single conductor power cables - Üntel · 2019. 11. 28. · off-shore oil rings. the cables are...

2
ÜNTEL OFFSHORE CABLES 12 Single Conductor Power Cables DESIGN Conductor Separation Tape Insulation/Jacket Outer Sheath Color Reference Standard Temperature Rating Flame Retardant Cold Bend/Impact Physical Characteristics These cables are intended for use as control and power cables aboard ship and on off-shore oil rings. The cables are constructed in accordance with the recommended practice for marine cable for use on fixed or floating facilities, IEEE 1580. Excellent resistance to oil, abrasion petrochem fluids, moisture salty water and sunlight. Soft annealed stranded bare or tinned copper per IEEE1580 Polyester tape if required Type P flame retardant cross-linked polyolefin compound, X110 meeting the requirements for IEEE 1580 Type P and UL1309 Black IEEE 1580, UL 1309, CSA C22.2 No.245 Untel 125°C / UL CSA 110°C / IEEE 100°C IEEE 1202 & IEC 60332-3 cat. A -40°C / -35°C (CSA 22.2 No.03) 2kV Unarmoured Size AWG Diameter (inches) Weight (lbs/Mft) 110ºC A 100ºC A 18 0,232 29 17 16 16 0,245 34 24 23 14 0,259 42 39 37 12 0,281 53 49 45 10 0,302 68 61 58 8 0,354 95 77 72 6 0,384 130 100 96 4 0,484 210 134 128 2 0,576 314 178 169 1 0,629 393 205 194 1/0 0,687 485 236 227 2/0 0,737 596 274 262 3/0 0,788 709 317 300

Upload: others

Post on 08-Mar-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Single Conductor Power Cables - Üntel · 2019. 11. 28. · off-shore oil rings. The cables are constructed in accordance with the recommended practice for marine cable for use on

ÜNTEL OFFSHORE CABLES12

Single Conductor Power Cables

DESIGNConductorSeparation TapeInsulation/Jacket

Outer Sheath ColorReference StandardTemperature RatingFlame RetardantCold Bend/Impact

Physical Characteristics

These cables are intended for use as control and power cables aboard ship and on off-shore oil rings. The cables are constructed in accordance with the recommended practice for marine cable for use on fixed or floating facilities, IEEE 1580. Excellent resistance to oil, abrasion petrochem fluids, moisture salty water and sunlight.

Soft annealed stranded bare or tinned copper per IEEE1580Polyester tape if requiredType P flame retardant cross-linked polyolefin compound, X110meeting the requirements for IEEE 1580 Type P and UL1309BlackIEEE 1580, UL 1309, CSA C22.2 No.245Untel 125°C / UL CSA 110°C / IEEE 100°CIEEE 1202 & IEC 60332-3 cat. A-40°C / -35°C (CSA 22.2 No.03)

2kV Unarmoured

SizeAWG

Diameter (inches)

Weight(lbs/Mft)

110ºCA

100ºCA

18 0,232 29 17 16

16 0,245 34 24 23

14 0,259 42 39 37

12 0,281 53 49 45

10 0,302 68 61 58

8 0,354 95 77 72

6 0,384 130 100 96

4 0,484 210 134 128

2 0,576 314 178 169

1 0,629 393 205 194

1/0 0,687 485 236 227

2/0 0,737 596 274 262

3/0 0,788 709 317 300

Page 2: Single Conductor Power Cables - Üntel · 2019. 11. 28. · off-shore oil rings. The cables are constructed in accordance with the recommended practice for marine cable for use on

ÜNTEL OFFSHORE CABLES 13ÜNTEL OFFSHORE CABLES 13