Page 1: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Server Technology Solutions for the Data Center Equipment Cabinet

Sentry Power Tower XL

- PTXL-xxxx - PTXM-xxxx

Installation and Operations Manual

© 2003-2005 Server Technology, Inc. All rights reserved

Page 2: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Instructions This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. Dangerous Voltage This symbol is intended to alert the user to the presence of un-insulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons. Protective Grounding Terminal This symbol indicates a terminal that must be connected to earth ground prior to making any other connections to the equipment.

Life-Support Policy

As a general policy, Server Technology does not recommend the use of any of its products in the following situations: • life-support applications where failure or malfunction of the Server Technology product can be

reasonably expected to cause failure of the life-support device or to significantly affect its safety or effectiveness.

• direct patient care. Server Technology will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Server Technology that: • the risks of injury or damage have been minimized, • the customer assumes all such risks, and • the liability of Server Technology is adequately protected under the circumstances.

The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief or other purposes), auto-transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults or infants), anesthesia ventilators, infusion pumps, and any other devices designated as “critical” by the U.S. FDA.

Please Recycle Shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.

Page 3: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Table of Contents CHAPTER 1: INTRODUCTION 4

Quick Start Guide.............................................................................................................................4 Technical Support ............................................................................................................................4 Equipment Overview........................................................................................................................4

CHAPTER 2: INSTALLATION 5 Standard Accessories........................................................................................................................5 Additional Required Items ...............................................................................................................5 Safety Precautions ............................................................................................................................5 Installing the Power Input Retention Bracket...................................................................................6 Mounting ..........................................................................................................................................6 Attaching the Expansion Module .....................................................................................................7 Connecting to the Power Source ......................................................................................................7 Connecting Devices..........................................................................................................................7 Connecting to the Unit .....................................................................................................................7

CHAPTER 3: OPERATIONS 9 Interfaces ........................................................................................................................................10 HTML Interface .............................................................................................................................11 Command Line Interface................................................................................................................22

CHAPTER 4: ADVANCED OPERATIONS 43 SSL.................................................................................................................................................44 SSH ................................................................................................................................................45 SNMP.............................................................................................................................................46 LDAP .............................................................................................................................................52 TACACS+......................................................................................................................................58

CHAPTER 5: APPENDICES 63 Appendix A: Resetting to Factory Defaults ...................................................................................63 Appendix B: Uploading Firmware .................................................................................................63 Appendix C: Technical Specifications ...........................................................................................64 Appendix D: Warranty, Product Registration and Support ............................................................70

Page 4: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Chapter 1: Introduction Quick Start Guide

The following instructions will help you quickly install and configure your Power Tower for use in your data center equipment cabinet. For detailed information on each step, go to the page number listed to the right.

1. Mount the Power Tower.............................................................................................................5 2. Connect to the power source ......................................................................................................6 3. Connect the devices....................................................................................................................7 4. Connect to the Power Tower ......................................................................................................7 5. Configure the Power Tower .......................................................................................................9

• Login as the predefined Administrator (admn/admn) .......................................................10 • Configure the network settings .........................................................................................13 • Create new administrative user account............................................................................15 • Configure location and Power Tower names ....................................................................13 • Configure new user account(s) .........................................................................................15 • Remove the predefined Administrator ..............................................................................16

6. Connect the Power Tower to the network.

Technical Support Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is provided from 8:30 AM to 5:00 PM, Monday-Friday, Pacific Time.

Server Technology, Inc. 1040 Sandhill Drive Tel: 775.284.2000 Web: www.servertech.com Reno, Nevada 89521 USA Fax: 775.284.2065 Email: [email protected]

Equipment Overview A number is printed above each Power Tower XL outlet. These numbers may be used in commands that require an outlet name. See Outlet Naming and Grouping in Chapter 3: Operations for more information. The power inlet of the Power Tower XL connects to the electrical power source.

InputCurrent

1

4

3

2

88 Input CurrentLED

Outlet PowerStatus LED

SentryPowerTower

Server Technology

Inc.www.servertech.com

AC Power Inlet

8 7 6 5 4 3 2 1

8 7 6 5 4 3 2 1

16 15 14 13 12 11 10 9

RJ45 NET

Input Current LEDAC Power Inlet

RJ12 Link(for connection to optional Power Tower Expansion Moduleand/or Environmental Monitor)

Outlet PowerStatus LED

Inpu tCurrent

1

4

3

2

88

TMSentryPower Towerwww.servertech.com

Server Technology, Inc.Link

InputCurrent

8888Serial

InputCurrent

8888 Ethernet

InputCurrent

8888Serial

Ethernet

TMSentryPower Tower

www.servertech.comServer Technology, Inc.

Link

RJ45 SER (RS-232)

RJ12 LNK(for connection to optional Power Tower Expansion Moduleand/or Envieronmental Monitor)

RJ45 Serial (RS-232)

RJ45 Ethernet

NET

SER

LNK

31 2 4 5

6 7 8 9

31 2 4 5

6 7 8 9

31

24

5

67

89

MODEM

Modem

Modem

DB9M MODEM(for connection to an external modemor a 46 Commander)PT

DB9M Modem(for connection to an external modemor a 46 Commander)PT

Figure 1.1 Power Tower XL Views

4 • Introduction Sentry Power Tower XL Installation and Operations Manual

Page 5: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Chapter 2: Installation Before installing your Sentry Power Tower XLo, refer to the following lists to ensure that you have all the items shipped with the unit as well as all other items required for proper installation.

Standard Accessories • Mounting hardware

Vertical models - two removable flanges with four M4 screws and two mounting L-brackets with nut plates, four sets of screws and washers and optional button mounts. Horizontal models – two removable flanges with M4 screws.

• RJ45 to RJ45 crossover cable • DB9F to DB25M modem cable • RJ45 to DB9F serial port adapter (for connection to standard DB9M DTE serial port) • Outlet retention clips (208-240V models)

Additional items for PTXx-xxxx-02 models:

• Separate power input cord. • Power input retention bracket hardware.

Two removable T-brackets with two 40mm screws.

Additional Required Items • Flathead and Phillip screwdrivers • Screws, washers and nuts to attach the Power Tower to your rack

Safety Precautions This section contains important safety and regulatory information that should be reviewed before installing and using the Sentry Power Tower. For input and output current ratings, see Power Ratings in Appendix C: Technical Specifications.

Only for installation and use in a Service Access Location in accordance with the following installation and use instructions.

Destiné à l'installation et l'utilisation dans le cadre de Service Access Location selon les instructions d'installation et d'utilisation.

Nur für Installation und Gebrauch an Anschlusszugriffspunkten gemäß der folgenden Installations- und Gebrauchsanweisungen.

This equipment is designed to be installed on a dedicated circuit.

Cet équipement est conçu à être installé sur un circuit spécialisé.

Diese Ausrüstung ist zur Installation in einem festen Stromkreis vorgesehen.

Dedicated circuit must have circuit breaker or fuse protection. Power Towers have been designed without a master circuit breaker or fuse to avoid becoming a single point of failure. It is the customer’s responsibility to provide adequate protection for the dedicated power circuit. Protection of capacity equal to the current rating of the Power Tower must be provided and must meet all applicable codes and regulations. In North American, protection must have a 10,000A interrupt capacity.

Le circuit spécialisé doit avoir un disjoncteur ou une protection de fusible. Power Towers ont été conçus sans disjoncteur général ni fusible pour éviter que cela devient un seul endroit de panne. C’est la responsabilité du client de fournir une protection adéquate pour le circuit-alimentation spécialisé. Protection de capacité équivalant à la puissance de l'équipement, et respectant tous les codes et normes applicables. Les disjoncteurs ou fusibles destinés à l'installation en Amérique du Nord doivent avoir une capacité d'interruption de 10.000 A.

Der feste Stromkreis muss mit einem Schutzschalter oder einem Sicherungsschutz versehen sein. Power Towers verfügt über keinen Hauptschutzschalter bzw. über keine Sicherung, damit kein einzelner Fehlerpunkt entstehen kann. Der Kunde ist dafür verantwortlich, den Stromkreis sachgemäß zu schützen. Der Kapazitätsschutz entspricht der aktuellen Stromstärke der Geräte und muss alle relevanten Codes und Bestimmungen erfüllen. Für Installation in Nordamerika müssen Ausschalter bzw. Sicherung über 10.000 A Unterbrechungskapazität verfügen.

The plug on the power supply cord shall be installed near the equipment and shall be easily accessible.

La prise sur le cordon d’alimentation sera installée près de l’équipement et sera facilement disponible.

Der Stecker des Netzkabels muss in der Nähe der Ausrüstung installiert werden und leicht zugänglich sein.

Installation Orientation: PTXx-Vxxx units are design to be installed in vertical orientation.

Installation Orientation : Les unités PTXx-Vxxx sont conçues pour être installées dans une orientation verticale.

Installationsausrichtung: PTXx-Vxxx Einheiten sind zur vertikalen Installation vorgesehen.

Always disconnect the power supply cord before opening to avoid electrical shock.

Toujours déconnecter le cordon d’alimentation avant d’ouvrir pour éviter un choque électrique.

Ziehen Sie vor dem Öffnen immer das Netzkabel heraus, um die Gefahr eines elektrischen Schlags zu vermeiden.

WARNING! High leakage current! Earth connection is essential before connecting supply!

ATTENTION ! Haut fuite très possible ! Une connection de masse est essentielle avant de connecter l’alimentation !

ACHTUNG! Hoher Ableitstrom! Ein Erdungsanschluss ist vor dem Einschalten der Stromzufuhr erforderlich!

Sentry Power Tower XL Installation • 5 Installation and Operations Manual

Page 6: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Installing the Power Input Retention Bracket

For units with a total maximum output <30A, it may be necessary to install the power input retention bracket prior to mounting the unit within the rack.

To install the power input retention bracket: 1. Remove the two screws attaching the IEC 60320 C19 inlet

to the enclosure. 2. Assemble and attach the retention bracket to the enclosure

as shown.

Figure 2.1 Retention Bracket assembly

Mounting

Figure 2.2 Mounting

Horizontal/Rack 1. Select the appropriate bracket mounting points for proper mounting depth within the rack. 2. Attach the brackets to these mounting points with two screws for each bracket. 3. Install the enclosure into your rack, using the slots in each bracket. The slots allow about ¼ inch

of horizontal adaptability to align with the mounting holes of your rack.

NOTE: A mounting bracket kit for 23” wide racks or cabinets is available. Contact your Server Technology Sales Representative for more information.

Vertical 1. Attach the removable flanges to the mount points on the rear of the enclosure using M4 screws. 2. Attach the mounting L-brackets to the flanges with the supplied screws, washers and nut plates.

The slots allow about 1½ inches of vertical adaptability. 3. Attach the top and bottom brackets to your rack. NOTE: Contact your Server Technology Sales Representative for information regarding custom bracket design and fabrication services if you are unable to find a suitable manner for utilizing the included mounting brackets.

6 • Installation Sentry Power Tower XL Installation and Operations Manual

Page 7: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Attaching the Expansion Module Connect the Power Tower Expansion Module (PTXM) with the provided RJ11 crossover cable at the at the Link port on the Power Tower XL.

NOTE: The overall length of the RJ11 crossover cable should not exceed 10 feet.

Connecting to the Power Source On 30A units, the input power cord is attached to the base of the unit. On units with a total maximum output <30A, you must first attach the power cord to the unit before connecting the unit to the power source.

To attach a power cord to the unit: 1. Plug the female end of the power cord firmly into its connector at the base. 2. Use a screwdriver to tighten the two screws on the retention bracket.

To connect to the power source: Plug the male end of the power cord into the AC power source.

Connecting Devices NOTE: For PTXx-HFxx units, mis-matched polarity/phases of the two power sources will damage the unit. Verify proper synchronization of the polarity/phases before connecting to the power sources.

To avoid the possibility of noise due to arcing:

1. Keep the device’s on/off switch in the off position until after it is plugged into the outlet. 2. Connect devices to the Power Tower outlets.

NOTE: Server Technology recommends even distribution of attached devices across all available outlets to avoid exceeding the outlet, branch or phase limitations. See Power Ratings on page 64 for more information.

Always disconnect both power supply cords before opening to avoid electrical shock. Afin d’éviter les chocs électriques, débranchez les cables électrique avant d’ouvrir. Immer beiden Netzleitungen auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.

Connecting to the Unit Serial (RS232) port

The Power Tower XL is equipped with an RJ45 Serial RS-232 port for attachment to a PC or networked terminal server using the supplied RJ45 to RJ45 crossover cable and RJ45 to DB9F serial port adapter as required. See Data Connections in Appendix C: Technical Specifications for more information on the Serial RS-232 port.

Ethernet port The Power Tower XL is equipped with an RJ45 10/100Base-T Ethernet port for attachment to an existing network. This connection allows access to the Switched Power Tower via Telnet or HTML.

The Power Tower XL is configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet or HTML:

• IP address: 192.168.1.254 • Subnet Mask: 255.255.255.0 • Gateway: 192.168.1.1

The local PC network connection must be configured as noted below:

NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.

• IP address: 192.168.1.x (where x is 2-253) • Subnet Mask: 255.255.255.0

Modem port The Power Tower XL is equipped with a DB9 male Modem serial port for connection to an external modem using the supplied DB9 female to DB25 male serial cable. See Data Connections in Appendix C: Technical Specifications more information on the Modem port.

Sentry Power Tower XL Installation • 7 Installation and Operations Manual

Page 8: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower
Page 9: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Chapter 3: Operations INTERFACES 10

Outlet Naming and Grouping 10 Models with a Single Power Infeed ......................................................................................10 Models with Multiple Power Infeeds ....................................................................................10

Usernames and Passwords 10 HTML INTERFACE 11

Logging In 11 Outlet Control 12

Individual..............................................................................................................................12 Group....................................................................................................................................12

Environmental Monitoring 12 Input Load ............................................................................................................................12

Configuration 13 System...................................................................................................................................13 Network ................................................................................................................................13 Telnet/SSH ............................................................................................................................14 HTTP/SSL.............................................................................................................................14 Serial Ports...........................................................................................................................15 Outlets ..................................................................................................................................16 Groups ..................................................................................................................................16 Users.....................................................................................................................................16 FTP.......................................................................................................................................17 SNTP.....................................................................................................................................18 SNMP....................................................................................................................................18 LDAP....................................................................................................................................18 TACACS+.............................................................................................................................20

Tools 21 Restart ..................................................................................................................................21 Ping ......................................................................................................................................21

COMMAND LINE INTERFACE 22 Logging In 22 Operations Commands 24 Administration Commands 28

User Administration .............................................................................................................28 Outlet Administration ...........................................................................................................31 Group Administration...........................................................................................................33 Serial Port Administration....................................................................................................34 System Administration ..........................................................................................................36 TCP/IP Administration .........................................................................................................38 HTTP Administration ...........................................................................................................39 Telnet Administration ...........................................................................................................40 FTP Administration ..............................................................................................................40 SNTP Administration............................................................................................................41

Page 10: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Interfaces The Power Tower XL has two interfaces: the HTML interface accessed via the HTTP enabled Ethernet connections and the command line for serial and Telnet connections.

Outlet Naming and Grouping For commands requiring an outlet name, you may specify it in one of two ways: a predefined absolute name or a descriptive name assigned by an administrator.

Models with a Single Power Infeed Absolute names are specified by a period (.) followed by a tower letter and outlet number. The tower letter for the Power Tower XL is A and the tower letter for the optional Expansion Module is B.

Models with Multiple Power Infeeds For units with multiple infeed connectors, absolute names are specified by a period (.) followed by the tower letter, the infeed letter and outlet number.

Example: The absolute name for outlet 8 on the B infeed of tower A is .AB8.

Outlets may also be included in one or more named groups of outlets, enabling you to issue a command that affects all outlets in a named group.

Usernames and Passwords The Power Tower XL has one predefined administrative user account (username/password: admn/admn) and supports a maximum of 128 defined user accounts

NOTE: For security, Server Technology recommends removal of the predefined administrative user account after a new account with administrative rights has been created.

Only an administrative-level user may perform operations such as creating/removing user accounts and command privileges, changing passwords and displaying user information. An administrator may also view the status of all sensors and power inputs.

Usernames may contain from 1-16 characters and are not case sensitive; spaces are not allowed. Passwords may contain up to 16 characters, and are case sensitive.

10 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 11: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

HTML Interface The HTML interface is constructed of three major components: the System Location bar, the User/Navigation bar and the Control Screen. The System Location bar displays the Sentry’s location and IP address as well as the current Control Screen title. The User/Navigation bar displays the current user and privilege level and provides access to all HTML pages. And the Control Screen is used to display current data and allow changes to outlet states or system configuration.

The following sections describe each interface section/page and their use.

Log

User/Navigation System Location Control Screen

Figure 3.1 Example HTML page

ging In Logging in through HTML requires directing the HTML client to the configured IP address of the unit.

Tter a valid username and password and press OK.

nation. If all three fail, the

o log in by HTML: In the login window, en

If you enter an invalid username or password, you will be prompted again.

You are given three attempts to enter a valid username and password combisession ends and a protected page will be displayed.

NOTE: The default Sentry username/password is admn/admn.

Sentry Power Tower XL Operations • 11 Installation and Operations Manual

Page 12: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Outlet Control The Outlet Control section offers access to the Individual and Group outlet control pages. From the Individual and Group pages, the user can review and manipulate power control functions for all outlets and groups assigned to the current user. Both pages include the outlets absolute and descriptive names, the Outlet Status reported to the Sentry by the outlet, the current Control State being applied by the Sentry and the outlet load in amperes.

Available outlet and group power states may be set to on, off or reboot.

Individual The Individual outlet control page displays all outlets assigned to the current user. The user may apply on, off or reboot actions to individual, multiple or all accessible outlets.

To apply actions to individual or multiple outlets: In the Individual Outlet Control section, select the desired action from the Control Action drop-down menu for each individual outlet to be changed and press Apply.

To apply an action to all outlets: In the Global Control section, select the desired action from the Control Action drop-down menu and press Apply.

Group The Group outlet control page displays all groups assigned to the current user as well as the outlets for each group.

To select a group: Select the group name from the drop-down menu and press Select. The page will refresh to display all outlets associated to the selected group name.

To apply an action to a group: Select the desired action from the drop-down menu and press Apply.

Outlet State/Control State Field Values Outlet State Control State Description

On On Outlet is on

Off Off Outlet is off

Off Pend On Outlet is off and about to turn on in response to a sequence timer

Off Reboot Outlet is off and a Reboot action has been initiated

On Idle On A restart has occurred – Last Control State has been maintained

Off Idle Off A restart has occurred – Last Control State has been maintained

On Wake On A power-loss has occurred – Wakeup State has been applied

Off Wake Off A power-loss has occurred – Wakeup State has been applied

On/Wait Off Outlet state in transition – Requery of outlet status required

Off/Wait On Outlet state in transition – Requery of outlet status required

On/Error varies Error State – Outlet should be off but current is sensed at the outlet

Off/Error varies Error State – Outlet should be on but no current is sensed at the outlet

No Comm varies Communication to the outlet has been lost*

* Control State will be applied when communication is re-established

Environmental Monitoring

Input Load The Input Load page displays the tower(s) absolute and descriptive name and the cumulative input load in amperes of all devices attached to the Sentry at the time the page was loaded. This page will refresh automatically every 10 seconds

12 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 13: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Configuration The Configuration section offers access to all unit configuration options including Network, Telnet/SSH, HTTP/SSL, Serial Ports, Users, FTP, Proxy/SNTP and SNMP. This section is available to administrative level users only.

System The System configuration page is used for reference of system information such as Ethernet NIC Serial Number, Ethernet MAC address and system firmware and hardware revisions as well as assignment and maintenance of the system location and tower descriptive names.

For description names, up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal – spaces are not allowed) are allowed.

NOTE: Spaces may be used for the location description only.

Creating a descriptive system location name: Enter a descriptive name and press Apply.

Creating a descriptive unit name: Click on the Tower Names link.

On the subsequent Tower Names page, enter a descriptive name and press Apply.

Creating a descriptive input feed name: Click on the Input Feed Names link.

On the subsequent Input Feed Names page, enter a descriptive name and press Apply.

Creating a descriptive outlet name: Click on the Outlet Names link which will open the Outlets configuration page. See Outlets on page 16 for additional information on creating descriptive outlet names.

Creating a descriptive serial port/Pass-Thru name: Click on the Serial Port Names link which will open the Serial Ports configuration page. See Serial Ports on page 15 for additional information on creating descriptive serial port names.

Network The Network configuration page is used for maintenance of the network interface. From this page an administrator may configure the IP address, subnet mask, gateway address, DNS addresses as well as view the link status, speed and duplex value.

The Sentry is configured with the following network defaults to allow unit configuration out-of-the-box through either Telnet or HTML:

• IP address: 192.168.1.254 • Subnet Mask: 255.255.255.0 • Gateway: 192.168.1.1

The initial local PC network connection must be configured as noted below:

NOTE: Contact your system administrator for instructions in reconfiguring the network connection. Reconfiguration of your network connection may require a restart to take effect.

• IP address: 192.168.1.x (where x is 2-253) • Subnet Mask: 255.255.255.0

NOTE: The unit must be restarted after network configuration changes. See Performing a warm boot: on page 21.

Setting the IP address, subnet mask, gateway or DNS address: In the appropriate field, enter the IP address, subnet mask, gateway address or DNS address and press Apply.

Sentry Power Tower XL Operations • 13 Installation and Operations Manual

Page 14: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Telnet/SSH The Telnet/SSH configuration page used to enable or disable Telnet and SSH support and configure the port number that the Telnet or SSH server watches. For more information on SSH see page 45 in Chapter 4: Advanced Operations.

Enabling or disabling Telnet or SSH support: Select Enabled or Disabled from the appropriate Server drop-down menu and press Apply.

Changing the Telnet or SSH server port number: In the appropriate Port field, enter the port number and press Apply.

HTTP/SSL The HTTP/SSL configuration page used to enable or disable HTTP and SSL support, configure the port number that the HTTP server watches and responds to, selection of the method of authentication used and SSL access level. For more information on SSL see page 43 in Chapter 4: Advanced Operations.

Enabling or disabling HTTP or SSL support: Select Enabled or Disabled from the appropriate Server drop-down menu and press Apply.

Changing the HTTP server port number: In the HTTP Port field, enter the port number and press Apply.

Setting the HTTP authentication method: The Sentry HTTP server supports two authentication methods for security and validation of the username-password – Basic and MD5 digest.

The Basic method utilizes Base64 encoding to encode and deliver the username-password over the network to the HTTP server for decoding and authentication. This basic method is supported by all web browsers and offers a minimum level of security.

NOTE: The Base64 algorithm is widely-known and susceptible to packet-sniffer attack for acquisition of the encoded username-password string.

The MD5 digest method provides stronger protection utilizing one-way encoded hash numbers, never placing the username-password on the network. Instead, the sending browser creates a challenge code based on the hash algorithm, provided username-password and unique items such as the device IP address and timestamp, which is compared against the HTTP server internal user database of valid challenge codes. The MD5 digest method offers a higher level of security than the Basic method but at present is not supported by all browsers.

NOTE: MD5 is known to be fully supported by Internet Explorer 5.0+

Select Basic or MD5 from the Authentication drop-down menu and press Apply.

Setting SSL access level Sentry SSL supports configuration of SSL connections as being either optional or required. The default access level is set to optional.

• Optional –Both non-secure (HTTP) and SSL encrypted connections (HTTPS) are allowed access. • Required – ONLY SSL encrypted connections (HTTPS) are allowed access.

Select Optional or Required from the Secure Access drop-down menu and press Apply.

14 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 15: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Serial Ports The Serial Ports configuration page is used for maintenance of all serial/Pass-Thru ports.

NOTE: Pass-Thru connections may only be initiated from the command line interface via a direct serial or Telnet session.

Setting the data-rate for all serial/Pass-Thru ports: Select the serial/Pass-Thru port data-rate from the drop-down menu and press Apply.

Setting the serial/Pass-Thru port timeout value: Enter the timeout value (in minutes) in the Connection Timeout field and press Apply.

Creating a descriptive serial/Pass-Thru port name: Click on the Edit link in the Action column next to the port to be configured.

On the subsequent Serial Port Edit page, enter the descriptive name. Up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal, spaces and colon characters are not allowed) are allowed. Press Apply.

NOTE: Port names ‘1’ thru ‘64’, ‘CONSOLE’ and ‘MODEM’ are reserved system names and may not be used.

Enabling or disabling serial/Pass-Thru port active signal checking: Click on the Edit link in the Action column next to the port to be configured.

On the subsequent Serial Port Edit page, select On or Off from the DSR Check drop-down menu and press Apply.

Enabling or disabling modem initialization strings: By default, the Sentry assumes an external modem is attached to the Modem port and sends initialization strings to that modem as necessary. The Sentry sends the initialization strings under the following conditions:

• System start –DSR is high and DCD is low • Normal operations – If DSR transitions from low to high and DCD is low • Normal operations – After a session initiated from the Modem port ends • Normal operations – After a Pass-Thru connection to the Modem port is disconnected

Click on the Edit link in the Modem port Action column.

On the subsequent Serial Port Edit page, select On or Off from the Modem Initializations drop-down menu and press Apply.

Editing modem initialization strings: Click on the Edit link in the Modem port Action column.

On the subsequent Serial Port Edit page, enter the initialization string in the appropriate field and press Apply.

The Init1 and Init2 strings may be up to 48 characters. The Attention and Hang-up strings may be up to 16 characters.

Predefined Modem Initialization Strings String Type String Description Init 1 AT Gets modem attention

Init 2 AT E0 Q1 S0=1 S2=64 S12=50 &C1 &D2 Initializes default settings required

Attention @@@ Switches the modem to command mode

Hang-up ATH Forces a hang-up of an active connection

NOTE: Sentry Remote Power Managers do NOT support variable data-rate mode modems. The modem operating mode must be set to fixed data-rate mode to avoid the data-rate being changed after initialization. The modem manual must be referred to as the command(s) required to set the configuration to fixed data-rate mode vary significantly from manufacturer to manufacturer. The modem should be configured directly from a PC using a terminal program and the command &W be used to save the new configuration to memory and set it to default.

Sentry Power Tower XL Operations • 15 Installation and Operations Manual

Page 16: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Outlets The Outlets configuration page is used for assignment and/or editing of outlet sequence and reboot timers, descriptive names and wakeup states.

Setting the outlet sequencing interval: Enter the sequencing interval (in seconds) in the Sequence Interval field and press Apply.

Setting the outlet reboot delay: Enter the reboot interval (in seconds) in the Reboot Delay field and press Apply.

Editing the outlet descriptive name: Click on the Edit link in the Action column next to the outlet to be configured.

On the subsequent Outlet Edit page, enter the descriptive name. Up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal, spaces are not allowed) are allowed. Press Apply.

Changing the outlet wakeup state: Click on the Edit link in the Action column next to the outlet to be configured.

On the subsequent Outlet Edit page, select On, Off or Last from the Wakeup State drop-down menu and press Apply.

Groups The Groups configuration page is used for creation and deletion of group and assignment of outlets to groups.

Creating a group: Enter a descriptive group name in the Group Name field. Up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal, spaces are not allowed) are allowed. Press Apply.

Removing a group: Click on the Remove link in the Action column for the group to be removed and press Yes on the subsequent confirmation window.

Adding and Deleting outlets from a group: Press the Edit link in the Action column for the associated group.

On the subsequent Group Edit page, select or deselect outlets to be included in that group. Press Apply.

Users The Users configuration page is used for creation and removal of usernames, assignment of accessible outlets and group, assignment of privilege levels and the changing of user passwords.

Creating a new user: Enter a user name in the Username field. Up to 16 alphanumeric and other typeable characters (ASCII 33 to 126 decimal, spaces are not allowed) are allowed.

Enter a password for the new user and verify in the Password and Verify Password fields. For security, password characters are not displayed. Press Apply.

Removing a user: Click on the Remove link in the Action column for the user to be removed and press Yes on the subsequent confirmation window.

Changing a user password: Click on the Edit link in the Action column for the associated user.

On the subsequent User Edit page, enter a password and verify the new password for the new user in the Password and Verify Password fields. For security, password characters are not displayed. Press Apply.

16 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 17: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Changing a user’s access privilege level: The Sentry has four defined access privilege levels; Admin, User, On-Only and View-Only:

• Admin: Full-access for all configuration, control (On, Off, Reboot), status and Pass-Thru. • User: Partial-access for control (On, Off, Reboot), status and Pass-Thru of assigned

outlets, groups and serial/Pass-Thru ports. • On-Only: Partial-access for control (On), status and Pass-Thru of assigned outlets, groups

and serial/Pass-Thru ports. • View-Only: Partial-access for status and Pass-Thru of assigned outlets, groups and

serial/Pass-Thru ports.

The administrator may also grant administrative privileges to other user accounts allowing the Sentry to have more than one administrative-level user.

NOTE: You cannot remove administrative privileges from the Admn user unless another user has already been given administrative access level privileges created.

Click on the Edit link in the Action column for the associated user.

On the subsequent User Edit page, select Admin, User, On-only or View-only from the Access Level drop-down menu and press Apply.

Granting or removing Environmental Monitoring viewing privileges: Click on the Edit link in the Action column for the associated user.

On the subsequent User Edit page, select Yes or No from the Environmental Monitoring drop-down menu and press Apply.

NOTE: This also grants or removes viewing privileges for the optional Equipment Cabinet Environmental Manager. See the Equipment Cabinet Environmental Manager Installation and Operations manual for more information.

Adding and Deleting outlet access: Click on the Outlets link in the Access column for the associated user.

On the subsequent User Outlets page, select or deselect outlets to be accessed by the user and press Apply.

Adding and Deleting group access: Click on the Groups link in the Access column for the associated user.

On the subsequent User Groups page, select or deselect group to be accessed by the user and press Apply.

Adding and Deleting serial/Pass-Thru port access: Click on the Ports link in the Access column for the associated user.

On the subsequent User Ports page, select or deselect ports to be accessed by the user and press Apply.

FTP The FTP configuration page is used for setup and maintenance of all settings required to perform an FTP firmware upload. See Appendix B: Uploading Firmware for more information on uploading firmware.

Setting the FTP Host IP Address: Enter the IP address in the Host IP Address field and press Apply.

Setting the FTP username: Enter the FTP server username in the Username field, and press Apply.

Setting the FTP password: Enter the FTP server password in the Password field, and press Apply.

Setting the filepath: Enter the path of the file to be uploaded in the Directory field, and press Apply.

Setting the filename for upload: Enter the filename of the file to be uploaded in the Filename field, and press Apply.

Sentry Power Tower XL Operations • 17 Installation and Operations Manual

Page 18: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Testing the FTP upload configuration: This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware file and verify that the firmware file is valid for this unit.

Press Test.

SNTP The SNTP configuration page is used for setup and maintenance of SNTP support.

Setting the SNTP Server Address: Enter the IP address in the primary and/or secondary address field and press Apply.

SNMP The SNMP configuration page is used for setup and maintenance of all settings required to enable SNMP support as well as access to the trap configuration pages. For additional information on SNMP support and detailed descriptions of available traps, see SNMP on page 46.

NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal.

Enabling or disabling SNMP support: Select Enabled or Disabled from the drop-down menu and press Apply.

Setting the community strings: Enter the community string in the appropriate field and press Apply. Community strings may be 1 to 24 characters

Setting the trap timer: Enter a trap timer value in the Error Trap Repeat Time field and press Apply. The Error Trap Repeat Time value may be 1 to 65535 (in seconds).

Setting trap destinations: Enter an IP address in the appropriate Trap Destination field and press Apply.

Enabling or disabling tower traps: Click on the Tower Traps link.

On the subsequent Tower Traps page, select or deselect the desired traps and press Apply.

Configuring input feed traps: Click on the Input Feed Traps link.

On the subsequent Input Feed Traps page, select or deselect the desired traps and press Apply.

For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and press Apply. The High Load Threshold value may be 0 to 255 (in amperes).

Configuring outlet traps: Click on the Outlet Traps link.

On the subsequent Outlet Traps page, select or deselect the desired traps and press Apply.

LDAP The LDAP configuration page is used for setup and maintenance of all settings required to enable LDAP support. For additional information and configuration requirements, see LDAP on page52.

Enabling or disabling LDAP support: Select Enabled or Disabled from the LDAP drop-down menu and press Apply.

Setting the LDAP server IP address: Enter the IP address in the Host IP1 and/or Host IP2 address field and press Apply.

Setting the LDAP server domain component: Enter the domain component in the Host DC1 and/or Host DC2 and press Apply.

18 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 19: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Setting the LDAP bind password type: Select Simple or MD5 from the drop-down menu and press Apply.

For more information on LDAP bind password types, see Setting the LDAP bind password type on page 53.

Setting the DNS IP address: See Network on page 13 for information on how to set the DNS IP address.

Configuring the authentication order: Select Remote -> Local or Remote Only from the drop-down menu and press Apply.

For more information on remote authentication order, see Setting the authentication order on page 53.

NOTE: Server Technology recommends NOT setting the authentication order to Remote Only until the LDAP has been fully configured and tested.

Configuring LDAP groups: Click on the LDAP Groups link at the bottom of the page.

Creating an LDAP group:

Enter a descriptive group name in the LDAP Group Name field. Up to 24 alphanumeric and other typeable character (ASCII 33 to 126 decimal, spaces are not allowed) are allowed. Press Apply.

Removing an LDAP group:

Click on the Remove link in the Action column for the group to be removed and press OK on the subsequent confirmation window.

Changing an LDAP group’s access privilege level:

Click on the Edit link in the Action column for the associated LDAP Group.

On the subsequent LDAP Group - Edit page, select Admin, User, On-only or View-only from the Access Level drop-down menu and press Apply.

For more information on access privilege levels, see Changing a user’s access privilege level: on page 17.

Granting or removing Environmental Monitoring viewing privileges:

Click on the Edit link in the Action column for the associated LDAP Group.

On the subsequent LDAP Group - Edit page, select Yes or No from the Environmental Monitoring drop-down menu and press Apply.

Adding and Deleting outlet access:

Click on the Outlets link in the Access column for the associated LDAP Group.

On the subsequent LDAP Group - Outlets page, select or deselect outlets to be accessed by the LDAP Group and press Apply.

Adding and Deleting outlet group access:

Click on the Groups link in the Access column for the associated LDAP Group.

On the subsequent LDAP Group - Groups page, select or deselect outlet groups to be accessed by the LDAP Group and press Apply.

Adding and Deleting serial port access:

Click on the Ports link in the Access column for the associated LDAP Group.

On the subsequent LDAP Group - Ports page, select or deselect ports to be accessed by the LDAP Group and press Apply.

Sentry Power Tower XL Operations • 19 Installation and Operations Manual

Page 20: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

TACACS+ The TACACS+ configuration page is used for setup and maintenance of all settings required to enable TACACS+ support. For additional information and configuration requirements, see TACACS+ on page 58.

Enabling or disabling TACACS+ support: Select Enabled or Disabled from the TACACS+ drop-down menu and press Apply.

Setting the TACACS+ server IP address: Enter the IP address in the Host IP1 and/or Host IP2 address field and press Apply.

Setting the TACACS+ encryption key: Enter a key and verify the new key the Encryption Key and Verify Encryption Key fields. Press Apply.

For security, key characters are not displayed.

Configuring the authentication order: Select Remote -> Local or Remote Only from the drop-down menu and press Apply.

For more information on remote authentication order, see Setting the authentication order on page 59.

NOTE: Server Technology recommends NOT setting the authentication order to Remote Only until the LDAP has been fully configured and tested.

Configuring TACACS+ privilege levels: Click on the TACACS+ Privilege Levels link at the bottom of the page.

Changing an TACACS+ Privilege Level’s access privilege level:

Click on the Edit link in the Action column for the associated TACACS+ Privilege Level.

On the subsequent TACACS+ Privilege Level - Edit page, select Admin, User, On-only or View-only from the Access Level drop-down menu and press Apply.

For more information on access levels, see Changing a user’s access privilege level: on page 17.

Granting or removing Environmental Monitoring viewing privileges:

Click on the Edit link in the Action column for the associated TACACS+ privilege level.

On the subsequent TACACS+ Privilege Level - Edit page, select Yes or No from the Environmental Monitoring drop-down menu and press Apply.

Adding and Deleting outlet access:

Click on the Outlets link in the Access column for the associated TACACS+ Privilege Level.

On the subsequent LDAP Group - Outlets page, select or deselect outlets to be accessed by the TACACS+ Privilege Level and press Apply.

Adding and Deleting outlet group access:

Click on the Groups link in the Access column for the associated TACACS+ Privilege Level.

On the subsequent LDAP Group - Groups page, select or deselect outlet groups to be accessed by the TACACS+ Privilege Level and press Apply.

Adding and Deleting serial port access:

Click on the Ports link in the Access column for the associated TACACS+ Privilege Level.

On the subsequent LDAP Group - Ports page, select or deselect ports to be accessed by the TACACS+ Privilege Level and press Apply.

20 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 21: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Tools The Tools section contains access to rebooting the unit, uploading new firmware as well as resetting the unit to factory defaults. This section is available to administrative level users only.

Restart

Performing a warm boot: Select the Restart from the Action drop-down menu and press Apply.

Note: System user/outlet/group configuration or outlet states are NOT changed or reset with this command.

Resetting to factory defaults: See Chapter 5: for more information on resetting a Sentry to factory defaults from the HTML interface.

Uploading new firmware: See Appendix B: for more information on uploading new firmware from the HTML interface.

Ping The Ping feature may be used to test the Sentry’s ability to contact another Ethernet enabled device’s IP address. For LDAP support, it may also be used to test the configuration of the Domain Name server IP address by testing for proper name resolution.

Sentry Power Tower XL Operations • 21 Installation and Operations Manual

Page 22: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Command Line Interface Logging In

Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit.

Logging in through the Console (RS232) port requires the use of a terminal or terminal emulation software configured to support ANSI or VT100 and a supported data rate (300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 BPS) - 8 data bits-no parity-one stop bit and Device Ready output signal (DTR or DSR).

To log in by RS-232 or Telnet: 1. Press Enter. The following appears, where x.xx is the firmware version:

Sentry Version x.xx Username:

NOTE: Logging in by Telnet will automatically open a session. It is not necessary to press Enter.

2. At the Username: and Password: prompts, enter a valid username and password. And press Enter.

You are given three attempts to enter a valid username and password combination. If all three fail, the session ends. NOTE: The default Sentry username/password is admn/admn.

When you enter a valid username and password, the command prompt (Sentry:) appears. If a location identifier was defined, it will be displayed before the Sentry: prompt. See Creating a location description on page 36 for more information.

You may enter commands in any combination of uppercase and lowercase. You must enter all command characters correctly; there are no command abbreviations. There are two types of commands: operations and administration. A user must have administrative privileges to use the administration commands. The following tables list and briefly describe each command.

Operations Command Summary Command Description

On Turns one or more outlets on

Off Turns one or more outlets off

Reboot Reboots one or more outlets

Status Displays the on/off status of one or more outlets

ILoad Displays the total cumulative input load

Istat Displays the status of the infeeds

Connect Connects to a serial/Pass-Thru port

Login Ends the current session and brings up the Username: prompt

Logout Ends a session

Quit Ends a session

List Outlets Lists all accessible outlets for the current user

List Ports Lists all accessible serial/Pass-Thru ports for the current user

List Group Lists all assigned outlets for a group name

List Groups Lists all accessible groups for the current user

Administrative Command Summary Add Grouptouser Grants a user access to one or more groups

Add Outlettogroup Adds an outlet to a group name

Add Outlettouser Grants a user access to one or all outlets

Add Porttouser Grants a user access to one or all serial/Pass-Thru ports

Create Group Adds a group name

Create User Adds a user account

Delete Groupfromuser Removes access to one or more groups for a user

Delete Outletfromgroup Deletes an outlet from a group name

Delete Outletfromuser Removes access to one or all outlets for a user

22 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 23: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Administrative Command Summary (continued) Delete Portfromuser Removes access to one or all serial/Pass-Thru ports

List User Displays all accessible outlets/groups/ports for a user

List Users Displays privilege levels for all users

Remove Group Deletes a group name

Remove User Deletes a user account

Restart Performs a warm boot

Set DNS Sets the IP address of the Domain Name server

Set FTP Filename Specifies the file to be uploaded via FTP

Set FTP Filepath Specifies the filepath for the file to be uploaded

Set FTP Host Sets the FTP Host IP address

Set FTP Password Sets the password for the FTP Host

Set FTP Username Sets the username for the FTP Host

Set Gateway Sets the Gateway

Set HTTP Enables or disables HTTP access

Set HTTP Port Specifies the target port for HTTP access

Set HTTP Security Specifies the HTTP server authentication method

Set Infeed Name Specifies a descriptive field for the infeed

Set Ipaddress Sets the IP address

Set Location Specifies a descriptive field for the HTML control screen and login banner

Set Modem Inits Enables or disables Modem port initialization strings

Set Modem Specifies Modem port initialization strings

Set Outlet Name Specifies a descriptive field for a device attached to an outlet

Set Outlet RebootDelay Sets the reboot delay for all outlets

Set Outlet SeqInterval Sets the sequencing interval for all outlets

Set Outlet Wakeup Sets the wakeup state for an outlet

Set Subnet Mask Sets the Subnet Mask

Set Telnet Port Sets the Telnet server port number

Set Telnet Enables or disables Telnet access

Set Tower Name Specifies a descriptive field for the Sentry

Set User Access Sets the access level for a user

Set User Envmon Grants or removes privileges to view input and environmental monitoring status

Set User Password Changes the password for a user

Set Port Name Specifies a descriptive field for a serial/Pass-Thru port

Set Port Dsrchk Sets the DSR active signal checking for a serial/Pass-Thru port

Set Port Speed Set the connection speed for all serial/Pass-Thru ports

Set Port Timeout Sets the inactivity timer for Pass-Thru sessions

Show FTP Displays FTP configuration information

Show Infeeds Displays infeed configuration information

Show Network Display network configuration information

Show Outlets Displays configuration information for all outlets

Show Ports Displays serial/Pass-Thru port configuration information

Show System Displays system configuration information

Show Towers Displays tower configuration information

Version Displays the Sentry firmware version

To display the names of commands that you may execute: At the command prompt, press Enter. A list of valid commands for the current user appears.

Sentry Power Tower XL Operations • 23 Installation and Operations Manual

Page 24: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Operations Commands Operations commands manage outlet states, provide information about the Sentry environment and control session operations.

Turning outlets on The On command turns on one or more outlets. When the command completes, a display indicating all outlets affected and their current states will be displayed.

To turn outlets on:

At the Sentry: prompt, type on, followed by an outlet name, and press Enter, or

Type on, followed by a group name, and press Enter, or

Type on all and press Enter.

Examples The following command turns the second outlet on, using the outlet’s absolute name:

Sentry: on .a2<Enter>

The following command turns on all the outlets in the group named ServerGroup_1: Sentry: on ServerGroup_1<Enter>

Turning outlets off The Off command turns off one or more outlets. When the command completes, a display indicating all outlets affected and their current states will be displayed.

To turn outlets off:

At the Sentry: prompt, type off, followed by an outlet name, and press Enter, or

Type off, followed by a group name, and press Enter, or

Type off all and press Enter

Examples The following command turns off the outlet named FileServer_1:

Sentry: off FileServer_1<Enter>

The following command turns off all outlets: Sentry: off all<Enter>

Rebooting outlets The Reboot command reboots one or more outlets. This operation turns the outlet(s) off, delays for a user configurable period and then turns the outlet(s) on. When the command completes, a display indicating all outlets affected and their current states will be displayed.

NOTE: It is necessary to reissue the Status command to verify that the outlets have rebooted. See Displaying outlet status for more information.

To reboot one or more outlets:

At the Sentry: prompt, type reboot, followed by an outlet name, and press Enter, or

Type reboot, followed by a group name, and press Enter, or

Type reboot all and press Enter.

Example The following command reboots all the outlets in the group named ServerGroup_1:

Sentry: reboot ServerGroup_1<Enter>

24 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 25: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying outlet status The Status command displays the on/off status of one or more outlets. The command displays the status of only those outlets for which the current username has power control access.

This display includes the outlet absolute and descriptive names, the Outlet State reported to the Sentry by the outlet and the current Control State being applied by the Sentry. If you do not specify any parameter with this command, the status of all accessible outlets is displayed.

NOTE: If the user has access to more than 16 total outlets, the Status command will display the first 16 outlets with a prompt to view the remaining outlets.

For more information on outlet and control state values, see Outlet Control on page 12.

To display on/off status of one or more outlets:

At the Sentry: prompt, type status, followed by an outlet name, and press Enter, or

Type status, followed by a group name, and press Enter, or

Type status and press Enter.

Examples The following command displays the on/off status of the outlet named FileServer_1:

Sentry: status FileServer_1<Enter>

Outlet Outlet Outlet Control ID Name State State

.A3 FileServer_1 On On

The following command displays the on/off status of all accessible outlets: Sentry: status<Enter>

Outlet Outlet Outlet Control ID Name State State

.A1 DataServer_1 On On .A2 WebServer_1 On On .A3 FileServer_1 On On .A4 On On .A5 On On .A6 On On .A7 On On .A8 On On .A9 On On .A10 On On .A11 On On .A12 On On .A13 On On .A14 On On .A15 On On .A16 On On

More (Y/es N/o):

The following command displays the on/off status for outlets in the group ServerGroup_1: Sentry: status ServerGroup_1<Enter>

Group: ServerGroup_1

Outlet Outlet Outlet Control ID Name State State

.A1 DataServer_1 On On .A2 WebServer_1 On On .A3 FileServer_1 On On

Sentry Power Tower XL Operations • 25 Installation and Operations Manual

Page 26: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying accessible outlets The List Outlets command displays accessible outlets for the current user. The display includes the absolute and descriptive name of all outlets assigned to the current user.

To display accessible outlets:

At the Sentry: prompt, type list outlets and press Enter.

Example The follow command displays all accessible outlets for the current user:

Sentry: list outlets<Enter>

Outlet Outlet ID Name

.A1 DataServer_1 .A2 WebServer_1

Displaying accessible groups The List Groups command displays accessible groups for the current user.

To display accessible groups:

At the Sentry: prompt, type list groups and press Enter.

Example The follow command displays all accessible groups for the current user:

Sentry: list groups<Enter>

Groups:

ServerGroup_1 RouterGroup_1

Displaying outlets assigned to a group The List Group command displays outlets assigned to the specified group name.

To display outlets assigned to a group:

At the Sentry: prompt, type list group, followed by the group name and press Enter.

Example The follow command displays the outlets assigned to the group ServerGroup_1:

Sentry: list group ServerGroup_1<Enter>

Group: ServerGroup_1

Outlet Outlet ID Name

.A1 DataServer_1 .A2 WebServer_1 .A3 FileServer_1

Displaying accessible serial/Pass-Thru ports The List Ports command displays accessible serial/Pass-Thru ports for the current user.

To display accessible serial/Pass-Thru ports:

At the Sentry: prompt, type list ports and press Enter.

Example The follow command displays all accessible serial/Pass-Thru ports for the current user:

Sentry: list ports<Enter>

Port Port ID Name

Console Console Modem Modem

26 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 27: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying infeed status The Istat or Iload command displays the status of one or more infeed.

This display includes the infeed absolute and descriptive names and the Input Status and current Load reported to the Sentry by the infeed.

To display status of one or more infeeds:

Type istat and press Enter, or

Type iload and press Enter.

Examples The following command displays the infeed status: Sentry: istat

Input Input Input Input Feed ID Feed Name Status Load

.AA HQ_1_Infeed_A On 10.5 Amps

Connecting to a serial device The Connect command allows Pass-Thru serial connection to devices attached to one of the two standard serial ports (Console, Modem,) or a Pass-Thru port.

To connect to a serial device:

At the Sentry: prompt, type connect, followed by the serial/Pass-Thru port name and press Enter.

Examples The follow command connects to the serial device connected to the Modem port:

Sentry: connect modem<Enter>

To disconnect from a serial device:

Type !*break and press Enter.

Starting a new session The Login command activates the Username: prompt. The current session ends, allowing a user to log in and start a new session under a different username.

To start a new session:

At the Sentry: prompt, type login and press Enter. The Username: prompt appears.

Ending a session The Quit or Logout commands ends a session. A session ends automatically when no activity is detected for five minutes, or upon loss of connection.

To end a session:

At the Sentry: prompt, type quit and press Enter, or

Type logout and press Enter.

Sentry Power Tower XL Operations • 27 Installation and Operations Manual

Page 28: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Administration Commands Administration commands may only be issued by a user with administrative privileges, such as the predefined Admn user or another user who has been granted administrative privileges with the Set User Admnpriv command.

User Administration

Creating a user account The Create User command creates a user account with the specified username and password. See Usernames and Passwords in this chapter for more information.

To create a user account:

At the Sentry: prompt, type create user, optionally followed by a 1-16 character username (Spaces are not allowed, and usernames are not case sensitive). Press Enter.

At the Password: prompt, type a password of up to 16 alphanumeric and other typeable characters (ASCII 32 to 126 decimal). Passwords are case sensitive. Press Enter. To specify no password, press Enter at the prompt.

At the Verify Password: prompt, retype the password. Press Enter. To verify no password, press Enter at the prompt.

Example The following command creates the user account JaneDoe:

Sentry: create user JaneDoe<Enter> Password: <Enter> Verify New Password: <Enter>

For security, password characters are not displayed.

Removing a user account The Remove User command removes a user account.

NOTE: You may remove the predefined user account Admn only if another user account has been granted administrative privileges using the Set User Admnpriv command.

To remove a user account:

At the Sentry: prompt, type remove user, optionally followed by a username. Press Enter.

Changing a password The Set User Password command changes a user’s password. For security, when you type a password, the characters are not displayed on the screen. See Usernames and Passwords for more information.

To change a password:

At the Sentry: prompt, type set user password, followed by a username and press Enter.

At the Password: prompt, type the new password and press Enter. Passwords may contain up to 16 characters, and spaces are not allowed. To specify no password, press Enter at the prompt.

At the Verify Password: prompt, retype the new password and press Enter. To verify no password, press Enter at the prompt.

Examples The following command changes the password for the user JohnDoe:

Sentry: set user password johndoe<Enter> Password: <Enter> Verify Password: <Enter>

The following command blanks the password for the user JaneDoe: Sentry: set user password<Enter> Username: janedoe<Enter> Password: <Enter> Verify Password: <Enter>

28 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 29: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Setting user access level privileges The Set User Access command sets the access level privileges for a user. The Sentry has four defined access privilege levels; Admin, User, On-Only and View-Only. For more information on user access levels, see Changing a user’s access privilege level: on page 17.

The administrator may also grant administrative privileges to other user accounts allowing the Sentry to have more than one administrative-level user.

NOTE: You cannot remove administrative privileges from the Admn user unless another user has already been given administrative access level privileges created.

To set the access level privilege for a user:

At the Sentry: prompt, type set user access, followed by admin or user, optionally followed by a username and press Enter.

Examples The following command sets the user access level for JohnDoe to Admin:

Sentry: set user access admin johndoe<Enter>

The following command sets the user access level for JaneDoe to User: Sentry: set user access user janedoe<Enter>

Granting and removing input load viewing privileges The Set User Envmon command grants or removes input load viewing privileges to/from a general or view-only user.

NOTE: This command also grants or removes viewing privileges for the status of the optional Equipment Cabinet Environmental Manager and attached sensors. See the Equipment Cabinet Environmental Manager Installation and Operations manual for more information.

To grant or remove input load viewing privileges for a user:

At the Sentry: prompt, type set user envmon followed by on or off, optionally followed by a username and press Enter.

Example The following command grants input load privileges to the user JohnDoe:

Sentry: set user envmon on johndoe<Enter>

Displaying the access privilege levels The List Users command displays all defined users with their access privilege level.

To display user access privilege levels:

At the Sentry: prompt, type list users and press Enter.

Example The following command displays all users with their access privilege level:

Sentry: list users<Enter>

User Privilege Environmental Name Level Monitoring

JOHNDOE Admin Allowed JANEDOE User Allowed JOSEYDOE On-Only Not Allowed JOEDOE View-Only Not Allowed

Sentry Power Tower XL Operations • 29 Installation and Operations Manual

Page 30: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Adding outlet access to a user The Add OutletToUser command grants a user access to one or all outlets. To grant access for more than one outlet, but not all outlets, you must use multiple Add OutletToUser commands.

To grant outlet access to a user:

At the Sentry: prompt, type add outlettouser, optionally followed by an outlet name and a username. Press Enter, or

Type add outlettouser all, followed by a username and press Enter.

Examples The following commands grant the user JaneDoe access to outlets A1 and Webserver_1:

Sentry:add outlettouser .a1 janedoe<Enter> Sentry:add outlettouser WebServer_1 janedoe<Enter>

Deleting outlet access for a user The Delete OutletFromUser command removes a user’s access to one or all outlets. You cannot remove access to any outlet for an administrative level user.

To delete outlet access for a user:

At the Sentry: prompt, type delete outletfromuser, optionally followed by an outlet name and a username. Press Enter, or

Type delete outletfromuser all, followed by a username and press Enter.

Adding group access to a user The Add GroupToUser command grants a user access to a group. To grant access for more than one group, you must use multiple Add GroupToUser commands.

To grant group access to a user:

At the Sentry: prompt, type add grouptouser, optionally followed by a group name and a username. Press Enter.

Examples The following commands grants to user JaneDoe access to the groups ServerGroup_1 and ServerGroup_2:

Sentry:add GroupToUser ServerGroup_1 janedoe<Enter> Sentry:add GroupToUser ServerGroup_2 janedoe<Enter>

Deleting group access for a user The Delete GroupFromUser command removes a user’s access to a group. You cannot remove access to any group for an administrative level user.

To delete group access for a user:

At the Sentry: prompt, type delete GroupFromUser, optionally followed by a group name and a username. Press Enter.

Adding serial/Pass-Thru port access to a user The Add PortToUser command grants a user access to a serial/Pass-Thru port. To grant access for more than one port, you must use multiple Add PortToUser commands.

To grant serial/Pass-Thru port access to a user:

At the Sentry: prompt, type add porttouser, optionally followed by a Port name and a username. Press Enter.

Examples The following commands grants to user JaneDoe access to the Modem port:

Sentry:add PortToUser modem janedoe<Enter>

30 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 31: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Deleting serial/Pass-Thru port access for a user The Delete PortFromUser command removes a user’s access to a serial/Pass-Thru port. You cannot remove access to any serial/Pass-Thru port for an administrative level user.

To delete serial/Pass-Thru port access for a user:

At the Sentry: prompt, type delete portfromuser, optionally followed by a Port name and a username. Press Enter.

Displaying user outlet, group and serial/Pass-Thru port access The List User command displays all accessible outlets, groups and serial/Pass-Thru ports for a user.

To display user outlet, group and serial/Pass-Thru port access:

At the Sentry: prompt, type list user, optionally followed by a username. Press Enter.

Example The following command displays information about the user JaneDoe:

Sentry: list user janedoe<Enter>

Username: JANEDOE

Outlet Outlet ID Name

.A1 DataServer_1 .A2 WebServer_1

Groups:

ServerGroup_1 ServerGroup_2

More (Y/es N/o): Y

Ports:

Port Port ID Name

Console Console Modem Modem

JaneDoe may access the following outlets, groups and serial ports: outlet A1 which has a descriptive name of DataServer_1, outlet A2 which has a descriptive name of WebServer_1, group ServerGroup_1 group ServerGroup_2, Console serial port and Modem serial port.

Outlet Administration

Setting the sequencing interval The Set Outlet SeqInterval commands sets the power on sequencing interval for all outlets.

To set the sequencing interval:

At the Sentry: prompt, type set outlet seqinterval all, followed by a value from 2 to 15 (in seconds) and press Enter.

Setting the reboot delay The Set Outlet RebootDelay commands sets the reboot delay for all outlets.

To set the sequencing interval:

At the Sentry: prompt, type set outlet rebootdelay all, followed by a value from 5 to 60 (in seconds) and press Enter.

Sentry Power Tower XL Operations • 31 Installation and Operations Manual

Page 32: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Creating a descriptive outlet name The Set Outlet Name command assigns a descriptive name to an outlet. You may use this name in commands that require an outlet name as an alternative to using the outlet’s absolute name.

To create an outlet name:

At the Sentry: prompt, type set outlet name, followed by the absolute outlet name and a descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed). Outlet names are not case sensitive. Press Enter.

Example The following command adds the descriptive name DataServer_1 to outlet .a1:

Sentry: set outlet name .a1 DataServer_1<Enter>

Setting the outlet wakeup state The Set Outlet Wakeup command set the default wakeup state for that outlet. In the event of a system-wide power loss, this state will be applied to the outlet when power is restored.

The wakeup state may be set to On, Off or Last. Upon restoration of system power; If set to On, the Sentry will apply power to that outlet. If set to Off, the Sentry will not apply power to that outlet. If set to Last, the Sentry will apply the last known power state.

To set the wakeup state:

At the Sentry: prompt, type set outlet wakeup, followed by on, off or last and the outlet name. Press Enter.

Example The following command sets the wakeup state for outlet .a1 to off:

Sentry: set outlet wakeup off .a1<Enter>

Displaying outlet information The Show Outlets command displays information about all outlets. This information includes:

• Sequencing and reboot timer values • Descriptive outlet name, if applicable • Outlet wakeup state setting

To display outlet information:

At the Sentry: prompt, type show outlets and press Enter.

Example The following command displays all outlet information:

Sentry: show outlets<Enter>

Outlet Outlet Wakeup ID Name State

.A1 DataServer_1 off .A2 WebServer_1 on .A3 FileServer_1 on .A4 on .A5 on .A6 on .A7 on .A8 on .A9 on .A10 on .A11 on .A12 on .A13 on .A14 on .A15 on .A16 on

More (Y/es N/o):

Outlet Options:

Sequence Interval: 2 seconds Reboot Delay: 15 seconds

32 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 33: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Group Administration

Creating a group name The Create Group command creates a new group name.

To create a group name:

At the Sentry: prompt, type create group, optionally followed by a descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed. Group names are not case sensitive). Press Enter.

Example The following command creates group name ServerGroup_1:

Sentry: create group ServerGroup_1<Enter>

Removing a group name The Remove Group command removes a group name.

To remove a group name:

At the Sentry: prompt, type remove group, optionally followed by a username. Press Enter.

Example The following command removes group name ServerGroup_1: Sentry: remove group ServerGroup_1<Enter>

Adding an outlet to a group The Add OutletToGroup command adds an outlet to a group. To add more than one outlet, but not all outlets, you must use multiple Add OutletToGroup commands.

To add an outlet to a group:

At the Sentry: prompt, type add outlettogroup, optionally followed by an outlet name and group name. Press Enter, or

Type add OutletToGroup, followed by all and the group name. Press Enter.

Examples The following commands uses absolute outlet names to add outlets A1 and A2 to group name ServerGroup_1:

Sentry:add OutletToGroup .a1 ServerGroup_1<Enter> Sentry:add OutletToGroup .a2 ServerGroup_1<Enter>

The following commands usese the outlets’ descriptive names to add outlets DataServer_1 and WebServer_1 to group name ServerGroup_1:

Sentry:add OutletToGroup DataServer_1 ServerGroup_1<Enter> Sentry:add OutletToGroup WebServer_1 ServerGroup_1<Enter>

The following command add all outlets to group name ServerGroup_1: Sentry: add OutletToGroup<Enter> Outletname: all<Enter> Groupname: ServerGroup_1<Enter>

Deleting an outlet from a group The Delete OutletFromGroup command deletes an outlet from a group. To delete more than one outlet, but not all outlets, you must use multiple Delete OutletToGroup commands.

To delete an outlet from a group:

At the Sentry: prompt, type delete outletfromgroup, optionally followed by an outlet name and a group name. Press Enter, or

Type delete outletfromgroup, followed by all then the group name. Press Enter.

Sentry Power Tower XL Operations • 33 Installation and Operations Manual

Page 34: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Serial Port Administration

Creating a descriptive serial port name The Set Port Name command assigns a descriptive name to a serial port. You may use this name in commands that require a port name as an alternative to using the port’s absolute name.

To create an port name:

At the Sentry: prompt, type set port name, followed by the absolute outlet name and a descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed). Port names are not case sensitive. Press Enter.

Example The following command adds the descriptive name Rack1 to Console port:

Sentry: set port name console Rack1<Enter>

Setting the serial ports data-rate The Set Port Speed command sets the default data-rate for the serial port. Valid data-rates are 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.

To set the serial port data-rate:

At the Sentry: prompt, type set port speed, follow by the data-rate and press Enter.

Example The following command sets the serial ports data-rate to 38400 BPS:

Sentry: set port speed 38400<Enter>

Enabling or disabling active signal checking for serial/Pass-Thru connections The Set Port Dsrchk command enables or disables active signal checking for serial/Pass-Thru connections to devices attached to any of the available serial ports.

To enable or disable active signal checking for serial connections:

At the Sentry: prompt, type set port dsrchk, followed by serial port name, on or off, and press Enter, or

Type set port dsrchk all, on or off, and press Enter.

Examples The following command disables active signal checking for the Modem serial port:

Sentry: set port dsrchk modem off<Enter>

The following command enables active signal checking for Pass-Thru port 1: Sentry: set port dsrchk 1 on<Enter>

The following command disables active signal checking for all serial/Pass-Thru ports: Sentry: set port dsrchk all off<Enter>

Setting the serial port timeout value The Set Port Timeout command is used to set the serial port inactivity timeout period. The timeout period defines the maximum period of inactivity before automatically closing the Pass-Thru session. The valid range for the period parameter is 0 to 5 (in minutes). The default period is 5.

NOTE: Setting the timeout to ‘0’ disables the timer.

To set the serial port timeout value:

At the Sentry: prompt, type set port timeout, followed by a value from 0 to 5 (in minutes) and press Enter.

34 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 35: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Enabling or disabling modem initialization strings By default, the Sentry assumes an external modem is attached to the Modem port and sends initialization strings to that modem as necessary. The Sentry sends the initialization strings under the following conditions:

• System start –DSR is high and DCD is low • Normal operations – If DSR transitions from low to high and DCD is low • Normal operations – After a session initiated from the Modem port ends • Normal operations – After a Pass-Thru connection to the Modem port is disconnected

The Set Modem command is used to enable or disable these initialization strings. Predefined initializations strings are enabled by default.

To enable or disable the modem initialization strings:

At the Sentry: prompt, type set modem inits, followed by on or off, and press Enter.

Example The following command disables the modem initialization strings for the Modem serial port:

Sentry: set modem inits off<Enter>

Editing modem initialization strings The predefined modem initialization strings may be edited by an administrative user. The Init 1 and Init 2 strings may be up to 48 characters each and the Attention and Hang-up strings may be up to 16 characters.

For more information on the predefined initialization strings, see Enabling or disabling modem initialization strings: on page 15.

Editing modem initialization strings:

At the Sentry: prompt, type set modem, followed by attn, hangup, init1, or init 2 and the initialization string. Press Enter.

Examples The following command set the Init 2 string to ‘AT E0 Q1 S0=3 S2=64 S12=50 &C1 &D2’:

Sentry: set modem init2 AT E0 Q1 S0=3 S2=64 S12=50 &C1 &D2<Enter>

Displaying serial port information The Show Ports command displays information about all serial ports. This information includes:

• Serial port data rate • Descriptive port name, if applicable • DSR signal checking settings

To display serial port information:

At the Sentry: prompt, type show ports and press Enter.

Example The following command displays all serial port information:

Sentry: show ports<Enter>

Serial Port Configuration

ALL Ports:

Baud Rate: 38400 Connection Timeout: 5 minutes

Port ID: Console Port Name: CONSOLE

DSR Check: ON

Port ID: Modem Port Name: MODEM

DSR Check: ON

Initializations: ON

Init String 1: AT Init String 2: AT E0 Q1 S0=1 S2=64 S12=50 &C1 &D2 Attention String: @@@

Sentry Power Tower XL Operations • 35 Installation and Operations Manual

Page 36: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

System Administration

Creating a location description The Set Location command specifies text that appears in the HTML control screen’s Location field. The text is also appended to a Welcome to banner that appears when a user successfully logs in serially or through a Telnet session.

If you do not issue this command, or if you issue this command without specifying any text, the control screen ’s Location field will be blank and no Welcome to banner will be displayed.

To create a location description:

At the Sentry: prompt, type set location, followed by a descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 32 to 126 decimal - spaces are allowed). Press Enter.

Omitting any characters after typing ‘set location’ deletes any previously specified text.

Examples The following command specifies Florida HQ as the descriptive location for the control screen and the login banner:

Sentry: set location Florida HQ<Enter>

The following command deletes any previously specified location description: Sentry: set location<Enter>

In this case, the control screen’s Location field will be blank, and no welcome banner will be displayed after a successful login.

Displaying system configuration information The Show System command displays all system configuration information.

• Firmware version • NIC module serial number and MAC address • Hardware revision code and Flash size • Uptime since last system restart • System location description

See Chapter 4: Advanced Operations on page 43 for more information on SNMP.

To display system configuration information:

At the Sentry: prompt, type show system and press Enter.

Example System Information

F/W Version: Sentry Version 5.2b NIC S/N: 1600001 MAC Address: 00-0a-9c-10-00-01 H/W Rev Code: 0 Flash Size: 1 MB Uptime: 0 days 6 hours 14 minutes 1 second

Location: Florida HQ

Creating a descriptive tower name The Set Tower Name command assigns a descriptive name to a tower. This descriptive name is displayed when the Show Traps command is issued. See Displaying trap configuration information on page 37 for more information on the Show Traps command.

To create a tower name:

At the Sentry: prompt, type set tower name, followed by the absolute tower name, then the descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed). Press Enter.

Example The following command adds the descriptive name Florida_HQ_1 to tower .a:

Sentry: set tower name .a Florida_HQ_1<Enter>

36 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 37: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying tower information The Show Towers command displays information about the Sentry. This information includes the absolute and descriptive Sentry names.

To display tower information:

At the Sentry: prompt, type show towers and press Enter.

Example Sentry: show towers<Enter>

Tower Tower ID Name

.A Florida_HQ_1

Creating a descriptive infeed name The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is displayed when the Show Traps command is issued. See Displaying trap configuration information on page 37 for more information on the Show Traps command.

To create a infeed name:

At the Sentry: prompt, type set infeed name, followed by the absolute infeed name, then the descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed). Press Enter.

Example The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the Sentry:

Sentry: set infeed name .aa HQ_1_Infeed_A<Enter>

Displaying Infeed information The Show Infeeds command displays information about all infeeds. This information includes the absolute and descriptive infeed names.

To display tower information:

At the Sentry: prompt, type show infeeds and press Enter.

Example Sentry: show infeeds<Enter>

Input Input Feed ID Feed Name

.AA HQ_1_Infeed_A .AB HQ_1_Infeed_B .BA HQ_2_Infeed_A .BB HQ_2_Infeed_B

Displaying the Sentry firmware version The Version command displays the Sentry firmware version.

To display the firmware version:

At the Sentry: prompt, type version and press Enter.

Performing a warm boot The Restart command performs a warm boot of the Sentry.

NOTE: System user/outlet/group/port configuration or outlet states are NOT changed or reset with this command.

To perform a warm boot:

At the Sentry: prompt, type restart and press Enter.

Sentry Power Tower XL Operations • 37 Installation and Operations Manual

Page 38: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

TCP/IP Administration NOTE: A restart of the Sentry is required after setting or changing ANY TCP/IP configurations. See Performing a warm boot on page 37 for more information.

Setting the IP address The Set Ipaddress command sets the TCP/IP address of the network interface controller.

To set the IP address:

At the Sentry: prompt, type set ipaddress, followed by the IP address and press Enter.

Example The following command sets the IP address to 12.34.56.78:

Sentry: set ipaddress 12.34.56.78<Enter>

Setting the subnet mask The Set Subnet command sets the subnet mask for the network the PT40 will be attached to.

To set the subnet mask:

At the Sentry: prompt, type set subnet, followed by the subnet mask and press Enter.

Example The following command sets the subnet mask to 255.0.0.0

Sentry: set subnet 255.0.0.0<Enter>

Setting the gateway The Set Gateway command sets the IP address of the default gateway the Sentry uses to access external networks.

To set the gateway IP address:

At the Sentry: prompt, type set gateway, followed by the gateway IP address and press Enter.

Example The following command set the gateway IP address to 12.34.56.1:

Sentry: set gateway 12.34.56.1<Enter>

Setting the DNS IP address The Set DNS command sets the TCP/IP address of the Domain Name server (DNS).

To set the DNS IP address:

At the Sentry: prompt, type set, followed by dns1 or dns2 and the Domain Name server’s IP address. Press Enter.

Example The following command sets the primary Domain Name server IP address to 98.76.54.254:

Sentry: set dns1 98.76.54.254<Enter>

38 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 39: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying network configuration information The Show Network command displays TCP/IP, Telnet, SSH, Web, SSL and SNMP configuration information.

• IP address, subnet mask, gateway and DNS IP addresses • Enabled-disabled status and port numbers for Telnet, SSH, HTTP,SSL and SNMP support • HTTP authentication method and SSL access setting • Network status

See Chapter 4: Advanced Operations on page 43 for more information on SNMP and Remote Authentication

To display network configuration information:

At the Sentry: prompt, type show network and press Enter.

Example The following command displays the network configuration information:

Sentry: show network<Enter>

Network Configuration

IP Address: 12.34.56.78 DNS1: 98.76.54.254 Subnet Mask: 255.0.0.0 DNS2: 0.0.0.0 Gateway: 12.34.56.1

Telnet: Enabled Port: 23 SSH: Enabled Port: 65535 HTTP: Enabled Port: 80 Security: BASIC SSL: Enabled Access: Required SNMP: Enabled

Network Status

Link: Up Speed: 100 Mbps Duplex: Full Negotiation: Auto

HTTP Administration NOTE: A restart is required after setting or changing ANY Telnet/Web configurations. See Performing a warm boot on page 37 for more information.

Enabling and disabling HTTP support The Set HTTP command is used to enable or disable HTTP support.

To enable or disable HTTP support:

At the Sentry: prompt, type set http, followed by enabled or disabled and press Enter.

Changing the HTTP server port With HTTP support enabled, the HTTP server watches and responds to requests on the default HTTP port number 80. This port number may be changed using the Set HTTP Port command.

To change the HTTP port:

At the Sentry: prompt, type set http port, followed by the port number and press Enter.

Example The following changes the HTTP port number to 2048:

Sentry: set HTTP port 2048<Enter>

Setting the HTTP authentication method The Set HTTP Security command is used to set the method of authentication. The Sentry HTTP server supports two authentication methods for security and validation of the username-password – Basic and MD5 digest.

For more information on authentication methods, see Setting the HTTP authentication method: on page 14.

To set the HTTP authentication method:

At the Sentry: prompt, type set http security, followed by basic or md5 and press Enter.

Sentry Power Tower XL Operations • 39 Installation and Operations Manual

Page 40: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Telnet Administration NOTE: A restart of the Sentry is required after setting or changing ANY Telnet/Web configurations. See Performing a warm boot on page 37 for more information.

Enabling and disabling Telnet support The Set Telnet command is used to enable or disable Telnet support.

To enable or disable Telnet support:

At the Sentry: prompt, type set telnet, followed by enabled or disabled and press Enter.

Changing the Telnet port With Telnet support enabled, the Telnet server watches and responds to requests on the default Telnet port number 23. This port number may be changed using the Set Telnet Port command.

To change the Telnet socket:

At the Sentry: prompt, type set telnet port, followed by the port number and press Enter.

Example The following changes the Telnet port number to 7001:

Sentry: set telnet port 7001<Enter>

FTP Administration You may upload new versions of firmware into the Sentry using File Transfer Protocol (FTP). This allows access to new firmware releases for firmware improvements and new features additions. The following commands are used to configure the Sentry for an FTP firmware upload. See Appendix B: Uploading Firmware for more information on initiating a FTP firmware upload.

Setting the FTP Host IP address The Set FTP Host command sets the FTP host IP address allowing for firmware file uploads.

To set the FTP Host IP address:

At the Sentry: prompt, type set ftp host, followed by the Host IP address and press Enter.

Example The following command sets the FTP Host IP address to 12.34.56.99:

Sentry: set ftp host 12.34.56.99<Enter>

Setting the FTP username The FTP Username command sets the username as required by the FTP Host.

To set the FTP username:

At the Sentry: prompt, type set ftp username, followed by the FTP username and press Enter.

Example The following command sets the FTP username to Guest:

Sentry: set ftp username guest<Enter>

Setting the FTP Password The FTP Password command sets the password as required by the FTP Host.

To set the FTP password:

At the Sentry: prompt, type set ftp password, followed by the FTP password and press Enter.

Example The following command sets the FTP password to OpenSesame:

Sentry: set ftp password OpenSesame<Enter>

40 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 41: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Setting the filename to be uploaded The FTP Filename command sets the filename of the firmware file to be uploaded.

To set the FTP filename:

At the Sentry: prompt, type set ftp filename, followed by the firmware filename and press Enter.

Example The following command sets the FTP filename to snb_s50a.bin:

Sentry: set ftp filename snb_s50a.bin<Enter>

Setting the filepath for the file to be uploaded The FTP Filepath command sets the filepath for the firmware file to be uploaded.

To set the FTP filepath:

At the Sentry: prompt, type set ftp filepath, followed by the filepath and press Enter.

Example The following command sets the FTP filepath to ftp://Sentry:

Sentry: set ftp filepath ftp://sentry<Enter>

Displaying FTP configuration information The Show FTP command displays all FTP configuration information.

• FTP Host IP address • FTP Host username and password • Firmware filepath and filename

To display FTP configuration information:

At the Sentry: prompt, type show ftp and press Enter.

Example The following command displays the FTP configuration information:

Sentry: show ftp<Enter>

FTP Configuration

Host IP Address: 12.34.56.99 Username: guest Password: OpenSesame Directory: ftp://sentry Filename: snb_s52a.bin

SNTP Administration Sentry supports the use of a network time service to provide a synchronized time reference.

Setting the SNTP server address The Set SNTP command is used to set the primary and secondary SNTP server addresses.

To set the SNTP server address:

At the Sentry: prompt, type set sntp, followed by primary or secondary, and the SNTP server IP address. Press Enter.

Example The following command set the primary SNTP server address to 204.152.184.72:

Sentry: set sntp primary 204.152.184.72<Enter>

Sentry Power Tower XL Operations • 41 Installation and Operations Manual

Page 42: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying SNTP configuration information The Show SNTP command displays all SNTP configuration information.

To display SNTP configuration information

At the Sentry: prompt, type show sntp and press Enter.

Example The following command displays the SNTP configuration information:

Sentry: show sntp <Enter>

SNTP Date/Time (GMT): 2003-02-21 21:32:48 SNTP Primary IP Address: 204.152.184.72 SNTP Secondary IP Address: 0.0.0.0

42 • Operations Sentry Power Tower XL Installation and Operations Manual

Page 43: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Chapter 4: Advanced Operations SSL 44

Enabling and Setting up SSL Support 44 SSL Technical Specifications 44

SSH 45 Enabling and Setting up SSH Support 45 SSH Technical Specifications 45

SNMP 46 MIB, OID and Support 46 Enabling and Setting up SNMP Support 46 SNMP Traps 48 Configuring Traps 49

LDAP 52 Enabling and Setting up LDAP Support 52 Configuring LDAP Groups 55

TACACS+ 58 Enabling and Setting up TACACS+ Support 58 Configuring TACACS+ Privilege Levels 60 TACACS+ Technical Specifications 62

Page 44: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

SSL Secure Socket Layers (SSL) version 3 enables secure HTML sessions between a Sentry Remote Power Manager and a remote user. SSL provides two chief features designed to make TCP/IP (Internet) transmitted data more secure:

• Authentication – The connecting client is assured of the identity of the server. • Encryption – All data transmitted between the client and the server is encrypted rendering any

intercepted data unintelligible to any third party.

SSL uses the public-and-private key encryption system by RSA, which also requires the use of digital certificates. An SSL Certificate is an electronic file uniquely identifying individuals or websites and enables encrypted communication; SSL Certificates serve as a kind of digital passport or credential. The Sentry product’s SSL Certificate enables the client to verify the Sentry’s authenticity and to communicate with the Sentry securely via an encrypted session, protecting confidential information from interception and hacking.

SSL Command Summary Command Description Set SSL Enables/disables SSL support

Set SSL access Sets SSL access as optional or required

Enabling and Setting up SSL Support NOTE: A restart of the Sentry is required after setting or changing ANY SSL configurations. See Performing a warm boot on page 37 for more information.

Enabling or disabling SSL support The Set SSL command is used to enable or disable SSL support.

To enable or disable SSL support:

At the Sentry: prompt, type set ssl, followed by enabled or disabled and press Enter.

Setting SSL access level The Set SSL Access command is used to assign use of SSL as optional or required. The default access level is set to optional.

To change the access level:

At the Sentry: prompt, type set ssl access, followed optional or required, and press Enter.

Example The following changes the access level to required:

Sentry: set ssl access required<Enter>

SSL Technical Specifications Secure Socket Layer (SSL) version 3

Transport Layer Security (TLS) version 1 (RFC 2246)

SSL/TLS-enabled HTTPS server (RFC 2818)

Self-Signed X.509 Certificate version 3 (RFC 2459)

Asymmetric Cryptography: 1024-bit RSA Key Exchange

Symmetric Cryptography Ciphers: TLS_RSA_WITH_AES_256_CBC_SHA TLS_RSA_WITH_3DES_EDE_CBC_SHA TLS_RSA_WITH_AES_128_CBC_SHA TLS_RSA_WITH_DES_CBC_SHA

44 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 45: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

SSH Secure Shell (SSH) version 2 enables secure network terminal sessions between a Sentry Remote Power Manager and a remote user over insecure network. SSH provides an encrypted terminal sessions with strong authentication of both the server and client, using public-key cryptography and is typically used as a replacement for unencrypted Telnet. In addition to enabling secure network terminal sessions to the Sentry for configuration and power management, the SSH session may be used for secure Pass-Thru connections to attached devices.

SSH requires the configuration and use of a client agent on the client PC. There are many freeware, shareware or for-purchase SSH clients available. Two examples are the freeware client PuTTY and the for-purchase client SecureCRT® by VanDyke® Software. For configuration and use of these clients, please refer to the applicable software documentation.

SSH Command Summary Command Description Set SSH Enables/disables SSH support

Set SSH port Sets the SSH server port number

Enabling and Setting up SSH Support NOTE: A restart of the Sentry is required after setting or changing ANY SSH configurations. See Performing a warm boot on page 37 for more information.

Enabling or disabling SSH support The Set SSH command is used to enable or disable SSH support.

To enable or disable SSH support:

At the Sentry: prompt, type set ssh, followed by enabled or disabled and press Enter.

Changing the SSH server port With SSH support enabled, the SSH server watches and responds to requests on the default SSH port number 22. This port number may be changed using the Set SSH Port command.

To change the SSH port:

At the Sentry: prompt, type set ssh port, followed by the port number and press Enter.

Example The following changes the SSH port number to 65535:

Sentry: set ssh port 65535<Enter>

SSH Technical Specifications Secure Shell (SSH) version 2

Asymmetric Cryptography: Diffie-Hellman DSA/DSS 512-1024 (random) bits per NIST specification

Symmetric Cryptography: AES256-CBC RIJNDAEL256-CBC 3DES-192-CBC AES192-CBC RIJNDAEL192-CBC BLOWFISH-128-CBC AES128-CBC RIJNDAEL128-CBC ARCFOUR-128

Message Integrity: HMAC-SHA1-160 HMAC-SHA1-96 HMAC-MD5-128 HMAC-MD5-96

Authentication: Username/Password

Session Channel Break Extension (for RS232 Break)

Sentry Power Tower XL Advanced Operations • 45 Installation and Operations Manual

Page 46: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

SNMP The Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information and control power for the individual outlets.

The Sentry includes an SNMP v2c agent supporting standard MIB I and MIB II objects. A private enterprise MIB extension (Sentry3 MIB) is also supported to provide remote power control.

See SNMP on page 18, for information on enabling and configuring SNMP.

NOTE: For security, SNMP support is disabled by default.

SNMP Command Summary Command Description Set snmp Enables or disables SNMP support

Set snmp getcomm Sets the ‘get’ community string

Set snmp setcomm Sets the ‘set’ community string

Set snmp trapdest1 Sets a destination IP addresses for traps

Set snmp trapdest2 Sets a destination IP addresses for traps

Set snmp traptime Sets the delay for steady state condition traps

Show snmp Displays all SNMP configuration information

MIB, OID and Support The Sentry SNMP MIB and OID are available on the Server Technology website:

ftp://ftp.servertech.com/pub/SNMP/sentry3

Technical support is available 8:30AM to 5:00 PM Pacific Time, Monday-Friday.

For SNMP Support, email: [email protected]

Enabling and Setting up SNMP Support Sentry SNMP support must be enabled and configured for access to Sentry3 MIB objects and generation of all Sentry3 traps.

Enabling/disabling SNMP support The Sentry SNMP command is used to enable or disable SNMP support.

To enable SNMP support:

At the Sentry: prompt, type set snmp, followed by enabled or disabled and press Enter.

NOTE: A restart of the Sentry is required after enabling or disabling SNMP support. See Performing a warm boot on page 37 for more information.

Setting trap destinations The Set SNMP Trapdest1 and Trapdest2 commands are used to set the IP addresses of SNMP management stations receiving all traps. Sentry supports a maximum of two trap destinations; one must be defined to enable trap generation.

To set the trap destination:

At the Sentry: prompt, type set snmp, trapdest1 or trapdest2, the Ipaddress and press Enter.

Example The following sets the trap destination 1 to 64.42.31.208:

Sentry: set snmp trapdest1 64.42.31.208<Enter>

To reset the trap destination:

At the Sentry: prompt, type set snmp, trapdest1 or trapdest2, 0.0.0.0 and press Enter.

46 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 47: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Setting the trap timer The Set Traptime command sets the timer period between repeated error-condition traps. The valid range for the timer period is 1 to 65535 (in seconds). The default value for the timer period is 60 seconds.

To set the trap timer:

At the Sentry: prompt, type set traptime, followed by the timer period and press Enter.

Example The following sets the timer period to 180 seconds:

Sentry: set traptime 180<Enter>

Setting the Get/Set community strings Sentry supports two SNMP community strings that provide varying levels of access to objects defined in the Sentry3 MIB.

Community strings may be 1 to 24 characters.

Setcomm The Setcomm string provides read-write access to sentry3 MIB objects. The default Setcomm string is “private”

To set the Setcomm community string:

At the Sentry: prompt, type set snmp setcomm, followed by the string and press Enter.

Getcomm The Getcomm string provides read-only access to sentry3 MIB objects. The default Getcomm string is “public”.

To set the Getcomm community string:

At the Sentry: prompt, type set snmp getcomm, followed by the string and press Enter.

Setting the Trap community string The Set SNMP Trapcomm command is used to set the community string that is included with all generated traps. This string must be defined to enable trap generation.

The trap community string may be 1 to 24 characters. The default Trapcomm string is “trap”.

To set the Trapcomm community string:

At the Sentry: prompt, type set snmp trapcomm, followed by the string and press Enter.

Displaying SNMP configuration information The Show SNMP command displays all SNMP configuration information.

• SNMP support status • SNMP community strings • Trap timer value • Trap destinations

To display SNMP configuration information:

At the Sentry: prompt, type show snmp and press Enter.

Example The following command displays the SNMP configuration information:

Sentry: show snmp<Enter>

SNMP Configuration

Sentry Power Tower XL Advanced Operations • 47

SNMP: Enabled SET Community String: private GET Community String: public TRAP Community String: trap Error Trap Repeat Time (seconds): 180 Trap Destination 1: 64.42.31.208 Trap Destination 2: (undefined)

Installation and Operations Manual

Page 48: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

SNMP Traps The Sentry supports three types of SNMP traps. Traps are enabled at the tower (T), infeed (I) or outlet (O) level.

Trap Summary Name Level(s) Description Status T, I, O Operational status change

Change O Control status change

Load I Input load out of limit

All traps include the Location of the Sentry as defined with the Set Location command.

Status trap A Status trap is generated when an error condition occurs on a tower, infeeed, Environmental Monitor or individual sensor. Status traps include the reported Status, the Location of the Sentry and identifier and name of the affected tower, infeed, outlet, environmental monitor or sensor.

Any error state generates a Status trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Status returns to a non-error status. All status traps are enabled by default.

Tower Status traps Status Error Description Normal Tower is working correctly

NoComm x Communication to the tower has been lost

Infeed Status traps Status Error Description On Infeed is on

OffError x Infeed should be on but no current is sensed at the infeed

NoComm x Communication to the infeed has been lost

Outlet Status traps Status Error Description On Outlet is on

Off Outlet is off

OnWait Outlet Status in transition

OffWait Outlet Status in transition

OnError x Outlet should be off but current is sensed at the outlet

OffError x Outlet should be on but no current is sensed at the outlet

OffFuse x Outlet should be on but a blown fuse has been detected

NoComm x Communication to the outlet has been lost

NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal.

Change trap The Change trap is generated for all outlet status changes between any on/off conditions. Change traps include the outlet status, Location of the Sentry, and identifier and name of the affected outlet. For descriptions of the outlet status types, please refer to the prior table.

48 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 49: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Load Trap The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps include the reported input load, load status, Location of the Sentry, and identifier and name of the affected infeed.

Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Load returns to a non-error status.

Load traps Status Error Description Normal Infeed is on and within preset thresholds

NotOn Infeed is off

Reading Non-error state – Load status currently being read

LoadHigh x Infeed current load exceeds preset threshold

OverLoad x Infeed current load exceeds the measurable range for the infeed

ReadError x Unable to read Load status

NoComm x Communication to the infeed has been lost

Configuring Traps

SNMP Trap Command Summary Command Description Set Trap Tower Status Enables or disables the Tower Status trap

Set Trap Infeed Status Enables or disables the Infeed Status trap off

Set Trap Infeed Load Enables or disables the Infeed Load trap

Set Trap Infeed HighThresh Sets the Infeed Load trap high limit

Set Trap Outlet Change Enables or disables the Outlet Change trap

Set Trap Outlet Status Enables or disables the Outlet Status trap

Show Traps Displays trap configurations

Enabling or Disabling a Status trap The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.

To Enable or Disable a Status trap:

At the Sentry: prompt, type set trap (tower, infeed, outlet, em or ths) status, followed by the tower, infeed or outlet name, and on or off. Press Enter, or\

Type set trap (tower, infeed, outlet, em or ths) Status all, followed by on or off and press Enter.

Examples The following command enables the Status trap for the first tower, using the tower’s absolute name:

Sentry: set trap tower status .a on<Enter>

The following command enables the Status trap for the tower named Florida_HQ_1: Sentry: set trap tower status Florida_HQ_1 on<Enter>

NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.

Sentry Power Tower XL Advanced Operations • 49 Installation and Operations Manual

Page 50: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Enabling or Disabling a Load trap The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.

To Enable or Disable a Load trap:

At the Sentry: prompt, type set trap infeed load, followed by the infeed name, and on or off. Press Enter, or

Type set trap infeed load all, followed by on or off and press Enter.

Examples The following command enables the Load trap for second infeed on the first tower, using the infeed’s absolute name:

Sentry: set trap infeed load .AB on<Enter>

The following command disables the Load trap for all infeeds: Sentry: set trap infeed load all off<Enter>

NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Infeed Load trap automatically enables the Infeed and Tower Status traps for that infeed.

Setting the Infeed Load limit The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.

To set the infeed load limit:

At the Sentry: prompt, type set trap infeed loadhigh, followed by the infeed name, and a value from 0 to 255 in amperes. Press Enter.

Example The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes, using the infeed’s absolute name:

Sentry: set trap infeed loadhigh .ab 25<Enter>

Enabling or Disabling a Change trap The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.

To Enable or Disable a Change trap:

At the Sentry: prompt, type set trap outlet change, followed by the outlet name and on or off. Press Enter, or

Type set trap outlet change all, followed by on or off and press Enter.

Example The following command enables the Change trap for the third outlet on the first infeed of the second tower, using the outlet’s absolute name:

Sentry: set trap outlet change .ba3 on<Enter>

50 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 51: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying trap configuration information The Show Traps command displays information about all traps.

To display trap information:

At the Sentry: prompt, type show traps and press Enter.

Example The following command requests trap configuration information:

Sentry: show traps <Enter>

Tower trap configuration:

Tower Tower Status ID Name Trap

.A Florida_HQ_1 ON .B Florida_HQ_2 ON

More (Y/es N/o): y

Input feed trap configuration:

Input Input Status Load High Feed ID Feed Name Trap Trap Thresh

.AA HQ_1_Infeed_A ON ON 255 A .BA HQ_2_Infeed_A ON ON 255 A

More (Y/es N/o): y

Outlet trap configuration:

Outlet Outlet Change Status ID Name Trap Trap

.AA1 DataServer_1 OFF ON .AA2 WebServer_1 OFF ON .AA3 FileServer_1 OFF ON .AA4 OFF ON .AA5 OFF ON .AA6 OFF ON .AA7 OFF ON .AA8 OFF ON .AB1 OFF ON .AB2 OFF ON .AB3 OFF ON .AB4 OFF ON .AB5 OFF ON .AB6 OFF ON .AB7 OFF ON .AB8 OFF ON

More (Y/es N/o): y

Sentry Power Tower XL Advanced Operations • 51 Installation and Operations Manual

Page 52: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

LDAP The Sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3. This support enables authentication with Active Directory, a network Directory Service; user accounts do not need to be individually created locally on each Sentry device.

This allows administrators to pre-define and configure (in each Sentry product, and in Active Directory) a set of necessary LDAP Groups, and access rights for each. User’s access rights can then be assigned or revoked simply by making the user a member of one-or-more pre-defined Sentry LDAP Groups. User accounts can be added, deleted, or changed in the Active Directory without any changes needed on individual Sentry products.

LDAP Command Summary Command Description Set Authorder Specifies the authentication order for each new session attempt

Set LDAP Enables/disables LDAP support

Set LDAP HostIP Sets the IP address of the Directory Services server

Set LDAP HostDC Sets the domain component of the Directory Services server

Set LDAP Bind Specifies the LDAP bind request password type

Show LDAP Displays LDAP configurations

Set DNS Sets the IP address of the Domain Name server

Ping Verifies proper DNS configuration by name resolution

Show Network Displays network configuration information

Create LDAPGroup Adds an LDAP group name

Remove LDAPGroup Deletes an LDAP group name

Add GrouptoLDAP Grants an LDAP group access to one or more groups

Add OutlettoLDAP Grants an LDAP group access to one or all outlets

Add PorttoLDAP Grants an LDAP group access to one or serial ports

Delete GroupfromLDAP Removes access to one or more groups for an LDAP group

Delete OutlettoLDAP Removes access to one or more outlets for an LDAP group

Delete PortfromLDAP Removes access to one or more serial ports for an LDAP group

Set LDAPGroup Access Sets the access level for an LDAP group

Set LDAPGroup Envmon Grants or removes privileges to view input and environmental monitoring status

List LDAPGroup Displays all accessible outlet/groups/ports for an LDAP group

List LDAPGroups Displays privilege levels for all LDAP groups

Enabling and Setting up LDAP Support There are a few configuration requirements for properly enabling and setting up LDAP support. Below is an overview of the minimum requirements.

Directory Services server configuration requirements:

1. Define at least one LDAP group. 2. Assign users to that LDAP group.

Sentry configuration requirements:

1. Enable LDAP support. 2. Define the IP address and domain component of at least one Directory Services server. 3. Set the LDAP bind request method being utilized by the Directory Services server. 4. Define the IP address of at least one DNS server. 5. Test DNS server configuration using Sentry ‘ping’ support. 6. Define at least one LDAP group and assign access rights for that group.

NOTE: LDAP group names on the Directory Service server and the Sentry must match.

52 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 53: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Enabling and disabling LDAP support The Set LDAP command is used to enable or disable LDAP support.

To enable or disable LDAP support:

At the Sentry: prompt, type set ldap, followed by enabled or disabled and press Enter.

Setting the LDAP host IP address The Set LDAP HostIP command sets the TCP/IP address of the Directory Services server.

To set the LDAP host IP address:

At the Sentry: prompt, type set ldap, followed by hostip1 or hostip2 and the Directory Services server’s IP address. Press Enter.

Example The following command sets the primary Directory Services server IP address to 98.76.54.32:

Sentry: set ldap hostip1 98.76.54.32<Enter>

Setting the LDAP host domain component The Set LDAP HostDC command sets the domain component of the Directory Services server.

To set the LDAP host domain component:

At the Sentry: prompt, type set ldap, followed by hostdc1 or hostdc2 and the domain component. Press Enter.

Example The following command sets the primary Directory Services server domain component to servertech.com:

Sentry: set ldap hostdc1 servertech.com<Enter>

Setting the LDAP bind password type The Set LDAP Bind command sets the password type used in the bind requests. The Sentry supports two LDAP bind methods – Simple and MD5.

The Simple method utilizes unencrypted delivery of a username-password over the network to the Active Directory server for authentication.

The MD5 digest method provides much stronger protection utilizing one-way encoded hash numbers, never placing the username-password on the network. For more information on MD5, see Setting the HTTP authentication method: on page 14.

NOTE: Windows 2000 is known only to support Simple binding. Windows 2003 supports both Simple and MD5 binding.

To set the bind password type:

At the Sentry: prompt, type set ldap bind, followed by simple or md5 and press Enter.

Setting the authentication order The Set Authorder command sets the authentication order for remote authentication sessions. The Sentry supports two methods for authentication order - Remote -> Local and Remote Only.

The Remote -> Local method first attempts authentication with the Active Directory server and if unsuccessful with the local user database on the Sentry device.

The Remote Only method attempts authentication only with the Active Directory server and if unsuccessful, access is denied.

NOTE: With the Remote Only method, if authentication fails due to a communication failure with the Active Directory server automatic authentication fallback will occur to authenticate with the local user data base on the Sentry device.

To set the authentication order:

At the Sentry: prompt, type set authorder, followed by remotelocal or remoteonly and press Enter.

NOTE: Server Technology recommends NOT setting the authentication order to Remote Only until the LDAP has been fully configured and tested.

Sentry Power Tower XL Advanced Operations • 53 Installation and Operations Manual

Page 54: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying LDAP configuration information The Show LDAP command displays LDAP configuration information.

• Remote authentication order • Enabled-disabled status of LDAP support • Directory Services server IP address and domain components • Bind request password type

To display the LDAP configuration information:

At the Sentry: prompt, type show ldap and press Enter.

Example The following command displays the LDAP configuration information:

Sentry: show ldap

LDAP Configuration

LDAP: Enabled

Host IP1: 98.76.54.32 Host IP2: 0.0.0.0

Host DC1: servertech.com Host DC2:

Bind Type: MD5

Auth Order: Remote->Local

Setting the DNS IP address The Set DNS command sets the TCP/IP address of the Domain Name server (DNS).

NOTE: LDAP requires the definition of at least one Domain Name server.

To display the DNS configuration information, use the Show Network command as described on page 38.

To set the DNS IP address:

At the Sentry: prompt, type set, followed by dns1 or dns2 and the Domain Name server’s IP address. Press Enter.

Example The following command sets the primary Domain Name server IP address to 98.76.54.254:

Sentry: set dns1 98.76.54.254<Enter>

Verifying the DNS configuration The Ping command may be used to verify the configuration of the DNS IP address.

To verify the DNS configuration:

At the Sentry: prompt, type ping, followed by the domain component of the Directory Services server previously configured and press Enter.

Example The following command verifies the DNS configuration:

Sentry: ping servertech.com

Pinging servertech.com [98.76.54.32] with 64 bytes of data:

Reply from 98.76.54.32: bytes=64 pseq=0 triptime=0 Reply from 98.76.54.32: bytes=64 pseq=1 triptime=0 Reply from 98.76.54.32: bytes=64 pseq=2 triptime=0 Reply from 98.76.54.32: bytes=64 pseq=3 triptime=0 Reply from 98.76.54.32: bytes=64 pseq=4 triptime=0

Command successful

54 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 55: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Configuring LDAP Groups

Creating an LDAP group The Create LDAPGroup command creates an LDAP group.

To create an LDAP group:

At the Sentry: prompt, type create ldapgroup, optionally followed by a 1-16 character group name (Spaces are not allowed, and LDAP group names are not case sensitive). Press Enter.

Example The following command creates the LDAP group PowerUser:

Sentry: create ldapgroup PowerUser<Enter>

Removing an LDAP group The Remove LDAPGroup command removes an LDAP group.

To remove an LDAP group:

At the Sentry: prompt, type remove ldapgroup, optionally followed by a group name. Press Enter.

Setting LDAP group access level privileges The Set LDAPGroup Access command sets the access level privileges for an LDAP group. The Sentry has four defined access privilege levels; Admin, User, On-Only and View-Only. For more information on user access levels, see Changing a user’s access privilege level: on page 17.

To set the access level privilege for an LDAP group :

At the Sentry: prompt, type set ldapgroup access, followed by admin, user, ononly or viewonly, optionally followed by a LDAP group name and press Enter.

Examples The following command sets the LDAP group access level for LDAPAdmin to Admin:

Sentry: set ldapgroup access admin ldapadmin<Enter>

The following command sets the LDAP group access level for PowerUser to User: Sentry: set ldapgroup access user poweruser<Enter>

Granting and removing input status viewing privileges The Set LDAPGroup Envmon command grants or removes input status viewing privileges to/from an LDAP group.

To grant or remove input status viewing privileges for an LDAP group:

At the Sentry: prompt, type set ldapgroup envmon followed by on or off, optionally followed by a group name and press Enter.

Example The following command grants intput status viewing privileges to the LDAP group PowerUser:

Sentry: set ldapgroup envmon on poweruser<Enter>

Sentry Power Tower XL Advanced Operations • 55 Installation and Operations Manual

Page 56: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying the LDAP access privilege levels The List LDAPGroups command displays all defined LDAP group with their access privilege level.

To display LDAP group access privilege levels:

At the Sentry: prompt, type list ldapgroups and press Enter.

Example The following command displays all LDAP groups with their access privilege level:

Sentry: list ldapgroups<Enter>

LDAP Access Environmental Group Name Level Monitoring

LDAPAdmin Admin Allowed PowerUser User Allowed User On-Only Not Allowed Guest View-Only Not Allowed

Adding outlet access to an LDAP group The Add OutletToLDAP command grants an LDAP group access to one or all outlets. To grant access for more than one outlet, but not all outlets, you must use multiple Add OutletToLDAP commands.

To grant outlet access to an LDAP group:

At the Sentry: prompt, type add outlettoldap, optionally followed by an outlet name and a group name. Press Enter, or

Type add outlettoldap all, followed by a group name and press Enter.

Examples The following commands grant the LDAP group PowerUser access to outlets A1 and Webserver_1:

Sentry:add outlettoldap .a1 poweruser<Enter> Sentry:add outlettoldap WebServer_1 poweruser<Enter>

Deleting outlet access for an LDAP group The Delete OutletFromLDAP command removes an LDAP group’s access to one or all outlets. You cannot remove access to any outlet for an administrative level group.

To delete outlet access for an LDAP group:

At the Sentry: prompt, type delete outletfromldap, optionally followed by an outlet name and a group name. Press Enter, or

Type delete outletfromldap all, followed by a group name and press Enter.

Adding outlet group access to an LDAP group The Add GroupToLDAP command grants an LDAP group access to a outlet group. To grant access for more than one outlet group, you must use multiple Add GroupToLDAP commands.

To gran toutlet group access to an LDAP Group:

At the Sentry: prompt, type add grouptoldap, optionally followed by an outlet group name and an LDAP group name. Press Enter.

Examples The following commands grants to LDAP group PowerUser access to the outlet groups ServerGroup_1 and ServerGroup_2:

Sentry:add grouptoldap servergroup_1 poweruser<Enter> Sentry:add grouptoldap servergroup_2 poweruser<Enter>

Deleting outlet group access for an LDAP group The Delete GroupFromLDAP command removes an LDAP group’s access to a outlet group. You cannot remove access to any group for an administrative level group.

To delete outlet group access for an LDAP group:

At the Sentry: prompt, type delete groupfromldap, optionally followed by a outlet group name and an LDAP group name. Press Enter.

56 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 57: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Adding serial port access to an LDAP group The Add PortToLDAP command grants an LDAP group access to the serial port.

To grant serial port access to an LDAP group:

At the Sentry: prompt, type add porttoldap console and a group name. Press Enter.

Deleting serial port access for an LDAP group The Delete PortFromLDAP command removes an LDAP group’s access to the serial port. You cannot remove access to the serial port for an administrative level group.

To delete serial port access for a user:

At the Sentry: prompt, type delete portfromldap console and a group name. Press Enter.

Displaying outlet, outlet group and serial port access The List LDAPGroup command displays all accessible outlets, outlet groups and serial ports for an LDAP group.

To display outlet, outlet group and serial port access:

At the Sentry: prompt, type list ldapgroup, optionally followed by a group name. Press Enter.

Example The following command displays information about the LDAP group PowerUser:

Sentry: list ldapgroup poweruser<Enter>

Username: PowerUser

Outlet Outlet ID Name

.A1 DataServer_1 .A2 WebServer_1

Groups:

ServerGroup_1 ServerGroup_2

More (Y/es N/o): Y

Ports:

Port Port ID Name

Console Console

Members of the PowerUser LDAP group may access the following outlets, outlet groups and serial ports: outlet A1 which has a descriptive name of DataServer_1, outlet A2 which has a descriptive name of WebServer_1, group ServerGroup_1 group ServerGroup_2 and Console serial port.

Sentry Power Tower XL Advanced Operations • 57 Installation and Operations Manual

Page 58: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

TACACS+ The Sentry family of products supports the Terminal Access Controller Access Control System (TACACS+) protocol. This enables authentication and authorization with a central TACACS+ server; user accounts do not need to be individually created locally on each Sentry device.

This allows administrators to pre-define and configure (in each Sentry product, and in the TACACS+ server) a set of necessary TACACS+ privilege levels, and users access rights for each. User’s access rights can then be assigned or revoked simply by making the user a member of one-or-more pre-defined Sentry TACACS+ privilege levels. User account rights can be added, deleted, or changed within TACACS+ without any changes needed on individual Sentry products.

The Sentry supports 16 different TACACS+ privilege levels; 15 are entirely configurable by the system administrator (1 is reserved for default Admin level access to all Sentry resources).

TACAC+ Command Summary Command Description Set Authorder Specifies the authentication order for each new session attempt

Set TACACS Enables/disables SSL support

Set TACACS HostIP Sets the IP address of the TACACS server

Set TACACS Key Sets the TACACS encryption key

Show TACACS Displays TACACS configurations

Add GrouptoTACACS Grants a TACACS account access to one or more groups

Add OutlettoTACACS Grants a TACACS account access to one or all outlets

Add PorttoTACACS Grants a TACACS account access to one or serial ports

Delete GroupfromTACACS Removes access to one or more groups for a TACACS account

Delete OutlettoTACACS Removes access to one or more outlets for a TACACS account

Delete PortfromTACACS Removes access to one or more serial ports for a TACACS account

Set TacPriv Access Sets the access level for a TACACS account

Set TacPriv Envmon Grants or removes privileges to view input and environmental monitoring status

List TacPrivs Displays access levels for all TACACS accounts

List TacPriv Displays all accessible outlet/groups/ports for a TACACS account

Enabling and Setting up TACACS+ Support There are a few configuration requirements for properly enabling and setting up TACACS+ support. Below is an overview of the minimum requirements:

1. Enable TACACS+ support. 2. Define the IP address and domain component of at least one TACACS+server. 3. Set the TACACS+ key configured on the supporting TACACS+server.

Enabling and disabling TACACS+ support The Set TACACS command is used to enable or disable TACACS+ support.

To enable or disable TACACS+ support:

At the Sentry: prompt, type set tacacs, followed by enabled or disabled and press Enter.

Setting the TACACS+ server IP address The Set TACACS HostIP command sets the TCP/IP address of the TACACS+ server.

To set the TACACS+ server IP address:

At the Sentry: prompt, type set tacacs, followed by hostip1 or hostip2 and the TACACS+ server’s IP address. Press Enter.

Example The following command sets the primary TACACS+ server IP address to 98.76.54.32:

Sentry: set tacacs hostip1 98.76.54.32<Enter>

58 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 59: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Setting the TACACS+ encryption key The Set TACACS Key command sets the encryption key used to encrypt all data packets between the Sentry and the TACACS+ server. This key must match the key configured on the TACACS+ server.

To set the encryption key:

At the Sentry: prompt, type set tacacs key and press Enter.

At the TACACS+ Key: prompt, type a key of up to 60 alphanumeric and other typeable characters (ASCII 32 to 126 decimal). Keys are case sensitive. Press Enter. To specify no password, press Enter at the prompt.

At the Verify TACACS+ Key: prompt, retype the key. Press Enter. To verify no password, press Enter at the prompt.

Example Sentry: set tacacs key<Enter> TACACS+ Key: <Enter> Verify TACACS+ Key: <Enter>

For security, key characters are not displayed.

NOTE: A key size of zero results in no encryption being applied which may not be supported by the TACACS+ server and is not recommended for a production environment.

Setting the authentication order The Set Authorder command sets the authentication order for remote authentication sessions. The Sentry supports two methods for authentication order - Remote -> Local and Remote Only.

The Remote -> Local method first attempts authentication with the TACACS+ server and if unsuccessful with the local user database on the Sentry device.

The Remote Only method attempts authentication only with the TACACS+ server and if unsuccessful, access is denied.

NOTE: With the Remote Only method, if authentication fails due to a communication failure with the TACACS+ server automatic authentication fallback will occur to authenticate with the local user data base on the Sentry device.

To set the authentication order:

At the Sentry: prompt, type set authorder, followed by remotelocal or remoteonly and press Enter.

NOTE: Server Technology recommends NOT setting the authentication order to Remote Only until the TACACS+ has been fully configured and tested.

Displaying TACACS+ configuration information The Show TACACS command displays TACACS+ configuration information.

• Remote authentication order • Enabled-disabled status of LDAP support • Directory Services server IP address and domain components • Bind request password type

To display the LDAP configuration information:

At the Sentry: prompt, type show ldap and press Enter.

Example The following command displays the LDAP configuration information:

TACACS+ Configuration

TACACS+: Disabled

Host IP1: 98.76.54.32 Host IP2: 0.0.0.0

TACACS+ Key: (Set)

Auth Order: Remote->Local

Sentry Power Tower XL Advanced Operations • 59 Installation and Operations Manual

Page 60: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Configuring TACACS+ Privilege Levels

Setting TACACS+ account access level privileges The Set TacPriv Access command sets the access level privileges for a TACACS+ account. The Sentry has four defined access privilege levels; Admin, User, On-Only and View-Only. For more information on user access levels, see Changing a user’s access privilege level: on page 17.

To set the access level privilege for a TACACS+ account :

At the Sentry: prompt, type set tacpriv access, followed by admin, user, ononly or viewonly, optionally followed by a TACACS+ account number and press Enter.

Examples The following command sets the TACACS+ account access level for account 14 to Admin:

Sentry: set tacpriv access admin 14<Enter>

The following command sets the TACACS+ account access level for account 5 to User: Sentry: set tacpriv access user 5<Enter>

Granting and removing input status viewing privileges The Set TacPriv Envmon command grants or removes input status viewing privileges to/from a TACACS+ account.

To grant or remove input status viewing privileges for a TACACS+ account:

At the Sentry: prompt, type set tacpriv envmon, followed by on or off, optionally followed by a TACACS+ account number and press Enter.

Example The following command grants input status viewing privileges to the TACACS+ account 5:

Sentry: set tacpriv envmon on 5<Enter>

Displaying the TACACS+ access privilege levels The List TacPrivs command displays all TACACS+ accounts with their access privilege levels.

To display TACACS+ account access privilege levels:

At the Sentry: prompt, type list tacprivs and press Enter.

Example The following command displays all TACACS+ account with their access privilege level:

Sentry: list tacprivs<Enter>

TACACS Access Environmental Account Name Level Monitoring

TACAdmin Admin Allowed PowerUser User Allowed User On-Only Not Allowed Guest View-Only Not Allowed

Adding outlet access to a TACACS+ account The Add OutletToTACACS command grants a TACACS+ account access to one or all outlets. To grant access for more than one outlet, but not all outlets, you must use multiple Add OutletToTACACS commands.

To grant outlet access to a TACACS+ account:

At the Sentry: prompt, type add outlettotacacs, optionally followed by an outlet name and a TACACS+ account number. Press Enter, or

Type add outlettotacacs all, followed by a TACACS+ account number and press Enter.

Examples The following commands grant the a TACACS+ account 5 access to outlets A1 and Webserver_1:

Sentry:add outlettotacacs .a1 5<Enter> Sentry:add outlettotacacs WebServer_1 5<Enter>

60 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 61: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Deleting outlet access for a TACACS+ account The Delete OutletFromTACACS command removes a TACACS+ account’s access to one or all outlets. You cannot remove access to any outlet for an administrative level account.

To delete outlet access for a TACACS+ account:

At the Sentry: prompt, type delete outletfromtacacs, optionally followed by an outlet name and a TACACS+ account number. Press Enter, or

Type delete outletfromtacacs all, followed by a TACACS+ account number and press Enter.

Adding outlet group access to a TACACS+ account The Add GroupToTACACS command grants a TACACS+ account access to an outlet group. To grant access for more than one outlet group, you must use multiple Add GroupToTACACS commands.

To grant outlet group access to a TACACS+ account:

At the Sentry: prompt, type add grouptotacacs, optionally followed by an outlet group name and a TACACS+ account number. Press Enter.

Examples The following commands grants to a TACACS+ account number 5 access to the outlet groups ServerGroup_1 and ServerGroup_2:

Sentry:add grouptotacacs servergroup_1 5<Enter> Sentry:add grouptotacacs servergroup_2 5<Enter>

Deleting outlet group access for a TACACS+ account The Delete GroupFromTACACS command removes a TACACS+ account’s access to an outlet group. You cannot remove access to any group for an administrative level account.

To delete outlet group access for a TACACS+ account:

At the Sentry: prompt, type delete groupfromtacacs, optionally followed by a outlet group name and a TACACS+ account number. Press Enter.

Adding serial port access to a TACACS+ account The Add PortToTACACS command grants a TACACS+ account access to the serial port.

To grant serial port access to a TACACS+ account:

At the Sentry: prompt, type add porttotacacs console and a TACACS+ account number. Press Enter.

Deleting serial port access for a TACACS+ account The Delete PortFromTACACS command removes a TACACS+ account’s access to the serial port. You cannot remove access to the serial port for an administrative level account.

To delete serial port access for a TACACS+ account:

At the Sentry: prompt, type delete portfromtacacs console and a TACACS+ account number. Press Enter.

Sentry Power Tower XL Advanced Operations • 61 Installation and Operations Manual

Page 62: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Displaying outlet, outlet group and serial port access The List TacPriv command displays all accessible outlets, outlet groups and serial ports for a TACACS+ account.

To display outlet, outlet group and serial port access:

At the Sentry: prompt, type list tacpriv, optionally followed by a TACACS+ account. Press Enter.

Example The following command displays information about the TACACS+ account 1:

Sentry: list tacpriv 1<Enter>

TACACS+ Privilege Level: 1

Ports:

Port ID Port Name

Console Console

Members of PowerUser TACACS+ account members may access the Console serial port.

TACACS+ Technical Specifications Authentication START Packet includes:

action = 1 (TAC_PLUS_AUTHEN_LOGIN) priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN) authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII) service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN) user = (entered username) port = (access path into the Sentry) rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of MAC address) data = ‘‘ (null)

NOTE: The password is sent in a CONTINUE packet.

Authorization REQUEST Packet includes:

authen_method = 6 (TAC_PLUS_AUTHEN_METH_TACACSPLUS) priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN) authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII) authen_service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN) user = (entered username) port = (access path into the Sentry) rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of Ethernet MAC address) service = ‘shell’ (for exec) cmd = ‘‘ (null)

NOTE: The access paths into the Sentry which support TACACS+ are ‘Console’, ‘Telnet’, ‘SSH’, ‘HTTP’ and ‘HTTPS’. In the case of ‘Console’ and ‘Modem’, an administrator is allowed to rename these ports in which case the assigned name is used.

62 • Advanced Operations Sentry Power Tower XL Installation and Operations Manual

Page 63: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Chapter 5: Appendices Appendix A: Resetting to Factory Defaults

You may reset the non-volatile RAM that stores all configurable options. This clears all administrator-editable fields and resets all command line configurable options to their default values, including all user accounts.

You may reset the unit to factory defaults from the command line or the HTML interface, or by pressing the reset button. You must have administrator-level privileges to issue the command. Using the reset button may be necessary when a forgotten password prevents administrator login. Each of the methods updates the current working configuration to the factory defaults.

NOTE: Resetting the unit resets all TCP/IP and Telnet/Web configurations. Reconfiguring the TCP/IP and Telnet/web settings will be required.

To reset to factory defaults from the HTML interface On the Restart page in the Tools section of the HTML interface, select Restart and reset to factory defaults from the drop-down menu and press Apply.

To reset to factory defaults from the command line At the Sentry: prompt, type restart factory and press Enter.

To reset to factory defaults using the reset button Locate the recessed reset button directly beside the Serial & Ethernet ports. You will need a non-conductive, non-metallic tool that fits inside the recess.

Insert the tool in the recess, then depress and hold the reset button for at least ten seconds.

NOTE: If the reset button is depressed and held for more than 15 seconds, the reset will abort.

Appendix B: Uploading Firmware You may upload new versions of firmware using File Transfer Protocol (FTP). This allows access to new firmware releases for firmware improvements and new features additions.

NOTE: To begin an FTP upload session, you must first configure the FTP Host address, username/password, filename and filepath. For information on configuring the FTP settings required for firmware upload see Chapter 3: Operations.

You may initiate an FTP upload session by issuing a command or from the HTML interface. You must have administrator-level privileges to initiate an upload.

To initiate an FTP upload session from the HTML interface On the Restart page in the Tools section of the HTML interface, select Restart and upload firmware via FTP from the drop-down menu and press Apply.

Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host. See See FTP Administration in Chapter 3: for more information.

To initiate an FTP upload session from the command line The Restart FTPLoad command initiates an upload of firmware. Upon issuing this command the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host. See FTP Administration in Chapter 3: for more information.

To initiate an FTP firmware upload session:

At the Sentry: prompt, type restart ftpload and press Enter.

Sentry Power Tower XL Appendices • 63 Installation and Operations Manual

Page 64: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Appendix C: Technical Specifications Domestic Models

Power Tower XL

Model Rated Voltage Input Cordset and Plug (10’) Outlets PTXL-H008-1-02 100-120V 50/60Hz IEC 60320 C201 8 NEMA 5-20R PTXL-H008-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 8 NEMA 5-20R PTXL-H008-2-02 208-240V 60Hz IEC 60320 C201 8 IEC 60320 C13 PTXL-H008-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 8 IEC 60320 C13 PTXL-H016-1-02 100-120V 50/60Hz IEC 60320 C201 16 NEMA 5-20R PTXL-H016-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXL-H016-2-02 208-240V 60Hz IEC 60320 C201 16 IEC 60320 C13 PTXL-H016-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 PTXL-HD16-1-02 100-120V 50/60Hz 2 x IEC 60320 C201 16 NEMA 5-20R PTXL-HD16-1-05 100-120V 50/60Hz 2 x NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXL-HD16-2-02 208-240V 60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXL-HD16-2-06 208-240V 60Hz 2 x NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 PTXL-HF16-1-02 100-120V 50/60Hz 2 x IEC 60320 C201 16 NEMA 5-20R PTXL-HF16-1-05 100-120V 50/60Hz 2 x NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXL-HF16-2-02 208-240V 60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXL-HF16-2-06 208-240V 60Hz 2 x NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 PTXL-V008-1-02 100-120V 50/60Hz IEC 60320 C201 8 NEMA 5-20R PTXL-V008-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 8 NEMA 5-20R PTXL-V008-2-02 208-240V 60Hz IEC 60320 C201 8 IEC 60320 C13 PTXL-V008-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 8 IEC 60320 C13 PTXL-V016-1-02 100-120V 50/60Hz IEC 60320 C201 16 NEMA 5-20R PTXL-V016-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXL-V016-2-02 208-240V 60Hz IEC 60320 C201 16 IEC 60320 C13 PTXL-V016-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13

Power Tower Expansion Module

Model Rated Voltage Input Cordset and Plug (10’) Outlets PTXM-H008-1-02 100-120V 50/60Hz IEC 60320 C201 8 NEMA 5-20R PTXM-H008-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 8 NEMA 5-20R PTXM-H008-2-02 208-240V 60Hz IEC 60320 C201 8 IEC 60320 C13 PTXM-H008-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 8 IEC 60320 C13 PTXM-H016-1-02 100-120V 50/60Hz IEC 60320 C201 16 NEMA 5-20R PTXM-H016-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXM-H016-2-02 208-240V 60Hz IEC 60320 C201 16 IEC 60320 C13 PTXM-H016-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 PTXM-HD16-1-02 100-120V 50/60Hz 2 x IEC 60320 C201 16 NEMA 5-20R PTXM-HD16-1-05 100-120V 50/60Hz 2 x NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXM-HD16-2-02 208-240V 60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXM-HD16-2-06 208-240V 60Hz 2 x NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 PTXM-HF16-1-02 100-120V 50/60Hz 2 x IEC 60320 C201 16 NEMA 5-20R PTXM-HF16-1-05 100-120V 50/60Hz 2 x NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXM-HF16-2-02 208-240V 60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXM-HF16-2-06 208-240V 60Hz 2 x NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 PTXM-V008-1-02 100-120V 50/60Hz IEC 60320 C201 8 NEMA 5-20R PTXM-V008-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 8 NEMA 5-20R PTXM-V008-2-02 208-240V 60Hz IEC 60320 C201 8 IEC 60320 C13 PTXM-V008-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 8 IEC 60320 C13 PTXM-V016-1-02 100-120V 50/60Hz IEC 60320 C201 16 NEMA 5-20R PTXM-V016-1-05 100-120V 50/60Hz NEMA L5-30P, 30A/120V locking 16 NEMA 5-20R PTXM-V016-2-02 208-240V 60Hz IEC 60320 C201 16 IEC 60320 C13 PTXM-V016-2-06 208-240V 60Hz NEMA L6-30P, 30A/208V locking 16 IEC 60320 C13 1 Input cordset selected at time of purchase

64 • Appendices Sentry Power Tower XL Installation and Operations Manual

Page 65: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

International Models

Power Tower XL

Model Rated Voltage Input Cordset and Plug (10’) Outlets PTXL-H008-2-02 230 50/60Hz IEC 60320 C201 8 IEC 60320 C13 PTXL-H016-2-02 230 50/60Hz IEC 60320 C201 16 IEC 60320 C13 PTXL-HD16-2-02 230 50/60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXL-HF16-2-02 230 50/60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXL-V008-2-02 230 50/60Hz IEC 60320 C201 8 IEC 60320 C13 PTXL-V016-2-02 230 50/60Hz IEC 60320 C201 16 IEC 60320 C13

Power Tower Expansion Module

Model Rated Voltage Input Cordset and Plug (10’) Outlets PTXM-H008-2-02 230 50/60Hz IEC 60320 C201 8 IEC 60320 C13 PTXM-H016-2-02 230 50/60Hz IEC 60320 C201 16 IEC 60320 C13 PTXM-HD16-2-02 230 50/60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXM-HF16-2-02 230 50/60Hz 2 x IEC 60320 C201 16 IEC 60320 C13 PTXM-V008-2-02 230 50/60Hz IEC 60320 C201 8 IEC 60320 C13 PTXM-V016-2-02 230 50/60Hz IEC 60320 C201 16 IEC 60320 C13 1 Input cordset selected at time of purchase

Sentry Power Tower XL Appendices • 65 Installation and Operations Manual

Page 66: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Power Ratings

Domestic Models

ls

Model Voltage Current Voltage Outlet Branch Circuit Phase TotalModele Tension Courrant Tension Prise Circuit de la Branche TotalModell Spannung Strom Spannung Anschlussstelle Zweigstromkreis Insgesamt

PTxx-x008-1-02 100-120V50/60Hz 16 100-120V

50/60Hz 16 16 16

PTxx-x008-1-05 100-120V50/60Hz 24 100-120V

50/60Hz 16 16 24

PTxx-x016-1-02 100-120V50/60Hz 16 100-120V

50/60Hz 16 16 16

PTxx-x016-1-05 100-120V50/60Hz 24 100-120V

50/60Hz 16 16 24

PTxx-xD16-1-02 100-120V50/60Hz

A: 16B: 16

100-120V50/60Hz 16 16 A: 16

B: 16

PTxx-xD16-1-05 100-120V50/60Hz

A: 24B: 24

100-120V50/60Hz 16 16 A: 24

B: 24

PTxx-xF16-1-02 100-120V50/60Hz 16 100-120V

50/60Hz 16 16 16

PTxx-xF16-1-05 100-120V50/60Hz 24 100-120V

50/60Hz 16 16 24

PTxx-x008-2-02 208-240V60Hz 16 208-240V

60Hz 12 16 16

PTxx-x008-2-06 208-240V60Hz 24 208-240V

60Hz 12 16 24

PTxx-x016-2-02 208-240V60Hz 16 208-240V

60Hz 12 16 16

PTxx-x016-2-06 208-240V60Hz 24 208-240V

60Hz 12 16 24

PTxx-xD16-2-02 208-240V60Hz

A: 16B: 16

208-240V60Hz 12 16 A: 16

B: 16

PTxx-xD16-2-06 208-240V60Hz

A: 24B: 24

208-240V60Hz 12 16 A: 24

B: 24

PTxx-xF16-2-02 208-240V60Hz 16 208-240V

60Hz 12 16 16

PTxx-xF16-2-06 208-240V60Hz 24 208-240V

60Hz 12 16 24

Eingangsstromstärke Ausgangsstromstärke

208-240V 60Hz

100-120V 50/60Hz

Input Current Ratings1 Output Current RatingsL’indice du courant d’entrée L’indice du courant de sortie

International Mode

1 All current ratings are in amperes. Tous les indices de courant sont en ampères. Alle Angaben der Stromstärke erfolgen in Ampere.

Model Voltage Current Voltage Outlet Branch Circuit Phase TotalModele Tension Courrant Tension Prise Circuit de la Branche TotalModell Spannung Strom Spannung Anschlussstelle Zweigstromkreis Insgesamt

PTxx-x008-2-02 230V 50/60Hz 16 230V

50/60Hz 12 16 16

PTxx-x016-2-02 230V 50/60Hz 16 230V

50/60Hz 12 16 16

PTxx-xD16-2-02 230V 50/60Hz

A: 16B: 16

230V 50/60Hz 12 16 A: 16

B: 16

PTxx-xF16-2-02 230V 50/60Hz 16 230V

50/60Hz 12 16 16

230V 50/60Hz

Current Ratings1 Output Current Ratingsdu courant d’entrée L’indice du courant de sortie

Input L’indice

Eingangsstromstärke Ausgangsstromstärke

66 • Appendices Sentry Power Tower XL Installation and Operations Manual

Page 67: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Physical Specifications

Operating Storage Temperature 32° to 122° F (0° to 50° C) -40° to 185° F (-40° to 85° C)

Elevation(above MSL) 0 to 10,000 ft (0 to 3000m) 0 to 50,000 ft (0 to 15000m)

Relative Humidity 10 to 90%, non-condensing 10 to 90%, non-condensing

Dimensions (H x W x D) Weight PTXx-V008 43.0 x 1.75 x 2.25 in. (1092 x 45 x 57 mm) 8.2 lbs (3.7 kg) PTXx-V016 65.0 x 1.75 x 2.25 in. (1651 x 45 x 57 mm) 13.2 lbs (6.0 kg) PTXx-Hx08 1.75 x 17.0 x 7.0 in. (45 x 432 x 178 mm) 8.2 lbs (3.7 kg) PTXx-Hx16 3.5 x 17.0 x 7.0 in. (89 x 432 x 178 mm) 11.8 lbs (5.4 kg)

Data Connections

RS-232 port Power Tower XLs are equipped standard with an RJ45 DTE RS-232c serial port. This connector may be used for direct local access or from other serial devices such as a terminal server. An RJ45 crossover cable is provided for connection to an RJ45 DCE serial port.

Pin DTE Signal Name Input/Output 1 Request to Send RTS Output

2 Data Terminal Ready DTR Output

3 Transmit Data TD Output

4 Signal Ground

5 Signal Ground

6 Receive Data RD Input

7 Data Set Ready DSR Input

8 Clear to Send CTS Input

RJ45 to DB9F serial port adapter Additionally, an RJ45 to DB9F serial port adapter is provided for use in conjunction with the RJ45 crossover cable to connect to a PC DB9M DCE serial port. The adapter pinouts below reflect use of the adapter with the provided RJ45 crossover cable.

Pin DCE Signal Name Input/Output 1

2 Receive Data RD Output

3 Transmit Data TD Input

4 Data Terminal Ready DTR Input

5 Signal Ground

6 Data Set Ready DSR Output

7 Request to Send RTS Input

8 Clear to Send CTS Output

67 543218

12345

6789

Sentry Power Tower XL Appendices • 67 Installation and Operations Manual

Page 68: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Modem Port Power Tower XLs are equipped standard with a DB9-male RS-232C DTE Modem serial port. This connector is typically used to connect to an external modem, but may also be used to connect to any RS-232C device. A 9-pin female to 25-pin male cable is included for connecting the Power Tower XLs to an external modem.

Pin DTE Signal Name Input/Output 1 Data Carrier Detect DCD Input

2 Receive Data RD Input

3 Transmit Data TD Output

4 Data Terminal Ready DTR Output

5 Signal Ground

6 Data Set Ready DSR Input

7 Request to Send RTS Output

8 Clear to Send CTS Input

NOTE: To connect to a PC serial port, a null-modem adapter and a female-to-female gender changer are required in addition to the included cable.

LED Indicators Units are equipped with a status LED for each power receptacle. A lit/on LED indicates that power is being supplied at the port and a darkened/off LED indicates that there is no power at the port.

1 2 3 4 5

6 7 8 9

68 • Appendices Sentry Power Tower XL Installation and Operations Manual

Page 69: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Regulatory Compliance

Product Safety Units have been safety tested and certified to the following standards:

• USA/Canada UL 60950:2003 and CAN/CSA 22.2 No. 60950-1-03 • European Union EN60950-1:2001

This product is also designed for Norwegian IT power system with phase-to phase voltage 230V.

USA Notification Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Modifications not expressly approved by the manufacturer could void the user's authority to operated the equipment under FCC rules.

Canadian Notification This Class A digital apparatus complies meets all requirements of the Canadian Interference-Causing Equipment Regulations.

Cet appareil numérique de la classe A respecte toutes les exigencies du Règlement sur le matériel brouilleur du Canada.

European Union Notification Products with the CE Marking comply with both the EMC Directive (89/336/EEC) and the Low Voltage Directive (73/23/EEC) issued by the Commission of the European Community.

Compliance with these directives implies conformity to the following European Norms:

• EN55022 Electromagnetic Interference • EN55024 Electromagnetic Immunity • EN60950-1 Product Safety • EN61000-3 Harmonics and Flicker

Japanese Notification

この装置は、情報処理装置等電波障害自主規制協議会(VCCI)の基準に基づくクラスA情報技術装置です。この装置を家庭環境で使用すると電波妨害を引き起こすことがあります。この場合には使用者が適切な対策を講ずるよう要求されることがあります。

Sentry Power Tower XL Appendices • 69 Installation and Operations Manual

Page 70: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Appendix D: Warranty, Product Registration and Support Warranty and Limitation of Liability

Server Technology, Inc. agrees to repair or replace Products that fail due to a defect within twelve (12) months after the shipment date of each Product unit to Buyer (“Warranty Period”). For purposes of this Agreement the term “defect” shall mean the Product fails to operate or fails to conform to its applicable specifications. Any claim made pursuant to this Agreement shall be asserted or made in writing only by Buyer. Buyer shall comply with Server Technology’s Standard Return Merchandise Authorization (“RMA”) procedure for all warranty claims as set forth in Server Technology’s operation manual. Buyer must return Products in original packaging and in good condition. This limited warranty does not include labor, transportation, or other expenses to repair or reinstall warranted Products on site or at Buyer’s premises.

Server Technology reserves the right to investigate any warranty claims to promptly resolve the problem or to determine whether such claims are proper. In the event that after repeated efforts Server Technology is unable to repair or replace a defective Product, then Buyer’s exclusive remedy and Server Technology’s entire liability in contract, tort, or otherwise shall be the payment by Server Technology of Buyer’s actual damages after mitigation, but shall not exceed the purchase price actually paid by Buyer for the defective Product.

Server Technology shall have no responsibility or liability for any Product, or part thereof, that (a) has had the Serial Number, Model Number, or other identification markings altered, removed or rendered illegible; (b) has been damaged by or subject to improper installation or operation, misuse, accident, neglect and/or has been used in any way other than in strict compliance with Server Technology’s operation and installation manual; (c) has become defective or inoperative due to its integration or assembly with any equipment or products not supplied by Server Technology; (d) has been repaired, modified or otherwise altered by anyone other than Server Technology and/or has been subject to the opening of any sealed cabinet boxes without Server Technology’s prior written consent. If any warranty claim by Buyer falls within any of the foregoing exceptions, Buyer shall pay Server Technology its then current rates and charges for such services.

THE ABOVE WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ALL OF WHICH ARE EXPRESSLY DISCLAIMED. SERVER SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, SPECIAL, OR EXEMPLARY DAMAGES; EVEN OF IT HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.

For warranty issues, contact the Product Support Department at the number listed above. All repair and return shipments must be approved by Server and must be accompanied by a RMA (Return Merchandise Authorization) number and dated proof of purchase.

Product Registration Registration is your key to special offers and services reserved for Registered Users.

• Excellent Technical Support Services • Special Update and Upgrade Programs • Warranty Protection • Extended Warranty Service • New Product Information

Register your products online today!

www.servertech.com

70 • Appendices Sentry Power Tower XL Installation and Operations Manual

Page 71: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Technical Support Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is provided from 8:30 AM to 5:00 PM, Monday-Friday, Pacific Time.

Server Technology, Inc. 1040 Sandhill Drive Tel: 775.284.2000 Web: www.servertech.com Reno, Nevada 89521 USA Fax: 775.284.2065 Email: [email protected]

Return Merchandise Authorization If you have a unit that is not functioning properly and is in need of technical assistance or repair:

Submit a request for support by phone at the above number, or via the web at www.servertech.com/support

Be ready to provide: Company Name Contact Name, Phone Number, and Email address Model or Part Number (from the label on the equipment) Server Technology Serial Number Version of firmware Description of problem

1. Technical Support will work to diagnose/resolve the problem remotely, if possible. If the problem cannot be resolved, Technical Support will then issue an RMA# for the return/repair of the equipment in question. RMA#’s are valid for 30 days only from the issue date.

2. Shipping charges for the return of the equipment to Server Technology shall be the responsibility of the customer. For warranty repairs, Server Technology shall assume return shipping charges but for non-warranty repairs, the shipping charges shall be billed.

3. The RMA# shall be placed conspicuously on all shipping documentation, associated correspondence, and the shipping container.

4. Equipment must be returned in proper/original packaging to protect the equipment in transit. The customer shall be financially responsible for any damage/destruction of the equipment due to improper packaging.

5. Equipment shall typically be turned around within 48-72 hours of receipt at Server Technology. Equipment under warranty shall be repaired at no cost. Equipment NOT under warranty shall be repaired at the standard labor rate plus parts. Upon diagnosis of the equipment, the customer shall be notified of estimated charges prior to repair.

6. For non-warranty repairs, return of the equipment will be expedited with the inclusion of a Purchase Order or credit card number for incurred charges.

Sentry Power Tower XL Appendices • 71 Installation and Operations Manual

Page 72: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower
Page 73: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower
Page 74: Sentry - 42U: Cooling, Power, Monitoring & Server … • Installation Sentry Power Tower XL Installation and Operations Manual . Attaching the Expansion Module Connect the Power Tower

Solutions for the Data Center Equipment Cabinet Server Technology, Inc. +1.800.835.1515 TF 1040 Sandhill Drive +1.775.284.2000 Tel Reno, NV 89521 +1.775.284.2065 Fax www.servertech.com [email protected]

Sentry, Power Tower, Power Tower XL, Power Tower XM, Environmental Monitoring Control Unit and Pass-Thru are trademarks of Server Technology, Inc. Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Server Technology, Inc. disclaims any proprietary interest in trademarks and trade names other than its own. 301-0120-3 Rev. G (050505) © 2003-2005 Server Technology, Inc. All rights reserved.