smoke management calc for car park
TRANSCRIPT
![Page 1: Smoke Management Calc for Car Park](https://reader035.vdocument.in/reader035/viewer/2022073120/563db972550346aa9a9d6d3f/html5/thumbnails/1.jpg)
ECG Engineering Consultants Group
PROJECT NAME: Nozha City Centre. DATE: MAY-2007
PROJECT NO.: 1127 COMPUTED BY: A.Salah
Area Served: Car Park
Ventilation Type: Mechanical Ventilation Fans
Brief description: Exhaust through high temperature rated fans.
Fresh Air make-up through Ramps and slab openings.
Design Parameters:
Fire Size = 3 x 3
Fire Area = 9 m2
Heat Rate ( Qr) = 278 kw/m2
Heat Production (Q) = 2502 kw
Perimeter ( P ) = 12 m
Smoke Layer Height (Y) = 2.5 m
Smoke Layer Depth (Db) = 1.5 m
Air Specific Heat ( Cp) = 1.01 kj/kg.k
Outside Air Temp. (To) = 30 deg.c (303 k)
Calculations
Min. Smoke Flow Rate (Mf) = 0.188 x P x Y1.5
= 0.188 x 12 x 3.95
= = 8.918 kg/s
Temperature Rise (Tr) = Q / (Mf x Cp)
= = 277.8 Deg.c
Max. Smoke Temp. (Tc) = To + Tr
= = 307.8 deg.c ( 581 k )
Air Volume Flow rate (Ma) = Mf x Tc / (1.2 x To)
= 8.918 x 581 / (1.2 x 303)
= 14.24 m3/s =
= 30,182 CFM Note:
As per ANSI/ASHRAE standards 62.1.2004
Recommendation provide 3.7 lit/sec/m2
For 12000 m2
As per NFPA part 92B
Direct drive two speed smoke exhaust fans of 14.1 m3/s (30,000 cfm) rating shall be provided in each parking zone ,
Fire rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.
SMOKE MANAGEMENT DESIGN CALCULATION SHEET
Car parking area divided into 5 fire zones 2500 m2 each , Total exhaust 150,000 cfm.
Make up fresh air shall be supplied from Ramps and Slab opening.
cfm = 12000 x 3.7 x 2.1 = 93.240 cfm.
Shall be divided into 5 exhaust fans two speed fire protected each one is 20 000 cfm for ventilation.