    Notifier Canada Rollout 201

    Product Updates B200SRA Sounder Base Update

    B710LPA / B350LPA / B210LPABase Changes

    B224BIA and B224RB Changes

    New Products

    FCO-851APhoto/CO Detector

    B200SCOA Addressable Sounder Base

    2-in / 2-out Module

    Dual Strobe Appliance

    ExitPoint

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    4/39

    B200SRA Sounder Base

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    5/39

    B200SRA Sounder Base Update

    New terminal block size and added mounting holes

    New mounting holes

    for 3.0/4.0 plaster

    rings

    Smaller terminal

    block fits inside

    more junction boxes

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    6/39

    B210LPA Base Changes

    New center allows for 400% larger wire opening

    CURRENT NEW

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    7/39

    B210LPA Base Changes

    New terminal markings are easier to see in all

    situations and reduce the possibility of mis-wiring

    Easy to

    see

    cutouts

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    8/39

    B210LPA Base Changes

    New trim ring streamlines the overall appearance

    Old style trim ring (F110) will continue to be available

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    9/39

    B224BIA and B224RBA updates

    These two models will be moving to the sounder

    base platform

    B224BIA B224RBA

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    10/39

    B224BI A and B224RBA updates

    Same installation benefits gained with the new

    sounder base will now be shared by these twomodels

    Easier wiring

    Common look

    Better terminal marking Ability to wire the base and later install the electronics

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    11/39

    IntelliQuad Plus/FCO-851A + B200SCOA

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    12/39

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    13/39

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    14/39

    CO/S k dB200SCOA S i

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    15/39

    SMOKE WITH

    SOUNDER BASE

    DETECTOR IN

    HALLWAY

    HORN STROBE IN

    HALLWAY

    SMOKE WITH

    SOUNDER BASE

    1. Local event- Turn on local

    sounders

    - Volume = high

    - Tone = cont

    2. General evac- Turn on all

    horns & strobes

    - Turn on all

    sounders

    - Volume = high

    - Tone = T3

    CO/Smoke and B200SCOA - Scenario

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    16/39

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    17/39

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    18/39

    FAAST Fire Alarm Aspiration Sensing Technology

    Dual Vision. Single Purpose.

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    19/39

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    20/39

    Data Rooms

    Application Requirements Very early warning provided by

    sensitivities 100 times greater than

    standard photoelectric

    High-value equipment and data

    protection through point location ofalarm

    Detect smoke dispersed by high air

    velocity with high sensitivity and high

    airflow tolerant chamber design

    Open area and duct smokedetection

    Other areas are data rooms for telecommun icat ioncenters or server farms for Internet companies.

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    21/39

    Maximum Coverage

    8,000 sq. ft. of coverage area

    Earliest warning: 30-60 minutes before

    combustion

    Unsurpassed sensitivity .00046%/ft obs.

    (competition offers .0015%/ft)

    UL/ULC listing for EWFD and VEWFD

    Dual source smoke detection improves decision

    making

    Blue LED covers the widest ranges of

    fires (competition uses only single

    infrared laser, which is prone to

    nuisance issues)

    Infrared laser detects dust

    Advanced algorithms discriminate dust

    from smoke

    FAAST 8100A

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    22/39

    FAAST 8100A

    Multi-stage filtering to preventdust

    and nuisance alarms

    Patented particle separator

    Replaceable 30 micron filter

    Electronic nuisance

    rejection through algorithms

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    23/39

    FAAST 8100A

    E-Mail Notification Examples

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    24/39

    VIEWLaser Detector

    To provide early warning, a laseris used to deliver ultra-high

    sensitivity

    0.02% to 2.0% per foot

    100 times more sensitive than astandard photoelectric smoke

    detector

    Advanced algorithms eliminate

    most false and nuisance alarms

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    25/39

    FSL-751DNR Laser Duct Smoke Detector

    Provides Very Early Warning FireProtection per NFPA 76

    Ideal where high air velocity / high

    air changes per hour exists

    Combines InnovairFlex housingand addressable laser sensor

    (included) to achieve a ready-

    made solution

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    26/39

    SpectrAlertAdvance

    Dual Strobe Appliance

    D l S b S l i f S S

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    27/39

    Dual Strobe Solutions from System Sensor

    Single device plate

    Perform the function of 2-3 devices for MNS/ECSapplications

    Designed to be used in12 or 24 volt, DC or FWR(full wave rectified) systems

    ULC listed amber lens strobe

    Th V l f D l S b

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    28/39

    The Value of Dual Strobe

    Reduces installed back boxes

    Minimizes overall job cost

    Only one junction box

    Improved aesthetics

    Better than two installed units,

    low profile

    Simpler install than competitors

    Maintains current product feature set,

    including plug-in design

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    29/39

    Directional Sound Presentation

    Fire Alarm vs Directional Signal technology

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    30/39

    Fire Alarm vs. Directional Signal technology

    Fire Alarm(Detect ion & Alert ing )Early detection

    Warn of imminent danger

    Provide notification / warning via bells, horns,

    strobes, electronic sounders

    Directional SoundAudible sound to locate exits (or exit paths)

    Equivalence to Low Location Lighting notfire

    alarm sounder

    Different Types of Systems!

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    31/39

    The Evacuation Process

    Sounders sound Voice Evacuation

    Public start

    to evacuate

    % Successful Evacuation

    Fire Alarm Activated

    The Missing Link-

    Directional Signal

    Delay in evacuation

    Due to unwanted alarms

    creating public apathy

    Which way to go?

    How does the brain locate sound?

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    32/39

    How does the brain locate sound?

    Needs all 3 frequency bands:

    Low band

    Mid band

    High band

    All three elements above provide:

    broad band, directional sound

    Th H H i R

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    33/39

    20Hz 20KHz

    500Hz 3.5KHz

    5KHz3KHz1KHz

    Human

    speech *

    Low Mid High

    The Human Hearing Range

    *Between 2-3KHz is the frequency which is most

    sensitive to the human hearing and where all alarm

    sounders are placed.

    Between 1-3KHz gives no

    location cues.

    All 3 cues are required

    for accurate localization

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    34/39

    Problems exist when no smoke is present

    Visual clutter

    Airport terminal

    Shopping Mall

    Supermarket

    How do occupants find theemergency exits?

    Staircase Missed No Smoke

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    35/39

    Staircase Missed No Smoke

    Staircase Missed in Smoke

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    36/39

    Staircase Missed in Smoke

    Staircase Found in Smoke

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    37/39

    Staircase Found in Smoke

    Additional Resources

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    38/39

    Visit www.systemsensor.ca

    Orwww.notifier.comfor: Brochures

    Data sheets

    Engineering specifications

    Competitive matrix

    Competitive test report

    Informational videos

    PipeIQ software download

    Accessory details

    EASE Software

    Additional Resources

    Schedule a demo, tra in ing session or webinar for your

    staff and/or cus tomers to day

  • 8/10/2019 System Sensor Notifier Canada 2013 Rollout

    39/39

    Thank You