Velo Track Designed to 15-22 lux, 0.4 Uo (as requested) Car Park Designed to 10 lux, 0.25 Uo Medium Use Car Park. MF 0.83 - Performance Results MF 1.0 - Spill Lighting (Worst case when new) Column height 5m (as requested) All luminaires are Post Top Mounted on 5m columns at 0 degree tilt. Luminaires used are all LumiStreet GEN 2. Extra Warm White 2200k. 2200k used to reduce influence to small Mammels reducing environmental impact Colour Rendition 70 Ra 83 No fittings used in total for Both Phases Phase 1 52 No DX10 fittings used for Phase 1 Velo Track 16 No DW50 fittings used for Phase 1 Car Park 68 No fittings used in Phase 1 Phase 2 15 No DX10 fittings used for Phase 2 Velo Track Velo Track Luminaires are LumiStreet GEN 2 BGP292 DX10 BL2 1xLED-HB 9 Klm 5.2S 722 BL2 full cut off internal louvres fitted to all Velo Track fittings for full light cut off behind luminaire Car Park Luminaires are LumiStreet GEN 2 BGP292 DW50 BL1 1xLED-HB 6.4 Klm 5.2S 722 BL Semi cut off internal louvres fitted to all Car Park fittings for semi light cut off behind luminaire This shceme is to be carried out in two Phases, with the Majority of the track & Car Park in Phase 1 and the extension loop to the right in Phase 2 This scheme shows results for Phase 1 & 2 If no motor access is available for future maintenance, the Raise & Lower columns are recommended. Spill Isolux values shown are 0.1,0.5,1.0,1.5,2.0,2.5 & 3.0 lux values 5m columns with 6.4 Klm Mini LumiStreet BGP292 G2 DW50 70 Ra 2200k LED fitting - 56w 5m columns with 9 Klm Mini LumiStreet G2 BGP292 DX10 70 Ra 2200k LED fitting - 79w LiAS Design Notes This preliminary design is produced by the Lighting Application Specialist (LiAS) team of Signify UK based on information supplied by the Customer for the purpose of identifying suitable products and costing the proposal. This design cannot be used for Construction, as this design does not purport to eliminate health and safety risks as a CDM Regulation risk assessment has not been undertaken. Depending on the level of information received, a number of assumptions may have been applied in order to create an indicative lighting proposal and costing model, according to lighting industry guidelines and incorporating industry best practice methods. These assumptions are documented below and will require confirmation by the Principle Designer (which is not Signify UK) during the detailed design phase. Project Specific Assumptions See Opposite Generic Assumptions (unless specifically informed differently) x Preliminary Design proposals produced by the Signify LiAS Team are not to be used for installation purposes. It is the responsibility of the Principle Designer and/or Principle Contractor to ensure all Installation and Maintenance can be done in a safe manner, carried out by competent persons, based on their agreed Risk Assessments and Method Statements. x The Luminaire Maintenance Factors have been based on 6-year cleaning intervals within an E3/E4 Environmental Zone and it is assumed that lamp/luminaire failures will be replaced on a 'spot replacement'. x Energy consumptions have been based on the luminaire/s having Constant Light Output (CLO) enabled and the quoted wattage/s are the average over 100,000 hours (without dimming). x The design calculations produced by Signify do not account for the effect obstructions, such as trees, will cause. x Signify has not been provided with utility plans showing Buried, Above Ground or Overhead utilities. Therefore, all column/luminaire locations are indicative and are subject to review/verification by the Principle Designer. x Unless stated otherwise, Signify has not visited site. Therefore, all column/luminaire locations are indicative and are subject to an onsite verification arranged/performed by the Principle Designer. x Signify has not produced any Private Cable Network electrical calculations or reviewed the DNO network to confirm power supplies to the proposed lighting. x Signify has not performed any asset condition testing and therefore assumes that any existing lighting columns/wall mounted brackets are structurally capable of supporting the weight & windage of the proposed luminaire/s. This must be verified by the Principle Designer before installation works commence. x Unless stated otherwise, Signify is not supplying the new lighting columns (including brackets etc) and therefore it is the responsibility of the Principle Designers to confirm that all proposed equipment is suitable for the intended locations (e.g. raise & lower, ground condition, foundation type, saline environment, etc). x Unless stated otherwise, luminaires will be supplied in their standard colour. Luminaire Schedule Project Name Drawing Name LiAS DESIGN NOTES & LUMINAIRE SCHEDULE PROPOSAL (NOT FOR CONSTRUCTION) Scale & Sheet Size NTS @ A3 Sheet No DWG 00 Project Number Lighting Proposal Terms and Conditions of Use These terms apply to the use of this preliminary proposal produced by Signify UK. This “Proposal” is understood to mean this document, a CAD drawing, lighting calculations, written documents, verbal conversations or any medium used to demonstrate or communicate the proposed lighting scheme using products from Signify's brands. A “Customer” is the person or organisation for whom the Proposal is intended. The “CDM Regulations” means The Construction, Design and Management Regulations 2015, the Safety, Health & Welfare at Work Act 2005, The Construction (Design & Management) Regulations (Northern Ireland) 2015. This Proposal is for guidance only and cannot be relied upon for purposes of installation or Health and Safety. The supply and installation of this lighting scheme are subject to a contract being agreed between Customer and Signify. Abergavenny Velo Park, Wales - Phase 1 Rev DSR no. Comment Date 0 D-349772 8m scheme to 30 lux ave, 0.4 Uo 02/04/20 KAM LiAS AP SJ 400448639 1 D-363152 6m LumiStreet G2 BL2 LO scheme to 30 lux ave, 0.4 Uo 20/07/20 AP SJ 2 D-363984 27/07/20 AP SJ 3 D-370992 Change to Warm White 3000k 25/09/20 AP SJ 5m LumiStreet G2 BL2 scheme to 15-22 lux ave, 0.4 Uo WW 2200k Signify Lighting Contacts Andy Poplett, Key Account Manager - 07810 832266 - [email protected]

Upload: others

Post on 19-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Signify Lighting Contacts · BGP292 DX10 70 Ra 2200k LED fitting - 79w LiAS Design Notes This preliminary design is produced by the Lighting Application Specialist (LiAS) team of

Velo Track Designed to 15-22 lux, 0.4 Uo (asrequested)Car Park Designed to 10 lux, 0.25 Uo MediumUse Car Park.MF 0.83 - Performance ResultsMF 1.0 - Spill Lighting (Worst case whennew)Column height 5m (as requested)All luminaires are Post Top Mounted on 5mcolumns at 0 degree tilt.Luminaires used are all LumiStreet GEN 2.Extra Warm White 2200k. 2200k usedto reduce influence to small Mammelsreducing environmental impactColour Rendition 70 Ra

83 No fittings used in total for Both PhasesPhase 152 No DX10 fittings used for Phase 1 VeloTrack16 No DW50 fittings used for Phase 1 CarPark68 No fittings used in Phase 1

Phase 215 No DX10 fittings used for Phase 2 VeloTrack

Velo Track Luminaires areLumiStreet GEN 2 BGP292 DX10 BL21xLED-HB 9 Klm 5.2S 722BL2 full cut off internal louvres fitted to all VeloTrack fittings for full light cut off behindluminaire

Car Park Luminaires areLumiStreet GEN 2 BGP292 DW50 BL11xLED-HB 6.4 Klm 5.2S 722BL Semi cut off internal louvres fitted to allCar Park fittings for semi light cut off behindluminaire

This shceme is to be carried out in twoPhases, with the Majority of the track &Car Park in Phase 1 and the extension loop tothe right in Phase 2

This scheme shows results for Phase 1 & 2

If no motor access is available for futuremaintenance, the Raise & Lowercolumns are recommended.

Spill Isolux values shown are0.1,0.5,1.0,1.5,2.0,2.5 & 3.0 lux values

5m columns with 6.4 Klm Mini LumiStreetBGP292 G2 DW50 70 Ra 2200k LED fitting - 56w

5m columns with 9 Klm Mini LumiStreet G2BGP292 DX10 70 Ra 2200k LED fitting - 79w

LiAS Design NotesThis preliminary design is produced by the Lighting Application Specialist (LiAS) team of Signify UK based oninformation supplied by the Customer for the purpose of identifying suitable products and costing the proposal.This design cannot be used for Construction, as this design does not purport to eliminate health and safety risks as aCDM Regulation risk assessment has not been undertaken.

Depending on the level of information received, a number of assumptions may have been applied in order to createan indicative lighting proposal and costing model, according to lighting industry guidelines and incorporatingindustry best practice methods. These assumptions are documented below and will require confirmation by thePrinciple Designer (which is not Signify UK) during the detailed design phase.

Project Specific AssumptionsSee Opposite

Generic Assumptions (unless specifically informed differently)x Preliminary Design proposals produced by the Signify LiAS Team are not to be used for installation purposes. It is the

responsibility of the Principle Designer and/or Principle Contractor to ensure all Installation and Maintenance can bedone in a safe manner, carried out by competent persons, based on their agreed Risk Assessments and MethodStatements.

x The Luminaire Maintenance Factors have been based on 6-year cleaning intervals within an E3/E4 Environmental Zoneand it is assumed that lamp/luminaire failures will be replaced on a 'spot replacement'.

x Energy consumptions have been based on the luminaire/s having Constant Light Output (CLO) enabled and the quotedwattage/s are the average over 100,000 hours (without dimming).

x The design calculations produced by Signify do not account for the effect obstructions, such as trees, will cause.

x Signify has not been provided with utility plans showing Buried, Above Ground or Overhead utilities. Therefore, allcolumn/luminaire locations are indicative and are subject to review/verification by the Principle Designer.

x Unless stated otherwise, Signify has not visited site. Therefore, all column/luminaire locations are indicative and aresubject to an onsite verification arranged/performed by the Principle Designer.

x Signify has not produced any Private Cable Network electrical calculations or reviewed the DNO network to confirmpower supplies to the proposed lighting.

x Signify has not performed any asset condition testing and therefore assumes that any existing lighting columns/wallmounted brackets are structurally capable of supporting the weight & windage of the proposed luminaire/s. This must beverified by the Principle Designer before installation works commence.

x Unless stated otherwise, Signify is not supplying the new lighting columns (including brackets etc) and therefore it is theresponsibility of the Principle Designers to confirm that all proposed equipment is suitable for the intended locations (e.g.raise & lower, ground condition, foundation type, saline environment, etc).

x Unless stated otherwise, luminaires will be supplied in their standard colour.

Luminaire Schedule

Project Name

Drawing Name

LiAS DESIGN NOTES &LUMINAIRE SCHEDULE

PROPOSAL(NOT FOR CONSTRUCTION)

Scale & Sheet Size

NTS @ A3Sheet No

DWG 00

Project NumberLighting Proposal Terms and Conditions of UseThese terms apply to the use of this preliminary proposal produced by Signify UK. This “Proposal” is understood to mean this document, a CADdrawing, lighting calculations, written documents, verbal conversations or any medium used to demonstrate or communicate the proposed lightingscheme using products from Signify's brands. A “Customer” is the person or organisation for whom the Proposal is intended. The “CDMRegulations” means The Construction, Design and Management Regulations 2015, the Safety, Health & Welfare at Work Act 2005, TheConstruction (Design & Management) Regulations (Northern Ireland) 2015.

This Proposal is for guidance only and cannot be relied upon for purposes of installation or Health and Safety.The supply and installation of this lighting scheme are subject to a contract being agreed between Customer and Signify.

Abergavenny Velo Park,Wales - Phase 1

Rev DSR no. Comment Date0 D-349772 8m scheme to 30 lux ave, 0.4 Uo 02/04/20

KAMLiASAPSJ

4004486391 D-363152 6m LumiStreet G2 BL2 LO scheme to 30 lux ave, 0.4 Uo 20/07/20 APSJ2 D-363984 27/07/20 APSJ3 D-370992

Change to Warm White 3000k25/09/20 APSJ5m LumiStreet G2 BL2 scheme to 15-22 lux ave, 0.4 Uo WW 2200k

Signify Lighting ContactsAndy Poplett, Key Account Manager - 07810 832266 - [email protected]

Page 2: Signify Lighting Contacts · BGP292 DX10 70 Ra 2200k LED fitting - 79w LiAS Design Notes This preliminary design is produced by the Lighting Application Specialist (LiAS) team of

Road

1

Road 3

Road 4

Ex G

as Pi

pelin

e

PROWPath 1

L.P. 56.670

L.P. 53.752

L.P. 5

5.856

H.P.

55.85

6

H.P.

58.48

0

H.P. 62.144

H.P. 59.669

H.P.

56.44

1

L.P. 46.306

L.P. 48.700

H.P.

56.00

6

H.P.

58.55

8

H.P. 61.843

H.P. 59.969

H.P.

56.59

1

L.P. 56.276

H.P. 55.479

L.P. 55.359

55.886

55.286

54.686

54.136

53.536

53.002

52.384

51.781

51.18

1

50.50

0

50.022

49.811

49.13

2

48.549

48.035

47.535

47.035

46.591

46.314

46.23

6

46.25

3

46.34

3

46.57

3

46.97

3

47.542

48.281

49.132

49.986

50.840

51.694

52.548

53.402

54.256

55.110

55.964

56.818

57.662

58.248

58.486

58.310

57.910

57.510

57.70

2

58.60

0

59.57

5

60.57

3

61.35

3

61.733

61.712

61.292

60.473

59.473

58.473

57.473

56.473

55.49

7

54.745

54.355

54.209

54.034

53.848

53.914

54.326

57.64

3

58.47

6 59.309

59.868

59.720

58.892

57.842

53.980

53.550

53.365

53.183

53.001

52.788

52.384

51.762

50.930

50.555

50.110

49.445

49.026

48.73

6

48.616

48.717

48.925

48.997

49.383

49.863

50.489

51.155

51.822

52.489

53.155

53.822

55.902

55.982

56.062

56.142

56.222

56.302

56.382

56.432

56.442

56.111

55.886

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0 100.0

110.0

120.0

130.0

140.0

150.0

160.0

170.0

180.0

190.0

200.0

210.0

220.0

230.0

240.0

250.0

260.0

270.0

280.0

290.0

300.0

310.0

320.0

330.0

340.0

350.0

360.0

370.0

380.0

390.0

400.0

410.0

420.0

430.0

440.0

450.0

460.0

470.0

480.0

490.0

500.0

510.0

520.0

530.0

540.0

550.0 560.0

570.0

580.0

590.0

600.0

610.0

620.0

630.0

640.0

650.0

660.0

670.0

680.0 690.0

700.0

710.0

720.0

730.0

740.0

750.0

760.0

770.0

780.0

790.0

800.0

810.0

820.0

830.0

840.0

850.0

860.0

870.0

880.0

890.0

900.0

910.0

920.0

930.0

940.0

950.0

960.0

970.0

980.0

990.0

1000.0

1010.0

1020.0

1030.0

1040.0

1050.0

1060.0

1070.0

1080.0

1090.0

1100.0

1110.0

1120.0

1130.0

1133.8

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

100.0

110.0

120.0

130.0

140.0

150.0

160.0

170.0

180.0

190.0

200.0

210.0

220.0

230.0

240.0

250.0

260.0

270.0

280.0

290.0

300.0

310.0

320.0

330.0

340.0

350.0

360.0

370.0

380.0

390.0

400.0

410.0

420.0

430.0

440.0

450.0

460.0

470.0

480.0

490.0

500.0

20.0

19.9

20.0

20.0

20.0

19.8

20.0

19.9

20.1

19.9

19.9

20.1

19.8

19.9

19.6

16.3

16.0

12.0

13.318.3

18.3

17.7

17.6

18.0

19.8

19.9

20.1

20.5

19.8

20.0

21.4

20.3

17.7

17.6

20.2

18.9

19.9

19.8

17.7

18.2

17.5

17.7 19.4

19.9

19.8

17.7

15.9

13.614.6

13.6

12.5

19.7

20.3

19.7

20.3

19.2

17.2

17.517.8

17.0

17.1

20.4

20.3

Velo Track Designed to 15-22 lux, 0.4 Uo (asrequested)Car Park Designed to 10 lux, 0.25 Uo MediumUse Car Park.MF 0.83 - Performance ResultsMF 1.0 - Spill Lighting (Worst case whennew)Column height 5m (as requested)All luminaires are Post Top Mounted on 5mcolumns at 0 degree tilt.Luminaires used are all LumiStreet GEN 2.Extra Warm White 2200k. 2200k usedto reduce influence to small Mammelsreducing environmental impactColour Rendition 70 Ra

83 No fittings used in total for Both PhasesPhase 152 No DX10 fittings used for Phase 1 VeloTrack16 No DW50 fittings used for Phase 1 CarPark68 No fittings used in Phase 1

Phase 215 No DX10 fittings used for Phase 2 VeloTrack

Velo Track Luminaires areLumiStreet GEN 2 BGP292 DX10 BL21xLED-HB 9 Klm 5.2S 722BL2 full cut off internal louvres fitted to all VeloTrack fittings for full light cut off behindluminaire

Car Park Luminaires areLumiStreet GEN 2 BGP292 DW50 BL11xLED-HB 6.4 Klm 5.2S 722BL Semi cut off internal louvres fitted to allCar Park fittings for semi light cut off behindluminaire

This shceme is to be carried out in twoPhases, with the Majority of the track &Car Park in Phase 1 and the extension loop tothe right in Phase 2

This scheme shows results for Phase 1 & 2

If no motor access is available for futuremaintenance, the Raise & Lowercolumns are recommended.

Spill Isolux values shown are0.1,0.5,1.0,1.5,2.0,2.5 & 3.0 lux values

5m columns with 6.4 Klm Mini LumiStreetBGP292 G2 DW50 70 Ra 2200k LED fitting - 56w

5m columns with 9 Klm Mini LumiStreet G2BGP292 DX10 70 Ra 2200k LED fitting - 79w

N

Project Name

Drawing Name

5m LumiStreet G2 LED15-22 lux Ave, 0.4 Uo - R3

PROPOSAL(NOT FOR CONSTRUCTION)

Notes:

1) Unless agreed otherwise, the lighting proposal produced by the Lighting Application Specialist (LiAS) team of Signify UK&I is not intended forconstruction purposes, as it does not take into account the elimination of health and safety risks at this stage. For further details please referto sheet number DWG 00

2) Do not scale for this drawing

Scale & Sheet Size

1:500 @ A1Sheet No

DWG 01

Project Number

Key:

Abergavenny Velo Park,Wales - Phase 1

Rev DSR no. Comment Date0 D-349772 8m scheme to 30 lux ave, 0.4 Uo 02/04/20

KAMLiASAPSJ 4004486391 D-363152 6m LumiStreet G2 BL2 LO scheme to 30 lux ave, 0.4 Uo 20/07/20 APSJ

2 D-363984 27/07/20 APSJ3 D-370992

Change to Warm White 3000k25/09/20 APSJ5m LumiStreet G2 BL2 scheme to 15-22 lux ave, 0.4 Uo WW 2200k

Page 3: Signify Lighting Contacts · BGP292 DX10 70 Ra 2200k LED fitting - 79w LiAS Design Notes This preliminary design is produced by the Lighting Application Specialist (LiAS) team of

Road

1

Road 3

Road 4

Ex G

as Pi

pelin

e

PROWPath 1

L.P. 56.670

L.P. 53.752

L.P. 5

5.856

H.P.

55.85

6

H.P.

58.48

0

H.P. 62.144

H.P. 59.669

H.P.

56.44

1

L.P. 46.306

L.P. 48.700

H.P.

56.00

6

H.P.

58.55

8

H.P. 61.843

H.P. 59.969

H.P.

56.59

1

L.P. 56.276

H.P. 55.479

L.P. 55.359

55.886

55.286

54.686

54.136

53.536

53.002

52.384

51.781

51.18

1

50.50

0

50.022

49.811

49.13

2

48.549

48.035

47.535

47.035

46.591

46.314

46.23

6

46.25

3

46.34

3

46.57

3

46.97

3

47.542

48.281

49.132

49.986

50.840

51.694

52.548

53.402

54.256

55.110

55.964

56.818

57.662

58.248

58.486

58.310

57.910

57.510

57.70

2

58.60

0

59.57

5

60.57

3

61.35

3

61.733

61.712

61.292

60.473

59.473

58.473

57.473

56.473

55.49

7

54.745

54.355

54.209

54.034

53.848

53.914

54.326

57.64

3

58.47

6 59.309

59.868

59.720

58.892

57.842

53.980

53.550

53.365

53.183

53.001

52.788

52.384

51.762

50.930

50.555

50.110

49.445

49.02648

.736

48.616

48.717

48.925

48.997

49.383

49.863

50.489

51.155

51.822

52.489

53.155

53.822

55.902

55.982

56.062

56.142

56.222

56.302

56.382

56.432

56.442

56.111

55.886

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0 100.0

110.0

120.0

130.0

140.0

150.0

160.0

170.0

180.0

190.0

200.0

210.0

220.0

230.0

240.0

250.0

260.0

270.0

280.0

290.0

300.0

310.0

320.0

330.0

340.0

350.0

360.0

370.0

380.0

390.0

400.0

410.0

420.0

430.0

440.0

450.0

460.0

470.0

480.0

490.0

500.0

510.0

520.0

530.0

540.0

550.0 560.0

570.0

580.0

590.0

600.0

610.0

620.0

630.0

640.0

650.0

660.0

670.0

680.0 690.0

700.0

710.0

720.0

730.0

740.0

750.0

760.0

770.0

780.0

790.0

800.0

810.0

820.0

830.0

840.0

850.0

860.0

870.0

880.0

890.0

900.0

910.0

920.0

930.0

940.0

950.0

960.0

970.0

980.0

990.0

1000.0

1010.0

1020.0

1030.0

1040.0

1050.0

1060.0

1070.0

1080.0

1090.0

1100.0

1110.0

1120.0

1130.0

1133.8

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

100.0

110.0

120.0

130.0

140.0

150.0

160.0

170.0

180.0

190.0

200.0

210.0

220.0

230.0

240.0

250.0

260.0

270.0

280.0

290.0

300.0

310.0

320.0

330.0

340.0

350.0

360.0

370.0

380.0

390.0

400.0

410.0

420.0

430.0

440.0

450.0

460.0

470.0

480.0

490.0

20.0

19.9

20.0

20.0

20.0

19.8

20.0

19.9

20.1

19.9

19.9

20.1

19.8

19.9

19.6

16.3

16.0

12.0

13.318.3

18.3

17.7

17.6

18.0

19.8

19.9

20.1

20.5

19.8

20.0

21.4

20.3

17.7

17.6

20.2

18.9

19.9

19.8

17.7

18.2

17.5

17.7 19.4

19.9

19.8

17.7

15.9

13.614.6

13.6

12.5

19.7

20.3

19.7

20.3

19.2

17.2

17.517.8

17.0

17.1

20.4

20.3

Velo Track Designed to 15-22 lux, 0.4 Uo (asrequested)Car Park Designed to 10 lux, 0.25 Uo MediumUse Car Park.MF 0.83 - Performance ResultsMF 1.0 - Spill Lighting (Worst case whennew)Column height 5m (as requested)All luminaires are Post Top Mounted on 5mcolumns at 0 degree tilt.Luminaires used are all LumiStreet GEN 2.Extra Warm White 2200k. 2200k usedto reduce influence to small Mammelsreducing environmental impactColour Rendition 70 Ra

83 No fittings used in total for Both PhasesPhase 152 No DX10 fittings used for Phase 1 VeloTrack16 No DW50 fittings used for Phase 1 CarPark68 No fittings used in Phase 1

Phase 215 No DX10 fittings used for Phase 2 VeloTrack

Velo Track Luminaires areLumiStreet GEN 2 BGP292 DX10 BL21xLED-HB 9 Klm 5.2S 722BL2 full cut off internal louvres fitted to all VeloTrack fittings for full light cut off behindluminaire

Car Park Luminaires areLumiStreet GEN 2 BGP292 DW50 BL11xLED-HB 6.4 Klm 5.2S 722BL Semi cut off internal louvres fitted to allCar Park fittings for semi light cut off behindluminaire

This shceme is to be carried out in twoPhases, with the Majority of the track &Car Park in Phase 1 and the extension loop tothe right in Phase 2

This scheme shows results for Phase 1 & 2

If no motor access is available for futuremaintenance, the Raise & Lowercolumns are recommended.

Spill Isolux values shown are0.1,0.5,1.0,1.5,2.0,2.5 & 3.0 lux values

5m columns with 6.4 Klm Mini LumiStreetBGP292 G2 DW50 70 Ra 2200k LED fitting - 56w

5m columns with 9 Klm Mini LumiStreet G2BGP292 DX10 70 Ra 2200k LED fitting - 79w

N

Project Name

Drawing Name

5m LumiStreet G2 LEDSpill Lighting Results

PROPOSAL(NOT FOR CONSTRUCTION)

Notes:

1) Unless agreed otherwise, the lighting proposal produced by the Lighting Application Specialist (LiAS) team of Signify UK&I is not intended forconstruction purposes, as it does not take into account the elimination of health and safety risks at this stage. For further details please referto sheet number DWG 00

2) Do not scale for this drawing

Scale & Sheet Size

1:1000 @A1Sheet No

DWG 02

Project Number

Key:

Abergavenny Velo Park,Wales - Phase 1

Rev DSR no. Comment Date0 D-349772 8m scheme to 30 lux ave, 0.4 Uo 02/04/20

KAMLiASAPSJ 4004486391 D-363152 6m LumiStreet G2 BL2 LO scheme to 30 lux ave, 0.4 Uo 20/07/20 APSJ

2 D-363984 27/07/20 APSJ3 D-370992

Change to Warm White 3000k25/09/20 APSJ5m LumiStreet G2 BL2 scheme to 15-22 lux ave, 0.4 Uo WW 2200k