smartonline hot-swappable modular ups systems tab english (95-2862)

12
TECHNICAL APPLICATION BULLETIN #95-2862 Realizing the Goal of Uninterruptible Power: SmartOnline Hot-Swappable Modular UPS Systems SmartOnline Hot-Swappable Modular UPS Systems address the practical requirements of enterprise customers and mission-critical applications. The innovative hot-swappable design eliminates power-related downtime, guaranteeing that power is never the weak link in high-availability systems. The key component of the hot-swappable design is a modular power distribution unit (PDU) that combines all input and output power connections with a manual bypass switch. End users can detach the PDU during power module maintenance, repair or replacement without interrupting the flow of power to connected equipment. Additional SmartOnline Hot-Swappable Modular UPS System features: True on-line operation—continuous AC-to-DC-to-AC power conversion with zero transfer time to battery—completely isolates connected equipment from power problems Precision-regulated, pure sine wave output assures maximum equipment safety and stability Runtime is expandable via daisy-chainable external battery packs Internal and external batteries are hot-swappable and user-replaceable Automatic internal bypass keeps equipment powered during UPS fault conditions Optional SNMPWEBCARD enables remote management via SNMP, Web or telnet Ideal for mission-critical servers, VoIP, telecom, security, storage, internetworking and more 1111 W. 35th Street, Chicago, IL 60609 USA (773) 869-1234 • www.tripplite.com See inside for complete specifications, product diagrams and more. SmartOnline Hot-Swappable Modular UPS Systems SU5000RT4U (5kVA/3.8kW; 4U total; 208/240V + 120V output) 2 SU6000RT4U (6kVA/4.2kW; 4U total; 208/240V + 120V output) 3 SU8000RT4U (8kVA/5.6kW; 4U total; 208/240V + 120V output including hardwire) 4 SU8000RT3U and SU8000RT3UN50 (8kVA/6.4kW; 6U total; 208/240V output) 5 SU8000RT3UHW (8kVA/6.4kW; 6U total; 208/240V hardwire-only output) 6 SU8000RT3U1TF and SU8000RT3UN50TF (8kVA/6.4kW; 8U total; 208V + 120V output) 7 SU10000RT3U (10kVA/8kW; 6U total; 208/240V output) 8 SU10000RT3U2TF (10kVA/8kW; 10U total; 208V + 120V output) 9 SU16000RT4U (16kVA/11.2kW; 8U total; 208/240V + 120V output including hardwire) 10 SU16000RT4UHW (16kVA/11.2kW; 8U total; 208/240V + 120V hardwire-only output) 11 Extended Battery Backup Runtime Chart 12

Upload: tripp-lite

Post on 07-Mar-2016

224 views

Category:

Documents


2 download

DESCRIPTION

SU5000RT4U (5kVA/3.8kW; 4U total; 208/240V + 120V output) 2 SU6000RT4U (6kVA/4.2kW; 4U total; 208/240V + 120V output) 3 SmartOnline Hot-Swappable Modular UPS Systems SU8000RT3UHW (8kVA/6.4kW; 6U total; 208/240V hardwire-only output) 6 SU8000RT3U and SU8000RT3UN50 (8kVA/6.4kW; 6U total; 208/240V output) 5 SU8000RT4U (8kVA/5.6kW; 4U total; 208/240V + 120V output including hardwire) 4 SU16000RT4UHW (16kVA/11.2kW; 8U total; 208/240V + 120V hardwire-only output) 11

TRANSCRIPT

Page 1: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

T E C H N I C A L A P P L I C A T I O N B U L L E T I N # 9 5 - 2 8 6 2

Realizing the Goal of Uninterruptible Power:SmartOnline™ Hot-Swappable Modular UPS Systems

SmartOnline Hot-Swappable Modular UPS Systems address the practical requirements of enterprise customers and mission-critical applications.

The innovative hot-swappable design eliminates power-related downtime, guaranteeing that power is never the weak link in high-availability

systems. The key component of the hot-swappable design is a modular power distribution unit (PDU) that combines all input and output power

connections with a manual bypass switch. End users can detach the PDU during power module maintenance, repair or replacement without

interrupting the flow of power to connected equipment.

Additional SmartOnline Hot-Swappable Modular UPS System features:

• True on-line operation—continuous AC-to-DC-to-AC power conversion with zero transfer time to battery—completely isolates connected

equipment from power problems

• Precision-regulated, pure sine wave output assures maximum equipment safety and stability

• Runtime is expandable via daisy-chainable external battery packs

• Internal and external batteries are hot-swappable and user-replaceable

• Automatic internal bypass keeps equipment powered during UPS fault conditions

• Optional SNMPWEBCARD enables remote management via SNMP, Web or telnet

• Ideal for mission-critical servers, VoIP, telecom, security, storage, internetworking and more

1111 W. 35th Street, Chicago, IL 60609 USA

(773) 869-1234 • www.tripplite.com

See inside for complete specifications, product diagrams and more.

SmartOnline Hot-Swappable Modular UPS Systems

SU5000RT4U (5kVA/3.8kW; 4U total; 208/240V + 120V output) 2

SU6000RT4U (6kVA/4.2kW; 4U total; 208/240V + 120V output) 3

SU8000RT4U (8kVA/5.6kW; 4U total; 208/240V + 120V output including hardwire) 4

SU8000RT3U and SU8000RT3UN50 (8kVA/6.4kW; 6U total; 208/240V output) 5

SU8000RT3UHW (8kVA/6.4kW; 6U total; 208/240V hardwire-only output) 6

SU8000RT3U1TF and SU8000RT3UN50TF (8kVA/6.4kW; 8U total; 208V + 120V output) 7

SU10000RT3U (10kVA/8kW; 6U total; 208/240V output) 8

SU10000RT3U2TF (10kVA/8kW; 10U total; 208V + 120V output) 9

SU16000RT4U (16kVA/11.2kW; 8U total; 208/240V + 120V output including hardwire) 10

SU16000RT4UHW (16kVA/11.2kW; 8U total; 208/240V + 120V hardwire-only output) 11

Extended Battery Backup Runtime Chart 12

Page 2: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

2

SmartOnline Hot-Swappable ModularUPS System

Model: SU5000RT4U

• 5,000VA / 3,800W Capacity in Only 4U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V + 120V Pure Sine Wave Output• Variety of High- and Low-Voltage Outlets

• Hardwire PDU Option Available

4UAll-In-One: Power, Dual VoltageOutput Circuit& Battery

Front View

3-Dimensional Rear View

4U

AC Input Connection: Insert L14-30P twist-lock plug into compatible outlet.

B C K

A

II

G E

F

HDJ

FeaturesExternal Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA 5-15/20R Outlets NEMA L6-30R Outlets NEMA L6-20R Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboot and Shutdown**

Emergency Power Off (EPO) Connector

HID-Compliant USB and RS-232 Serial (DB9) Communication Ports***

Output Breakers Ventilation Fans Manual Bypass Switch

10 ft. Cord with NEMA L14-30P Twist-Lock Plug

* Model BP192V12-3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB C DEFGH I JK

SpecificationsOutput Capacity (VA): 5,000VA

Output Capacity (Watts): 3,800W

Output Voltage (Nominal): 208/240V + 120V AC

Output Frequency: 60 Hz.

AC Outlet Quantity (NEMA Type): 2 (L6-30R), 2 (L6-20R), 8 (5-15/20R)

Input Voltage (Nominal): 208/240V AC, 4 Wire

Input Frequency: 60 Hz.

Input Plug (NEMA Type): L14-30P

Input Power Cord Length: 10 ft.

Backup Time, Half/Full Load (Typical): 17 min./8 min.

Total Rack Space: 4U*

Communication Ports: 1 RS-232 (DB9), 1 USB, 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D): 7 x 17.5 x 30.75 in.

Unit Weight: 150 lb.

* Mounting Options: 4-post rackmount with included rackmount rails; 2-post rackmount with 2POSTRMKITWM (available

separately); tower mount with 2-9USTAND (available separately).

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

• Provides a variety of 120V and 208/240V outlets.

• Manual bypass feature allows complete hot-swap removal of the

power module, eliminating maintenance-related downtime. The

detachable PDU continues to supply utility power to connected

equipment.PDU model SUPDMB56 shown (included with UPS system).

HH

DJ

KCB

Optional Accessories

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

E

Hardwire Input/Output PDU (Model: SUPDM56HW)

Replaces detachable cord/outlet PDU that

is included with the UPS System.

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

External Battery Pack (Model: BP192V12-3U)

B B

A

H

Set of 4-PostRackmount Rails

(Included)Supports Sides of

UPS System**

B

A

LED/LCD Control PanelDisplays Detailed Status andAlarm Information*

*Reports more than 45 separate operating

conditions. Can be rotated for tower

applications.

**For 2-post rack applications, order one

2POSTRMKITWM mounting kit

(available separately).

Page 3: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

3

• 6,000VA / 4,200W Capacity in Only 4U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V + 120V Pure Sine Wave Output• Variety of High- and Low-Voltage Outlets

• Hardwire PDU Option Available

SmartOnline Hot-Swappable ModularUPS System

Model: SU6000RT4U

4UAll-In-One: Power, Dual VoltageOutput Circuit& Battery

Front View

3-Dimensional Rear View

4U

AC Input Connection: Insert L14-30P twist-lock plug into compatible outlet.

H

B C L

A

II

G E

F

HDJ

FeaturesExternal Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA 5-15/20R Outlets NEMA L6-30R Outlets NEMA L6-20R Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboot and Shutdown**

Emergency Power Off (EPO) Connector

HID-Compliant USB and RS-232 Serial (DB9) Communication Ports***

Output Breakers Ventilation Fans Manual Bypass Switch

Charge Rate Switch 10 ft. Cord with NEMA L14-30P Twist-Lock Plug

* Model BP192V12-3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB C DEFGH I JK L

SpecificationsOutput Capacity (VA): 6,000VA @ 240V; 5,400VA @ 208V

Output Capacity (Watts): 4,200W

Output Voltage (Nominal): 208/240V + 120V AC

Output Frequency: 60 Hz.

AC Outlet Quantity (NEMA Type): 2 (L6-30R), 2 (L6-20R), 8 (5-15/20R)

Input Voltage (Nominal): 208/240V AC, 4 Wire

Input Frequency: 60 Hz.

Input Plug (NEMA Type): L14-30P

Input Power Cord Length: 10 ft.

Backup Time, Half/Full Load (Typical): 24 min./9 min.

Total Rack Space: 4U*

Communication Ports: 1 RS-232 (DB9), 1 USB, 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D): 7 x 17.5 x 30.75 in.

Unit Weight: 189 lb.

* Mounting Options: 4-post rackmount with included rackmount rails; 2-post rackmount with 2POSTRMKITWM (available

separately); tower mount with 2-9USTAND (available separately).

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

• Provides a variety of 120V and 208/240V outlets.

• Manual bypass feature allows complete hot-swap removal of the

power module, eliminating maintenance-related downtime. The

detachable PDU continues to supply utility power to connected

equipment.PDU model SUPDMB56 shown (included with UPS system).

HH

DJ

LCB

Optional Accessories

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

E

Hardwire Input/Output PDU (Model: SUPDM56HW)

Replaces detachable cord/outlet PDU that

is included with the UPS System.

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

External Battery Pack (Model: BP192V12-3U)

K

Advantages Versus SU5000RT4U: Longer Runtime and Larger Battery Charger for Faster Recharge Rate (Ideal for Multiple Battery Packs)

B B

A

Set of 4-PostRackmount Rails

(Included)Supports Sides of

UPS System**

B

A

LED/LCD Control PanelDisplays Detailed Status andAlarm Information*

*Reports more than 45 separate operating

conditions. Can be rotated for tower

applications.

**For 2-post rack applications, order one

2POSTRMKITWM mounting kit

(available separately).

Page 4: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

4

• 8,000VA / 5,600W Capacity in Only 4U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V + 120V Pure Sine Wave Output• Variety of High- and Low-Voltage Outlets

• Detachable PDU Also Includes Hardwire Output

SmartOnline Hot-Swappable ModularUPS System

Model: SU8000RT4U

Front View

3-Dimensional Rear View

4U

FeaturesExternal Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA 5-15/20R Outlets NEMA L6-30R Outlets

NEMA L6-20R Outlets Mounted on Flexible Cables

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboot and Shutdown**

Emergency Power Off (EPO) Connector

HID-Compliant USB and RS-232 Serial (DB9) Communication Ports***

Output Breakers Ventilation Fans Manual Bypass Switch

Charge Rate Switch Hardwire Input and Output

* Model BP192V12-3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB CDEFGH I J

K L

SpecificationsOutput Capacity (VA): 8,000VA @ 240V; 7,200VA @ 208V

Output Capacity (Watts): 5,600W

Output Voltage (Nominal): 208/240V + 120V AC

Output Frequency: 60 Hz.

AC Outlet Quantity (NEMA Type): 2 (L6-30R), 2 (L6-20R), 4 (5-15/20R) + Hardwire

Input Voltage (Nominal): 208/240V AC, 4 Wire

Input Frequency: 60 Hz.

Input Connection: Hardwire

Backup Time, Half/Full Load (Typical): 12 min./5 min.

Total Rack Space: 4U*

Communication Ports: 1 RS-232 (DB9), 1 USB, 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D): 7 x 17.5 x 30.75 in.

Unit Weight: 177 lb.

* Mounting Options: 4-post rackmount with included rackmount rails; 2-post rackmount with 2POSTRMKITWM (available

separately); tower mount with 2-9USTAND (available separately).

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

• Provides a variety of 120V and 208/240V outlets and hardwire

output.

• Manual bypass feature allows complete hot-swap removal of the

power module, eliminating maintenance-related downtime. The

detachable PDU continues to supply utility power to connected

equipment.PDU model SUPDMB8K shown (included with UPS system).

Optional Accessories

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

E

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

External Battery Pack (Model: BP192V12-3U)

Advantages Versus SU8000RT3U: Smaller Rack Size, Simultaneously Available Outlets and Hardwire Output, Low Voltage Output

A

C

D

E

H

I

JL

B

C

D

H

JL

H

H

4UAll-In-One: Power, Dual VoltageOutput Circuit& BatteryB B

A

Set of 4-PostRackmount Rails

(Included)Supports Sides of

UPS System**

B

A

LED/LCD Control PanelDisplays Detailed Status andAlarm Information*

*Reports more than 45 separate operating

conditions. Can be rotated for tower

applications.

**For 2-post rack applications, order one

2POSTRMKITWM mounting kit

(available separately).

B

H

F

GK

Page 5: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

5

SmartOnline Hot-Swappable ModularUPS Systems

Models: SU8000RT3U and SU8000RT3UN50

• 8,000VA / 6,400W Capacity in Only 6U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V Pure Sine Wave Output• Variety of High-Voltage Outlets

• High-Capacity Battery Pack

6U

3U

3U

Power Module

Battery Pack (Hot-Swappable)

Rackmount Front View

Power Module Battery Pack(Hot-Swappable)

One Set ofAdjustable TowerMount Feet(Included)

Two Sets ofIndependent 4-Post

Rackmount Rails(Included)

Support Sides ofEach Module*

* For 2-post rack applications, order two 2POSTRMKITWM mounting kits (available separately).

Tower Front View

A

3-Dimensional Rear View

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

Optional Accessories

• Provides a variety of 208/240V outlets.

• Manual bypass feature allows complete

hot-swap removal of the power module,

eliminating maintenance-related downtime.

The detachable PDU continues to supply

utility power to connected equipment.PDU model SUPDMB710 shown

(included with UPS system).

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

External Battery Pack (Model: BP240V10RT3U)

D

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

6U

3U

3U

HKD

E

F

AB

G

J I

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA L6-20R Outlets NEMA L6-30R Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboots and Shutdowns**

Emergency Power Off (EPO) Connector

RS-232 Serial (DB9) and Contact Closure (DB9) Communication Ports***

Output Breakers Ventilation Fan Manual Bypass Switch

Hardwire Input (SU8000RT3UN50 has pre-wired input with 10 ft. cord and L6-50P.)

Primary Battery Pack Connector

* Model BP240V10RT3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB CDEFG H IJ

Specifications (SU8000RT3U and SU8000RT3UN50)Output Capacity (VA): 8,000VA

Output Capacity (Watts): 6,400W

Output Voltage (Nominal): 208/240V AC

Output Frequency: 50/60 Hz.

AC Outlet Quantity (NEMA Type): 4 (L6-20R) & 2 (L6-30R)

Input Voltage (Nominal): 208/240V AC

Input Frequency: 50/60 Hz.

Input Connection: Hardwire (SU8000RT3U)

10 ft. Cord and L6-50P (SU8000RT3UN50)

Backup Time Half/Full Load (Typical): 15 min./6 min.

Total Rack Space: 6U

Communication Ports: 1 RS-232 (DB9), 1 Contact Closure (DB9), 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D):* 10.5 x 17.5 x 32.5 in.

Unit Weight :* 220 lb.

* All modules.

A

A A

A

C C

C

C

Advantages Versus SU8000RT4U: Higher Watt Capacity and Longer Runtime

K

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

B

B

B

LED/LCD ControlPanel DisplaysDetailed Statusand AlarmInformation**Reports more than 45

separate operating

conditions. Can be rotated

for tower applications.

SU8000RT3UN50 Includes 50-Amp Cord and Plug• UPS includes detachable PDU with heavy-

duty 10 ft. input cord and 50A Hubbell

twist-lock plug (L6-50P)

• Otherwise identical to the SU8000RT3U

Detachable PDU from UPS model SU8000RT3UN50 shown

Page 6: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

6

SmartOnline Hot-Swappable ModularUPS System

Model: SU8000RT3UHW

• 8,000VA / 6,400W Capacity in Only 6U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V Pure Sine Wave Output• Hardwire Input and Output• High-Capacity Battery Pack

6U

3U

3U

Power Module

Battery Pack (Hot-Swappable)

Rackmount Front View

Two Sets ofIndependent 4-Post

Rackmount Rails(Included)

Support Sides ofEach Module*

* For 2-post rack applications, order two 2POSTRMKITWM mounting kits (available separately).

Tower Front View

A

3-Dimensional Rear View

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

Optional Accessories

• Provides 208/240V hardwire output.

• Manual bypass feature allows

complete hot-swap removal of the

power module, eliminating

maintenance-related downtime.

The detachable PDU continues to

supply utility power to connected

equipment.PDU model SUPDMB710HW shown

(included with UPS system).

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

External Battery Pack (Model: BP240V10RT3U)

D

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

6U

3U

3U

HBD

E

F

A

C G

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

Primary Battery Pack Connector

Hardwire Input and Output

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboots and Shutdowns**

Emergency Power Off (EPO) Connector

RS-232 Serial (DB9) and Contact Closure (DB9) Communication Ports***

Manual Bypass Switch Ventilation Fan

* Model BP240V10RT3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite.*** PowerAlert Software CD-ROM and cabling included.

ABCDEFG H

SpecificationsOutput Capacity (VA): 8,000VA

Output Capacity (Watts): 6,400W

Output Voltage (Nominal): 208/240V AC

Output Frequency: 50/60 Hz.

Output Connection: Hardwire

Input Voltage (Nominal): 208/240V AC

Input Frequency: 50/60 Hz.

Input Connection: Hardwire

Backup Time Half/Full Load (Typical): 15 min./6 min.

Total Rack Space: 6U

Communication Ports: 1 RS-232 (DB9), 1 Contact Closure (DB9), 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D):* 10.5 x 17.5 x 32.5 in.

Unit Weight :* 220 lb.

* All modules.

A

A A

A

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

C G

Power Module Battery Pack(Hot-Swappable)

One Set ofAdjustable TowerMount Feet(Included)

C C

C

B

B

B

LED/LCD ControlPanel DisplaysDetailed Statusand AlarmInformation**Reports more than 45

separate operating

conditions. Can be rotated

for tower applications.

Page 7: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

7

• 8,000VA / 6,400W Capacity in 8U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208V + 120V Pure Sine Wave Output• Includes 120V Transformer

• Variety of High- and Low-Voltage Outlets

8U

2UTransformer

3U

3U

(Hot-Swappable)

PowerModule

BatteryPack

Rackmount Front View Tower Front View

3-Dimensional Rear View

3U

2U

8U

3U

PowerModule

BatteryPack

Transformer (Hot-Swappable)

Three Sets ofIndependent 4-Post

Rackmount Rails(Included)

Support Sides ofEach Module*

SU8000RT3UN50TF Includes 50-Amp Cord and Plug

* For 2-post rack applications, order three 2POSTRMKITWM mounting kits (available separately).

SmartOnline Hot-Swappable ModularUPS Systems

Models: SU8000RT3U1TF and SU8000RT3UN50TF

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA L6-20R Outlets NEMA L6-30R Outlets NEMA 5-15/20R Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboots and Shutdowns**

Emergency Power Off (EPO) Connector

RS-232 Serial (DB9) and Contact Closure (DB9) Communication Ports***

Output Breakers Ventilation Fan

Manual Bypass Switch Input Breaker

Hardwire Input (SU8000RT3UN50TF has pre-wired input with 10 ft. cord and L6-50P.)

Transformer Input Cord (Connects Transformer to Detachable PDU)

Primary Battery Pack Connector

* Model BP240V10RT3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB C DEFGH IJ

Specifications (SU8000RT3U1TF and SU8000RT3UN50TF)Output Capacity (VA): 8,000VA

Output Capacity (Watts): 6,400W

Output Voltage (Nominal): 208V AC + 120V AC (Transformer)

Output Frequency: 60 Hz.

AC Outlet Quantity (NEMA Type): 4 (L6-20R), 2 (L6-30R) & 12 (5-15/20R)

Input Voltage (Nominal): 208V AC*

Input Frequency: 60 Hz.

Input Connection: Hardwire (SU8000RT3U1TF)

10 ft. Cord and L6-50P (SU8000RT3UN50TF)

Backup Time Half/Full Load (Typical): 15 min./6 min.

Total Rack Space: 8U

Communication Ports: 1 RS-232 (DB9), 1 Contact Closure (DB9), 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D):** 14 x 17.5 x 32.5 in.

Unit Weight:** 280 lb.

* The transformer requires 208V for proper operation. **All modules.

KLM

A

C

B M

H

JL K

GF

E N I

H DC DH

Detachable PDU with Manual Bypass Switch

• Provides a variety of 208V outlets.

• Manual bypass feature allows complete hot-

swap removal of the power module, eliminating

maintenance-related downtime. The detachable

PDU continues to supply utility power to

connected equipment.PDU model SUPDMB710 shown (included with UPS system).

Optional Accessories

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

External Battery Pack (Model: BP240V10RT3U)

E

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet. Remove the accessory slot cover to

insert internal SNMPWEBCARD.

CC

A

A

A

AA

A

A

N

B

B

One Set ofAdjustable TowerMount Feet(Included)

C

B

LED/LCD ControlPanel DisplaysDetailed Statusand AlarmInformation**Reports more than 45

separate operating

conditions. Can be rotated

for tower applications.

• UPS includes detachable PDU with heavy-

duty 10 ft. input cord and 50A Hubbell

twist-lock plug (L6-50P)

• Otherwise identical to the

SU8000RT3U1TF

Detachable PDU from UPS model SU8000RT3UN50TF shown

Page 8: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

8

SmartOnline Hot-Swappable ModularUPS System

Model: SU10000RT3U

• 10,000VA / 8,000W Capacity in Only 6U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V Pure Sine Wave Output• Variety of High-Voltage Outlets

• High-Capacity Battery Pack

6U

3U

3U

Power Module

Battery Pack (Hot-Swappable)

Rackmount Front View

Two Sets ofIndependent 4-Post

Rackmount Rails(Included)

Support Sides ofEach Module*

* For 2-post rack applications, order two 2POSTRMKITWM mounting kits (available separately).

Tower Front View

A

3-Dimensional Rear View

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

Optional Accessories

• Provides a variety of 208/240V outlets.

• Manual bypass feature allows complete

hot-swap removal of the power module,

eliminating maintenance-related downtime.

The detachable PDU continues to supply

utility power to connected equipment.PDU model SUPDMB710 shown

(included with UPS system).

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

External Battery Pack (Model: BP240V10RT3U)

D

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

6U

3U

3U

HKD

E

F

AB

G

J I

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA L6-20R Outlets NEMA L6-30R Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboots and Shutdowns**

Emergency Power Off (EPO) Connector

RS-232 Serial (DB9) and Contact Closure (DB9) Communication Ports***

Output Breakers Ventilation Fan Manual Bypass Switch

Hardwire Input Primary Battery Pack Connector

* Model BP240V10RT3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB CDEFG H IJ

SpecificationsOutput Capacity (VA): 10,000VA

Output Capacity (Watts): 8,000W

Output Voltage (Nominal): 208/240V AC

Output Frequency: 50/60 Hz.

AC Outlet Quantity (NEMA Type): 4 (L6-20R) & 2 (L6-30R)

Input Voltage (Nominal): 208/240V AC

Input Frequency: 50/60 Hz.

Input Connection: Hardwire

Backup Time Half/Full Load (Typical): 10 min./4 min.

Total Rack Space: 6U

Communication Ports: 1 RS-232 (DB9), 1 Contact Closure (DB9), 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D):* 10.5 x 17.5 x 32.5 in.

Unit Weight :* 220 lb.

* All modules.

A

A A

A

C

K

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

Power Module Battery Pack(Hot-Swappable)

One Set ofAdjustable TowerMount Feet(Included)

C C

C

B

B

B

LED/LCD ControlPanel DisplaysDetailed Statusand AlarmInformation**Reports more than 45

separate operating

conditions. Can be rotated

for tower applications.

Page 9: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

9

10U

2UTransformer

#1

2UTransformer

#2

3U

3U

(Hot-Swappable)

PowerModule

BatteryPack

Rackmount Front View

3U

3U

2U

2U

10U

Tower Front View

Power Module Battery PackTransformer #1

Transformer #2 (Hot-Swappable)

Rear View (Transformer Module)

Four Sets ofIndependent

4-PostRackmount Rails

(Included)Support Sides ofEach Module*

NOTE: The transformer requires 208V for proper operation.

Optional Accessories

* For 2-post rack applications, order four 2POSTRMKITWM mounting kits (available separately).

3-Dimensional Rear View

SmartOnline Hot-Swappable ModularUPS System

Model: SU10000RT3U2TF

One Set of Extra-Wide AdjustableTower Mount Feet (Included)

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA L6-20R Outlets NEMA L6-30R Outlets NEMA 5-15/20R Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboots and Shutdowns**

Emergency Power Off (EPO) Connector

RS-232 Serial (DB9) and Contact Closure (DB9) Communication Ports***

Output Breakers Ventilation Fan Manual Bypass Switch

Input Breaker Hardwire Input

Transformer Input Cord (Connects Transformer to Detachable PDU)

Primary Battery Pack Connector

* Model BP240V10RT3U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software and cabling included.

AB C DEFGH I J

SpecificationsOutput Capacity (VA): 10,000VA

Output Capacity (Watts): 8000W

Output Voltage (Nominal): 208V AC + 120V AC (Transformer)

Output Frequency: 60 Hz.

AC Outlet Quantity (NEMA Type): 4 (L6-20R), 2 (L6-30R) & 24 (5-15/20R)

Input Voltage (Nominal): 208V AC

Input Frequency: 60 Hz.

Input Connection: Hardwire

Backup Time (Typical Minutes) Half/Full Load: 10 min./4 min.

Total Rack Space: 10U

Communication Ports: 1 RS-232 (DB9), 1 Contact Closure (DB9), 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions (H x W x D):* 17.5 x 17.5 x 32.5 in.

Unit Weight:* 340 lb.

*All modules.

K LM

A

B

C

DD

E

F G

H

H

H

I

C

J

K

L

M

Transformer Specifications (per module)Input Voltage: 208V AC (60 Hz.)

Input Plug (NEMA Type): L6-30P

Input Power Cord Length: 10 ft.

Output Voltage: 120V + 208V AC (60 Hz.)

AC Output Receptacle Quantity (NEMA Type): 1 (L6-30R) & 12 (5-15/20R)

Dimensions (H x W x D): 3.5 x 17.5 x 20.75 in.

Unit Weight: 60 lb.

2U

H

D DC

M

K

H

Detachable PDU with Manual Bypass Switch• Provides a variety of 208V outlets.

• Manual bypass feature allows complete hot-

swap removal of the power module, eliminating

maintenance-related downtime. The detachable

PDU continues to supply utility power to

connected equipment.PDU model SUPDMB710 shown (included with UPS system).

3UBattery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

External Battery Pack (Model: BP240V10RT3U)

E

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

CCC

A

A

A

A

AA

A

A

A

N

• 10,000VA / 8,000W Capacity in 10U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208V + 120V Pure Sine Wave Output• Includes Two 120V Transformers

• Abundance of High- and Low-Voltage Outlets

N

Transformer model SU5000XFMRT2U shown (2 included with UPS system).

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

B

B BLED/LCD Control Panel Displays

Detailed Status and AlarmInformation*

*Reports more than 45 separate operating

conditions. Can be rotated for tower applications.

H

H

Page 10: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

10

• 16,000VA / 11,200W Capacity in 8U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V + 120V Pure Sine Wave Output• Variety of High- and Low-Voltage NEMA and IEC Outlets

• Detachable PDU Also Includes Hardwire Output

SmartOnline Hot-Swappable ModularUPS System

Model: SU16000RT4U

4U

4U

8U

PowerModule

BatteryPack(Hot-Swappable)

Front View

3-Dimensional Rear View

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

NEMA 5-15/20R Outlets NEMA L6-30R Outlets IEC-60320-C19 Outlets

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboot and Shutdown**

Emergency Power Off (EPO) Connector

HID-Compliant USB and RS-232 Serial (DB9) Communication Ports***

Output Breakers Ventilation Fans Manual Bypass Switch

Charge Rate Switch Hardwire Input and Output

Primary Battery Pack Connector

* Model BP192V18-4U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

AB C DEFGH I JK L

SpecificationsOutput Capacity (VA): 16,000VA @ 240V; 13,860VA @ 208V

Output Capacity (Watts): 11,200W

Output Voltage (Nominal): 208/240V + 120V AC

Output Frequency: 60 Hz.

AC Outlet Quantity (Type): 2 (NEMA L6-30R), 6 (IEC-60320-C19),

5 (NEMA 5-15/20R) + Hardwire

Input Voltage (Nominal): 208/240V AC, 4 Wire

Input Frequency: 60 Hz.

Input Connection: Hardwire

Backup Time, Half/Full Load (Typical): 12 min./5 min.

Total Rack Space: 8U*

Communication Ports: 1 RS-232 (DB9), 1 USB, 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions** (H x W x D): 14 x 17.5 x 37 in.

Unit Weight**: 338 lb.

* Mounting Options: 4-post rackmount with included rackmount rails; tower mount with 2-9USTAND (available separately).

** Includes both modules.

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

• Provides a variety of 120V and 208/240V outlets.

• Manual bypass feature allows complete hot-swap removal of the

power module, eliminating maintenance-related downtime. The

detachable PDU continues to supply utility power to connected

equipment.PDU model SUPDMB16K shown (included with UPS system).

H

Optional Accessories

4U

Battery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

E

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

External Battery Pack (Model: BP192V18-4U)

Longer Runtime and Larger Battery Charger for Faster Recharge Rate (Ideal for Multiple Battery Packs)

M

4U

4U

8U

B C B

E

F

G

H

I

J

K

L

H

C B

H

J

LD

BH

H

B B

A

B B

Two Sets of 4-Post RackmountRails (Included)Support Sides of

Each Module

A

LED/LCD Control PanelDisplays Detailed Status andAlarm Information*

*Reports more than 45 separate operating

conditions. Can be rotated for tower

applications.

A

M

M

D

B

Page 11: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

11

• 16,000VA / 11,200W Capacity in 8U Total Rack Space• Hot-Swappable Design Eliminates Power-Related Downtime• True On-Line Operation with Zero Transfer Time to Battery

• 208/240V + 120V Pure Sine Wave Output• Hardwire Input and Output

SmartOnline Hot-Swappable ModularUPS System

Model: SU16000RT4UHW

Front View

3-Dimensional Rear View

FeaturesExpansion Battery Pack* Connector (Enables Extended Runtime Capability)

Primary Battery Pack Connector

Ventilation Fans Charge Rate Switch

SNMP/Web Accessory Card Slot for Remote Monitoring, Reboot and Shutdown**

Emergency Power Off (EPO) Connector

HID-Compliant USB and RS-232 Serial (DB9) Communication Ports***

Manual Bypass Switch

Hardwire Input and Output

* Model BP192V18-4U available separately from Tripp Lite. ** For use with internal accessory card model

SNMPWEBCARD available separately from Tripp Lite. *** PowerAlert Software CD-ROM and cabling included.

ABC DEFGHI

SpecificationsOutput Capacity (VA): 16,000VA @ 240V; 13,860VA @ 208V

Output Capacity (Watts): 11,200W

Output Voltage (Nominal): 208/240V + 120V AC

Output Frequency: 60 Hz.

Output Connection: Hardwire

Input Voltage (Nominal): 208/240V AC, 4 Wire

Input Frequency: 60 Hz.

Input Connection: Hardwire

Backup Time, Half/Full Load (Typical): 12 min./5 min.

Total Rack Space: 8U*

Communication Ports: 1 RS-232 (DB9), 1 USB, 1 EPO

SNMP/Web Accessory Slot: Yes

Unit Dimensions** (H x W x D): 14 x 17.5 x 37 in.

Unit Weight**: 338 lb.

* Mounting Options: 4-post rackmount with included rackmount rails; tower mount with 2-9USTAND (available separately).

** Includes both modules.

Tripp Lite World Headquarters: 1111 W. 35th Street, Chicago, IL 60609 USA, (773) 869-1234, www.tripplite.com

Detachable PDU with Manual Bypass Switch

• Provides a variety of 120V and 208/240V outlets.

• Manual bypass feature allows complete hot-swap removal of the

power module, eliminating maintenance-related downtime. The

detachable PDU continues to supply utility power to connected

equipment.PDU model SUPDMB16KHW shown (included with UPS system).

H

Optional Accessories

4U

Battery packs extend runtime for

mission-critical systems. They can

be daisy-chained for additional

expansion.

E

Internal SNMP/Web Card (Model: SNMPWEBCARD)

Allows users to operate the UPS as a managed device on a

network. Enables remote monitoring, shutdown, reboot and

more using SNMP network management system, Web

browser or telnet.

Remove the accessory slot cover to

insert internal SNMPWEBCARD.

External Battery Pack (Model: BP192V18-4U)

Longer Runtime and Larger Battery Charger for Faster Recharge Rate (Ideal for Multiple Battery Packs)

4U

4U

8U

IA

B

C D

E

F

G

H I

4U

4U

8U

PowerModule

BatteryPack(Hot-Swappable)

B B

A

B B

A

LED/LCD Control PanelDisplays Detailed Status andAlarm Information*

*Reports more than 45 separate operating

conditions. Can be rotated for tower

applications. Two Sets of 4-Post RackmountRails (Included)Support Sides of

Each Module

B

Page 12: SmartOnline Hot-Swappable Modular UPS Systems TAB English (95-2862)

1111 W. 35th Street, Chicago, IL 60609 USA

(773) 869-1234 • www.tripplite.com

Copyright © 2008 Tripp Lite. All rights reserved. All trademarks are the property of their respective owners.

The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

200706081

95-286212

Extended Battery Backup Runtime SmartOnline Hot-Swappable Modular UPS Systems

Model Number Battery Pack 1kW 2kW 3kW 4kW 5kW 6kW 7kW 8kW 9kW 10kW 11kWSU5000RT4U Internal Batteries 31 13 8 - - - - - - - -

+1 BP192V12-3U 200 92 56 - - - - - - - -+2 BP192V12-3U 318 149 93 - - - - - - - -+3 BP192V12-3U 436 209 131 - - - - - - - -

SU6000RT4U Internal Batteries 50 22 13 9 - - - - - - -+1 BP192V12-3U 200 92 56 39 - - - - - - -+2 BP192V12-3U 318 149 93 65 - - - - - - -+3 BP192V12-3U 436 209 131 93 - - - - - - -

SU8000RT4U Internal Batteries 45 20 12 8 6 - - - - - -+1 BP192V12-3U 150 69 42 29 22 - - - - - -+2 BP192V12-3U 309 147 92 65 50 - - - - - -+3 BP192V12-3U 424 206 130 93 71 - - - - - -

SU8000RT3U and SU8000RT3UN50 Included External Battery Pack 73 33 19 10 9 8 - - - - -

+1 BP240V10RT3U 168 80 50 35 26 20 - - - - -+2 BP240V10RT3U 268 131 82 59 44 34 - - - - -+3 BP240V10RT3U 370 183 117 84 63 50 - - - - -

SU8000RT3UHW Included External Battery Pack 73 33 19 10 9 8 - - - - -+1 BP240V10RT3U 168 80 50 35 26 20 - - - - -+2 BP240V10RT3U 268 131 82 59 44 34 - - - - -+3 BP240V10RT3U 370 183 117 84 63 50 - - - - -

SU8000RT3U1TF and SU8000RT3UN50TF Included External Battery Pack 73 33 19 10 9 8 - - - - -

+1 BP240V10RT3U 168 80 50 35 26 20 - - - - -+2 BP240V10RT3U 268 131 82 59 44 34 - - - - -+3 BP240V10RT3U 370 183 117 84 63 50 - - - - -

SU10000RT3U Included External Battery Pack 73 33 20 10 9 8 6 4 - - -+1 BP240V10RT3U 168 80 50 35 26 20 16 14 - - -+2 BP240V10RT3U 268 131 82 59 44 34 28 23 - - -+3 BP240V10RT3U 370 183 117 84 63 50 41 34 - - -

SU10000RT3U2TF Included External Battery Pack 73 33 20 10 9 8 6 4 - - -+1 BP240V10RT3U 168 80 50 35 26 20 16 14 - - -+2 BP240V10RT3U 268 131 82 59 44 34 28 23 - - -+3 BP240V10RT3U 370 183 117 84 63 50 41 34 - - -

SU16000RT4U Included External Battery Pack 95 45 28 20 15 12 9 8 7 6 5+1 BP192V18-4U 278 139 88 63 48 39 32 27 23 20 18+2 BP192V18-4U 436 223 144 104 80 64 53 45 39 34 30+3 BP192V18-4U 594 309 202 147 114 92 76 64 56 49 43

SU16000RT4UHW Included External Battery Pack 95 45 28 20 15 12 9 8 7 6 5+1 BP192V18-4U 278 139 88 63 48 39 32 27 23 20 18+2 BP192V18-4U 436 223 144 104 80 64 53 45 39 34 30+3 BP192V18-4U 594 309 202 147 114 92 76 64 56 49 43

*Runtime varies with specific load characteristics, ambient temperature, battery condition and other factors.

Estimated Runtime (Minutes) at Indicated Wattage Load*