public works and travaux publics et services immobiliers
TRANSCRIPT
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E0.0
COVER PAGE AND LEGEND
DRAWING LISTE0.0 COVER PAGE AND LEGENDE0.1 SITE PLAN AND DETAILSE1.0 ELECTRICAL LAYOUTSE2.0 DETAILS AND IMAGESE2.1 IMAGESE2.2 IMAGESE2.3 IMAGESS1 GENERAL NOTES, PLANS & SECTIONS
ELECTRICAL SYMBOL LEGENDABBREVIATIONS
NOTE EQUIPMENT SHOWN DOTTED IS EXISTING AND TO REMAIN UNLESS INDICATED OTHERWISE
J
POWER
JUNCTION BOX
M
GEN
MECHANICAL MOTOR CONNECTION
SINGLE LINE
FEEDER/CONDUCTOR
BUSBAR/CDP
BREAKER
CABLE POTHEAD
METERING TRANSFORMER
SERVICE PROVIDER METER
GENERATOR
WILLIAMS LAKE DETACHMENTNEW GENERATOR
575 BORLAND STREET, WILLIAMS LAKE, BC
LOCATION PLAN1:1000
BORLAND ST
PROJECT LOCATION
7 AVE N
LOCATION OF ELECTRICALROOM ON LOWER FLOOR
NOTE 1
#6 CU BOND TO BUILDINGSERVICE GROUND IN NEW21mm RPVC CONDUIT.
3E0.1
11503600
5700
1500
1024
PROPOSED LOCATION OFTEMPORARY GENERATOR.REFER TO DETAIL 1/E2.3
1000
3500
CONCRETE WALLNOTE 2
125kW OUTDOOR RATED GENERATORC/W BASE TANK ON HOUSEKEEPINGPAD. COORDINATE WITH STRUCTURAL
NOTE 4
NOTE 3
FAA
APPROXIMATE LOCATION OF EXISTINGFIRE ALARM ANNUNCIATOR. REFER TODETAILS 5 AND 6 ON E2.2
4E2.0
3E2.0
1E2.3
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E0.1
SITE PLAN AND DETAILS1E0.1
SITE PLAN4000 8000 12000
1:2000
3E0.1
TRENCH SECTIONNOT TO SCALE
2E0.1
GENERATOR ENCLOSURE1000 2000 3000
1:500
GRADE
BACKFILL. HUMP TOALLOW FOR SETTLEMENTAND REPAIR ASPHALT
CLEAN SAND
WARNING TAPE
MIN.
450m
mBE
LOW
FIN
ISHE
D GR
ADE
150
7575
27mm RPVC FOR GENERATORBATTERY CHARGER BLOCKHEATER, LIGHT & REC.
2 x 78mm RPVC FORGENERATOR FEEDER
27mm RPVC FORGENERATOR CONTROLS
MIN.
300m
m 75 75
21mm RPVC FOR#6 BONDING CONDUCTOR
EVERY CONDUCTIVESECTION OF FENCETO BE BONDED (TYP)
NOTE 1
1000
1150
4574
3176
5000
1200
6000
AIR INTAKEABOVE PAD
NOTES:1. INSTALL NEW FIVE (5) SIDED CHAIN LINK FENCE 1000mm OFFSET ON ALL SIDE OF THE
GENERATOR COMPLETE WITH THE FOLLOWING:.1 CHAIN LINK ROOF INSTALLED ON ENCLOSURE..2 POST SIZE AND SPACING AS INDICATED ON STRUCTURAL DRAWINGS AND DETAIL
2/E0.1..3 LOCKABLE DOUBLE DOORS ON THE SIDE C/W COMMERCIAL HEAVY DUTY HASP AND
PADLOCK..4 PENETRATION THROUGH THE CHAIN LINK ROOF TO ACCOMMODATE EXHAUST PIPING..5 ENCLOSURE TO BE BONDED TO GROUND..6 FENCE TO PROVIDE A MINIMUM 600mm CLEARANCE FROM TOP OF GENERATOR UNIT.
2. EXISTING GRASS AREA IS SLOPED. CONTRACTOR TO LEVEL AREA WITH MINOR SLOPE TOEXISTING CATCH BASIN TO ENSURE HOUSEKEEPING PAD AND FENCING IS ALL LEVEL. ALLSURFACES TO BE MADE GOOD UPON PROJECT COMPLETION.
3. EXISTING CATCH BASIN TO REMAIN. EXTENT OF DRAIN PIPES IS UNKNOWN. CONTRACTORTO GPR AND HAND EXCAVATE. REROUTE ELECTRICAL INFRASTRUCTURE TO AVOIDCONFLICT AS REQUIRED ON SITE.
4. APPROXIMATE LOCATION OF EXISTING SEA-CAN. SEA-CAN POWER CONNECTION TO REMAIN.
NEMA 3R GENERATORENCLOSURE. ROOF TOBE SLOPED TO PREVENTWATER POOLING
GENERATOR SHALL BE DIESELFUELED PRIME MOVER, RATEDFOR STANDBY POWER AT 125kW@ 208V, 3Ø, 4W @ 0.8 POWERFACTOR, REFER TO SINGLE LINEDIAGRAM FOR CONNECTIONAND ROUTING DETAILS
POWDER COATED DOORS C/W LATCHEDLOCKABLE HANDLES, ALL EXTERIORHANDLES, LATCHES, HINGES ECT. TO BESTAINLESS STEEL. EXTERNAL HINGESSHALL EACH FEATURE A WATERPROOFCAP AND LOWER GREASE FITTING TOPERMIT PRESSURE LUBRICATION
GENERATORHINGED ACCESS
DOOR
GFCIWP RECFED FROM PANEL 'A'
GENERATOR SHALL COMMUNICATE VIA DRYCONTACTS TO THE EXISTING FIRE ALARMSYSTEM THE FOLLOWING:-GENERATOR RUNNING-GENERATOR FAULT (INCLUDESINTERSTITIAL ALARM)-GENERATOR FUEL LOW (VIA FLOAT SENSOR)
GRADE
GENERATOR BELLY TANK, DOUBLEWALLED, SIZED FOR 24 HOURS OFOPERATION @ 100% LOAD C/WINTERSTITIAL LEAK SENSOR
SEAL EDGE OF SLABAND EQUIPMENT WITHRUBBERIZED SEALANT
GENERATORHINGED
ACCESS DOOR
GENERATOR FOUNDATION PAD.CONCRETE THICKNESS, DIMENSIONS, ANDREINFORCING AS PER STRUCTURALDRAWINGS
3500
483
1433
COMPACTED GRANULAR FILLAS SPECIFIED BYGEOTECHNICAL ENGINEER
4E0.1
GENERATOR ELEVATION DETAILNOT TO SCALE
PROJECTNORTH
UP
UPUP
UP
UP
GENERATORANNUNCIATOR
EXISTINGPANEL 'M'
PANEL 'S'
PANEL 'R'
PANEL 'C'
2,3E1.0
ELECTRICALROOM
MECHANICALROOM
INCOMING CONDUITS FROMGENERATOR. COORDINATE EXACTROUTING ON SITE WITHDEPARTMENTAL REPRESENTATIVE.REFER TO DETAILS 1/E2.1 AND 2/E2.1
NOTE 1
2E2.3
4E2.3
3E2.3
2E2.1
1E2.1
6,7E2.0
ROOM109
EXISTING FIRE ALARMPANEL NOTIFIER AFP-200TO BE RELOCATED.REFER TO DETAIL 1/E2.2
EXISTING MAIN DISTRIBUTIONBOARD 'DB'. REFER TODETAIL 4,5,6/E2.1
EXISTING METER CABINET
EXISTING PANEL 'A'
EXISTING FIRE ALARM JUNCTIONBOX TO BE REMOVED. REFERTO DETAIL 1/E2.21
E2.2
3E2.1
2E2.2
NEW 600A DOUBLE BYPASSAUTOMATIC TRANSFER SWITCH
EXISTING MAIN DISTRIBUTIONBOARD 'DB' TO BE MODIFIED ANDRECERTIFIED FOR ATS FEEDS.
EXISTING METER CABINET
EXISTING PANEL 'A'RELOCATED FIRE ALARMPANEL NOTIFIER AFP-200.REFER TO DETAIL 2/E2.2
NEW FIRE ALARMJUNCTION BOX MOUNTEDABOVE FIRE ALARM PANEL.REFER TO DETAIL 2/E2.2
INCOMING AND OUTGOING ATSFEEDS
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E1.0
ELECTRICAL LAYOUTS
1E1.0
LOWER FLOOR ELECTRICAL LAYOUT2000 4000 6000
1:1000
3E1.0
REVISED ELECTRICAL ROOM LAYOUT1000 2000 3000
1:500
2E1.0
EXISTING ELECTRICAL ROOM LAYOUT1000 2000 3000
1:500
NOTES:1. CONDUIT FOR GENERATOR ANNUNCIATOR TO BE RECESS MOUNTED IN CORRIDOR. SHOULD
SPACE NOT BE AVAILABLE WITHIN THE CEILING, THE CONDUIT MAY BE INSTALLED SURFACEMOUNTED. ANY SURFACE MOUNTED CONDUIT SHALL BE INSTALLED TIGHT TO THE CORNERAND PAINTED TO MATCH THE WALLS. CONTRACTOR TO AVOID CONFLICT WITH EXISTINGLIGHTS AND FIRE ALARM DEVICES. ENSURE EXISTING BUZZER AND LIGHT SWITCH ATENTRANCE TO ROOM 109 ARE RETAINED AND NOT IMPACTED AS PART OF CORING IN THEBLOCK WALL.
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E2.0
DETAILS AND IMAGES
M
BC HYDRO120/208V, 3P, 4W
600A-3P
800A MAIN DISTRIBUTION BOARD 'DB'
15A-1P
FIRE ALARMPANEL
70A-3P
PANEL 'C'
70A-3P
PANEL 'S'
125A-3P
PANEL 'R'
200A-3P
PANEL 'N'
90A-3P
ELEVATOR
150A-3P
PANEL 'RT'
70A-3P
PANEL 'M'
100A-3P
PANEL 'D'
150A-3P
PANEL 'A'
100A-3P
ELEVATOR
150A-3P
PANEL 'B'
M
BC HYDRO120/208V, 3P, 4W
600A-3P
800A MAIN DISTRIBUTION BOARD 'DB'
15A-1P
FIRE ALARMPANEL
70A-3P
PANEL 'C'
70A-3P
PANEL 'S'
125A-3P
PANEL 'R'
200A-3P
PANEL 'N'
90A-3P
ELEVATOR
150A-3P
PANEL 'RT'
70A-3P
PANEL 'M'
100A-3P
PANEL 'D'
150A-3P
PANEL 'A'
100A-3P
ELEVATOR
150A-3P
PANEL 'B'
CSA TYPE 1600A, 208Y/120V 3-POLE DOUBLE BYPASSAUTOMATIC TRANSFER SWITCH
GEN
125kW, 0.8PF, 208Y/120VOUTDOOR GENERATOR
LOAD BANKTEST BREAKER
ATS BYPASSSECTION
ATS ISOLATIONSECTION
600A-3P 600A-3P
2 x (4#350kcmil +GND) IN 78mm C.
2 x (4#350kcmil +GND) IN 78mm C.
NOTE 1
2E2.0
REVISED SINGLE LINE DIAGRAMNOT TO SCALE
1E2.0
EXISTING SINGLE LINE DIAGRAMNOT TO SCALE
3E2.0
LOCATION OF NEW EXTERIOR GENERATORNOT TO SCALE
NOTES:1. LOCATION OF NEW EXTERIOR GENERATOR.2. EXISTING CATCH BASIN TO BE PROTECTED FOR THE DURATION OF WORK. HAND EXCAVATE
AND RELOCATE ELECTRICAL CONDUIT TO AVOID EXISTING SITE CONDITIONS.3. CONTRACTOR TO SAW CUT EXISTING CONCRETE PATH AS REQUIRED. ALL CONCRETE TO
BE PATCHED UPON COMPLETION OF PROJECT. COORDINATE WITH STRUCTURAL DIVISION.4. CONTRACTOR TO MAKE GOOD ALL GRASS SURFACES AFTER COMPLETION OF WORK
INCLUDING BUT NOT LIMITED TO GRADING, SEEDING AND/OR SODDING.5. CONTRACTOR TO TEMPORARILY REMOVE GUARDRAIL AND REINSTALL UPON COMPLETION
OF PROJECT.
1
NOTES:1. UPON COMPLETION OF MAIN DISTRIBUTION BUS MODIFICATIONS,
CONTRACTOR TO HAVE SWITCHBOARD TESTED AND RECERTIFIEDIN ACCORDANCE WITH CSA SPE-1000.
2. CONTRACTOR TO PROVIDE 11"x17" DRAWINGS OF FINAL SINGLELINE DIAGRAM UNDER PLEXIGLASS INSTALLED WITHIN ELECTRICALROOM.
4
2
3
5
4E2.0
EXTERIOR MECHANICAL ROOM WEST WALLNOT TO SCALE
NOTES:1. ROUTE OF CONDUIT ON BUILDING EXTERIOR FROM MECHANICAL ROOM TO NEW
GENERATOR. OPTION ONE ROUTED TO THE LEFT AND OPTION TWO SHOWNDIRECTLY UPWARD. EXACT POINT OF ENTRY FROM OUTSIDE TO MECHANICAL ROOMTO BE CONFIRMED AFTER REVIEW OF EXISTING MECHANICAL INSTALLATION ON THEOTHER SIDE OF THE WALL. CONTRACTOR TO X-RAY WALL PRIOR TO ANY CORING.ALL EXTERIOR CONDUIT TO BE RIGID GALVANIZED STEEL COMPLETE WITHTAMPER-PROOF FITTINGS.
2. CONTRACTOR TO INSTALL HEAVY DUTY GALVANIZED STEEL SCREEN SHROUD OVEREXPOSED ELECTRICAL INFRASTRUCTURE. SHROUD SHALL BE FIXED TO THE WALLUSING TAMPER-PROOF BOLTS.
3. ROUTE OF UNDERGROUND CONDUIT TO NEW GENERATOR. ALL ROUTES MUST BECONFIRMED ON SITE BASE ON EXISTING CONDITIONS.
1
3
1
5E2.0
EXTERIOR WALL BESIDE RETAINING BOARDNOT TO SCALE
NOTES:1. EXISTING BUILDING GROUND TO BE MAINTAINED DURING CONSTRUCTION. CONTRACTOR TO
INCLUDE RELOCATION OF GROUND IF REQUIRED TO ALLOW FOR INSTALLATION OF NEWCONDUIT.
6E2.0
MECHANICAL ROOM WEST WALL OPTION 1NOT TO SCALE
1
NOTES:1. APPROXIMATE LOCATION OF CONDUIT ENTERING FROM
EXTERIOR USING OPTION ONE. CONTRACTOR TO INSTALLUNI-STRUT BELOW MECHANICAL DUCTWORK FOR SUPPORT OFCONDUIT. EXISTING FLUORESCENT FIXTURE TO BE REMOVEDTO ALLOW FOR INSTALLATION AND RE-INSTALLED UPONCOMPLETION OF CONDUIT RUN TO ELECTRICAL ROOM.
7E2.0
MECHANICAL ROOM WEST WALL OPTION 2NOT TO SCALE
NOTES:1. APPROXIMATE LOCATION AND ROUTING OF CONDUIT FROM
EXTERIOR USING OPTION TWO.1
2
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E2.1
IMAGES
1E2.1
MECHANICAL ROOM VIEWING WEST WALLNOT TO SCALE
NOTES:1. OPTION ONE ROUTING CONDUIT WITHIN MECHANICAL ROOM. CONDUIT
TO BE INSTALLED A MINIMUM OF 7" BELOW CEILING. NO POINT OFINSTALLATION SHALL BE LOWER THAN DUCTWORK ABOVE DOOR OFROOM. LIGHTS TO BE REMOVED AND RE-INSTALLED AS REQUIRED.
2. OPTION TWO ROUTING OF CONDUIT WITHIN MECHANICAL ROOM.CONDUIT TO BE INSTALLED A MINIMUM OF 7" BELOW CEILING. NO POINTOF INSTALLATION TO BE LOWER THAN DUCTWORK ABOVE DOOR OFROOM.
3. NO POINT OF CONDUIT INSTALLATION TO BE LOWER THAN DUCTWORKABOVE THE DOOR.
2
1
3
2E2.1
MECHANICAL ROOM NE WALLNOT TO SCALE
NOTES:1. CONDUIT FROM GENERATOR TO ELECTRICAL ROOM.2. FIRE ALARM CONDUITS TO BE RELOCATED. REFER TO NOTE 2 ON
DETAIL 3/E2.1.3. WIRING FROM JUNCTION BOX TO BE RELOCATED TO NEW FIRE
ALARM JUNCTION BOX WITHIN ELECTRICAL ROOM. REFER TONOTE 1 ON DETAIL 3/E2.1.
1
2
3
3E2.1
MAIN ELECTRICAL ROOM SOUTH HALLNOT TO SCALE
NOTES:1. EXISTING JUNCTION BOX TO BE REMOVED AND WIRING TO BE RE-ROUTED WITHIN MECHANICAL
ROOM ON OTHERSIDE OF THE WALL. WIRING TO BE ROUTED TO GUTTER BOX ABOVE EXISTING FIREALARM JUNCTION BOX. EXISTING FIRE ALARM JUNCTION BOX TO BE RE-WIRED TO NEW FIRE ALARMPANEL LOCATION. REFER TO DETAIL 4/E2.2 FOR EXISTING GUTTER BOX LOCATION AND DETAIL 2/E2.2FOR NEW FIRE ALARM JUNCTION BOX LOCATION.
2. EXISTING CONDUIT TO BE REMOVED AND WIRING TO BE RE-ROUTED WITHIN MECHANICAL ROOM ONOTHERSIDE OF THE WALL. WIRING TO BE ROUTED TO GUTTER BOX ABOVE EXISTING FIRE ALARMJUNCTION BOX. EXISTING FIRE ALARM JUNCTION BOX TO BE RE-WIRED TO NEW FIRE ALARM PANELLOCATION. REFER TO DETAIL 4/E2.2 FOR EXISTING GUTTER BOX LOCATION AND DETAIL 2/E2.2 FORNEW FIRE ALARM JUNCTION BOX LOCATION.
1
2
4E2.1
EXISTING MAIN DISTRIBUTION BOARDNOT TO SCALE
5E2.1
NAMEPLATE INFORMATIONEXISTING MAIN DISTRIBUTION BOARD
NOT TO SCALE
6E2.1
TOP OF DISTRIBUTION SECTIONNOT TO SCALE
1
NOTES:1. CONTRACTOR TO MODIFY BUSSING IN THE DISTRIBUTION
SECTION FOR TRANSFER SWITCH FEEDS. CONTRACTOR TORE-CERTIFY THE EQUIPMENT AS PER SPE-1000. ALLMODIFICATIONS REQUIRE COORDINATION WITH DEPARTMENTALREPRESENTATIVE FOR SHUT DOWNS.
NOTES:1. CONTRACTOR TO MODIFY BUSSING IN THE DISTRIBUTION
SECTION FOR TRANSFER SWITCH FEEDS. CONTRACTOR TORECERTIFY THE EQUIPMENT AS PER CSA SPE-1000. ALLMODIFICATIONS REQUIRE COORDINATION WITH DEPARTMENTALREPRESENTATIVE FOR SHUT DOWNS.
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E2.2
IMAGES
4E2.2
MAIN ELECTRICAL ROOM ABOVE EXISTING FIRE ALARM JUNCTION BOXNOT TO SCALE
NOTES:1. EXISTING GUTTER BOX ABOVE EXISTING FIRE ALARM JUNCTION BOX.
GUTTER BOX TO BE RE-USED TO ROUTE EXISTING WIRE TO NEW FIREALARM PANEL ACROSS THE ROOM.
1
1E2.2
ELECTRICAL ROOM SOUTH WALLNOT TO SCALE
NOTES:1. EXISTING FIRE ALARM JUNCTION BOX TO BE REMOVED.2. EXISTING NOTIFIER AFP-200 FIRE ALARM PANEL TO BE RELOCATED.
2E2.2
ELECTRICAL ROOM NORTH WALLNOT TO SCALE
NOTES:1. NEW FIRE ALARM JUNCTION BOX TO BE INSTALLED. FIRE ALARM JUNCTION BOX SIZE TO BE
DETERMINED AFTER DETAILED SITE EXAMINATION TO HOUSE NECESSARY TERMINALBLOCK AND DEVICES THAT ARE REQUIRED TO BE REMOVED FROM EXISTING JUNCTION BOXAND RE-INSTALLED IN THE NEW JUNCTION BOX. JUNCTION BOX TO BE COLOURED RED.
2. EXISTING NOTIFIER AFP-200 FIRE ALARM PANEL IN NEW RELOCATED POSITION.3. EXISTING FIRE EXTINGUISHER TO BE RELOCATED AS REQUIRED.
1
2
1
2
3
3E2.2
EXISTING FIRE ALARM JUNCTION BOX CLOSE UPNOT TO SCALE
NOTES:1. EXISTING CONDUITS AND WIRING TO BE RELOCATED TO NEW FIRE ALARM
JUNCTION BOX ON THE OPPOSITE WALL.
5E2.2
EXISTING FIRE ALARM PANEL ANNUNCIATORNOT TO SCALE
NOTES:1. CONTRACTOR TO UPDATE FIRE ALARM ANNUNCIATOR PANEL TO INCLUDE
SUPERVISORY SIGNALS FOR GENERATOR RUN AND TROUBLE.
6E2.2
EXISTING FIRE ALARM PANEL ANNUNCIATORNOT TO SCALE
Public Works and
Canada
REAL PROPERTY SERVICES
Government ServicesCanadaServices gouvernementauxTravaux publics et
Pacific RegionSERVICES IMMOBILIERS
Région de Pacifique
DM5XXXXXX
5
4
3
2
1
ISSUED FOR TENDER0
0R.112602.001
Preetipal Paul
Masood Dezfooli
RS
JB
-
RCMP
08/20/21
NEW GENERATORWILLIAMS LAKE DETACHMENT
WILLIAMS LAKE, BC575 BORLAND STREET
AES PROJECT #1-20-307
CALGARY | VANCOUVER | VICTORIA
Designing A Better Tomorrow
E2.3
IMAGES
1E2.3
TEMPORARY GENERATOR LOCATIONNOT TO SCALE
NOTES:1. CONTRACTOR TO RELOCATE GARBAGE AND
RECYCLING BINS AS REQUIRED TO ALLOW SPACEFOR TEMPORARY GENERATOR. COORDINATE NEWLOCATION FOR THE BINS WITH DEPARTMENTALREPRESENTATIVE.
1
2E2.3
CORRIDOR TO ROOM 109NOT TO SCALE
3E2.3
ROOM 109 DOORNOT TO SCALE
NOTES:1. CONTRACTOR TO ENSURE BUZZER AND LIGHT
SWITCH ARE RETAINED AND NOT IMPACTED ASPART OF CORING IN THE BLOCK WALL.
1
4E2.3
ROOM 109 WEST WALLNOT TO SCALE
NOTES:1. APPROXIMATE LOCATION OF NEW GENERATOR
ANNUNCIATOR PANEL.
1