rtu7 3v3i protection manual ver. 112.01 2013-01-21.pdf

Upload: luigidumitrescu

Post on 01-Jun-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    1/36

     

    1

     

    Protections and Automatics 3V3I

    RTU7

    Protections and Automatics Manual

    Configuration 3V3I

    Version of the parameters 112.01

    Version of the records parameters 112.01

    FW 112.01 or greater

    Document version 2013-01-21

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    2/36

     

    2

    Protections and Automatics 3V3I 

    Contents

    CONTENTS 2 

    INTRODUCTION 4 

    MEASUREMENT 5 

    Sampling 5 

    Angles 5 

    Filtration 5 Frequency Measurement 5 

    Transmitting Measured Values 5 

    Ranges 6 

    Powers Measurement 6 

    Circuit Breaker Control 6 

    Group Switching 6 

    Initialization 6 

    Signalling 6 

    Signalling by the Relay Output 6 

    Open/Close Disabling 7 

    Signalling panel 7 

    ANSI Functions 7 

     ADDRESSES OF THE DIGITAL SIGNALS AND THE MEASUREMENTS 8 

    Measurements 8 

    Digital Signals 9 

    PROTECTIONS 15 

    Parameterization 15 

    Common parameters 16 

    General Overcurrent Protection 17 

    Overvoltage Protection 20 Undervoltage Protection 21 

    Overfrequency Protection 22 

    Underfrequency Protection 23 

    Earth Fault Protection 24 

    Impulse Protection 25 

    Conductance Protection 26 

    Wattmetrical Protection 26 

    Earth Fault Protection – Connection of the Resistor 27 

    Voltage Unbalance Protection 28 

    Current Unbalance Protection 29 

     AUTOMATICS 31 

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    3/36

     

    3

    Protections and Automatics 3V3I 

    Automatic Open after Unsuccessful Reclosing 31 

    Automatic Reclosing 32 

    FAULT RECORDS 34 

    Common Settings 34 

    Analogue Channels 35 

    Digital Channels 35 

    SIGNALLING 36 

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    4/36

     

    4

    Protections and Automatics 3V3I 

    IntroductionDear customer, this document explains the protections and automatics functions that are implemented in RTU7 based units

    manufactured by the company ELVAC a.s. The document contains a description of the particular protection functions and their

    parameters. The RTU User Center application is used for parameterization of the RTU units.

    Technical Support

    Our goal in writing this document was to create a clear guide for the users of our equipment. If you find a problem or experience

    any difficulties, please contact our technical support. Our technical support team is ready to explain any incomprehension. This

    document is continuously updated, so please check if your version is up to date.

    Training

    We offer training on protections and the other functions of the RTU units for our customers. If you are interested, please contact a

    product manager.

    Copyright

    Modifications or provision of the content to a third party in any form and without the expressive consent of the ELVAC a.s. is

    forbidden.

    Copyright © 2009-2013 ELVAC a.s.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    5/36

     

    5

    Protections and Automatics 3V3I 

    MeasurementThe following chapters describe the algorithms used for the measuring and for the calculation of the particular values.

    Sampling

    The RTU unit measures three phase voltages and three phase currents. Currents are measured by two inputs with two different

    input ranges (currents ix and ixH). Thanks to this feature the accurate values are measured up to a quadruple of the nominal current.

    Nominal range depends on the used input analogue module. A 10bit A/D converter with simultaneous sampling is used to avoid the

    phase shift among the measured channels. Additionally the phase shift compensation is carried out during the production process.

    All currents and voltages are sampled 180 times per 10 milliseconds. 3i0 and v0 are calculated every 10ms/180 as the sum of the

    instantaneous values of the phase currents and phase voltages. All instantaneous values of currents and voltages are filtered by

    band pass from 30 Hz to 80 Hz. These filtered values are used for the computation of i 0 and v0 and also for the computation of the

    effective values of 3I0 and V0. The measured values are processed 180 times per 10 milliseconds. The effective values are calculated

    every 10 milliseconds. These values are used in the protection functions. The one second average from 100 values is transmitted to

    the control system if the integral or differential filter is exceeded, or if the limit is exceeded. 

    Angles

    Angles are measured 180 times per 10 milliseconds (with 1° step). The angles 1/2/3 are measured between the phase currentsand the phase voltages. When the effective value of V1/V2/V3 is less than 1% (of the voltage range) and the effective value of I 1/ I2/ I3 

    is less than 0.5 % (of the current range), the angle is not measured and it is set to 0° (cos 0° = 1). 

    The angle 0  is measured between v0 and -i0. The filtered values of v0 and -i0 are used (see next chapter). The angle is measured

    constantly. However cos 0 = 1 is transmitted to the control system if the one second average of the effective value of the V0 is lessthan 1.08% (of the voltage range) or if the one second average of the effective value of 3I0 is less than 0.78% (of the current range).

    Filtration

    The instantaneous values ux and ix are filtered by the band pass from 30 Hz to 80 Hz. The phase shift of the output signal is the same

    as the input signal. The filter transfer is compensated by the constant.

    Frequency Measurement

    Frequency is measured from the positive sequence voltage which is given by V PS = (V1 + aV2 + a2V3)/3, where a = e

     j2/3. The measured

    range is from 10 to 100 Hz. The frequency is measured by counting of the zero crosses of the vPS

    . The frequency is set to 0 Hz, when

    all line to line voltages are less than 10% of the voltage range. The range of the frequency for the control system is from 0 to 100 Hz

    (for the normalized values in the range from 0 to 32767). The smallest step is 0.024 Hz. Accuracy of the frequency is ±0.07 % (i.e.

    ±0.035 Hz for 50 Hz) for frequencies between 30 Hz and 80 Hz.

    Transmitting Measured Values

    Actual values are transmitted when the integral or differential filter is exceeded. Group transfer is also available. When any of the

    analogue channels with enabled group transfer changes then all analogue channels with enabled group transfer are transmitted.

    Thanks to this feature the amount of transmitted data can be reduced. Moreover, the transmitted values are read at the same time.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    6/36

     

    6

    Protections and Automatics 3V3I 

    Ranges

    The ranges for protections are the same as the ranges for the current and voltage inputs. All ranges and parameters are set in the

    effective values. The following table contains ranges for both current and voltage inputs. The set value and the maximum value vary

    according to the nominal value. Values in the rows “without conversion” remain unchanged.

    Nominal range Set range Maximum value

    Current inputs [A] 100 400 400

    Current inputs (without conversion) 8192 32767 32767

    Voltage inputs [kV] 22 26.4 26.4Voltage inputs (without conversion) 27306 32767 32767

    Powers Measurement

    The RTU7 units measure active, reactive, and apparent power. Active power is given by the sum of the products of the

    instantaneous currents and voltages in all three phases. Reactive power is given by the sum of the products of the instantaneous

    currents and voltages in all three phases where voltages are shifted by 90°. Apparent power is calculated every 10 milliseconds from

    the active and reactive power. The range for the powers P, Q, S is from 0 to 3 * U * I.

    Circuit Breaker Control

    Circuit breaker can be controlled by the relay output. One relay output is defined for the open command of the circuit breaker andthe second is defined for the close command. Two additional parameters are used to define one and a half or two pole control.

    Open command has a greater priority than the close one. When the open command is performed during the close command the

    close command is interrupted.

    Group Switching

    The RTU7 unit in the 3V3I configuration provides two groups of protections. Only one group is used at a time. Switching between

    groups is done by the special signal with address 161. The currently used group is determined by the value of this signal. The

    protections are initialized after the group is switched.

    Initialization

    Initialization of the protections takes place after the unit restart, switching on, parameterization, and group switching. Theinitialization lasts 15 seconds. The signalling of pickups, trips, closing, and opening is disabled during the initialization. All pickups

    and trips are cleared and parameters are read at the beginning of initialization.

    Signalling

    Particular protections can signal pickups, trips and opening by signals. The signals have to be enabled to transmit its states to the

    control system. It is also possible to define additional parameters (single/double bit, enable negation) for each signal. The signals are

    transmitted with not topical attribute if the protection is disabled.

    Signalling by the Relay Output

    Trip of all protection can be signalled by relay closing. This must be enabled in the parameters of the particular protection. If the

    address of the signalling relay is set to none, the signalling is disabled. The signalling by relay is also disabled when the address of the

    signalling relay equals to the address of the breaker close relay, or breaker open relay, or heating relay, or cooling relay. Signalling

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    7/36

     

    7

    Protections and Automatics 3V3I 

    by relay is prolonged by 40 ms because of possible flicking of the trip. The same relay may be shared among more protection

    functions. The resulting state of the relay is given by the logical sum of particulars trips.

    Open/Close Disabling

    Open or close function provided by the protection can be blocked (disabled) by parameters and by the special virtual digital signals.

    These signals are set to block (its value is 1) open/close function by default. The logic of all virtual digital inputs including the special

    blocking signals for protections can be negated.

    Signalling panel

    The LED signalling panel can be connected to the RTU7 unit. The meaning of each LED is parameterized by the expressions.

    ANSI Functions

    In the following table there is a list of the ANSI function codes and its descriptions that are used in this document.

    Function number Description

    ANSI 50 Phase overcurrent protection

    ANSI 51 Time phase overcurrent protection

    ANSI 50N Earth fault protection

    ANSI 51N Time earth fault protection

    ANSI 67 Directional phase overcurrent protection

    ANSI 67N Directional earth fault protectionANSI 59 Phase to phase overvoltage protection

    ANSI 59N Neutral voltage displacement

    ANSI 27 Phase to phase undervoltage protection

    ANSI 81H Overfrequency protection

    ANSI 81L Underfrequency protection

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    8/36

     

    8

    Protections and Automatics 3V3I 

    Addresses of the Digital Signals and the MeasurementsAll signals and measurements provided by the RTU7 unit in the 3V3I configuration are described in the following table.

    Measurements

    Inputs

    Address Description Range

    0 I1  0 to IMAX 

    1 I2  0 to IMAX 2 I3  0 to IMAX 

    3 I - average I1, I2, I3  0 to IMAX 

    4 3I0 (filtered) 0 to IMAX 

    5 Vf1  0 to VMAX 

    6 Vf2  0 to VMAX 

    7 Vf3  0 to VMAX 

    8 Vf  - average Vf1, Vf2, Vf3  0 to VMAX 

    9 V0 (filtered) 0 to VMAX 

    10 V12  0 to VMAX 

    11 V23  0 to VMAX 12 V31  0 to VMAX 

    13 VS  – average V12 ,V23 ,V31  0 to VMAX 

    14 P 0 to 3 * IMAX * VMAX 

    15 Q 0 to 3 * IMAX * VMAX 

    16 S 0 to 3 * IMAX * VMAX 

    17 cos   0 to 1

    20 cos 0  0 to 1

    21 Frequency 0 to 100 Hz

    121 Maximum processor utilization since last reset (0 to 100%) 0 to 100 %

    122 Actual processor utilization in the last second (0 to 100%) 0 to 100 %

    123 Accumulator capacity 0 to 100 %

    124 Accumulator voltage 0 to 30 V

    125 Power supply voltage 0 to 60 V

    126 External temperature 0 to 130 °C 

    127 Internal temperature 0 to 130 °C 

    128 Fault records number 0 to 32767

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    9/36

     

    9

    Protections and Automatics 3V3I 

    Digital Signals

    Inputs

    Address Description

    0 to 19 Physical digital inputs

    104 Change buffer overflow

    105 Unit reset

    106 Power supply failure

    107 State of the cooling relay (0 when cooling is not enabled)

    108 State of the heating relay (0 when heating is not enabled)

    109 Accumulator charging failure

    110 Reserve

    111 Records error (wrong CRC of records or calibrations)

    112 Reserve

    113 Reserve

    114 Protections group 2 error (wrong CRC of protections or calibrations)

    115 Protections group 1 error (wrong CRC of protections or calibrations)

    116 Error – 1 = limited functionality , 0 = everything is OK

    117 Error of the inputs/outputs parameters – 1 error (wrong CRC), 0 = Parameters are OK118 Error of the system parameters – 1 = error (wrong CRC), 0 = Parameters are OK

    119 Low accumulator – 0 = accumulator capacity is OK, 1 = accumulator capacity is low

    120 Copy of the DI1

    121 Copy of the DI0

    122 Protections error – 1 = protections are disabled (wrong CRC of protections or calibrations)

    123 Time source – 0 = control system, 1 = device on the bus, 2 = external source

    125 Modem reset

    126 Power supply lost

    127 Automatic power off in 60 seconds

    128 Disabled open by any protection129 Disabled open by general overcurrent protection 1

    st group

    130 Disabled open by general overcurrent protection 2nd

     group

    131 Disabled open by general overcurrent protection 3rd

     group

    132 Disabled open by general overcurrent protection 4th

     group

    133 Disabled open by general overcurrent protection 5th

     group

    134 Disabled open by general overcurrent protection 6th

     group

    135 Disabled open by general overcurrent protection 7th

     group

    136 Disabled open by general overcurrent protection 8th

     group

    137 Disabled open by overvoltage protection 1st

     group

    138 Disabled open by overvoltage protection 2nd

     group

    139 Disabled open by overvoltage protection 3rd

     group

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    10/36

     

    10

    Protections and Automatics 3V3I 

    140 Disabled open by undervoltage protection 1st

     group

    141 Disabled open by undervoltage protection 2nd

     group

    142 Disabled open by overfrequency protection 1st

     group

    143 Disabled open by overfrequency protection 2nd

     group

    144 Disabled open by underfrequency protection 1st

     group

    145 Disabled open by underfrequency protection 2nd

     group

    146 Disabled signalling of voltage unbalance

    147 Disabled open by voltage unbalance protection

    148 Disabled signalling of current unbalance

    149 Disabled open by current unbalance protection

    150 Disabled open by earth fault protection

    151 Disabled open after unsuccessful reclosing

    152 Disabled close by automatic reclosing (AR)

    153AR status: 0 = off, 1 = fast (1

    st cycle enabled, 2

    nd cycle disabled),

    2 = slow (1st

     cycle enabled, 2nd

     cycle enabled), 3 = fast + slow (1st

     and 2nd

     cycles enabled)

    154 AR disabled (controlling by signals has to be enabled in the parameters of the AR)

    155 AR fast (controlling by signals has to be enabled in the parameters of the AR)

    156 AR slow (controlling by signals has to be enabled in the parameters of the AR)

    157 AR fast + slow (controlling by signals has to be enabled in the parameters of the AR)158 Simulations enabled

    159 Manual accumulator test

    160 Remote clear of the front panel (on the RTU7K unit)

    161 2n

     protection group selected

    162 Erase all fault records stored in the unit

    163 Manual record start

    255 Signal without meaning – can be used for test purposes

    256 Pickup of general overcurrent protection – I1  – 1st

     group

    257 Pickup of general overcurrent protection – I2  – 1st

     group

    258 Pickup of general overcurrent protection – I2  – 1

    st

     group 259 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 1

    st group

    260 Trip of general overcurrent protection – I1  – 1st

     group

    261 Trip of general overcurrent protection – I2  – 1st

     group

    262 Trip of general overcurrent protection – I2  – 1st

     group 

    263 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 1st

     group

    264 Close by general overcurrent protection – 1st

     group (0→1→0) 

    265 Pickup of general overcurrent protection – I1  – 2nd

     group

    266 Pickup of general overcurrent protection – I2  – 2nd

     group

    267 Pickup of general overcurrent protection – I3  – 2nd

     group 

    268 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 2nd

     group

    269 Trip of general overcurrent protection – I1  – 2nd

     group

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    11/36

     

    11

    Protections and Automatics 3V3I 

    270 Trip of general overcurrent protection – I2  – 2nd

     group

    271 Trip of general overcurrent protection – I3  – 2nd

     group 

    272 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 2nd

     group

    273 Close by general overcurrent protection – 2nd

     group (0→1→0) 

    274 Pickup of general overcurrent protection – I1  – 3rd

     group

    275 Pickup of general overcurrent protection – I2  – 3rd

     group

    276 Pickup of general overcurrent protection – I3  – 3rd

     group

    277 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 3rd

     group

    278 Trip of general overcurrent protection – I1  – 3rd group

    279 Trip of general overcurrent protection – I2  – 3rd

     group

    280 Trip of general overcurrent protection – I3  – 3rd

     group

    281 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 3rd

     group

    282 Close by general overcurrent protection – 3rd

     group (0→1→0) 

    283 Pickup of general overcurrent protection – I1  – 4th

     group

    284 Pickup of general overcurrent protection – I2  – 4th

     group

    285 Pickup of general overcurrent protection – I3  – 4th

     group 

    286 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 4th

     group

    287 Trip of general overcurrent protection – I1  – 4th

     group

    288 Trip of general overcurrent protection – I2  – 4th

     group289 Trip of general overcurrent protection – I3  – 4

    th group 

    290 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 4th

     group

    291 Close by general overcurrent protection – 4th

     group (0→1→0) 

    292 Pickup of general overcurrent protection – I1  – 5th

     group

    293 Pickup of general overcurrent protection – I2  – 5th

     group

    294 Pickup of general overcurrent protection – I3  – 5th

     group 

    295 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 5t

     group

    296 Trip of general overcurrent protection – I1  – 5t

     group

    297 Trip of general overcurrent protection – I2  – 5t

     group

    298 Trip of general overcurrent protection – I3  – 5

    t

     group 299 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 5

    t group

    300 Close by general overcurrent protection – 5t

     group (0→1→0) 

    301 Pickup of general overcurrent protection – I1  – 6th

     group

    302 Pickup of general overcurrent protection – I2  – 6th

     group

    303 Pickup of general overcurrent protection – I3  – 6th

     group 

    304 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 6th

     group

    305 Trip of general overcurrent protection – I1  – 6th

     group

    306 Trip of general overcurrent protection – I2  – 6th

     group

    307 Trip of general overcurrent protection – I3  – 6th

     group 

    308 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 6th

     group

    309 Close by general overcurrent protection – 6th

     group (0→1→0) 

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    12/36

     

    12

    Protections and Automatics 3V3I 

    310 Pickup of general overcurrent protection – I1  – 7th

     group

    311 Pickup of general overcurrent protection – I2  – 7th

     group

    312 Pickup of general overcurrent protection – I3  – 7th

     group 

    313 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 7th

     group

    314 Trip of general overcurrent protection – I1  – 7th

     group

    315 Trip of general overcurrent protection – I2  – 7th

     group

    316 Trip of general overcurrent protection – I3  – 7th

     group 

    317 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 7th

     group

    318 Close by general overcurrent protection – 7th group (0→1→0) 

    319 Pickup of general overcurrent protection – I1  – 8th

     group

    320 Pickup of general overcurrent protection – I2  – 8th

     group

    321 Pickup of general overcurrent protection – I3  – 8th

     group 

    322 Pickup of general overcurrent protection (I0 or I1 or I2 or I3) – 8th

     group

    323 Trip of general overcurrent protection – I1  – 8th

     group

    324 Trip of general overcurrent protection – I2  – 8th

     group

    325 Trip of general overcurrent protection – I3  – 8th

     group 

    326 Trip of general overcurrent protection (I0 or I1 or I2 or I3) – 8th

     group

    327 Close by general overcurrent protection 8th

     group (0→1→0) 

    328 Pickup of overvoltage protection 1st

     group329 Trip of overvoltage protection 1

    st group

    330 Open by overvoltage protection 1st

     group (0→1→0) 

    331 Pickup of overvoltage protection 2nd

     group

    332 Trip of overvoltage protection 2nd

     group

    333 Open by overvoltage protection 2nd

     group (0→1→0) 

    334 Pickup of overvoltage protection 3rd

     group

    335 Trip of overvoltage protection 3r

     group

    336 Open by overvoltage protection 3r

     group (0→1→0) 

    337 Pickup of undervoltage protection 1st

     group

    338 Trip of undervoltage protection 1

    st

     group339 Open by undervoltage protection 1

    st group (0→1→0) 

    340 Pickup of undervoltage protection 2n

     group

    341 Trip of undervoltage protection 2nd

     group

    342 Open by undervoltage protection 2nd

     group (0→1→0) 

    343 Pickup of overfrequency protection 1st

     group

    344 Trip of overfrequency protection 1st

     group

    345 Open by overfrequency protection 1st

     group (0→1→0) 

    346 Pickup of overfrequency protection 2nd

     group

    347 Trip of overfrequency protection 2nd

     group

    348 Open by overfrequency protection 2nd

     group (0→1→0) 

    349 Pickup of underfrequency protection 1st

     group

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    13/36

     

    13

    Protections and Automatics 3V3I 

    350 Trip of underfrequency protection 1st

     group

    351 Open by underfrequency protection 1st

     group (0→1→0) 

    352 Pickup of underfrequency protection 2nd

     group

    353 Trip of underfrequency protection 2nd

     group

    354 Open by underfrequency protection 2nd

     group (0→1→0) 

    355 Pickup of voltage unbalance

    356 Trip of voltage unbalance

    357 Open by voltage unbalance (0→1→0) 

    358 Pickup current unbalance

    359 Trip current unbalance

    360 Open by current unbalance (0→1→0) 

    361 Pickup of earth fault protection

    362 Trip of earth fault protection

    363 Open by earth fault protection (0→1→0) 

    364 Open after unsuccessful automatic reclosing (0→1→0) 

    365 Close by automatic reclosing (0→1→0) 

    366 Voltage B

    367 Fault records buffer overrun

    368 Simulation in progress (some input can be in the simulated state)

    Outputs

    Address Description

    0 to 19 Relay 0 to 19

    128 Disable open by any protection

    129 Disable open by general overcurrent protection 1st

     group

    130 Disable open by general overcurrent protection 2n

     group

    131 Disable open by general overcurrent protection 3r

     group

    132 Disable open by general overcurrent protection 4t

     group133 Disable open by general overcurrent protection 5

    t group

    134 Disable open by general overcurrent protection 6t

     group

    135 Disable open by general overcurrent protection 7th

     group

    136 Disable open by general overcurrent protection 8th

     group

    137 Disable open by overvoltage protection 1st

     group

    138 Disable open by overvoltage protection 2nd

     group

    139 Disable open by overvoltage protection 3rd

     group

    140 Disable open by undervoltage protection 1st

     group

    141 Disable open by undervoltage protection 2nd

     group

    142 Disable open by overfrequency protection 1

    st

     group143 Disable open by overfrequency protection 2

    nd group

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    14/36

     

    14

    Protections and Automatics 3V3I 

    144 Disable open by underfrequency protection 1st

     group

    145 Disable open by underfrequency protection 2nd

     group

    146 Disable signalling of voltage unbalance

    147 Disable open by voltage unbalance protection

    148 Disable signalling of current unbalance

    149 Disable open by current unbalance protection

    150 Disable open by earth fault protection

    151 Disable open after unsuccessful reclosing

    152 Disable close by automatic reclosing (AR)

    153 Set AR: 0 = off, 1 = fast (1st

     cycle enabled, 2nd

     cycle disabled),

    2 = slow (1st

     cycle enabled, 2nd

     cycle enabled), 3 = fast + slow (1st

     and 2nd

     cycles enabled)

    154 Disable AR (controlling by signals has to be enabled in the parameters of the AR)

    155 Set fast AR (controlling by signals has to be enabled in the parameters of the AR)

    156 Set slow AR (controlling by signals has to be enabled in the parameters of the AR)

    157 Set fast + slow AR (controlling by signals has to be enabled in the parameters of the AR)

    158 Enable simulations

    159 Start manual accumulator test

    160 Clear the front panel (on the RTU7K unit)

    161 Select protection group162 Erase all fault records stored in the unit

    163 Manual record start

    255 Signal without meaning – can be used for test purposes

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    15/36

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    16/36

     

    16

    Protections and Automatics 3V3I 

    Common parameters

    Description

    Common parameters contain a set of parameters that are used across many particular protections.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables protection functions.

    Channel 0, 1 0 = 1st

     protection block, 1 = 2nd

     protection block (typically backup).Conversion

    Values conversion YES/NO Enables/disabled conversion of analogue values according to the ranges

    in the RTU User Center application.

    Voltage range VMAX  Range of the voltage (depends on used input module and sensor).

    Voltage unit V, kV, …  Unit of the voltage.

    Current range IMAX  Range of the current (depends on used input module and sensor).

    Current unit mA, V, …  Unit of the current.

    Conductance range IMAX / VMAX  Range of the conductance.

    Conductance unit uS, mS, …  Unit of the conductance.

    Circuit Breaker

    Address of circuit breaker status

    signal

    0 to 19 The address of digital inputs to which the circuit breaker is connected.

    This digital input has to be set as double point. The first input of the

    double point input signals that the circuit breaker is open. The second

    input signals that the circuit breaker is closed.

    Address of circuit breaker open relay 0 to 19, none It defines the address of relay that is used for opening circuit breaker

    (none = Open by protection is disabled).

    Duration of open relay activation 0 to 2.55 s

    Step 0.01 s

    It defines the time interval how long the open relay is connected in the

    case of opening.

    Address of circuit breaker close relay 0 to 19, none It defines the address of relay that is used for closing circuit breaker

    (none = Close by protection is disabled).

    Duration of close relay activation 0 to 2.55 s

    Step 0.01 s

    It defines the time interval how long the close relay is connected in the

    case of closing.

    Address of circuit breaker aux. open

    relay

    0 to 19, none It defines the address of relay that is used together with the open relay.

    The one and half (this address is equal with the Address of circuit

    breaker aux. close relay) or two pole control can be enabled by defining

    this relay.

    Address of circuit breaker aux. close

    relay

    0 to 19, none It defines the address of relay that is used together with the close relay.

    The one and half (this address is equal with the Address of circuit

    breaker aux. open relay) or two pole control can be enabled by defining

    this relay.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    17/36

     

    17

    Protections and Automatics 3V3I 

    General Overcurrent Protection

    ANSI 50, 51, 67, 50N, 51N, 67N

    Description

    General overcurrent protection is processed every 10 milliseconds. Eight independent protection groups are available. Each group

    has its own parameters and signals. General overcurrent protection can work according to ANSI 50, 51, 67, 50N, 51N, 67N from the

    standard IEC 60255-151:2009. The dropout value equals 97% of the Current limit IS.

    The fault direction is determined by the polarity of active power in fault phase for phase protection or by the polarity of active

    power P0 for earth fault protection. Active power is calculated from the fundamental frequency. Voltage memory is used when the

    measured voltage during the fault is too small (less than 20% of its range). The voltage memory capacity is one second. The fault is

    in the “forward” direction when the active power is positive. The fault is in the “backward” direction when the active power is

    negative or zero.

    After the circuit breaker is closed the second, typically greater, limit of the current Raised current threshold after close is used. The

    second limit is valid only for a finite time that is set by the parameter Raised threshold duration. The circuit breaker close status is

    determined from the circuit breaker status signal. The remote close command is also considered as a circuit breaker close status.

    The second current limit is enabled only if the values of all the three line to line voltages are greater than Voltage to allow raised

    threshold.

    The protection works with filtered value of I0 if the parameter

    Protection type is set to Earth. Pickup is set when V

    0 is greater than

    Lower threshold of voltage V0  and I0  is greater than IS. Trip is set when the pickup is set for the time given by selected time

    characteristics. Pickup and trip are cleared when IX is less than 97% IS and V0 is less than 97% of Lower threshold of voltage V0 for

    the time given by selected time characteristics. 

    The protection works with phase values I1, I2, I3 if the parameter Protection type is set to Phase. The filtration of values is enabled by

    the parameter Filter. The pickup is set when IX is greater than IS. The trip is set when the pickup is set for the time given by selected

    time characteristics. The pickup and trip are cleared when IX is less than 97% IS for the time given by selected time characteristics. 

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    18/36

     

    18

    Protections and Automatics 3V3I 

    Time characteristics are as follows.

    Characteristics Pickup time

     Dropout time

     Characteristics name

    k [s] c [s]   tr   A 0.14 0 0.02 4.85 2 Standard inverse

    B 13.5 0 1 21.6 2 Very inverseC 50 0 2 29.1 2 Extremely inverse

    D 0.0515 0.114 0.02 4.85 2 IEEE moderately inverse

    E 19.61 0.491 2 21.6 2 IEEE very inverse

    F 28.2 0.121 2 29.1 2 IEEE extremely inverse

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Current limit IS  0 to IMAX  Pickup current limit IS that is used for calculation of the pickup time.

    Min. duration of threshold break 0 to 655.35 s

    Step 0.01 s

    The parameter for non-directional characteristics. The trip is set after the

    pickup is set for the time defined by this parameter.

    Time multiplier 0 to 2

    Step 0.01

    This parameter defines time multiplier TMS for time dependent

    characteristics.

    Raised current threshold after close 0 to IMAX  Typically raised current limit that is used instead of the IS after the circuit

    breaker close.

    Raised threshold duration 0 to 25.5 s

    Step 0.1 s

    This parameter defines the time for which the raised limit is valid.

    Voltage to allow raised threshold 0 to VMAX  The raised limit is valid only in case that all line to line voltages are

    greater than this parameter.

    Lower threshold of voltage V0  0 to VMAX  This parameter is used for earth fault protection. The earth faultprotection is enabled when V0 is grater then value of this parameter.

    Time reset 0 to 2.55 s

    Step 0.01 s

    The parameter for non-directional characteristics. The pickup and trip is

    cleared when the current is less than 97% of IS for the time defined by

    this parameter.

    Protection directivity Non-directional

    Forward

    Backward

    Directionality of the protection is selected by this parameter. The

    protection can work as non-directional (works in both directions), or it

    can works in the forward direction (active power is positive), or it can

    works in the backward direction (active power is negative or zero).

    Characteristic Time

    independent

    A to F

    This parameter is used to select time characteristic for this protection.

    Time independent and six standardized characteristics (see table above)

    are configurable.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    19/36

     

    19

    Protections and Automatics 3V3I 

    Filter

    Filter YES/NO The protection process filtered values of current when this parameter is

    to YES. Otherwise it process unfiltered values. The earth protection

    works with filtered value I0 always.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    Number of reclosing after overcurrent 0 to 5 This parameter defines maximum number of automatic reclosing.

    Signalling

    Address of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

    Evaluate Inputs

    Protection type Phase

    Earth

    The protection uses phase values I1, I2, and I3 when the value of this

    parameter is Phase, of it uses I0 (earth fault protection) when the value

    of this parameter is Earth.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    20/36

     

    20

    Protections and Automatics 3V3I 

    Overvoltage Protection

    ANSI 59, 59N

    Description

    Overvoltage protection is processed every 10 milliseconds. Effective values of phases, line to line, or V 0 voltages (it depends on the

    value of parameter Evaluated inputs) are compared with Voltage limit. Pickup is set if compared voltage is greater than Voltage

    limit. Trip is set when the pickup is set for the time given by the parameter Min. duration of threshold break. Pickup and trip are

    cleared when compared voltage is less than Lower voltage limit  (its value is typically about 95% of the Voltage limit). Two

    independent protection groups with its own parameters and signals are available.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Voltage limit 0 to VMAX  Pickup is set when compared voltage is greater than this value.

    Min. duration of threshold break 0 to 655.35 s

    Step 0,01 s

    Trip is set when the pickup is set for the time given by this parameter.

    Lower voltage limit 0 to VMAX  Pickup and trip are cleared when compared voltage is less than this

    value.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    Signalling

    Address of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

    Evaluated Inputs

    Evaluated inputs V1/V2/V3 V1, V2, V3 

    V12, V23, V31 

    V0 

    Processed inputs are selected by this parameter.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    21/36

     

    21

    Protections and Automatics 3V3I 

    Undervoltage Protection

    ANSI 27

    Description

    Undervoltage protection is processed every 10 milliseconds. Effective values of phases, line to line, or V0 voltages (it depends on the

    value of parameter Evaluated inputs) are compared with Voltage limit. Pickup is set if compared voltage is less than Voltage limit.

    Trip is set when the pickup is set for the time given by the parameter Min. duration of threshold break. Pickup and trip are cleared

    when compared voltage is greater than Upper voltage limit (its value is typically about 105% of the Voltage limit). The processing of

    this protection is disabled and all signals are cleared when all phase currents are less than Limit of minimal current. Twoindependent protection groups with its own parameters and signals are available.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Voltage limit 0 to VMAX  Pickup is set when compared voltage is less than this value and any

    phase current is greater than Limit of minimal current.

    Min. duration of threshold break 0 to 655.35 s

    Step 0.01 s

    Trip is set when the pickup is set for the time given by this parameter.

    Upper voltage limit 0 to VMAX  Pickup and trip are cleared when compared voltage is greater than this

    value.

    Limit of minimal current 0 to IMAX  Phase current above this limit enables this protection.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    SignallingAddress of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

    Evaluated Inputs

    Evaluated inputs V1/V2/V3

    V1, V2, V3 

    V12, V23, V31 

    Processed inputs are selected by this parameter.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    22/36

     

    22

    Protections and Automatics 3V3I 

    Overfrequency Protection

    ANSI 81H

    Description

    Overfrequency protection is processed every 10 milliseconds. Pickup is set if measured frequency is greater than Frequency limit 

    and voltage of all three line to line voltages is greater than Phase to phase voltage limit. Trip is set when the pickup is set for the

    time given by the parameter Min. duration of threshold break. Pickup and trip are cleared when the frequency is less than Lower

    limit of frequency (its value is typically about 95% of the Frequency limit) or any of line to line voltage is less than Phase to phase

    voltage limit. Two independent protection groups with its own parameters and signals are available.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Frequency limit 0 to 100 Hz

    Step 0.003 Hz

    Pickup is set if measured frequency is greater than this parameter and

    voltage of all three line to line voltages is greater than Phase to phase

    voltage limit.

    Min. duration of threshold break 0 to 25.5 s

    Step 0.1 s

    Trip is set when the pickup is set for the time given by this parameter.

    Lower limit of frequency 0 to 100 Hz

    Step 0.003 Hz

    Pickup and trip are cleared if the frequency is less than this parameter.

    Phase to phase voltage limit 0 to VMAX  Any phase to phase voltage under this limit disables this protection.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    SignallingAddress of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    23/36

     

    23

    Protections and Automatics 3V3I 

    Underfrequency Protection

    ANSI 81L

    Description

    Underfrequency protection is processed every 10 milliseconds. Pickup is set if measured frequency is less than Frequency limit and

    voltage of all three line to line voltages is greater than Phase to phase voltage limit. Trip is set when the pickup is set for the time

    given by the parameter Min. duration of threshold break. Pickup and trip are cleared when the frequency is greater than Upper

    limit of frequency (its value is typically about 105% of the Frequency limit) or any of line to line voltage is less than Phase to phase

    voltage limit. Two independent protection groups with its own parameters and signals are available.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Frequency limit 0 to 100 Hz

    Step 0.003 Hz

    Pickup is set if measured frequency is less than this parameter and

    voltage of all three line to line voltages is greater than Phase to phase

    voltage limit.

    Min. duration of threshold break 0 to 25.5 s

    Step 0.1 s

    Trip is set when the pickup is set for the time given by this parameter.

    Upper limit of frequency 0 to 100 Hz

    Step 0.003 Hz

    Pickup and trip are cleared if the frequency is greater than this

    parameter.

    Phase to phase voltage limit 0 to VMAX  Any phase to phase voltage under this limit disables this protection.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    SignallingAddress of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    24/36

     

    24

    Protections and Automatics 3V3I 

    Earth Fault Protection

    Earth fault protection contains several independent evaluation principles. The common parameters have to be set firstly then the

    parameters of each principle have to be set. Following internal statues related to earth fault protection are used in this document:

      ZS-I – Trip of the impulse principle

      ZS-K – Trip of the conductance principle

      ZS-R – Trip of the connection of the resistor principle

      ZS-W – Trip of the wattmetrical principle

     

    ZS-V0 – V0 is greater than Lover threshold of voltage V0 

    Description

    Pickup is set if any of the internal statuses ZS-I, ZS-K, ZS-R, ZS-W, ZS-V0 is set. Trip is set when the pickup is set for the time given by

    the parameter Time before open. Pickup and trip are cleared when all internal statuses are clear for the time given by parameter

    the Prolongation of earth fault signalling. Pickup and trip are cleared also when all internal statuses are clear and the circuit

    breaker is opened.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    Internal status ZS-V0 is set when V0  is greater of equal to Lover threshold of voltage V0. When V0  is less than Lover threshold of

    voltage V0, internal status ZS-V0 is cleared.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Lover threshold of voltage V0  0 to VMAX  Internal status ZS-V0 is set when V0 is greater of equal to this parameter.

    This parameter is also used for clearing internal statuses.

    AutomaticsOpen by protection YES/NO Enables/disables opening by this protection.

    Time before open 0 to 25.5 s

    Step 0.1 s

    Trip is set when the pickup is set for the time given by this parameter.

    Number of reclosing after earth fault 0 to 5 This parameter defines maximum number of automatic reclosing.

    Signalling

    Prolongation of earth fault signalling 0 to 25.5 s

    Step 0.1 s

    Signalling of the trip and pick up is prolonged for the time given by this

    parameter. Setting this parameter reduces possible flicking of the tri and

    pickup.

    Address of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    25/36

     

    25

    Protections and Automatics 3V3I 

    Impulse Protection

    Description

    Impulse earth protection is processed every 1 millisecond. For positive active power it is tested if (-i 0 * v0) > 0 and absolute value of

    v0 is greater than Voltage V0 threshold and absolute value of 3i0 is greater than Current 3I0 threshold. For negative active power it is

    tested if (i0 * v0) > 0 and absolute value of v0 is greater than Voltage V0 threshold and absolute value of 3i0 is greater than Current

    3I0  threshold. Internal status ZS-I is set when all three conditions mentioned above are true for the time given by the parameter

    Time of check. Internal status ZS-I is cleared when any of conditions above is not true and V 0 is less than Lover threshold of voltage

    V0 from common parameters. The direction of the active power is evaluated every 1 second. Active power is considered as positiveif its value is greater than 0.4% of its range. Active power is considered as negative if its value is less than -0.4% of its range. If the

    value of active power is between -0.4% and 0.4%, the sign of the active power remains unchanged.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Voltage V0 threshold 0 to VMAX  V0 must be greater than this parameter in order to set ZS-I.

    Current 3I0 threshold 0 to IMAX  3I0 must be greater than this parameter in order to set ZS-I.

    Time of check 0 to 255 ms

    Step 1 ms

    Internal status ZS-I is set if all conditions are true for the time given by

    this parameter.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    26/36

     

    26

    Protections and Automatics 3V3I 

    Conductance Protection

    Description

    Conductance earth protection is processed every 10 milliseconds. Internal status ZS-K is set when V0 > Voltage V0 threshold and 3I0 

    * cos(0) / V0 > Conductance threshold for the time given by the parameter Time of check. Internal status ZS-K is cleared when anyof conditions above is not true and V0 is less than Lover threshold of voltage V0 from common parameters.

    Parameters

    Main ParametersEnabled YES/NO Enables/disables this protection.

    Limits

    Voltage V0 threshold 0 to VMAX  V0 must be greater than this parameter in order to set ZS-K.

    Conductance threshold 0 to IMAX / VMAX  Conductance must be greater than this parameter in order to set ZS-K.

    Time of check 0 to 2.55 s

    Step 0.01 s

    Internal status ZS-K is set if all conditions are true for the time given by

    this parameter.

    Wattmetrical Protection

    Description

    Wattmetrical earth protection is processed every 10 milliseconds. Internal status ZS-W is set when |0| < Phase shift 0 threshold and V0 > Voltage V0 threshold and 3I0 > Current 3I0 threshold for the time given by the parameter Time of check. Internal status ZS-

    W is cleared when any of conditions above is not true and V0 is less than Lover threshold of voltage V0 from common parameters.

    0 is measured between -i0 and v0 if active power P0 is positive. If active power P0 is negative, 0 is measured between i0 and v0. Thedirection of the active power P0 is evaluated every 1 second. Active power is considered as positive if its value is greater than 0.4%

    of its range. Active power is considered as negative if its value is less than -0.4% of its range. If the value of active power is between -

    0.4% and 0.4%, the sign of the active power remains unchanged.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Voltage V0 threshold 0 to VMAX  V0 must be greater than this parameter in order to set ZS-W.

    Current 3I0 threshold 0 to IMAX  3I0 must be greater than this parameter in order to set ZS-W.

    Phase shift 0 threshold 0 to 180°  |0| must be less than this parameter in order to set ZS-W.

    Time of check 0 to 2.55 s

    Step 0.01 s

    Internal status ZS-W is set if all conditions are true for the time given by

    this parameter.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    27/36

     

    27

    Protections and Automatics 3V3I 

    Earth Fault Protection – Connection of the Resistor

    Description

    This protection is processed every 10 milliseconds. When V0 is greater than Voltage V0 threshold and 3I0 is greater than Current 3I0 

    threshold, the average 3I01 of 3I0  from ¼Time to subst. gnd. resistor connection  to ¾Time to subst. gnd. resistor connection  is

    calculated. After Time to subst. gnd. resistor connection  elapses, the average 3I02 of 3I0 from ¼Duration of gnd. resistor connection 

    to ¾Duration of gnd. resistor connection  is calculated. Internal status ZS-R is set if 3I 02 >= (3I01  + 3I0  rise after gnd. resistor

    connection). Internal status ZS-R is cleared when any of conditions above is not true and V 0 is less than Lover threshold of voltage

    V0 from common parameters.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Voltage V0 threshold 0 to VMAX  V0 must be greater than this parameter in order to set ZS-R.

    Current 3I0 threshold 0 to IMAX  3I0 must be greater than this parameter in order to set ZS-R.

    Time to subst. gnd. resistor connection 0 to 2.55 s

    Step 0.01 s

    This parameter indicates when the resistor is connected.

    Duration of gnd. resistor connection 0 to 2.55 s

    Step 0.01 s

    This parameter indicates for how long the resistor is connected.

    3I0 rise after gnd. resistor connection 0 to IMAX  This parameter determines the minimal raise of 3I0 after the resistor is

    connected.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    28/36

     

    28

    Protections and Automatics 3V3I 

    Voltage Unbalance Protection

    Description

    Voltage unbalance is processed every 100 milliseconds. Pickup is set if (100 * (VMAX  - VMIN) / VMAX) > Unbalance threshold  and

    VMAX > VMAX threshold, where VMIN is minimal value of line to line of phase voltage and VMAX is maximum value of line to line of phase

    voltage. Trip is set when pick up is set for the time given by the Time of threshold. Pickup is cleared when any of conditions above is

    not true. Trip is cleared when the pickup is not set for the time Time of threshold.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    The principle of the voltage unbalance function is shown in the following figures.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    29/36

     

    29

    Protections and Automatics 3V3I 

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Unbalance threshold 0 to 100 %

    Step 1 %

    This parameter defines unbalance threshold for the following equation:

    (100 * (VMAX - VMIN) / VMAX) > Unbalance threshold 

    Time of threshold 0 to 25.5 s

    Step 0.1 s

    Trip is set when pick up is set for the time given by the Time of

    threshold.

    VMAX threshold 0 to VMAX  The voltage unbalance protection is enabled when VMAX is greater than

    this parameter.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    Signalling

    Address of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

    Evaluated Inputs

    Evaluate from voltage Phase

    Line to line

    Processed inputs are selected by this parameter.

    Current Unbalance Protection

    Description

    Current unbalance is processed every 100 milliseconds. Current unbalance is blocked when trip of overcurrent protection is set.

    Additionally current unbalance can be blocked when trip of earth fault protection is set. Blocking by earth fault protection trip has to

    be enabled by parameter Blocking by signal of earth fault protection.

    Pickup is set when one of following condition is true:

    If IMAX  is between Lower threshold of current IMAX and Upper threshold of current IMAX, the following condition is evaluated:

    (100 * (IMAX - IMIN) / IMAX) > Unbalance threshold + ((100 - Unbalance threshold) * (Upper threshold of current IMAX - Imax)) / (Upper

    threshold of current IMAX - Lower threshold of current IMAX))).

    If IMAX  is greater or equal to Upper threshold of current IMAX, the following condition is evaluated:

    (100 * (IMAX - IMIN) / IMAX) > Unbalance threshold.

    IMIN  is minimal value of the current and IMAX  is maximum value of the current. The value of the current is averaged over 100

    milliseconds for current unbalance protection. The equations showed above are expressed in the following figure.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    30/36

     

    30

    Protections and Automatics 3V3I 

    Pickup of current unbalance is set when current unbalance ratio is over red line in the figure (the hatched area). Trip is set when pick

    up is set for the time given by the Min. duration of threshold break. Pickup is cleared when condition above is not true. Trip is

    cleared when the pickup is not set for the time Min. duration of threshold break.

    The protection opens the circuit breaker, when the trip is set. The open control of the circuit breaker is enabled if the value of the

    parameter Open by protection is YES and the signals blocking open function are set to 0.

    The trip can also be signalled by the relay output (see chapter Signalling by the Relay OutputSignalling by the Relay OutputSignalling

    by the Relay Output). The address of the signal relay is defined by the parameter Address of trip signal relay.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this protection.

    Limits

    Upper threshold of current IMAX  0 to IMAX  Upper threshold of current IMAX for current unbalance equation.

    Lower threshold of current IMAX  0 to IMAX  Lower threshold of current IMAX for current unbalance equation.

    Unbalance threshold 0 to 100 %

    Step 1 %

    This parameter defines unbalance threshold for the following equation:

    For Lower threshold of current IMAX ≤ IMAX ≤Lower threshold of current

    IMAX: (100 * (IMAX - IMIN)/IMAX) > Unbalance threshold + ((100 - Unbalance

    threshold) * (Upper threshold of current IMAX - Imax)) / (Upper

    threshold of current IMAX - Lower threshold of current IMAX))).

    For IMAX ≥ Upper threshold of current IMAX:

    (100 * (IMAX  – IMIN) / IMAX) > Unbalance threshold.

    Min. duration of threshold break 0 to 25.5 s

    Step 0.1 s

    Trip is cleared when the pickup is not set for the time defined by this

    parameter.

    Blocking by signal of earth fault

    protection

    YES/NO Enables/disables current unbalance blocking if earth fault protection trip

    is set.

    Automatics

    Open by protection YES/NO Enables/disables opening by this protection.

    SignallingAddress of trip signal relay 0 to 19, none This parameter defines the address of the relay for signalling of trip.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    31/36

     

    31

    Protections and Automatics 3V3I 

    AutomaticsThe RTU7 unit provides two automatic functions: Automatic open after unsuccessful reclosing and automatic reclosing. Their

    description follows.

    Automatic Open after Unsuccessful Reclosing

    Description

    Automatic open after an unsuccessful reclosing is processed every 10 milliseconds. The automatic is waiting for an open after the

    trip of the overcurrent/short circuit or earth fault protection occurs. The lines is considered as switched off if all currents are lessthan Dead line current threshold and all line to line voltages are less than Dead line voltage threshold for at least 40 milliseconds.

    After that the automatic waits for the second trip. The lines have to be switched off after the second trip for at least Min. duration

    of dead line. Otherwise the automatic do not open the circuit breaker.

    The time between the first trip and the opening by the automatic has to be less than Max. time to open by short circuit or Max.

    time to open by earth fault when the first trip was caused by the short circuit/overcurrent or by the earth fault, respectively. After

    this time elapses a next trip is considered as the first one.

    The open of the circuit breaker is enabled when the parameter Open after short circuit or Open after earth fault is YES if the circuit

    was open by the short circuit/overcurrent or by the earth fault, respectively. The both parameters have to be set to YES if the first

    open was caused by other source than the second one.

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this automatic.

    Limits

    Dead line voltage threshold 0 to VMAX  The line is considered as switched off if all line to line voltages are less

    than this parameter.

    Dead line current threshold 0 to IMAX  The line is considered as switched off if all phase voltages are less than

    this parameter.

    Automatics

    Open after short circuit YES/NO Enables/disables opening by this automatic after the short

    circuit/overcurrent.

    Open after earth fault YES/NO Enables/disables opening by this automatic after the earth fault.

    Max. time to open by short circuit 0 to 255 s

    Step 1 s

    The maximum time between the first trip by the short

    circuit/overcurrent and the opening by the automatic. The current cycle

    of the automatic is finished after this time elapses.

    Max. time to open by earth fault 0 to 255 s

    Step 1 s

    The maximum time between the first trip by the earth fault and the

    opening by the automatic. The current cycle of the automatic is finished

    after this time elapses.

    Min. duration of dead line 0 to 2.55 s

    Step 0.01 s

    The circuit is opened after this time.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    32/36

     

    32

    Protections and Automatics 3V3I 

    Automatic Reclosing

    Description

    Automatic reclosing (AR) is processed every 10 milliseconds. When the overcurrent/short circuit or earth fault protection opens, the

    automatic reclosing tries to close after the time defined by the parameter Time to xth

      reclosing. The parameters set of each

    protection contains the parameter which defines maximum number of the AR cycles (0 disables AR) after open by the protection.

    When the maximum number of the AR cycles is reached, no additional AR is performed and line stays off. The automatic reclosing is

    to be enabled by the parameter Enabled and by the signal.

    The reclosing mode is selected by the parameter Reclosing mode. Description of three available modes follows.

    1. 

    Standard

    In this mode any of protection can open the switch gear. It is not important which protection caused open. The maximum

    number of the AR cycles is given by the minimum of maximum numbers of the AR cycles of all protections that caused open.

    2. 

    Fast+slow

    Only two cycles (fast  – 1st

     time and slow  – 2nd

     time) are used in this mode. The VDOs/VDIs are used for selection of used

    cycles. It is not important which protection caused open.

    3. 

    Fast+slow limited

    Only two cycles (fast and slow) are used in this mode. The fast (1st

     time) cycle is used for the earth protection and the slow

    (2nd

     time) cycle is used for all protections. The VDOs/VDIs are used for selection of used cycles.

    The current reclosing cycle is cancelled by manual or remote control of the switch gear. The automatic reclosing is disabled after its

    cancellation (manual or remote control of the switch gear) for the time given by the parameter Reclos. blockade duration after

    close by op. Running reclosing cycle is cancelled also if the switch gear is closed for the time given by the parameter Time for

    cancellation of running reclosing. The automatic reclosing closes the switch gear if only the current switch gear status is open or

    indefinite and the value of current in all three phases is less than Dead line current threshold. Otherwise the current reclosing cycle

    is cancelled. The time between the open and the close is given by the parameters Time to first reclosing to Next cycle of reclosing.

    It is possible to define up to six different times that typically extend. The Time to first reclosing is used for the first reclosing cycle,

    the Time to second reclosing is used for the second reclosing cycle, and so on. 

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    33/36

     

    33

    Protections and Automatics 3V3I 

    Parameters

    Main Parameters

    Enabled YES/NO Enables/disables this automatic.

    Limits

    Dead line current threshold 0 to IMAX  The line is considered switched off if all phase currents are less than this

    parameter.

    Automatics

    Time to first reclosing 0 to 25.5 s

    Step 0.1 s

    The time between the open and the automatic reclose for the first cycle.

    Time to second reclosing 0 to 255 s

    Step 1 s

    The time between the open and the automatic reclose for the second

    cycle.

    Time to third reclosing 0 to 255 s

    Step 1 s

    The time between the open and the automatic reclose for the third

    cycle.

    Time to fourth reclosing 0 to 255 s

    Step 1 s

    The time between the open and the automatic reclose for the fourth

    cycle.

    Time to fifth reclosing 0 to 255 s

    Step 1 s

    The time between the open and the automatic reclose for the fifth cycle.

    Next cycle of reclosing 0 to 255 s

    Step 1 s

    The time between the open and the automatic reclose for the sixth and

    next cycle.

    Reclos. blockade duration after close

    by op

    0 to 255 s

    Step 1 s

    The automatic reclosing is disabled after its cancellation (due to the

    remote or manual control) for the time given by this parameter.

    Time for cancellation of running

    reclosing

    0 to 255 s

    Step 1 s

    Running reclosing cycle is cancelled if the switch gear is closed for the

    time given by this parameter.

    Reclosing mode Standard

    Fast+slow

    Fast+slow

    limited

    Standard – the maximum number of automatic reclosing cycles is given

    by the parameter in each protection.

    Fast+slow – two cycles (fast – 1st

     time and slow – 2nd

     time) are used. The

    VDOs/VDIs are used for selection of used cycles.

    Fast+slow limited – two cycles (fast – 1st

     time and slow – 2nd

     time) are

    used. The fast cycle is used for the earth protection and the slow (2

    nd

     time) cycle is used for all protections. The VDOs/VDIs are used for

    selection of used cycles

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    34/36

     

    34

    Protections and Automatics 3V3I 

    Fault Records

    Common Settings

    Description

    Six analogue channels (v1, v2, v3, i1, i2, i3) and sixteen digital channels (its source is selectable by the parameter Source) are recorded

    every 1 millisecond. The records are saved to the mass memory when the digital channel, whose parameter Record starting is set to

    YES, changes its state from 0 to 1. The length of the record is between the Min. total record duration and the Max. total duration of

    one record. The record is recorded if its length is less than Max. total duration of one record and at least one digital channel, whose

    parameter Record holding is set to YES, has state 1. A record can be started by the ON remote control of the special signal also. The

    record started this way has length approximately 150 milliseconds. All records can be deleted by the ON remote control of the

    special signal.

    Records are transmitted to the control system automatically (has to be enabled by the parameter Automatic transfer of records) or

    on the user request. If the parameter Delete record after transfer is set to YES, the successfully transmitted record is deleted from

    the memory. This parameter should have value NO if the parameter Circular rewriting has value YES. 

    The parameter Circular rewriting enables circular rewriting of the oldest records if there is no free space for a newer one.

    Parameters

    Main parameters

    Enabled YES/NO Enables/disables creation of the fault records.

    Channel 0 Channel of the fault recorder (only 0 is allowed).

    Station name text Name of the station with length up to 64 characters.

    Fault Records Settings

    Min. total record duration 0.2 to 25.5 s

    Step 0.1 s

    Determines minimal length of one record.

    Max. total duration of one record 0.2 to 25.5 s

    Step 0.1 s

    Determines maximum length of one record.

    Automatic transfer of records YES/NO Enables/disables automatic transmission of the record to the control

    system.

    Circular rewriting YES/NO Enables/disables circular rewriting of the records.

    Delete record after transfer YES/NO Enables/disables automatic deletion of the record after its transfer to the

    control system.

    Voltage Conversion

    Primary range Primary range of the voltage (depends on used input module and sensor).

    Secondary range Secondary range of the voltage (depends on used input module).

    Unit V, kV, …  Unit of the voltage.

    Current Conversion

    Primary range Primary range of the voltage (depends on used input module and sensor).

    Secondary range Secondary range of the voltage (depends on used input module).

    Unit mA, A, …  Unit of the current.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    35/36

     

    35

    Protections and Automatics 3V3I 

    Analogue Channels

    Description

    Fault record contains six analogue channels (i1, i2, i3, v1, v2, v3 in the REC format) or eight analogue channels (i1, i2, i3, i0, v1, v2, v3, v0 in

    the COMTRADE format). The RTU Behaviour Viewer application supports both formats. In both cases are available all channels

    because the application RTU Behaviour Viewer computes the missing channels.

    The parameter Channel name is available and contains channel identifier of the channel for the COMTRADE format.

    Parameters

    Main parameters

    Channel name Text Analogue channel identifier with length up to 30 characters.

    Digital Channels

    Description

    Fault record contains sixteen digital channels. The source of all channels is selectable by the parameter Source. The source can be a

    digital input, output, internal status, etc. State of the channel is the same as the state of its source if the parameter Negation has

    value NO. Otherwise it has opposite value than its source. The digital channel starts a new record if its value changes from 0 to 1 and

    its parameter Record starting is YES. The digital channel keeps recording in progress to the maximum length of the record given by

    the parameter Max. total duration of one record if its value is 1 and its parameter Record holding is YES.

    The parameter Channel name is available and contains channel identifier of the channel for the COMTRADE format.

    Parameters

    Main parameters

    Channel name text Digital channel identifier with length up to 30 characters.

    Fault Records Settings

    Record starting YES/NO Enables/disables start of recording by the change of this channel to 1.

    Record holding YES/NO Enables/disables holding of the record to the Max. total duration of one

    record if the value of this channel is 1.

    Source DI, VDI, …  Determines the source of the channel. The source can be a digital input,

    output, internal status, etc.

    Negation YES/NO Enables/disables negation of the channel.

  • 8/9/2019 RTU7 3V3I protection manual ver. 112.01 2013-01-21.pdf

    36/36

     

    Protections and Automatics 3V3I 

    SignallingThe signalling panel can be connected to the RTU7 unit. The meaning of each signalling LED is configurable in the expressions.

    Internal statuses are available in the expressions and expose for example internal states of protections. Internal statuses can be

    used as a source of digital channels in the fault records. A list of internal statuses follows.

    Address Description

    0 One second tick

    1 HioCom2 communication status

    2 Reserved3 Supply voltage lost

    4

    Voltage „A“ 

    DC power supply: active when DI02 is active

    AC power supply: active when power supply voltage is grater then 23% of its range

    5

    Voltage „B“ 

    Active when US >= 50 % of US range.

    Flashing 1 Hz when US >= 5 % of US range. Otherwise it is inactive. US is the average of the line to line voltages V12, V13,

    V23.

    6 Breaker status (double bit)

    7 Breaker status – open

    8 Breaker status – close

    9 Reclosing active

    10 Reclosing finished

    11 ZS-W

    12 ZS-K

    13 ZS-I

    14 ZS-R

    15 ZS-V0

    16 Active power is less than zero (-P)

    17 ZSW-0 (|0| < Phase shift 0 threshold)

    18 Open after reclose

    19 Reclosing – close