vdc bus - poweredDIGITAL INPUTS 6 PNP + 1 NPN 8 PNP 16 PNP 16 6 8 / 16 8

    DIGITAL OUTPUTS (PNP) 16 (700 mA each) 8..16 (700 mA MCM260-1/3) 8

    DIGITAL OUTPUTS (relay) 5 Relay 5A + 1 16A 8 Relay 2A 12 Relay 5A 12 Relay 5A 8 Relay 5A (MCM260-4) 0ANALOGUE INPUTS 4 (16 bit) 4 (10 bit) 4 (10 / 16 bit) 4 (16 bit) 4 (16 bit) 4 (16 bit) 4 (24 bit)

    ANALOGUE OUTPUTS 1 (0..5V - 8bit) 1 (0..10V - 8bit) 2 (0..10V - 8bit) 4 (0..10V2 8bit, 2 12bit) 2 (V / mA) 2 (V / mA) 2 (V/mA)

    SERIAL PORTS 1 RS232 - 1 RS485 1 USB - 2 RS485 2 RS232 - 1 RS485 1 RS232 - 1 RS4851 CAN or RS232 1 RS232 - 1 RS485 1 RS485 - 1 CAN

    PROTOCOLS Modbus - RTUFree portModbus - RTU

    Free portModbus - RTU

    Free port

    Modbus - RTUFree port -

    CAN Master (MCM260 only)

    Modbus - RTUModbus - RTU

    Free port - CAN Open/Slave

    MODBUS MASTERMODBUS SLAVE

    SOFTwARE FEATURESFLASH MEMORY 64 kbyte 64 kbyte 64 kbyte 64 kbyteRAM (variables area) 200 words 350 words (Back-up) 200 words (Back-up) 350 words (Back-up)EEPROM AREA 1000 words 1000 words 127 words 1000 words

    MEMORY AREA 32000 words (Optional) 13000 words32000 words

    (Optional) 13000 words

    REAL-TIME CLOCK (Optional)FIRMWARE UPDATE BY MEMORY CARDCONTROL ALGORITHMS P - PI - PID - PD P - PI - PID - PD P - PI - PID - PD P - PI - PID - PD P - PI - PID - PDSCANNING CYCLE Min. 2 ms Min. 2 ms Min. 2 ms Min. 2 ms

    pROgRAMMINg OpTIONSPIXSYS PLPROG (logic)EDS FILES

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    AppLIcATIONSFOOD INDUSTRYAIR CONDITIONINGWOODWORKINGPACKAGINGPLASTICS INDUSTRYTEXTILE / FOOTWEAR MACHINERYDOMOTICSKILNS / FURNACES

    8 Summary - Programmable systems

  • Click on page no. for product details p. 51 p. 51

    MAIN FEATURES NET 200SERIAL cONvERTER

    NET 250wIRELESS

    TRANSMITTER REcEIvER

    DIMENSIONS (mm) 101 x 71 x 28 101 x 71 x 28MOUNTING DIN Rail DIN RailPOWER SUPPLY 12..24 Vac / Vdc - USB 12..24 Vac / Vdc - USBCONFIGURATION / SET-UP Automatic Hyper terminalCONNECTION (pc-side) RS232 - USB USBCONNECTION (device-side) RS232 - RS422 - RS485 RS232 - RS485CHANNELS 7

    WORKING DISTANCE (standard antenna) Max 100 m free space

    WORKING DISTANCE (special antenna) Max 300 m free space

    Serial converters

    PLProgPixsys development environment for PLC and SOFT-PLC programming. It supports Ladder Diagram (LD) language for a straight-forward, simple approach to programming.

    Programming tools

    Click on page no. for product details p. 38 p. 39 p. 40 p. 41 p. 42 p. 43 p. 46

    MAIN FEATURES EpL101 - pLc pL110 - pLc pL250 - pLc pL260 - pLc pL300 - I/O MOD. McM260 - I/O MOD. ETD884 Exp.MOD.DIMENSIONS (mm) 151 x 80 x max 33 108 x 890 x 64 160 x 90 x 58 160 x 90 x 58 160 x 90 x 58 90 x 71 x 58 92 x 87 x 17POWER SUPPLY 24 / 230 Vac 24 Vac / Vdc 12..24 Vac / Vdc 12..24 Vdc 12..24 Vac / Vdc 12..24 Vac / Vdc bus - poweredDIGITAL INPUTS 6 PNP + 1 NPN 8 PNP 16 PNP 16 6 8 / 16 8

    DIGITAL OUTPUTS (PNP) 16 (700 mA each) 8..16 (700 mA MCM260-1/3) 8

    DIGITAL OUTPUTS (relay) 5 Relay 5A + 1 16A 8 Relay 2A 12 Relay 5A 12 Relay 5A 8 Relay 5A (MCM260-4) 0ANALOGUE INPUTS 4 (16 bit) 4 (10 bit) 4 (10 / 16 bit) 4 (16 bit) 4 (16 bit) 4 (16 bit) 4 (24 bit)

    ANALOGUE OUTPUTS 1 (0..5V - 8bit) 1 (0..10V - 8bit) 2 (0..10V - 8bit) 4 (0..10V2 8bit, 2 12bit) 2 (V / mA) 2 (V / mA) 2 (V/mA)

    SERIAL PORTS 1 RS232 - 1 RS485 1 USB - 2 RS485 2 RS232 - 1 RS485 1 RS232 - 1 RS4851 CAN or RS232 1 RS232 - 1 RS485 1 RS485 - 1 CAN

    PROTOCOLS Modbus - RTUFree portModbus - RTU

    Free portModbus - RTU

    Free port

    Modbus - RTUFree port -

    CAN Master (MCM260 only)

    Modbus - RTUModbus - RTU

    Free port - CAN Open/Slave

    MODBUS MASTERMODBUS SLAVE

    SOFTwARE FEATURESFLASH MEMORY 64 kbyte 64 kbyte 64 kbyte 64 kbyteRAM (variables area) 200 words 350 words (Back-up) 200 words (Back-up) 350 words (Back-up)EEPROM AREA 1000 words 1000 words 127 words 1000 words

    MEMORY AREA 32000 words (Optional) 13000 words32000 words

    (Optional) 13000 words

    REAL-TIME CLOCK (Optional)FIRMWARE UPDATE BY MEMORY CARDCONTROL ALGORITHMS P - PI - PID - PD P - PI - PID - PD P - PI - PID - PD P - PI - PID - PD P - PI - PID - PDSCANNING CYCLE Min. 2 ms Min. 2 ms Min. 2 ms Min. 2 ms

    pROgRAMMINg OpTIONSPIXSYS PLPROG (logic)EDS FILES

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    AppLIcATIONSFOOD INDUSTRYAIR CONDITIONINGWOODWORKINGPACKAGINGPLASTICS INDUSTRYTEXTILE / FOOTWEAR MACHINERYDOMOTICSKILNS / FURNACES

    9Summary - Programmable systems

  • HMI - Operator panels

    Click on page no. for product details p. 44 p. 45 p. 46 p. 47 p. 48 p. 49 p. 50MAIN FEATURES TD240 TD320 TD430 TD570 / TD700 TD750 TD850 TD900

    DISPLAY 3.5” TFT 5.7” TFT 4.3” TFT 480 x 272 5.7” TFT 640 x 4807” TFT 800 x 480 7” TFT 800 x 600 10.4” TFT 800 x 600 15” TFT 1024 x 768

    TOUCH-SCREEN Resistive Resistive Resistive Resistive Resistive Resistive Resistive

    DIMENSIONS (mm) 140 x 100 x 40 (AD) or 65 (11AD) 204 x 170 (front) x 48 140 x 100 (front) x 38 204 x 170 (front) x 48 204 x 160 (front) x 34 325 x 260 (front) x 34 435 x 330 (front) x 38

    PANEL CUT-OUT 132 x 90 181 x 144 132 x 90 181 x 144 181 x 144 302 x 242 416 x 313POWER SUPPLY 12..24 Vac / Vdc 12..24 Vac / Vdc 12..24 Vac / Vdc 12..24 Vac / Vdc 24 Vdc 24 Vdc 24 Vdc

    SERIAL PORT (11AD solo Vdc)2 RS232 / RS4851 RS232

    1 RS485 / 1 RS232 RS485 - CAN - 2 USBRS232 - RS485

    CAN - 2 USBRS232 - RS485

    CAN - 3 USBRS232 - RS485

    CAN - 3 USBRS232 - RS485

    CAN - 3 USB

    ETHERNET 10 / 100 Mbit/s 10 / 100 Mbit/s 10 / 100 Mbit/s 10 / 100 Mbit/s 10 / 100 Mbit/s

    DIGITAL I/O 16 Integrated (mod. 11AD)8 NPN on conn. DB25

    2 Relay 2A See ETD884 (max 1) See ETD884 (max 2) See ETD884 (max 1) See ETD884 (max 1) See ETD884 (max 1)

    ANALOGUE I/O 4 In + 4 Out (0..10V) Integrated (mod. 11AD) See ETD884 (max 1) See ETD884 (max 2) See ETD884 (max 1) See ETD884 (max 1) See ETD884 (max 1)

    SOFT-PLC

    SOFTwARE FEATURESOPERATING SYSTEM Proprietary Proprietary Win CE 6.0 Win CE 6.0 Windows x86 Windows x86 Windows x86

    PROTOCOLS Modbus - RTU Modbus - RTU Modbus - RTU - Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CAN

    CPU ARM V4i ARM V4i Intel® ATOM™ up to 1,6GhzIntel® ATOM™ up to

    1,6GhzIntel® ATOM™ up to

    1,6Ghz

    RAM Back-up 10000 words Back-up 10000 words 128Mb 128Mb Up to 1GB Up to 1GB Up to 1GB

    HARD DISK SSD 16GB SataSSD 64GB SataSSD 16GB SataSSD 64GB Sata

    SSD 16GB SataSSD 64GB Sata

    FANLESS (0-45°C op. temperature)UPS (assisted shut down)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    pROgRAMMINg TOOLSMOVICON X86 (logic - graphics) PLPROG (logic)TD-DESIGNER (graphics)MOVICON CE (logic - graphics)POWER HMI X86 (logic - graphics)POWER HMI CE (logic - graphics)LOGIC LAB (logic)PAGE LAB (graphics)

    10 Summary - Programmable systems

  • Panel PC Programming tools

    PageLabGraphic development environment for HMIs. It interfaces directly to PLC compiler LogicLab and thus interacts easily with SoftPLC variables defined in PLC applications. It also allows to implement small sections of logics in ST (structured text).

    Movicon 11All-in-one development environment for graphics and logic on Windows CE and Windows x86/x64. Inbuilt extensive library of symbols and graphical objects for powerful synoptics. It is also possible to create custom logics using editable scripts in VBA language, VB.Net and Instructions list (AWL).

    LogicLabSoft-PLC development environment. Supporting all 5 programming languages of the standard IEC 61131-3: Instruction List (IL), Structure Text (ST), Ladder Diagram (LD), Function Block Diagram (FDB), Sequential Function Chart (SFC). Pixsys devices and controllers may be easily integrated into networks thanks to “Drag and drop” function.

    Click on page no. for product details p. 44 p. 45 p. 46 p. 47 p. 48 p. 49 p. 50MAIN FEATURES TD240 TD320 TD430 TD570 / TD700 TD750 TD850 TD900

    DISPLAY 3.5” TFT 5.7” TFT 4.3” TFT 480 x 272 5.7” TFT 640 x 4807” TFT 800 x 480 7” TFT 800 x 600 10.4” TFT 800 x 600 15” TFT 1024 x 768

    TOUCH-SCREEN Resistive Resistive Resistive Resistive Resistive Resistive Resistive

    DIMENSIONS (mm) 140 x 100 x 40 (AD) or 65 (11AD) 204 x 170 (front) x 48 140 x 100 (front) x 38 204 x 170 (front) x 48 204 x 160 (front) x 34 325 x 260 (front) x 34 435 x 330 (front) x 38

    PANEL CUT-OUT 132 x 90 181 x 144 132 x 90 181 x 144 181 x 144 302 x 242 416 x 313POWER SUPPLY 12..24 Vac / Vdc 12..24 Vac / Vdc 12..24 Vac / Vdc 12..24 Vac / Vdc 24 Vdc 24 Vdc 24 Vdc

    SERIAL PORT (11AD solo Vdc)2 RS232 / RS4851 RS232

    1 RS485 / 1 RS232 RS485 - CAN - 2 USBRS232 - RS485

    CAN - 2 USBRS232 - RS485

    CAN - 3 USBRS232 - RS485

    CAN - 3 USBRS232 - RS485

    CAN - 3 USB

    ETHERNET 10 / 100 Mbit/s 10 / 100 Mbit/s 10 / 100 Mbit/s 10 / 100 Mbit/s 10 / 100 Mbit/s

    DIGITAL I/O 16 Integrated (mod. 11AD)8 NPN on conn. DB25

    2 Relay 2A See ETD884 (max 1) See ETD884 (max 2) See ETD884 (max 1) See ETD884 (max 1) See ETD884 (max 1)

    ANALOGUE I/O 4 In + 4 Out (0..10V) Integrated (mod. 11AD) See ETD884 (max 1) See ETD884 (max 2) See ETD884 (max 1) See ETD884 (max 1) See ETD884 (max 1)

    SOFT-PLC

    SOFTwARE FEATURESOPERATING SYSTEM Proprietary Proprietary Win CE 6.0 Win CE 6.0 Windows x86 Windows x86 Windows x86

    PROTOCOLS Modbus - RTU Modbus - RTU Modbus - RTU - Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CANModbus - RTU -

    Modbus TCP/IP - CAN

    CPU ARM V4i ARM V4i Intel® ATOM™ up to 1,6GhzIntel® ATOM™ up to

    1,6GhzIntel® ATOM™ up to

    1,6Ghz

    RAM Back-up 10000 words Back-up 10000 words 128Mb 128Mb Up to 1GB Up to 1GB Up to 1GB

    HARD DISK SSD 16GB SataSSD 64GB SataSSD 16GB SataSSD 64GB Sata

    SSD 16GB SataSSD 64GB Sata

    FANLESS (0-45°C op. temperature)UPS (assisted shut down)

    pRODUcTS cOMpARISONRATIO PRICE / PERFORMANCESTOCK TURNOVER

    pROgRAMMINg TOOLSMOVICON X86 (logic - graphics) PLPROG (logic)TD-DESIGNER (graphics)MOVICON CE (logic - graphics)POWER HMI X86 (logic - graphics)POWER HMI CE (logic - graphics)LOGIC LAB (logic)PAGE LAB (graphics)

    11Summary - Programmable systems

  • ADAPTERS/COVER PLATES INFRARED SENSORSNon-contact temperature measurement

    HUMIDITY TRANSMITTERS

    TEMPERATURE SENSORSEASY-UP password for quick set-up

    12 Summary - Sensors and complementary fittings

    Sensors and complementary fittings

    p. 71 p. 71

    PANEL-MOUNTINGADAPTERS

    DIN RAIL MOUNTING ADAPTERS

    p. 60 p. 60 p. 61 p. 60

    PC21-151-301 PC21-151-301-WJ PU151 PYROMINI

    Fixed emissivity-20 to 500°C

    Including air / water cooled housing

    Configurable emissivity USB cable

    for PC connection

    Miniature sensing head - optional

    touchscreendatalogging

    p. 65 p. 65 p. 66 p. 66 p. 67

    RH96 EE06 EE21 EE23 EE375

    Hum. / Temp.OEM applications

    Compact transmittersOEM applications

    High precision Hum. / Temp.

    HVAC

    Hum. / Temp.Industrial

    applications

    Dew pointTemp. transmittersOEM applications

    p. 67 p. 68 p. 68 p. 69 p. 69

    OKPAC SAL / SU / SUL SWTA SIT SGT

    Zero-crossingResistive loads25A..125A / 1ph

    Zero-crossingResistive loads30..75A / 1ph

    Phase-angleResistive / inductive

    Ctrl 4..20mA, 32A / 3ph

    Zero-crossingCtrl 90-240 Vac

    50A / 3ph

    Zero-crossingCtrl 8-32 Vdc

    50A / 3ph

    p. 55 p. 55 p. 57 p. 56 p. 59 p. 61 p. 57 p. 58 p. 58 p. 56

    PT100 PT100 PT100 (OPTIONAL

    TRANSMITTER 4..20mA)

    PT1000 PTC1K NTC10K TCJ TCJ TCK 2000.35.010 SIGNAL CONVERTER

    Class B3 wires

    GSC / TTS cable

    Air probes Class B3 wires

    Class BDIN-B head

    GSC / TTS cablePVC Thermoplastic sealing IP65 / IP67

    KTY82-121GSC / PVC cable

    β3435 Thermoplastic sealing

    IP65 / IP67GSC / TTS cable Washer TCJGSC / TTS cable GSC / TTS cable RTD to 4..20mA

  • THERMOCOUPLEShigh temperature

    POWER SUPPLIES

    PRESSURE TRANSMITTERS

    SSR - SOLID STATE RELAYS

    13Summary - Sensors and complementary fittings

    p. 59

    TC-K

    DIN-B headAlumina sheath

    up 1280°C

    p. 70 p. 70

    MDR DR

    1phOut 24Vdc

    1ph / 3phOut 24Vdc

    p. 62 p. 62 p. 63 p. 63 p. 64

    ECT ECT / NAT ATM.ECO FL-MEEcho

    PTx | MDx | SPX Vertex

    Low range up to 600mBar Range 1..1000Bar

    Submersible transmitters

    Flush membrane transmitters

    Dynisco Melt pressure transmitters

    p. 67 p. 68 p. 68 p. 69 p. 69

    OKPAC SAL / SU / SUL SWTA SIT SGT

    Zero-crossingResistive loads25A..125A / 1ph

    Zero-crossingResistive loads30..75A / 1ph

    Phase-angleResistive / inductive

    Ctrl 4..20mA, 32A / 3ph

    Zero-crossingCtrl 90-240 Vac

    50A / 3ph

    Zero-crossingCtrl 8-32 Vdc

    50A / 3ph

    p. 55 p. 55 p. 57 p. 56 p. 59 p. 61 p. 57 p. 58 p. 58 p. 56

    PT100 PT100 PT100 (OPTIONAL

    TRANSMITTER 4..20mA)

    PT1000 PTC1K NTC10K TCJ TCJ TCK 2000.35.010 SIGNAL CONVERTER

    Class B3 wires

    GSC / TTS cable

    Air probes Class B3 wires

    Class BDIN-B head

    GSC / TTS cablePVC Thermoplastic sealing IP65 / IP67

    KTY82-121GSC / PVC cable

    β3435 Thermoplastic sealing

    IP65 / IP67GSC / TTS cable Washer TCJGSC / TTS cable GSC / TTS cable RTD to 4..20mA

  • PARAMETRICDEVICES

  • 16 Parametric devices

    Memory cards with / without batteryMEMORY CARDSMemory Cards are conceived to support the installer/operator, allowing simplified and time-saving setting of parameters on Pixsys controllers/programmers/timers, particularly if involving serial production or repetitive applications.The version with internal battery (1000 programmings, replaceable) allows quick and error-saving duplication of parameters, not requiring connection to power supply for the controller. USB port ensures connection to PC and software tool Pixsys LABSOFTVIEW.

    Ordering codes2100.30.002 M.c.Par Series ATR171 -ATR236-ATR243-ATR401-DRR2452100.30.003 M.c.Par/Upgrade-Batt. Series ATR121 - ATR141 - ATR142 - ATR171 - ATR236 -

    ATR243 ATR401 - DRR132 - DRR2452100.30.005 M.c.Par Series ATR121-ATR141-ATR142-TCT1012100.30.006 M.c.Par Series ATR421-ATR6212100.30.007 M.c.Par/Upgrade-Batt. Series ATR421-ATR6212100.30.008 M.c.Par Series ATR6202100.30.009 M.c.Upgrade Series ATR500-ATR620

    SW- HW Kit for configuration / setting of Pixsys ATR/DRR/TCT devices

    LABSOFTVIEWConceived for the configuration and monitoring of Pixsys devices ATR/DRR/TCT, the software LabSoftView for Windows is easy to install and to operate. Labsoftview allows to set the parameters and setpoint values. Settings can be saved on file and recalled for further use. Process and setpoint trends can be monitored and graphically visualized to support eventual adjustments of control algorithm and PID settings. The kit includes software on CD, Memory Card with battery and USB cable.

    Ordering codes2100.10.020 KIT Labsoftview software + hardware (memory card + USB cable)

  • 17Parametric devices

    Wiring Plan

    Controller double setpointATR121Main featuresBox 32x74 (front panel) x 53 mmPower supply 12..24 Vac/Vdc or 24Vac/115Vac/230Vac ±15% 50/60 HzConsumption 2 WDisplay 3 digits, 0,56” red + 3 signaling ledsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; front panel: ABS UL94V0 self-extinguishingWeight Approx. 100 gSealing Front panel IP65 (with gasket) , Box IP30, Terminal bloks IP20Quick set-up options Memory Card with/without battery, software LABSOFTVIEW

    Inputs1 configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V,

    Potentiometer 1..6/160 KohmSampling frequency 66ms (frequency 15 Hz)

    Outputs2 Relays 1 Relay 10A/8A - 250 Vac resistive charge + 1 Relay 5A - 250 Vac resistive charge1 SSR 8 Vdc - 20 mA (codes A/B/C) - 15 Vdc - 30 mA (code AD)Serial communication RS485 Modbus RTU - Slave

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned, Dead bandTuning manual or automaticOperating modes Visualizer, Single setpoint, Double setpoint (selection by parameter)Data protection Lock of control / alarm setpoint - Access to parameters by passwordAlarm modes Absolute / Threshold, band, High / Low deviation. Alarm with optional manual resetDouble P.I.D. Heating / Cooling P.I.D.Open / Close logic Open / Close logic for motorized valves

    Ordering codesATR121-AD 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 12..24Vac/VdcATR121-A 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 24VacATR121-B 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 230VacATR121-C 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 115VacATR121-AD-T 1 Analogue Input + 1 Relay 8 A + 1 SSR 12Vdc + RS485 Modbus RTU Slave / Supp. 12..24Vac/Vdc

    summary

  • 18 Parametric devices

    Wiring Plan

    Controller double setpointATR141Main featuresBox 32x74 (front panel) x 53 mmPower supply 12..24 Vac/Vdc or 24Vac/115Vac/230Vac ±15% 50/60 HzConsumption 2 WDisplay 4 digits, 0.4”red + 3 signaling ledsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 100 gSealing Front panel IP65 (with gasket) , Box IP30, Terminal bloks IP20Quick set-up options Memory Card with / without battery, software LABSOFTVIEW

    Inputs1 configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V,

    Potentiometer 1..6/160 KohmSampling frequency 66ms (frequency 15 Hz)

    Outputs2 Relays 1 Relay 10A/8A - 250 Vac resistive charge + 1 Relay 5A - 250 Vac resistive charge1 SSR 8 Vdc - 20 mA (codes A/B/C) - 15 Vdc - 30 mA (code AD)Serial communication RS485 Modbus RTU - Slave

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned, Dead bandTuning manual or automaticOperating modes Visualizer, Single setpoint, Double setpoint (selection by parameter)Data protection Lock of control / alarm setpoint - Access to parameters by passwordAlarm modes Absolute / Threshold, band, High / Low deviation. Alarm with optional manual resetDouble P.I.D. Heating / Cooling P.I.D.Open / Close logic Open / Close logic for motorized valves

    Ordering codesATR141-AD 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 12..24Vac/VdcATR141-A 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 24VacATR141-B 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 230VacATR141-C 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc / Supp. 115VacATR141-AD-T 1 Analogue Input + 1 Relay 8 A + 1 SSR 12Vdc + RS485 Modbus RTU Slave / Supp. 12..24Vac/Vdc

    summary

  • 19Parametric devices

    Wiring Plan

    Three setpoint controllerATR142Main features Box 32x74 (front panel) x 53 mmPower supply 24..230Vac/dc ±15% 50/60 HzConsumption 2 WDisplay 4 digits 0,4” green + 4 digits 0,3” red + 6 signaling ledsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 112 gSealing Front panel IP65 (with gasket) , Box IP30, Terminal bloks IP20Quick set-up options Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes

    Inputs 1 configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V, 0..40mV,

    Potentiometer 1..6/160 Kohm.Sampling time Up to 4,1 ms (Frequency 242 Hz)1 digital input 1/2 setpoint selection, Hold, Run (only if TC, 0..10V, 0/4..20mA, 0..40mV)

    Outputs2 Relays 1 Relay 8A - 250 Vac resistive charge + 1 Relay 5A - 250 Vac resistive charge1 SSR 12 Vdc - 30 mASerial communication RS485 Modbus RTU - Master/Slave

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned, dead bandTuning manual or automaticData protection Lock of command / alarm setpoint - Access to parameters by passwordAlarm modes Absolute / Threshold, band, High / Low deviation. Alarm with optional manual resetSoft-Start Rising gradient expressed as Degrees / Hour Double P.I.D. Heating / Cooling P.I.D.Programmer function Start / Stop, 3 steps pre-programmed cycleTimer function Controller function + single / double Timer Open / Close logic Open / Close logic for motorized valves

    Ordering codesATR142-ABC 1 Analogue Input + 2 Relays 8/5 A + 1 SSR 12Vdc / Supp. 24..230Vac/VdcATR142-ABC-T 1 Analogue Input + 1 Relay 8 A + 1 SSR 12Vdc + RS485 / Supp. 24..230Vac/Vdc

    ATR142-ABC

    CONTROLLER TRIPLE SETPOINT 32X74

    4+4 Digit 1 AI-2 RL-SSR-24/220V

    ATR142-ABC

    MADE IN

    ITALY

    MADE IN

    ITALY

    P02139999

    99999

    LBL01001.RPT

    P0213999999999

    P0213999999999

    ATR142-ABC-T

    CONTROLLER DOUBLE SETPOINT 32X74

    4+4 Digit 1 AI-1 RL-SSR-RS485-24/220V

    ATR142-ABC-T

    MADE IN

    ITALY

    MADE IN

    ITALY

    P02139999

    99999

    LBL01001.RPT

    P0213999999999

    P0213999999999

    summary

  • 20 Parametric devices

    Wiring Plan

    Controller multi-setpoint / Dual inputATR171Main featuresBox 72x72 (front panel) x 99 mmPower supply 24..230Vac/dc ±15% 50/60 HzConsumption 5,5 VADisplay 4 digits 0,5” green + 4 digits 0,3” red + 6 signaling ledsOperating conditions Temperature 0-45 °C, 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; Front panel: Silicon rubber V0Weight Approx. 250 gSealing Front panel IP54 (with gasket), Box IP30, Terminal bloks IP20Quick set-up options Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes

    Inputs 1 Configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V, 0..40mV,

    Potentiometer 1..6/160 Kohm1 Configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K) - (code -23ABC-T)Sampling time Programmable up to 4,1 ms (Frequency up to 242 Hz)1 Digital input 1..4 setpoints selection, Hold, Run (codes -11/12/14ABC)

    Outputs1..3 Relays 1..3 Relays 8A - 250 Vac resistive charge + 1 Relay 5A - 30 V resistive charge (code -14ABC)1 Analogue Selection SSR 12 Vdc - 30 mA / 0..10Volt / 4..20mA as command or retransmission setpoint-process (code

    -23ABC-T)Serial communication RS485 Modbus RTU - Slave (code -23ABC-T)

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportioned. Automatic / Manual regulationTuning Manual / AutomaticData protection Lock of command / alarm setpoint - Access to parameters by passwordAlarm modes Absolute / Threshold, band, High / Low deviation. Alarm with optional manual reset and activation delay.

    Dead band functionSoft-Start Rising gradient expressed as Degrees / HourDouble P.I.D. Heating / Cooling P.I.D.Programmer function 3 steps pre-programmed cycle with Start / StopTimer function Controller function + decremental TimerRemote setpoint Command setpoint corresponding to AI1 4..20 mA / 0..10 V (code -23ABC-T)Double input mode AI1 and AI2 input correlation as mean, difference or addition of process (only for temperature sensors

    TC - RTD on code -23ABC-T)

    Ordering codesATR171-11ABC 1 Analogue Input + 1 Relay 8 A + 1 SSR 12Vdc - Supp. 24..230Vac/VdcATR171-12ABC 1 Analogue Input + 2 Relays 8 A + 1 SSR 12Vdc - Supp. 24..230Vac/VdcATR171-14ABC 1 Analogue Input + 3 Relays 8 A + 1 Relay 5 A(30V) + 1 SSR 12Vdc - Supp. 24..230Vac/VdcATR171-23ABC-T 2 Analogue Inputs + 3 Relays 8 A + 1 SSR / 0..10Volt / 4..20mA + RS485 - Supp. 24..230Vac/Vdc

    summary

  • 21Parametric devices

    Wiring Plan

    Temperature Controller / single setpointATR236Main featuresBox 48x48 (front panel) x 107 mmPower supply 24..230Vac/dc ±15% 50/60 Hz (galvanically isolated)Consumption 5,0 VA, 4WDisplay 4 digits 0,4” green + 4 digits 0,3” redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing, front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 165 gSealing IP65 (Front panel), IP20 (Box and terminal bloks)Quick set-up options Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codes

    Inputs1 Configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K)Sampling time Programmable up to 4,1 ms (frequency up to 242 Hz)

    Outputs1 Relay Relay 5 A - 250 Vac resistive charge1 SSR 12 Vdc - 30 mA max

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedTuning Manual or automaticData protection Lock of control / alarm setpoint, Access to parameters by passwordAlarm modes Absolute / Threshold, band, high / low deviation. Alarm with optional manual resetAuto / Man function Command output percentageSoft-Start Rising gradient expressed as Degrees / Hour

    Ordering codesATR236-ABC 1 Analogue input + 1 Relay 5 A + 1 Ssr - 12Volt

    ATR236-ABC

    TEMP. CONTROLLER DOUBLE SETPOINT 48x48

    4+4 Digit 1 AI-1 RL-SSR-24/220V

    Power consumption 5.5VA

    QC99

    MADE IN

    ITALY

    P02139999

    99999

    MADE IN

    ITALY

    ATR236-ABC

    Power consumption 5.5VA

    TEMP. CONTROLLER DOUBLE SETPOINT 48x484+4 Digit 1 AI-1 RL-SSR-24/220V

    LBL04001.RPT

    P0213999999999

    P0213999999999

    ATR236-ABC

    TEMP. CONTROLLER DOUBLE SETPOINT 48x48

    4+4 Digit 1 AI-1 RL-SSR-24/220V

    Power consumption 5.5VA

    QC99

    MADE IN

    ITALY

    P02139999

    99999

    MADE IN

    ITALY

    ATR236-ABC

    Power consumption 5.5VA

    TEMP. CONTROLLER DOUBLE SETPOINT 48x484+4 Digit 1 AI-1 RL-SSR-24/220V

    LBL04001.RPT

    P0213999999999

    P0213999999999

    summary

  • 22 Parametric devices

    Wiring Plan

    Controller multi-setpointATR243Main featuresBox 48x48 (front panel) x 125 mmPower supply 24..230Vac/dc ±15% 50/60 Hz (galvanic isolation)Consumption 5,5 VA, 4WDisplay 4 digits 0,4 “ green + 4 digits 0,3” redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing, front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 165 g (-20ABC) -185 g (-21ABC/31ABC)Sealing IP65 (Front panel), IP20 (Box and Terminal bloks)Quick set-up options Memory Card with / without battery, software LABSOFTVIEW, or EASY-UP codes

    Inputs1 Configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V,0..40mV,

    Potentiometer 1..6/160 Kohm, T.A (1024 points)Sampling time Programmable up to 4,1 ms (Frequency up to 242 Hz)1 Digital input 1/2..4 setpoint change , Hold, Run, Tuning launch, Start/stop cycle1 T.A. input Selection T.A. 50 mA - 100 ms - 1024 points (codes -21/-31ABC)

    Outputs2/3 Relays Relay 5 A - 250 Vac resistive charge1 SSR 12 Vdc - 30 mA max1 Analogue Selection 4 - 20 mA or 0 - 10 Vdc for command or retransmission PV/SPVSerial communication RS485 Modbus RTU - Slave (code 21ABC-T)

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedTuning Manual or automaticData protection Lock of control / alarm setpoint, Access to parameters by passwordAlarm modes Absolute / Threshold, Band, High / Low deviation. Alarm with optional manual reset. Loop Break Alarm

    functionAuto / Man function Output percentage command also with automatic change in case of sensor failureDouble P.I.D. Heating / Cooling P.I.D.Programmer function Start / Stop pre-programmed cyle with 2/3 stepsSoft-Start Rising gradient expressed as Degrees / HourOpen / Close logic Open / Close logic for motorized valves

    Ordering codesATR243-20ABC 1 Analogue input + 2 Relays 5 A or 1 Relay 5 A + 1Ssr/V/mAATR243-21ABC-T 1 Analogue input + 2 Relays 5 A + 1Ssr/V/mA + RS485 + TAATR243-31ABC 1 Analogue input + 3 Relays 5 A + 1Ssr/V/mA + TAATR243-20ABC-I 2 Analogue inputs (TC) + 2 relays 5A or 1 Relay 5A +1 SSR/v/mAATR243-31ABC-I 2 Analogue inputs (TC) + 3 relays 5A +1 SSR/v/mA+TA

    summary

  • 23Parametric devices

    Wiring Plan

    Controller multisetpoint / dual inputATR401Main featuresBox 48x96 (front panel) x 123 mmPower supply 24..230Vac/dc ±15% 50/60 Hz (with Jumper 24 - 110..230Vac)Consumption 5,5 VA, 4WDisplay 4 digits 0,4 “ green + 4 digits 0,3 “ redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing, front panel: Silicon rubber V0Weight Approx. 350 gSealing IP65 (Front panel), IP20 (Box and Terminal bloks)Quick set-up options Memory Card with /without battery, software LABSOFTVIEW, EASY-UP codes

    Inputs2 Configurables Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V,

    Potentiometer 6/160 Kohm, T.A.Sampling time Programmable up to 4,1 ms (Frequency up to 242 Hz)1 Digital input 2..4 setpoints selection, Hold, Run, Tuning launch, automatic / manual selection1 T.A. input Selection T.A. 50 mA - 100 ms overlapped to AI2

    Outputs2..4 Relays Relay 8 A - 250 Vac resistive charge1 SSR 24 Vdc - 25 mA max1 Analogue Selection SSR 12Vdc - 4..20 mA or 0..10 Vdc for command or retransmission PV/SPVSerial communication RS485 Modbus RTU - Slave

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedTuning Manual or automaticData protection Lock of control / alarm setpoint, Access to parameters by passwordAlarm modes Absolute / Threshold, band, High / Low deviation. Alarm with optional manual reset. Loop Break Alarm

    functionRemote setpoint Command setpoint corresponding to AI2 (4..20 mA / 0..10 V)Double P.I.D. Heating / Cooling P.I.D.Double input mode AI1 and AI2 inputs correlation as mean, difference or addition of process valuesSoft-Start Rising gradient expressed as Degrees / HourOpen / Close logic Open / Close logic for motorized valves

    Ordering codesATR401-22ABC 2 Analogue inputs + 2 Relays 8 A + 1 SSR 12VdcATR401-23ABC 2 Analogue inputs + 3 Relays 8 A + 1 SSR 12VdcATR401-24ABC 2 Analogue inputs + 4 Relays 8 A + 1 SSR 12VdcATR401-22ABC-T 2 Analogue inputs + 2 Relays 8 A + 1 SSR 12Vdc, 1 Output V/mA + RS485ATR401-22ABC-D 2 Analogue inputs + 2 Relays 8 A + 1 SSR 12Vdc, 1 Output V/mA + Digital input

    summary

  • 24 Parametric devices

    Wiring Plan

    Multisetpoint controller / Signals converterDRR245Main featuresBox DIN43880, DIN EN50022 rail mountedPower supply 24..230Vac/dc ±15% 50/60 Hz (galvanically isolated)Consumption 3 WDisplay 4 digits 0,4” green + 4 digits 0,3” redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Polycarbonate V0; Front panel: Silicon V0Weight Approx. 195 gSealing IP65 (Front panel), IP20 (Box and Terminal blocks)Quick set-up options Memory Card with / without battery, software LABSOFTVIEW, EASY-UP codesWiring With terminal extension

    Inputs1 configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V,0..40mV,

    Potentiometer 1..6/160 Kohm, T.A (1024 points)Sampling time Programmable up to 4,1 ms (Frequency up to 242 Hz)1 T.A. input Selection T.A. 50 mA - 100 ms - 1024 points1 Digital input 1/2..4 setpoints selection , Hold, Run, Tuning launch, Start/stop cycle

    Outputs2 Relays Relays 5 A - 250 Vac resistive charge1 SSR 12 Vdc - 30 mA max1 Analogue Selection 4 - 20 mA or 0 - 10 Vdc for command or retransmission PV/SPVSerial communication RS485 Modbus RTU - Slave

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedTuning Manual or automaticData protection Lock Command / alarm setpointAlarm modes Absolute / Threshold, band, High / Low deviation. Loop Break Alarm functionAuto/Man function Output percentage command also with automatic change in case of sensor failureDouble P.I.D. Heating / Cooling P.I.D.Programmer function Start/Stop pre-programmed cycle with 2/3 stepsSoft-Start Rising gradient expressed as Degrees / Hour

    Ordering codesDRR245-21ABC-T 1 Analogue input + 2 Relays 5 A + 1Ssr/V/mA + RS485 + TA

    summary

  • 25Parametric devices

    Wiring Plan

    Temperature controller integrated into SSR unit + current transformer

    DRR450Main featuresBox Module 22,5mm series Celduc ESUC DIN-rail mounting EN50022Power supply 24 Vdc ±10% (galvanically isolated) from RS485 and input (no OUT 2)Consumption 1 WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Polycarbonate V0Weight Approx. 75 gSealing IP20 (Box and Terminal blocks)Quick set-up options Software LABSOFTVIEWWiring Terminal extension on wiring system, Plug-in SSR module

    Inputs1 configurable Selection TC, K, J, T, E1 T.A. / Current transformer Integrated Current Transformer with 55A FS - resolution 0,1A

    Outputs1 SSR integrated 5Volt - 20mA1 SSR auxiliary 24 Vdc - 50 mA maxSerial communication RS485 Modbus RTU - Slave (9600..115200 Baud)

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedTuning Manual or automaticAlarm mode Absolute / Threshold, band, High / Low deviation. Loop Break Alarm functionAuto/Man function Output percentage command also with automatic change in case of sensor failureDouble P.I.D. Heating / Cooling P.I.D.

    Ordering codesDRR450-12AD 1 Analogue input + 1 SSR Out. integrated + 1 SSR Out auxiliary + RS485 + TA / Current Transformer

    Ordering codes series SSR series SU / SUL (terminal block for DRR450)2200.00.085 SSR 30A / 24-400Vac / Ctrl 3,5-32Vdc led and heatsink2200.00.083 SSR 35A / 24-600Vac / Ctrl 3,5-32Vdc2200.00.079 SSR 50A / 24-600Vac / Ctrl 3,5-32Vdc2200.00.084 SSR 75A / 24-600Vac / Ctrl 3,5-32Vdc2200.00.100 Heatsink for 32A with DIN adapter2200.00.099 Heatsink for 50A with DIN adapter

    summary

  • 26 Parametric devices

    Wiring Plan

    Indicator - Panel meterSTR550Main featuresBox 96x48 (Front panel) x 48 mm / or 1/8DinPower supply 24..230Vac/dc ±10% 50/60 Hz (galvanically isolated)Consumption 6 WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Polycarbonate V0Weight Approx. 165 gSealing IP54 (Front panel) with gasket - IP20 (Box and Terminal blocks)Quick set-up options Software LABSOFTVIEW and/or MemorycardWiring extractable terminal blocks and spring locking

    Inputs1 Analogue (16 bit) Selectable for TC type K, S, R, J, T, E, N, B (automatic compensation of the cold junction 0..50 °C), ther-

    moresistances PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (β 3435K), process signals 0-10 V (54000 points), 0/4-20mA (40000 points), 0-60 mV (16000 points), Potentiometer 6 KΩ, 150 KΩ (50000 points) Customizable linear input (max 16 steps)

    2 Digital PNP inputs programmable for Run / Hold / Tare-Zero / Alarms rearmament / Peaks reset/ Min. peak reset Activate-Reset Sum / Parameters-Setpoints Lock

    Outputs2 Relays Contacts 2A - 250Volt AC (resistive charge)2 analogue outputs 1 output 0..10Volt (60000 points) - 1 output 0/4..20mA (60000 points)1 Auxiliary output 24 Vdc / 30mA for external sensors supply (loop-powered)Serial communication RS485 Modbus RTU - Slave (1200..115200 Baud) galvanically isolated from Power supply / Inputs / Outputs

    Software featuresAlarms regulation ON - OFF with hysteresisAlarm mode Absolute / Threshold, Band with instantaneous / delayed / retentive / by digital input activation, Sensor

    failure / Activation by serial lineSum Function By digital input or by keyboard it is possible to sum different process measurements over timeTotalizer Function Visualisation of instant process value and total value since last resetTrend visualization Trend visualisation with selectable time basis 1s to 3600sAnalogue retransmission Process values / SetpointsDigital transmission via RS485 Process values / Setpoint / ParametersLatch-on function Semi-automatic setting of limits/ calibration values for analogue inputData Logger Data logger function with selectable time basis 1s to 3600s, tot memory 2,5k wordsText menus English/Italian/Deutsch/French/Spanish

    Ordering codesSTR550-12ABC-T 1 Analogue input + 2 Relays 2A + 1 Out 0..10V + 1 Out 0/4..20mA + RS485 Modbus RTU /Slave

    +-

    TC

    1812

    1711

    1610

    159

    148

    137

    RS485

    PTCNTC

    PT100-NI100

    V/I+-

    +-

    0V

    AO10/4...20mA

    +-

    +-

    AO20...10V

    SUPPLY24...230VAC/DC6

    5

    4

    3

    2

    1

    Q12A 230VResistive1/8HP

    Q22A 230VResistive1/8HP

    +24Vdc

    DI.1

    DI.2

    summary

  • 27Parametric devices

    Wiring Plan

    Process controller / Programmer 15 cycles / 45 stepsATR421Main featuresBox 48x96 (front panel) x 123 mmPower supply 24..230Vac/dc ±15% 50/60 Hz (selection 24 - 110..230Vac with jumper)Consumption 5,5 VA, 4WDisplay 4 digits 0,4” green + 4 digits 0,3” redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; Front panel: Silicon rubber V0Weight Approx. 350 gSealing IP65 (Front panel), IP20 (Box and Terminal bloks)Quick set-up options Memory Card with / without battery, software LABSOFTVIEW

    Inputs1 configurable Selection TC, K, J, S, R, PT100,PT500, PT1000, Ni100, PTC1K, NTC10K (B 3435K), 0/4..20 mA, 0..10 V1 digital input 1..9 cycle selection, Hold, Run, “Open door” lock (code -14ABC)1 potentiometer input Position signal by potentiometer for servo/motorized-valves

    Outputs2..4 Relays Relay 8 A - 250 Vac resistive charge1 SSR 24 Vdc - 25 mA max1 Analogue Selection SSR 12Vdc - 4..20 mA or 0..10 Vdc for command or retransmission PV/SPV (code -12ABC-T)Serial communication RS485 Modbus RTU - Slave (code -12ABC-T)

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time-proportionedTuning manual or automaticData protection Lock of control / alarm setpoint, Access to parameters by passwordAlarm modes Absolute / Threshold, band, High / Low deviation, timed auxiliary programmable for single stepsGas mode Open / Close logic for motorized valves, management of burners and fan, GID selection (management of

    burners during falling steps)Waiting function Special function to compensate differences SPV / PV in case of overloaded systemCycle recovery Resume the cycle after unexpected power failureSetpoint controller mode Regulation on a fixed setpoint (function might be enabled from general menu or during a cycle in

    progress)Delayed start Cycle start delayed by decremental timer

    Ordering codesATR421-14ABC 1 Analogue inputs + 1 digital input + 4 Relays 8 A + 1 SSR 12VdcATR421-12ABC-T 1 Analogue inputs+ 2 Relays 8 A + 1 SSR 12Vdc, 1 Output V/mA + RS485

    summary

  • 28 Parametric devices

    Wiring Plan

    Process controller / Programmer 15 cycles / 20 stepsATR620Main featuresBox 72x72 (front panel) x 99 mmPower supply 24/110/230Vac ±15% 50/60 Hz (selection with jumpers)Consumption 4WDisplay 4 digits 0,56” green + 4 digits 0,4” red + ledOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; Front panel: Silicon rubber V0Weight Approx. 530 grSealing IP65 (Front panel) , IP20 (Box and Terminal bloks)Quick set-up options Memory Card without battery

    Inputs2 configurables Selection TC, K, J, S, R, T, E, PT100, Ni100, 0/4..20 mA, 0/1..10 V2 digital input 1..9 cycle selection, Hold, Run, “open door” lock

    OutputsRelays 2 / 3 Relays 8 A - 250 Vac resistive charge1 SSR 12 Vdc - 30 mA maxSerial communication RS485 Modbus RTU - Master/Slave

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedData protections Lock of command / alarm setpoint, Access to parameters by passwordAlarm mode Absolute / Threshold, band, High / Low deviation, timed auxiliary programmable for single stepsWaiting function Special function to compensate differences SPV / PV in case of overloaded systemCycle recovery function Resume the cycle in case of unexpected power failureSetpoint controller mode Regulation on a fixed setpoint (function might be enabled from general menu or during a cycle in

    progress)Delayed start Cycle start delayed by decremental timer

    Ordering codesATR620-21ABC 2 Analogue inputs + 2 Relays 8 A + 1 SSR 12Vdc + RS485ATR620-22ABC 2 Analogue inputs + 3 Relays 8 A + RS485

    summary

  • 29Parametric devices

    Wiring Plan

    Process controller / Programmer 15 cycles / 45 stepsATR621Main featuresBox 72x72 (front panel) x 99 mmPower supply 24..230Vac/dc ±15% 50/60 HzConsumption 5,5 VADisplay Display 4 digit 0,5” green + Display 4 digit 0,3” red + 9 LedsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; Front panel: Silicon rubber V0Weight Approx. 250 gSealing Front panel IP54 (with gasket), Box IP30, Terminal bloks IP20Quick set-up options Memory Card whit/without battery, software LABSOFTVIEW

    Inputs1 configurable Selection TC, K, J, S, R, N, E, PT100, 0/4..20 mA, 0..10 V1 digital input 1..5 cycle selection, Hold, Run, “open door” lock, Emergency

    OutputsRelays 2 / 3 Relays 8 A - 250 Vac resistive chargesRelays 1 Relay 5 A - 30 Vac1 Linear 0/4..20mA or 0..10Volt1 SSR 12 Vdc - 30 mA maxSerial communication RS485 Modbus RTU - Master/Slave

    Software featuresControl Algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedAutotune Manual/AutomaticData protection Access to parameters by passwordAlarm mode Absolute/Threshold, band, High/Low deviation, timed auxiliary programmable for single steps.PV/SPV retransmission Analogue in Volt/mA or RS485 serialWaiting function Special function to compensate differences SPV / PV in case of overloaded systemCycle recovery function Resume the cycle in case of unexpected power failureSetpoint controller mode Regulation on a fixed setpoint (function might be enabled from general menu or during a cycle in

    progress)Delayed start Cycle start delayed by decremental timer

    Ordering codesATR621-12ABC 1 Analogue input + 2 Relays 8 A + 1 SSR 12Vdc + 1 Digital inputATR621-13ABC-T 1 Analogue input + 3 Relays 8 A + 1 Output V/mA/SSR + RS485ATR621-14ABC 1 Analogue input + 3 Relays 8 A + 1 Relay 5A (30V) + 1 Digital input

    summary

  • 30 Parametric devices

    Wiring Plan

    Plug-in process controller 15 cycles / 18 stepsATR902Main featuresBox 120 x 65 (front panel) x 65 mmPower supply 24..230Vac/Vdc ±15% 50/60 HzConsumption 4WDisplay Display 4 digits 0,56” red + 4 digits 0,4” green + BargraphOperating conditions Temperature 0-45 °C, Humidity 35..95 RH%Material Box: ABS; Front panel: polycarbonateWeight Approx. 550 grSealing IP65 (Front panel), IP20 (Box and Terminal bloks)Accessori Connector 7poles/female (kiln side), Bracket for panel mounting

    Inputs1 Configurable TC K, S, R, J ,T , E, N with selection by parameter

    OutputsRelay 1 Relay 1A - 250 Vac resistive charge + 1 Relay 1A - 250 Vac alarm / auxiliary

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedTuning Automatic, Automatic predictiveData protection Access to parameters by password, Setpoint modification during cycle only if enabled by parameterAlarm options Absolute / Threshold, band, High / Low deviation, timed auxiliary programmable on single stepsHold function Hold current setpoint value, with Start / Stop by keyboardWaiting function Special function to compensate differences SPV / PV in case of overloaded system or system inertiasCycle recovery function Resume the cycle after unexpected power failureSetpoint controller mode Regulation on a fixed setpoint (function might be enabled by general menu or during a cycle in progress)Delayed start cycle start delayed (function might be enabled by parameter)

    Ordering codesATR902-12ABC 1 Analogue input + 2 Relays 1A - 230Vac/Vdc0400.70.001 Harting connector 8P (optional)1300.20.043 Wall mounting support

    summary

  • 31Parametric devices

    Wiring Plan

    Main featuresBox 251x146 (front panel) x 66 mmPower supply 12..24Vac/Vcc ±10% 50/60 HzConsumption 10WDisplay Graphic LCD 240x128, monochrome, Reverse option, programmable contrast and backlighting operationOperating conditions Temperature 0-45 °C, Humidity 35..95 RH%Material Box: chromed steel; front frame: ABS; Keyboard: polycarbonateWeight Approx. 1350 grSealing IP65 (Front panel), IP20 (Box and Terminal bloks)Memory Card Upload/download parameters and cycles, Firmware upgrade

    InputsAnalogue-digital inputs See PL300

    OutputsAnalogue/digital outputs See PL300Serial communication RS485 Modbus RTU - Master, RS232, RS422

    Software featuresControl algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time proportionedData protection Access to parameter by password, special password to define operator access levelsAlarm options Absolute / Threshold, band, High / Low deviation, auxialiry functions programmable for each step,

    programmable type of action on the running cycle, text of alarm messages may be entered by keyboard, alarm source selectable by the user

    Waiting function Special function to compensate differences SPV / PV in case of overloaded systemCycle recovery function Resume the cycle after unexpected power failureFunctions for gas-fired kilns Management of modulanting valves by additional PL250Visualization options Selection of visualized process values, selection of menus related to function keys, selectable language

    (Italian, English, German), optional customer logo loaded at starting

    Ordering codesATR313-1AD Graphic terminal, LCD display, alphanumeric keyboardAcquisition modules See PL3002100.30.001 Memory card Series TD240-TD320-ATR313

    RS232C

    7

    12

    11

    0V

    TX232

    RX232

    RS422\485

    14

    18

    17

    16

    15

    RX +

    RX -

    0V

    TX+/RX+

    TX -/RX -

    5

    4

    9

    RS485

    RS485-

    RS485+

    0V

    DB25 DB9

    0V

    ALARM + V

    12 ÷ 24Vac /dc10VA

    1

    3

    2

    +V

    ALIMENTAZIONESUPPLY

    Graphic terminal / Process controller 20cycles / 30 stepsATR313

    summary

  • 32 Parametric devices

    Wiring Plan

    Timer - Counter - Tachometer - Multi-function device + RS485

    TCT101Main featuresBox 32x74 (front panel) x 53 mmPower supply 24..230Vac/Vdc ±15% 50/60 HzConsumption 3 VADisplay 4 digits 0,4” green + 4 digits 0,3” redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; Front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 100 gSealing Front panel IP65 (with gasket), Box IP30, Terminal blocks IP20Quick set-up options Memory Card with / without battery, software LabSoftView

    Inputs3 Digital Selectable as NPN - PNP - TTL, both high/low/rising edge levelInput I3 Input selection by potentiometer 5/10 KOhm for entering of setpoint value (resolution 1000 points)

    Outputs1/2 Relays 2 Relays 5A - 250 Vac resistive charge (codes -1/2/3) 1 Relay 5A - 250 Vac resistive charge (codes -4ABC-T)Serial communication RS485 Modbus RTU - Slave (code -4ABC-T)

    Software featuresTimer input selection Start, Stop, Hold, Reset, WaitRanges Programmable time bases (s/100 , s/10 , s, min , hours)Counter input selection Up, Down, Lock, HoldCounting frequency Incremental/Decremental up to 100KhzCounter functions Count frequency visualization on red display for Flowmeter functionTachometer input selection For mono/bi-directional Push/Pull or Line/Driver encoders up to 100KhzTachometer functions Maximum / Minimum peakData protection Parameters protected by password

    Ordering codesTCT101-1ABC Timer - settable in 5 modesTCT101-2ABC Counter - incremental, decremental or bi-directional (encoder)TCT101-3ABC Tachometer - for Push-Pull / Line-Driver encoders (mono/bi-directional)TCT101-4ABC-T Timer / Counter / Tachometer - with RS485 Modbus RTU/slave serial communication

    5A

    5A 5A 5A

    5A 5A 5A

    summary

  • 33Parametric devices

    Wiring Plan

    Timer - Counter TCT201Main featuresBox 48x48 (front panel) x 107 mmPower supply 24..230Vac/Vdc ±15% 50/60 HzConsumption 3 VADisplay 4 digits 0,4” green + 4 digits 0,3” red + ledOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing; Front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 100 gSealing Front panel IP65 (with gasket), Box IP30, Terminal blocks IP20Quick set-up options Memory Card with / without battery, software LabSoftView

    Inputs3 Digital Selectables as NPN - PNP - TTL, both on high/low/rising edge levelInput I3 Input selection by potentiometer 5/10 KOhm for setting of setpoint value (resolution 1000 points)

    Outputs2 Relays 2 Relays 8 A - 250 Vac resistive charge

    Software featuresTimer inputs selection Start, Stop, Hold, Reset, WaitRanges programmable Time basis s/100, s/10, s , min , hoursCounter inputs selections Up, Down, Lock, HoldCount frequency Incremental / Decremental up to 100KhzCounter functions Counting frequency visualization on red display for flowmeter functionTachometer input selection For mono/bi-directional Push/Pull or Line/Driver encoders up to 100KhzTachometer functions Maximum / Minimum peakData protection Parameters protected by password

    Ordering codesTCT201-1ABC Timer - settable in 5 modesTCT201-2ABC Counter - incremental or decrementalTCT201-3ABC Tachometer - for Push-Pull / Line-Driver encoders (mono/bi-directional)

    Same connections for TCT201-2/3

    summary

  • 34 Parametric devices

    Wiring Plan

    Thermostat for refrigeration / HVACATR131Main featuresBox 32x74 (front panel) x 53 mmPower supply 24Vac/115Vac/230Vac ±15% 50/60 HzConsumption 3 WDisplay 3 digits 0,56” red + 3 signaling ledsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: Noryl UL94V1 self-extinguishing, front panel: PC ABS UL94V0 self-extinguishingWeight Approx. 100 gSealing Front panel: IP54 (with gasket) , Box IP30, Terminal bloks IP20Quick set-up options Memory Card with / without battery

    InputsSensors 1 NTC10K - B 3435K (ATR131-1x) / 2 NTC10K - B 3435K (ATR131-3x)Accuracy 0.5%±1digit1 Digital input 1/2 setpoint selection, Heat/Cool regolation selection

    OutputsCompressor 1 Relay 10A - 250 Vac resistive chargeDefrosting 1 Relay 8A - 250 Vac resistive charge (ATR131-3x)Fans 1 Relay 5A - 250 Vac resistive charge (ATR131-3x)

    Software featuresControl algorithms ON - OFF with hysteresisDefrosting functions Programmable defrost frequency and mode, time counting type, end-defrosting temperature and

    maximum defrosting timeData protection Lock against close compressor starts, Lock of control setpoints, access to parameters by password.Heating function NTC range selection -40..50°C or 0..100°C

    Ordering codesATR131-1A 1 Inp. NTC - 1 Relay / Supp. 24 Vac +/- 10% 50/60HzATR131-1B 1 Inp. NTC - 1 Relay / Supp. 220 Vac +/- 10% 50/60HzATR131-1C 1 Inp. NTC - 1 Relay / Supp. 115 Vac +/- 10% 50/60HzATR131-3A 2 Inp. NTC - 3 Relays / Supp. 24 Vac +/- 10% 50/60HzATR131-3B 2 Inp. NTC - 3 Relays / Supp. 220 Vac +/- 10% 50/60HzATR131-3C 2 Inp. NTC - 3 Relays / Supp. 115 Vac +/- 10% 50/60Hz

    summary

  • 35Parametric devices

    Wiring Plan

    DIN rail mountedController for refrigeration / HVAC

    DRR132Main featuresBox DIN43880, Din rail mounted DIN EN50022Power supply 230Vac ±15% 50/60 Hz (galvanic isolation)Consumption 3 WDisplay 4 digits 0,4” green + 4 digits 0,3” redOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Box: polycarbonate V0; Front panel: silicon V0Weight Approx. 195 gSealing IP65 (Front panel), IP20 (Box and terminal bloks)Quick set-up options Memory Card with / without battery, extractable terminal blocks

    InputsSensor inputs 2 selectables for PTC1K, NTC10K (B 3435K)Fixed 1 for NTC10K (B 3435K)Sampling time 20 msAccuracy 0,5% +/- 1 digitDigital inputs 2, selectable for lights command or setpoint modification

    OutputsCompressor Relay 30 A - 250 Vac resistive chargeDefrosting Relay 8 A - 250 Vac resistive chargeLights Relay 8 A - 250 Vac resistive chargeFan Relay 8 A - 250 Vac resistive charge1 SSR 24 Vdc - 25 mA max for Buzzer / Auxiliary commandSerial communication RS485 Modbus RTU - Slave

    Software featuresControl algorithms ON - OFF with hysteresisDefrosting functions Programmable defrosting frequency and mode, time counting type and maximum defrosting timeData protections Lock against closer compressor starts, Lock of control setpoints, Access to parameters by password

    Ordering codesDRR132-4B-T 2 Inp. NTC10K, PTC1K + 4 Relays 30A/8 A + 1 Static 12Vdc + RS485 Modbus RTU / Slave

    summary

  • PROGRAMMABLESYSTEM

  • Wiring plan38 Programmable systems

    PLC board 11 Inp / 9 OutEPL101Main featuresSize 151 x 80 mmPower supply 24/230 Vac ±15% 50/60 Hz transformer with double primaryConsumption 4WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Weight Approx. 280 gr.Wiring harness Extractable terminal bloks or PlugConnection for display (Optional) 26 poles connector for customized displays (7 segments)

    InputsAnalogues 4 selectables for TC, K, J, S, R, T, E, PT100, Ni100, 0/4..20 mA, 0/1..10 V (for more details see technical

    documentation)Digitals 6 inputs PNP + 1 input NPNInputs for Encoders 2 Digitals (overlapped to input PNP) for bi-directional encoder (1Khz), 1 Digital (overlapped to input NPN)

    for mono-directional encoder (2 Khz)

    OutputsDigitals 5 Relays 5A resistive charge + 1 relay 16A resistive chargeAnalogues 1 0..5Volt 8 Bit for commandOpen- Collector 2 outputs max 20mACommunication ports 1 serial RS232 on plug + 1 serial RS485 on Plug or on extractable terminal block

    Software featuresProgramming Pixsys PLprog software, Ladder diagrams; 128 marker (logic relays), 64 bistables, 96 timer 16 bit, 32

    up-down counters, mathematic and logic functions, rescale functions, contacts on bitCommunication protocols Modbus RTU master / slave; Free-Port mode for Modem protocols or proprietary devicesMemory 64Kbyte Flash for programming, 200 words Ram, 1000 wors EEprom, external data memory MMC 32K

    words optionalClock Real-Time clock with Back-up battery (optional)Analogue input control algorithms P, PI, PID, PD

    Ordering codesEPL101-1AB PLC 4 An. Inp. + 6 Digital PNP + 1 NPN + 6 relays + 2 outputs Open-Collector 20mA + 1 output 0..5 Volt (8 bit)KIT-MORS-EPL101 Kit Terminal blocks for PLC board EPL1012100.30.010 M.c.Upgrade Series PL250-PL260-PL300-EPL1012100.30.011 Expansion Memory 32K PL250EPL101-RTC Clock for EPL 101SB-TERM5 LED Display for EPL101 (5 Digits, 6 keys, 5 LED)

    summary

  • Wiring plan39Programmable systems

    PLC 8+4 Inp. / 8+1 OutPL110Main featuresBox Standard DIN43880 108 x 90 x 64 (H) mm, Mounting clips DIN RAIL EN50022Power supply 2 4Vac/Vdc ±15% 50/60 HzConsumption 6WOperating conditions Temperature 0-45 °C, humidity 5..95 RH%Material Noryl V0Weight ca.250 gSealing IP20 BoxTerminal blocks Extractable

    InputsAnalogue AI 1 0/4..20mA (1024 points); AI 2 0..10Volt (1024 points); AI 3 NTC-10K (-40..+125°C accuracy 0,5°C) + AI 4

    NTC-10K (-40..+125°C accuracy 0,5°C), AI 3 and AI 4 Potentiometer (10K)Digital 8 PNPEncoder inputs 2 Encoder bidirectional (overlapped to 4 PNP inp.) 15 KHz / or 25KHz for single Encoder

    OutputsRelays 8 Out 2A/250Vac/30Vdc resistive load (cosφ=1) or 1A/250Vac/30Vdc inductive load (cosφ=0,4) 6A max

    total current (Q1..Q8)Analogue 1 0..10Volt (8 bit/256 points)Programming port 1 USB type B Serial port, 2 RS485 on extractable terminal block (max. 57600 Baud) galvanically isolated

    from power supply and inputs (not between themselves)

    Software featuresProgramming Software Pixsys PLprog, Ladder diagrams; 128 markers (logic relays), 32 bistables, 64 timers 16 bit, 16

    up-down counters, mathematical and logic functions, range - rescale, bit contacts, 2 timed interrupts (min. 1 ms)

    Scanning cycle min. 2 msCommunication protocols Modbus RTU Master/Slave; free-port for Modem or proprietary devicesMemory 64Kbyte Flash for programming, 350 words Ram retentive (accumulator, 6 months), 1000 words EEprom,

    internal MMC 13000 words data storageClock Real-Time clock, Back-up batteryControl algorithms for analogue inputs P, PI, PID, PD

    Ordering codesPL110-1A PLC 2 An.Inp. NTC-10K / Potentiometer + 1 0..10Volt (10Bit) + 1 0/4..20mA (10Bit)+ 8 Inp. PNP + 8 relay Out

    2A + 1 Out 0..10 Volt (8 bit)PL110-2A PLC 2 An.Inp. NTC-10K / Potentiometer + 1 0..10Volt (10Bit) + 1 0/4..20mA (10Bit)+ 8 Inp. PNP + 8 relay Out

    2A + 1 Out 0..10 Volt (8 bit) with optional graphic OLED display2100.30.010 M.c.Upgrade Series PL250-PL260-PL300-EPL101-PL110

    summary

  • Wiring plan40 Programmable systems

    PLC 20 Inp / 12 OutPL250Main featuresBox Standard DIN43880 160 x 90 x 58 (H) mm with DIN RAIL mounting fitting EN50022Power supply 12..24Vac/Vdc ±15% 50/60 HzConsumption 10WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Noryl V0Weight Approx. 375 gr.Sealing IP20 Box

    InputsAnalogue (10bit) 4 inp. 0..10Volt or 2 inp. 0..20mA (code -10AD)Analogue (16bit) 4 selectable for TC, K, J, S, R, T, E, PT100, Ni100, 0/4..20 mA, 0/1..10 V for more details see technical

    documentation (code -11AD)Digital 16 inputs PNPInputs for Encoders 2 bidirectional encoders (overlapped to 4 inputs PNP) 15 KHz simultaneously / 30KHz singleAuxiliary power supply Terminal for Potentiometer power supply 10,0 VoltTrimmer 2 for regulations and process variables

    OutputsDigital 12 relay outputs 5A - resistive chargeAnalogue 2 0..10Volt , 8 Bit (overlapped to 2 inputs)Programming port 2 serial RS232 on PlugCommunication port 1 serial RS485 on Plug or on extraible terminal ( max. 57600 Baud)

    Software featuresProgramming Software Pixsys PLprog, Ladder diagrams; 128 markers (logic relays), 64 bistables, 96 timers 16 bit, 32

    up-down counters, mathematical and logic functions, range - rescale, contact bits, 2 timed interrupt (min. 1 ms)

    Scanning cycle min. 2 msCommunication protocols Modbus RTU master/slave; Free-Port for Modem or proprietary devicesMemory 64Kbyte Flash for programming, 200 words non-volatile Ram memory (6 months), 1000 words EEprom,

    optional MMC 13000 wordsClock Real-Time clock, Back-up batteryControl algorithms P, PI, PID, PD

    Ordering codesPL250-10AD PLC with 4 An. Inp. (10 bit) + 12 relays 5APL250-11AD PLC with 4 An. Inp. (16 bit for Tc/RTD) + 12 relays 5A2100.30.010 M.c.Upgrade Series PL250-PL260-PL300-EPL1012100.30.011 Expansion Memory 32K PL250

    summary

  • Wiring plan41Programmable systems

    PLC 20 Inp / 16 OutPL260Main featuresBox Standard DIN43880 160 x 90 x 58 (H) mm with DIN rail mounting fitting EN50022Power supply 12..24 Vdc ±15% 50/60 HzConsumption 10WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Noryl V0Weight Approx. 375 gr.Sealing IP20 Box

    InputsAnalogue 4 Selectable for TC, K, J, S, R, T, E, PT100, Ni100, 0/4..20 mA, 0/1..10 V (for more details see technical

    documentation)Digitals 16 PNP inputsInputs for Encoders 2 Bidirectional encoders (overlapped to 4 PNP inputs) 15 KHz simultaneously / 30KHz single

    OutputsDigital 16 static outputs 700 mA /each output (4A max for groups of 8)Analogue 2 out 0..10Volt - 8 bit + 2 out 0..12,5Volt - 13 bitProgramming port 1 serial RS232 on PlugCommunication port 1 serial RS485 on Plug or on extractable terminal (max. 57600 Baud) + 1 Bus for CANopen (max. 1 MBaud)

    RS232

    Software featuresProgramming Pixsys PLprog software, Ladder diagrams; 128 marker (logic relays), 32 bistables, 64 timers 16 bit, 16

    up-down counters, mathematic and logic function, Range - rescale function, contact on bit, 2 timed interrupts (min. 1 ms)

    Scanning cycle minimum 2 msCommunication protocols Modbus RTU master/slave; Free-Port mode for Modem or proprietary devices; CANopen MasterMemory 64Kbyte Flash for programming, 350 words non-volatile Ram , 1000 words EEprom, internal MMC data

    memory 13000 wordsClock Real-Time clock , Back-up batteryControl algorithms for analogue inp. P, PI, PID, PD

    Ordering codesPL260-11AD PLC 4 An. Inp. + 16 Digitali PNP + 16 static outputs 700mA + 4 outputs 0..10 Volt (10/12 bit)2100.30.010 M.c.Upgrade Series PL250-PL260-PL300-EPL101

    summary

  • Wiring plan42 Programmable systems

    I/O - Data acquisition / actuation module for PLC / HMIPL300Main featuresBox Standard DIN43880 160 x 90 x 58 (H) mm with DIN RAIL mounting fittings EN50022Power supply 12..24Vac/Vdc ±15% 50/60 HzConsumption 10WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Noryl V0Weight Approx. 460 gr.Sealing IP20 Box

    InputsAnalogue 4 Selectable for TC, K, J, S, R, T, E, PT100,PT1000, Ni100, 0/4..20 mA, 0/1..10 V, 0..50mVSampling time 250 msResolution 14 bitDigital 6 PNP inputs

    OutputsDigital 12 Relays 5A resistive chargeAnalogue 2 selectable by dip-switch as 0..10Volt or 4..20mA for retransmission or commandCommunication ports 1 serial RS232 on plug + 1 serial RS485 on Plug or on extractable terminal

    Software featuresHMI - Operator interface ATR313/ATR640 for kilns or environmental chambers, TD240 / TD320 / SCADA for other industrial

    applications for supervisory/monitoring functionsCommunication protocol Modbus RTU SlaveAnalogue inputs control algorithms ON - OFF with hysteresis, P., P.I., P.I.D., P.D. time-proportioned

    Ordering codesPL300-10AD 4 An. Inp. + 6 Digital + 12 relays + 2 outputs V/mAPL300-30AD 4 An. Inp. + 6 Digital + 4 SSR-12Volt + 8 relays + 2 outputs V/mA2100.30.010 M.c.Upgrade Series PL250-PL260-PL300-EPL101

    summary

  • Wiring plan43Programmable systems

    I/O expansion module for PLC / HMIMCM260Main featuresBox Standard DIN43880 90 x 71 x 58 (H) mm with DIN RAIL mounting fitting EN50022Power supply 12..24Vac/Vdc ±15% 50/60 HzConsumption 2W .. 4WOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Noryl V0Weight Approx. 255 gr.Sealing IP20 Box

    InputsAnalogue 16 bit 4 Selectable for TC, K, J, S, R, PT100, PT500, PT1000, Ni100, PTC, NTC, 0/4..20 mA, 0/1..10 V, Potentiometer

    FS 6/160Kohm (code -5AD)Analogue 10 bit 2 Inputs 0..10Volt / 500 Hz (overlapped to 2 digital inputs on codes -2AD/-3AD/-4AD)Digital 8 Inputs PNP (codes -3AD/-4AD) 16 inputs PNP (code -2AD)Counters / Encoder 2 Input for counters of 2Khz or 1 input for incremental Encoder at 10Khz (overlapped to 2 digital inputs on

    codes -2AD/-3AD/-4AD)

    OutputsDigital 16 Digital 700mA (code -1AD), 8 Digital 700mA (code -3AD)Analogue 2 selectable as 0..10Volt or 4..20mA 12 Bit (code -5AD)Relays 8 relays 5A resistive charge (code -4AD)Communication ports 1 serial RS485 on extractable terminal + 1 Bus CANopen with EDS file for net configuration

    Software featuresHMI - Operator interface TD240 / TD320 / TD430 / TD570 / TD700 / TD750 / TD850 / TD900 / SCADA for control or supervision of any

    industrial plantsProtocol for RS485 Modbus RTU Slave up to 57600 Baud

    Ordering codesMCM260-1AD 16 Digital outputs 700mA (max 4A tot)MCM260-2AD 16 Digital outputs PNPMCM260-3AD 8 Digital outputs 700mA (max 4A tot) + 8 Digital inputs PNPMCM260-4AD 8 Relay outputs 5A + 8 Digital inputs PNPMCM260-5AD 4 Universal analogue inputs + 2 Analogue outputs V/mA

    summary

  • Wiring plan44 Programmable systems

    Touch-screen HMI 3,5” 256 colors, integrated PLCTD240Main featuresBox 140x100 (front panel) x 40 mm (-AD) or 65mm (-11AD)Power supply 12..24Vac/Vdc ±15% 50/60 Hz (12..24 Vdc for TD340-11AD)Consumption 8WDisplay Display LCD TFT 3,5” - 256 Colours, Integrated resistive Touch-screenOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Front panel: aluminium with polycarbonate coverage; Box: chromed steelWeight Approx. 690gr code-AD, approx. 750gr code-11ADSealing IP54 (Front panel), IP20 (Box and Terminal bloks)Quick set-up options SLOT Memory Card for programs download (Ladder+graphics)Expansions Modules MCM260-1/2/3/4/5 or other Modbus devices

    InputsAnalogue 4 Selectable for TC, K, J, S, R, T, E, PT100,PT1000, PT500, Ni100, NTC10K, (B 3435K), PTC1K (kty1000) 0/4..20

    mA, 0/1..10 V (code TD240-11AD)Digital 16 Selectable as inputs / outputs (code TD240-11AD)Input for encoder 3 encoder/counter 24bit up to 80Khz (overlapped 6 inputs PNP/TTL)

    OutputsDigital 16 Selectable as static outputs 700mA or digital inputs (code TD240-11AD)Analogue 4 outputs 0..10Volt (code TD240-11AD)Serial ports 2 serial ports RS232/RS485

    Software featuresProgramming Pixsys PLprog software, Ladder diagrams; 10K words variables VW, 800 marker (logic relays), 128 bistables,

    128 timer 16 bit, 64 up-down counters, mathematic and logic functions, rescale function, contact on bitGraphic interface programming Pixsys TDdesigner softwareCommunication protocols Modbus RTU master / slave; Free-Port mode for Modem protocols or proprietary devicesMemory 384Kbyte Flash for programming, 10K words non-volatile Ram (6 months), 1000 words EEprom, 30k words

    MMCClock Real-Time clock, Back-up batteryAnalogue inputs control algorithms P, PI, PID, PD

    Ordering codesTD240-AD HMi 3,5” with soft-plc, 2 serial RS232/RS485 - ModbusTD240-11AD HMi 3,5” with soft-plc + 16 digital I / O + 4 Universal analogue inp. + 4 analogue out 0..10Volt + 2 serial

    RS232/RS4852100.30.001 M.c.Par Series TD240-TD320-ATR313

    summary

  • Wiring plan45Programmable systems

    Touch-screen HMI 5,7” 256 colorsTD320Main featuresBox 204x170 (front panel) x 48Power supply 12..24Vac/Vdc ±15% 50/60 HzConsumption 10WDisplay Display LCD TFT 5,7” - 256 Colours, integrated resistive Touch-screenOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Front panel: aluminium with polycarbonate coverage; Box: chromed steelWeight Approx. 1430 grSealing IP54 (Front panel), IP20 (Box and Terminal bloks)Quick set-up options SLOT Memory Card or program download (Ladder+graphics)Expansions Pixsys modules MCM260-1/2/3/4/5 or other Modbus devices

    InputsDigitals 8 Inputs for external contacts on connector 25poles

    OutputsDigital 1 General alarm outputSerial ports 1 Programming / Communication port with RS232 interface, 1 communication port with RS485/RS422

    interface, galvanically isolated, 1 communication port with RS232/RS485 interface

    Software featuresOperating logic functioning Pixsys PLprog software for Ladder diagrams; 10K words variables VW, 800 marker (logic relays), 128

    bistables, 128 timer 16 bit, 64 up-down counters, mathematic and logic functions, rescale function, contact on bit

    Graphic interface programming Software Pixsys TDdesignerCommunication protocols Modbus RTU Master / slave; Free-Port mode for Modem protocols or proprietary devicesMemory 768Kbyte Flash for programming, 10K words non-volatile Ram (6 months), 1000 words EEprom, 30k words

    MMCClock Real-Time clock, Back-up battery

    Ordering codesTD320-AD HMI 5,7” with soft-plc + 3 serial portsRS232/RS485/RS4222100.30.001 M.c.Par Series TD240-TD320-ATR313

    summary

  • Wiring plan46 Programmable systems

    Touch-screen Panel PC / HMI with 4,3” Windows CETD430Main featuresBox 140x100 (front panel) x 38Power supply 12..24Vac/Vdc ±15% 50/60 HzConsumption 3,7WDisplay LCD TFT touch screen 4.3” , 480x272 pixel, 16M colorsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Front panel: aluminium with polycarbonate coverage; Box: chromed steelWeight Approx. 476 grSealing IP54 (Front panel), IP20 (Box and Terminal bloks)Expansion module 1 x ETD884-AD Expansion: 2 load cell inp. with integrated power supply for the cell, 8 digital inputs, 2

    encoder inputs 24bit PNP/TTL, 8 digital outputs, 2 analogue outputs V/mA, 4 analogue inp. NTC /PTC /V/mA

    Hardware features and communication portsProcessor ARM V4i 200 MHzMemory Flash 256 MBSerial communication RS485 galvanically isolatedField bus CAN galvanically isolatedUSB 1 USB for programming on frontal + 1 USB 2.0 on back sideEthernet 1 Ethernet 10/100 Base-T on RJ45 connectorMemory card SD/MMC Reader

    Software featuresOperating logic programming Pixsys Suite LogicLab IEC 61131-3 languagesGraphic interface programming Software Pixsys Suite PageLabCommunication protocols Modbus RTU Master / slave; Free-Port mode for Modem protocols or proprietary devices, Modbus TCP/IP

    Master / Slave, CAN Open MasterClock Real-Time clock, Back-up battery

    Ordering codesTD430-AD HMI 4,3” with soft-plc + RS485 + CANopenETD884-AD Expansion module 2 An. 16bit/1ms (load cells) + 8 Inp. + 8 Statics + 2 outputs Volt/mA

    summary

  • Wiring plan47Programmable systems

    Touch-screen Panel PC / HMI with 5,7” - 7” Windows CETD570 / TD700Main featuresBox 204x160 (front panel) x 38Power supply 12..24Vac/Vdc ±15% 50/60 HzConsumption 3,7WDisplay TD570: 5,7” LCD TFT 640x480 pixel, 16M colors - TD700: 7” LCD TFT 800x480 pixel, 16M colorsOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Front panel: aluminium with polycarbonate coverage; Box: chromed steelWeight Approx. 937 grSealing IP54 (Front panel), IP20 (Box and Terminal bloks)Expansions 2 x ETD884-AD Expansion: 2 load cell inp. with integrated power supply for the cell, 8 digital inputs, 2

    encoder inputs 24bit PNP/TTL, 8 digital outputs, 2 analogue outputs V/mA, 4 analogue inp. NTC /PTC /V/mA

    Hardware features and communication portsProcessor ARM V4i 200 MHzMemory Flash 256 MBSerial communication RS232-RS485 galvanically isolatedField bus CAN galvanically isolatedUSB 1 USB for programming on frontal + 1 USB 2.0 on back sideEthernet 1 Ethernet 10/100 Base-T on RJ45 connectorMemory card SD/MMC Reader

    Software featuresOperating logic programming Pixsys Suite LogicLab IEC 61131-3 languagesGraphic interface programming Software Pixsys Suite PageLabCommunication protocols Modbus RTU Master / slave; Free-Port mode for Modem protocols or proprietary devices, Modbus TCP/IP

    Master / Slave, CAN Open MasterClock Real-Time clock, Back-up battery

    Ordering codesTD570-AD HMI 5,7” with soft-plc + 3 serial ports RS232/RS485/RS422TD700-AD HMI 7” with soft-plc + 3 serial ports RS232/RS485/RS422ETD884-AD Expansion module 2 An. 16bit/1ms (load cells) + 8 Inp. + 8 Statics + 2 outputs Volt/mA

    summary

  • Wiring plan48 Programmable systems

    Panel PC Touch-screen 7”TD750Main features and displayBox 160 x 204 (front) x 34mmPower supply 24Vdc ±10%Consumption Approx. 11WDisplay Display 7” 800x600 24bit LVDS with integrated resistive Touch; backlight Led 500cd (lifetime > 50000h )Operating conditions Temperature 5 -50 °C, humidity 10-90 %RHFrontal panel 6mm aluminium alloy, milled, opaqueWeight Approx. 2 KgSealing IP65 (Front panel), IP20 (Box and Terminal bloks)Cooling FanlessUPS Integrated, assisted shut-down

    Hardware featuresCPU Intel (R) Atom(TM) Z530 @ 1,6Ghz / Intel (R) Atom(TM) Z510 @ 1,1GhzRAM Memory 1GB DDR2 SDRAMHard Disk Sata Solid State Disk 16 / 64GbEthernet 1 x LAN 10/100 Base-TX Ethernet RJ-45 interfaceSerial Interface 1 x RS232, 1 x CAN, 1 x RS485 Optoisolated from power supplyUSB 1 Front + 2 Rear USB 2.0 InterfaceAudio Stereo 600 Ohm OutClock Real-Time clock, Back-up batterySerial ATA 1 X SATA-300 mass storage Interfaces

    Software featuresOperating system Windows XP Professional / Windows 7 EmbeddedOperating logic programming Pixsys Suite LogicLab IEC 61131-3 languagesGraphic interface programming Software Pixsys Suite PageLabCommunication protocols Modbus RTU Master / slave; Free-Port mode for Modem protocols or proprietary devices, Modbus TCP/IP

    Master / Slave, CAN Open Master

    Ordering codesTD750-APC-WXP Panel PC 7” with DOM 64GbTD750-AEB-XPE Panel PC 7” with DOM 16GbETDWIF-AD Optional module Wi-Fi 802.11b,g,nETD2RS232-AD Optional module 2 x UART RS232ETDLAN1G-AD Optional module 1 x LAN 10/100/1000T RJ45ETDHCLEXP Cover for optional module hole

    summary

  • Wiring plan49Programmable systems

    Panel PC Touch-screen 10.4”TD850Main features and displayBox 325 x 260 (front) x 34mmPower supply 24Vdc ±10%Consumption approx. 12WDisplay Display 10.4” 800x600 24bit LVDS, integrated resistive Touchscreen; backlight Led 320cd (lifetime>

    20000h)Operating conditions Temperature 5 -50 °C, humidity 10-90 %RHFront panel Alluminium alloy 6mm, milled, opaqueWeight approx. 3 KgSealing IP65 (Front) , IP20 (Box and Terminal blocks)Cooling FanlessUPS Integrated, assisted shut-down

    Hardware dataCPU Intel (R) Atom(TM) Z530 @ 1,6GhzRAM Memory 1GB DDR2 SDRAMHard Disk Sata Solid State Disk 16 / 64GbEthernet 1 x LAN 10/100 Base-TX Ethernet RJ-45 interfaceSerial Interface 1 X RS232, 1 X CAN(optional), 1 X RS485 Optoisolated from power supplyUSB 1 Front + 2 USB 2.0 Interfaces on rear panelAudio 1 Stereo Output 600 OhmClock Real-Time clock including Back-up batteryATA Serial 1 X SATA-300 mass storage Interface

    Software dataOperating system Windows XP Professional / Windows XP EmbeddedOperating logic programming Pixsys Suite LogicLab IEC 61131-3 languagesGraphic interface programming Software Pixsys Suite PageLabCommunication protocols Modbus RTU Master / slave; Free-Port mode for Modem protocols or proprietary devices, Modbus TCP/IP

    Master / Slave, CAN Open Master

    Ordering codesTD850-APC-WXP Panel PC 10.4”, microprocessor Intel® Atom™ Z530 1.6Ghz, 1024Mb RAM DDR2, DOM SATA 64Gb, 24Vdc,

    Windows XP ProfessionalTD850-AEB-XPE Panel PC 10.4”, microprocessor Intel® Atom™ Z530 1.6Ghz, 1024Mb RAM DDR2, DOM SATA 16Gb, 24vdc,

    Windows XP Embedded SP3ETDWIF-AD Optional module Wi-Fi 802.11b,g,nETD2RS232-AD Optional module 2 x UART RS232ETDLAN1G-AD Optional module 1 x LAN 10/100/1000T RJ45ETDHCLEXP Cover for optional module hole

    summary

  • Wiring plan50 Programmable systems

    Panel PC Touch-screen 15”TD900Main features and displayBox 435 x 330 (front) x 38mmPower supply 24Vdc ±10%Consumption approx. 14WDisplay Display 15” 1024x768 24bit LVDS, integrated resistive Touchscreen; backlight Led 500cd (lifetime >

    20000h)Operating conditions Temperature 5 -50 °C, humidity 10-90 %RHFront panel Alluminium alloy 6mm, milled, opaqueWeight approx. 4 KgSealing IP65 (Frontal), IP20 (Box and terminal blocks)Cooling FanlessUPS Integrated, assisted shut down

    Hardware dataCPU Intel (R) Atom(TM) Z530 @ 1,6GhzRAM memory 1GB DDR2 SDRAMHard Disk Sata Solid State Disk 16 / 64Gb Ethernet 1 x LAN 10/100 Base-TX Ethernet RJ-45 interfaceSerial Interface 1 X RS232, 1 X CAN(optional), 1 X RS485 Optoisolated from power supplyUSB 1 Front + 2 USB 2.0 interface on rear panelAudio 1 Stereo Output 600 OhmClock Real-Time clock, Back-up batteryATA Serial 1 X SATA-300 mass storage Interface

    Software dataOperating system Windows XP Professional / Windows XP EmbeddedOperating logic programming Pixsys Suite LogicLab IEC 61131-3 languagesGraphic interface programming Software Pixsys Suite PageLabCommunication protocols Modbus RTU Master / slave; Free-Port mode for Modem protocols or proprietary devices, Modbus TCP/IP

    Master / Slave, CAN Open Master

    Ordering codesTD900-APC-WXP Panel PC 15”, processor Intel® Atom™ Z530 1.6Ghz, 1024Mb RAM DDR2, DOM SATA 64Gb, 24vdc, Windows

    XP ProfessionalTD900-AEB-XPE Panel PC 15”, processor Intel® Atom™ Z530 1.6Ghz, 1024Mb RAM DDR2, DOM SATA 16Gb, 24vdc, Windows

    XP Embedded SP3ETDWIF-AD Optional module Wi-Fi 802.11b,g,nETD2RS232-AD 2 x optional UART RS232ETDLAN1G-AD 1 x optional LAN 10/100/1000T RJ45ETDHCLEXP Cover for optional module hole

    summary

  • 51Programmable systems

    Serial converter RS232 / RS485 / USB

    Wireless modem - transmitter + receiver

    NET200

    NET250

    Main features Box 71x101 (front panel) x 28 mmPower supply 12..24Vac/Vdc ±15% 50/60 Hz or via USB portConsumption 2 WConnection Terminal blok 10poles - 3,81 instrumentation side - USB-B connector + DB 9

    poles PC sideOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Polycarbonate self-extinguishingWeight Approx. 120 gFixing Din Rail EN50022

    Software featuresBaud Rate Automatic selection up to 115000 Baud

    Ordering codesNET200-1AD RS232/USB > RS232/RS422/RS485

    Main features Box 101mm x 71mm x 28mm (H)Power supply 12..24 Vac/Vdc ±15% 50/60 Hz for NET250-1AD / From USB for NET250-2ADConsumption 5,5 VAGalvanic isolation Between power supply and serial on NET250-1ADOperating conditions Temperature 0-45 °C, humidity 35..95 RH%Material Polycarbonate V0Weight Approx. 120 gFixing Din Rail EN50022

    Software featuresBaud-Rate 9600, 19200 and 38400 bit/s (8,N,1) dip-switch selectableRadio channels setting Possibility to select (1..7) wireless transmission channel through Hyper-

    Terminal

    Ordering codesNET250-1AD Antenna > RS485, RS232NET250-2AD USB-B > Antenna4000.00.005 Ground plane antenna 900Mhz BNC4000.00.003 Whip antenna 900Mhz BNC for control panel4000.00.004 Adapter SMA / BNC female4000.00.006 Cable extension antenna SMA / BNC L=250mm4000.00.007 Cable extension antenna SMA - MA / FE L=250mm

    summary

  • SENSORS AND COMPLEMENTARY

    FITTINGS

  • 54 Sensors and complementary fittings

    for ordering codesGUIDELINES

    Sensor typePTCNTCPT100APT100B

    PT1000Ni100TCJTCK

    TCSTCETCROther..

    PackagingBLI BlisterBOX Carton

    example code: BLI - PT100B - 6x100 - A304 - 1/2”/F - DIN/B

    Diameter x Lenght4x505x606x158x20

    6x506x1008x15015x400

    OC/10x5AR/6x100 (air)Other..

    Material typeA304 (AISI 304 - 899°C)A316 (AISI 316 - 899°C)I600 (inconell 1180°C)MGO (mineral insulated, AISI

    304 sheath)

    OTTN (brass)KER1 (single ceramic sheath)KER2 (double ceramic sheath)KER3 (triple ceramic sheath)Other..

    Connector / Coupling0000 (no connector)MN/INOX (inox rod)1/8”/S (1/8” Gas sliding)1/4”/ (sliding)1/2”/F (F=fixed)3/8”/SM8/FM10/F

    M12/F (M12x1,5 fixed)FLNG/S (sliding flanges)1/8”÷MBAI (mini-bayonet)1/4”÷BAI (bayonet)M12”÷BAI (bayonet)M10X1:BAI (thread 1mm bayonet)Other..

    Head / Cable0000 (no head)DIN/ADIN/BDIN/M (mini DIN)Eex-DMCR (ceramic pin)MCR/90 (ceramic pin 90°)CNM/M (mini connector)0,5TTS (fibre glass cable temp.

    -60..250°C)

    3,0GSC (silicon cable temperature -60..200°C)

    5,0PVC (PVC cable temperature 30..80°C)

    6,0Tfe (Teflon cable temperature -60..250°C)

    BA/CER (ceramic basement)Other..

    Hot junction (only for TC)IS (isolated)MS (grounded)SC (open)

    IS(2) (double iso