rru emergency power control spec sheet - · pdf filecatalog # type date project comments...

2
Catalog # Type Date Project Comments Prepared by PS503016EN 09-05-17 COMPLIANCE cUL Listed UL924 listed LED compatible ORDERING INFORMATION The RRU-X-UNV can simultaneously bypass both a line voltage switch and a 0-10V dimming signal, ensuring that an emergency fixture illuminates at full brightness during a utility power interruption. Its small size makes it ideal for junction box or fixture mounting in wireless or other modern lighting control systems. An integral test switch and LED allow for quick testing and verification of proper function. The RRU-X-UNV includes a 20A rated high voltage Form C (N/O+N/C) relay and a low voltage Form A (N/O) relay and is UL924 Listed for emergency lighting control applications. DESCRIPTION FEATURES The powerful RRU-X-UNV includes: 20A Rated N/O & N/C Used for bypassing line voltage switching, occupancy sensors or dimmers. Also used as dry contact to signal relay panels or BMS systems or utility power interruption 1A Rated N/O contact Used for bypassing low voltage dimming or switching signals from room controllers or dimmers Integral test switch and green utility power indicator Flush or fixture mounted UL924 Listed Catalog Number Product Description RRU-X-UNV Emergency Power Control for 0-10V and Line Voltage Applications MOUNTING EMERGENCY POWER CONTROL FOR 0-10V AND LINE VOLTAGE APPLICATIONS

Upload: doanthuan

Post on 06-Feb-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Catalog # Type

Date

Project

Comments

Prepared by

PS503016EN09-05-17

C O M P L I A N C EcUL Listed

UL924 listed

LED compatible

ORDERING INFORMATION

The RRU-X-UNV can simultaneously bypass both a line voltage switch and a 0-10V dimming signal, ensuring that an emergency fixture illuminates at full brightness during a utility power interruption. Its small size makes it ideal for junction box or fixture mounting in wireless or other modern lighting control systems. An integral test switch and LED allow for quick testing and verification of proper function. The RRU-X-UNV includes a 20A rated high voltage Form C (N/O+N/C) relay and a low voltage Form A (N/O) relay and is UL924 Listed for emergency lighting control applications.

DESCRIPTION

FEATURES

The powerful RRU-X-UNV includes:• 20A Rated N/O & N/C• Used for bypassing line voltage switching, occupancy sensors or dimmers. Also used as dry contact

to signal relay panels or BMS systems or utility power interruption• 1A Rated N/O contact• Used for bypassing low voltage dimming or switching signals from room controllers or dimmers• Integral test switch and green utility power indicator• Flush or fixture mounted• UL924 Listed

Catalog Number Product Description

RRU-X-UNV Emergency Power Control for 0-10V and Line Voltage Applications

MOUNTING

EMERGENCY POWER

CONTROL FOR 0-10V AND

LINE VOLTAGE APPLICATIONS

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

page 2

WIRING DIAGRAM

#4 BLUE

EMERGENCYHOT

#2 WHITE

TEST

UTILITYPOWER

EMERGENCY PANEL OR INVERTER

20A

EMERGENCY NEUTRAL

#5 YELLOWEmergency Light

Note: Emergency Light is also called N/E Light or Normal/Emergency Light by

many specifiers

#3 BROWN

Switch or Dimmer REGULAR

PANEL

20AREGULAR HOT

REGULAR NEUTRAL

#1 BLACK

0-10 v Dimmer

Violet (+)

Gray (-)

VioletViolet

RRU-X-UNV EMERGENCY POWER CONTROL FOR 0-10V AND LINE VOLTAGE APPLICATIONS

Electrical

Sensing input 120V - 277V

Load rating 120V - 277V (20A)

Ballast load rating 20A (120-277V) (Contact #1)

Incandescent load 1200W (120V) / 1500W (277V)

LoadContact #1 20A (120-277V)

Contact #2 1A (30V DC)

Warranty 5 Year replacement warranty

SPECIFICATIONS

Mechanical

Mounting Fixture Mount

Rating UL94V-0A

Shipping weight 12 oz. / White

Color White

Temperature 32ºF - 140ºF (0ºC - 60ºC)

Size1.7W” x 3H” x 1.2D” (body)

2.75W” x 4.5H” x 1.2D” (with wallplate)

PS503016EN09-05-17