Cable conversion: Imperial to metric Welcome to the 3rd edition of the Technical Bulletin presented by Actemium ICS Gloucester. In this edition, we will consider the imperial and metric cable sizes. What is the difference? The AWG, or the American Wire Gauge, is a logarithmic stepped standard primarily used in America to measure the conducting wires using circular mil (kcmil) as a unit of measurement. In Europe and other parts of the world, the standard used to measure the conducting wires is expressed in a cross- Gloucester Instrumentation, Control & Switchgear Technical Bulletin 03/2019 sectional area in squared millimetre (mm2) and additionally, the amount of strand of wires in the diameter expressed in mm2. A conversion table from AWG/kcmil to mm2 and vice versa can be found on the second page.

Upload: others

Post on 09-Mar-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Technical Bulletin - Actemium UK...2019/12/03  · Instrumentation, Control & Switchgear. Technical Bulletin. 03/2019. sectional area in squared millimetre (mm2) and additionally,

Cable conversion: Imperial to metric

Welcome to the 3rd edition of the Technical Bulletin presented by Actemium ICS Gloucester.

In this edition, we will consider the imperial and metric cable sizes.

What is the difference?

The AWG, or the American Wire Gauge, is a logarithmic stepped standard primarily used in America to measure the conducting wires using circular mil (kcmil) as a unit of measurement.

In Europe and other parts of the world, the standard used to measure the conducting wires is expressed in a cross-

GloucesterInstrumentation, Control & Switchgear

Technical Bulletin

03/2019

sectional area in squared millimetre (mm2) and additionally, the amount of strand of wires in the diameter expressed in mm2.

A conversion table from AWG/kcmil to mm2 and vice versa can be found on the second page.

Page 2: Technical Bulletin - Actemium UK...2019/12/03  · Instrumentation, Control & Switchgear. Technical Bulletin. 03/2019. sectional area in squared millimetre (mm2) and additionally,

E: [email protected]: +44 (0)1452 713 222W: www.actemium.co.ukA: Actemium ICS GloucesterMeteor Business ParkCheltenham Road EastGloucester GL2 9QL

Switchgear

AWG to mm2 CONVERSION TABLE

AWG/kcmil [mm2]*

20 0.52

18 0.82

16 1.31

14 2.08

12 3.31

10 5.26

8 8.36

6 13.3

4 21.2

2 33.6

1 42.4

1/0 53.5

2/0 67.4

3/0 85.0

4/0 107250 127

300 152

350 177

400 203

450 228

500 253

600 304

750 380

800 405

1000 507

* Equivalent mm2 cross-sectional area

mm2 to AWGCONVERSION TABLE

mm2 [mm2]* AWG/kcmil

0.5 0.52 20

0.75 0.82 18

1.5 1.31 16

2.5 2.08 14

2.5 3.31 12

4 3.31 12

6 5.26 10

10 8.36 8

16 13.3 6

25 21.2 4

35 33.6 2

35 42.4 1

50 53.5 1/0

70 67/4 2/0

95 85.0 3/095 107 4/0

120 107 4/0

120 127 250

150 152 300

185 177 350

185 203 400

240 228 450

240 253 500

300 304 600

400 380 750

400 405 800

500 507 1000

Multiple AWG choices- consult responsible engineer for required ampacity

Actemium ICS products and solutions

Contact us

Control Systems Industrial Automation Package Solutions

www.actemium.co.uk

GloucesterInstrumentation, Control & Switchgear

Cable sizing: AWG (imperial) to mm2 (metric) conversion