test units and accessories - 2kshops.com · test units to test detectors and detector lines for...
TRANSCRIPT
-
A6V10203222_k_en_-- Building Technologies2018-08-24 Control Products and Systems
Cerberus™ PRO
Test units and accessoriesFDUL221, DX791, RE6, REF8, REF8-S, REF8-C, RE8, RE8-S, RE8-C, RE7T, RE8ST,RE8STCO, RE8-CO, RE7T-x, RE10, FDUM29x, FDLU291, LE3, StabexHF
Test units to test detectors and detector lines for FS720 fire detection installations.
Detector exchanger DX791 for the efficient installation and removal of Cerberuspoint detectors
Line tester FDUL221 for diagnosing detector lines Detector tester RE6 for use with environmentally-friendly test gas REF8, REF8-S,
REF8-C Detector tester RE7T with hot air generator, RE8ST with smoke capsule RE8-S,
RE8ST-CO with smoke capsule RE8-S, capsule RE8-CO, and CO capsule Detector tester RE10 for undertaking a function check on linear smoke detectors Telescope rods FDUM291/292 for extending detector exchangers and other
testers
-
2Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Line tester FDUL221
Properties 4-line display with 20 characters per line Menu-guided operation Supply with battery or via network adapter Possible to update the device software (firmware) via the MCL-USB adapter (radio)
FDUZ227 and via a PC Environmentally friendly processing Reusable materials Electronic parts and synthetic materials can be easily separated
FunctionDifferent functions can be called up, e.g.,:
Number of devices found at A and B connection Line errors found, location of the line error Short-circuit, open line, ground fault with indication of which conductor/s Total resistance is too high and/or charge voltage at the line end is too low Data transmission fault due to line capacitance being too high Browsing from detector to detector with screen displaying type and serial number Display of branches and choice of branch for scrolling Activating the internal alarm indicator of the selected detector and recognizing the
connected alarm sounder Extended operation and functionality on PC with line tester software FXS2017 The line tester software FXS2017 is included in the scope of delivery of the line tester
FDUL221.
Line tester software FXS2017
-
3Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
UseThe line tester FDUL221 is a universal device for the final testing of fully installed C-NET firedetector lines if a control panel is not connected. The device is used to search for errors forthe electrician, installer, or service technician.
3 421
578 6
1 On/Off button 5 2x terminal strips for the detector line
2 USB connection 6 Network adapter
3 Connection of a loop or stub line 7 Display
4 Shielding 8 Battery compartment on the underside for2x 9 V lithium batteries
Scope of delivery for FDUL221
-
4Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector exchanger DX791, adapter FDUD491
Properties Lightweight, robust design, made from reusable, environmentally friendly material Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods The point detector can be held in all positions. This makes it easier to work efficiently Compatible with
– Telescope rods FDUM291/292– Previous straight connectors VR10/11/12/13– MP/MT handles and straight connectors
FunctionEfficient installation and removal of the point detectors below.Adapter FDUD491 is an accessory part for detector exchanger DX791, which serves toinstall and remove point detectors OOH740 and OOHC740.
Installation/removal with detector exchanger DX791 Installation/removal with detector exchanger DX791 andadapter FDUD491
OH720 OOH740
OP720 OOHC740
HI720
HI722
1
2
82
4517
587
178
48
1 Point detector Detector exchanger DX791 withsuction cap 1)
Detector exchanger DX791 withadapter FDUD4912 Detector exchanger DX791
1) The suction cap is used to attach and remove the detector dust cap to and from thedetector.
-
5Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector tester RE6
The detector tester RE6 is used together with a test gas can REF8, REF8-S, or REF8-C.It is designed to test optical smoke detectors, ionization detectors, and CO detectors.
The detector tester is positioned over the detector for the testing process. Brief pressurecauses the test gas to flow into the measuring chamber of the detector and thereforesimulate the presence of fire aerosols. After a short period of time, the detector respondsand triggers the alarm.
REF8 and REF8-S are environmentally-friendly test gases and comply with strictenvironmental regulations. They do, however, contain flammable substances. REF8 isused for the temperature range 0…+40 °C and REF8-S for -20…+40 °C in dry and dampconditions. REF8-S is mainly used for temperatures below 0 °C or for point detectors thatonly trigger the alarm when there is a high level of smoke density or after longer signalintegration.
REF8-C is used to test the CO functionality of detectors with a CO sensor. REF8-C canbe used in dry and damp conditions at temperatures between -20 °C and +50 °C.
When transporting, e.g., in a car, we recommend protecting the detector tester and the testgas cans from heat.Please observe the notices on the detector tester for operation.
-
6Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector tester RE7T – Solo461 heat detector tester kit
The heat detector tester kit consists of 1x heat detector tester 2x rechargeable batteries 1x charger with 12 V connection cable 2x mains cables AC 110/120-220/240 V.
The heat detector tester contains a hot air generator. The heat detector tester is positionedover the detector for the function check. The hot air emitted heats the detector which triggersthis alarm.In high rooms, detectors positioned at an angle can be reached and tested using adaptersand telescope rods.The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The heat detector tester must not be used in electrical switching stations or areas wherethere is a danger of explosion.
-
7Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector tester RE8ST – Testifire 1001-101 RT test kit
The test kit RE8ST consists of 1x Testifire 1001-101 tester 1x RE8-S smoke capsule 2x rechargeable batteries 1x charger with 12 V connection cable 2x mains cables AC 110/120-220/240 V 1x USB cable.
The detector tester contains a smoke capsule. The detector tester is positioned over thedetector for the function check. The smoke that is emitted triggers an alarm.In high rooms, detectors positioned at an angle can be reached and tested using adaptersand telescope rods.The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The detector tester must not be used in electrical switching stations or areas where there isa danger of explosion.
-
8Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector tester RE8STCO – Testifire 1001-101 ST test kit
The test kit RE8STCO consists of 1x Testifire 2001-101 tester 1x RE8-S smoke capsule 1x RE8-CO CO capsule 2x rechargeable batteries 1x charger with 12 V connection cable 2x mains cables AC 110/120-220/240 V 1x USB cable.
The detector tester contains a smoke capsule or CO capsule. The detector tester ispositioned over the detector for the function check. The smoke or gas that is emitted triggersan alarm.In high rooms, detectors positioned at an angle can be reached and tested using adaptersand telescope rods.The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The detector tester must not be used in electrical switching stations or areas where there isa danger of explosion.
-
9Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Accessories and spare parts for RE7T/RE8ST/RE8STCO
RE7T-A – Solo719 adapter for FDUM29x
Mounting adapter for the detector testers RE7T, RE8ST, and RE8STCO on the telescoperods FDUM291 and FDUM292
RE7T-B1 – Solo770 battery
Battery as spare part
RE7T-C1 – Solo727 charger
Charger as spare part for charging the batteries RE7T-B1
RE8-S smoke capsule for RE8ST and RE8STCO
RE8-CO CO capsule for RE8STCO
-
10Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Telescope rods FDUM291 and FDUM292
Properties Light and robust yellow plastic pipes – non-conductive material. Plastic sockets and friction bearings ensure that the pipes run into each other easily. Quick spring-type locking mechanisms allow continuous adjustment of the length. The pipes can be extended to their maximum length. A stop is used to prevent them from
extending further. Previous testers can be used. The telescope rods cannot be extended.
WARNING
Falling objectsDanger of injury
Always wear a hardhat when working with telescope rods.
WARNING
Approaching or touching live linesElectric shock
Only use testers with telescope rods in volt-free areas.
-
11Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
FDUM291 Light telescope rod for all applications in rooms up to 5.5 m high Flap closure for continuous adjustment of the length Three-part telescope with tri-oval pipes as practical grip Twisting the pipe in the opposite direction is not possible Weight: 1.2 kg without tester fitted Retracted length 1.6 m, extended length 4.2 m
FDUM292 Long and robust telescope rod for all applications in rooms up to 8 m high Flip top closure for continuous adjustment of the length Sturdy four-sided telescope with round pipes Weight: 3.4 kg without tester fitted Retracted length 2.1 m, extended length 7.3 m
1 Flip top closure 2 Flap closure
-
12Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector tester RE10, alarm test filter TF04
For undertaking a function check on the linear smoke detectors. The alarm test filterTF04 is inserted into the detector tester in accordance with the type of detector to betested.An alarm test filter is also included in the adjustment kit FDLU291.
For testing, the detector tester is held in front of the detector lens in the IR beam. Thedetector responds after a few seconds.
Adjustment kit FDLU291
The adjustment kit is used for commissioning the linear smoke detector FDL241-9. The lensof the linear smoke detector can be efficiently aligned to the reflector by one man.
Scope of delivery: Case with adjustment device Alarm test filter Visor Magnet Spiral cable MC link cable 9 V battery Suspension fixture with cable grippers and chain
-
13Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
LE3 Test lamp
The test lamp LE3 is used to test the function of all flame detectors over distances up to10 m. It is housed in a transportable case together with the required accessories. In addition,the case enables the test lamp to be kept in a dust-free condition.The quartz-halogen lamp used creates an intense ray of light. This helps to align the lamp onthe detector which is to be tested. During the detector test, the ray of light is modulated. Theluminous intensity can be set in accordance with the distance.The power is supplied by a rechargeable battery. Since the color of the light depends on thecharge state of the battery, it must always be charged in buffer mode. A special charger isavailable for this.
WARNING
Use of test lamps in areas at risk of explosionRisk of explosion
Do not use the test lamp LE3 in areas at risk of explosion.
Test lamp Stabex HF
The test lamp Stabex HF is used to test the function of intrinsically safe flame detectors inzone 1 or 2 areas at risk of explosion.The lamp is used directly in front of the detector for the test. The ray of light must be pulsedwith the sliding switch at half-second intervals.
WARNING
Opening test lamps in areas at risk of explosionRisk of explosion
Do not open the test lamp Stabex HF in areas at risk of explosion.
-
14Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Technical data
Line tester FDUL221Supply voltageBattery or viaNetwork adapter
Min. DC 10 V, max. DC 30 V2 x 9 VAC 240 V / DC 24 V, 750 mA
Power consumption during measurement Depends on the number of devices and thedisplay backlight
Detector line voltage:C-NET (FS720)C-NET
DC 32 VDC 28 V
Max. detector key figures (MK) per line:MK with network adapterMK with battery
Min. 550Min. 150
Operating temperature -25…+40 °CStorage temperature without batteryStorage temperature with battery
-30…+75 °C-25…+60 °C
Air humidity (no condensation permitted) 95 % rel.
Detector exchanger DX791Dimensions (Ø x H):With suction capWith adapter FDUD491
82 x 175 mm87 x 178 mm
Detector tester RE6Operating temperature:REF8REF8-SREF8-C
0…+40 °C-20…+40 °C-20...+50 °C
Storage temperature -20…+40 °CNumber of detector tests; dependent on detector type Max. 400
Heat detector tester RE7TOperating temperature 5...+45 °CStorage temperature -10…+50 °CAir humidity (no condensation permitted) 95 % rel.Voltage Auto: DC 12 V
Mains: AC 110/120-220/240 VCharging time Approx. 1 hour per battery
-
15Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Detector tester RE8ST/RE8STCOOperating temperature 5...+45 °CStorage temperature -10…+50 °CAir humidity (no condensation permitted) 95 % rel.Voltage Auto: DC 12 V
Mains: AC 110/120-220/240 VCharging time Approx. 1 hour per battery
Adjustment kit FDLU291Dimensions of the adjustment device 120 x 65 x 22 mm
Test lamp LE3Power consumption 50 WModulation frequency 4 HzMax. distance for alarm activation 10 mMeasuring capacity with charged battery and max. distanceNumber of detectors ~ 50Operating and storage temperature -20...+45 °CAreas of use Areas not at risk of explosionIncandescent lamp Halogen 12 V / 50 WBattery 12 V / 7 Ah, lead, gas tightCharging time Min. 16 hMains connection charger AC 220 / 240 V, 50…60 HzDimensions:Test lampBattery
178 x 180 x 369 mm153 x 103 x 67 mm
Test lamp Stabex HFMax. distance for alarm activation A few cmOperating and storage temperature -20…+40 °CExplosion protection II 2 G EEx ib e IIC T4Ex approval PTB 98 ATEX 2062Areas of use Zones 1 and 2Protection category IP65Incandescent lamp Halogen 2.8 V / 0.5 ABattery 2x alkali batteries 1.5 V
Mono cell UM-1
-
16Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Disposal
The device is considered an electronic device for disposal in accordancewith the European Guidelines and may not be disposed of as domesticgarbage.
Dispose of the device through channels provided for this purpose. Comply with all local and currently applicable laws and regulations. Dispose of empty batteries in designated collection points.
Details for ordering
Type Item number Designation WeightLine tester FDUL221 A5Q00004397 Line tester with line connection kit
FDUL221-A, power unit setFDUL221-B and carry case
1.567 kg
Accessories – A5Q00004142 Lithium manganese dioxide battery9 V / 1.2 Ah
0.035 kg
Spare part FDUL221-A A5Q00008436 Line connection set 0.088 kgFDUL221-B A5Q00008437 Power unit set 0.278 kgFDUL221-C A5Q00008438 PC cable RS232 as spare part for
FDUL221 with interface RS2320.037 kg
Type Item number Designation WeightDetector exchanger DX791 S54319-F6-A1 Detector exchanger 0.082 kgAdapter FDUD491 S54319-F18-A1 Adapter 0.034 kg
Type Item number Designation WeightDetector tester RE6 BPZ:3680300001 Detector tester for smoke detectors 0.950 kgAccessories REF8 A5Q00011687 Test gas can 0.194 kg
REF8-S A5Q00011688 Test gas can 0.186 kgREF8-C S54370-N2-A1 Test gas can CO 0.203 kg
Type Item number Designation WeightDetector tester RE7T S54370-S3-A1 Solo461 heat detector tester kit
consisting of tester, 2 batteries,charger, cable
2.800 kg
Accessories RE7T-A S54370-N4-A1 Solo719 adapter for FDUM29x 0.260 kgSpare part RE7T-B1 S54370-N7-A1 Solo770 battery for RE7T 1.090 kg
RE7T-C1 S54370-N8-A1 Solo727 charger for RE7T 1.210 kg
Type Item number Designation WeightDetector tester RE8ST S54370-S23-A1 Testifire 1001-101 ST test kit 3.470 kg
RE8STCO S54370-S24-A1 Testifire 2001-101 STCO test kit 3.750 kgCapsule RE8-S S54370-N25-A1 TS3 smoke capsules (6 pieces) 0.079 kg
RE8-CO S54370-N22-A1 TS3 CO capsules (6 pieces) 0.077 kgAccessories RE7T-A S54370-N4-A1 Solo719 adapter for FDUM29x 0.260 kgSpare part RE7T-B1 S54370-N7-A1 Solo770 battery for RE7T 1 1.090 kg
RE7T-C1 S54370-N8-A1 Solo727 charger for RE7T 1 1.210 kg
1) Compatible with RE8ST and RE8STCO
-
17Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Type Item number Designation WeightTelescope rod FDUM291 A5Q00004996 Telescope rod – three-part telescope
with tri-oval pipes; 1.6 m / 4.2 m1.960 kg
Spare part – A5Q00009787 Lever with screw and nut –flip top closure
0.023 kg
– A5Q00009786 Adapter with lever, screw, and nutincl. mounting and sleeve bolt
0.088 kg
– A5Q00009788 Small flap with screw and nut – flapclosure
0.015 kg
– A5Q00009789 Large flap with screw and nut – flapclosure
0.016 kg
Type Item number Designation WeightTelescope rod FDUM292 A5Q00004997 Telescope rod – four-part telescope
with round pipes; 2.1 m / 7.3 m4.480 kg
Spare part – A5Q00009787 Lever with screw and nut – flip topclosure
0.023 kg
– A5Q00009786 Adapter with lever, screw, and nutincl. mounting and sleeve bolt
0.088 kg
Type Item number Designation WeightDetector tester RE10 BPZ:3685190001 Detector tester for linear smoke
detectors0.345 kg
Alarm test filter forRE10
TF04 BPZ:4931090001 Alarm test filter – absorption 77 % 0.005 kg
Type Item number Designation WeightAdjustment kit FDLU291 A5Q00004905 Adjustment kit for linear smoke
detectorincl. case
0.840 kg
Type Item number Designation WeightTest lamp LE3 BPZ:3669510001 Test lamp for flame detector incl.
case and charger, without battery5.260 kg
Accessories FA2003-A1 A5Q00019353 Battery 12 V / 7 Ah / VdS 2.293 kgSpare part BPZ:3679630001 Halogen lamp 12 V / 50 W 0.395 kg
Type Item number Designation WeightTest lamp Stabex HF BPZ:4620910001 Test lamp for areas at risk of
explosion0.175 kg
-
18Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Couper Crouse-Hinds GmbH; Neuer Weg-Nord 49D-69412 Eberbach
Technical data: see doc. A6V10203222
STABEX HF - Stabex HF Hand lamp. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/34/EU (ATEX): EN 60079-0 / EN 60079-7 / EN 60079-11 / EN 60079-31 ; 2011/65/EU (RoHS): EN 50581The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/downloadDoC: No.: CED-STABEX_HF
STABEX HF
Siemens Schweiz AG; Theilerstrasse 1aCH-6300 Zug
Technical data: see doc. 000252
LE3 - Test lamp. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 / EN 61010-1 / EN 55024 ; 2011/65/EU (RoHS): EN 50581The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/downloadDoC: No.: CED-LE3
LE3
Siemens Schweiz AG; Theilerstrasse 1aCH-6300 Zug
Technical data: see doc. 008250
FDUL221 - Line tester Sinteso. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581 / EN 55024The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/downloadDoC: No.: CED-FDUL221
FDUL221
Detectortesters (No Climb Products Limited), Edison House,163 Dixons Hill Road, Welham Green, Hertfordshire, AL9 7JE United Kingdom
Technical data: see doc. A6V10252901RE7T-B1 Solo770 Battery for RE7T
2014/30/EU (EMC): EN 55011 / EN 61000-4-2 / EN 61000-4-3 ; 2014/35/EU (LVD): EN 62133 ; 2011/65/EU (RoHS): EN 50581
The EU Declaration of conformity (DOC), which is obtainable via Detectortesters (No Climb Products Limited)
DoC No.: Solo 461 (Solo 460-770-727) New Framework EU Declaration of Conformity-M
RE7T-B1
RE7T-C1 Solo727 Charger for RET7.2014/30/EU (EMC): EN 55014-1 / EN 55014-2 ; EN 61000-3-2 / EN 61000-3-3 ; 2014/35/EU (LVD): EN 60335-1 / EN 60335-2-29 ; 2011/65/EU (RoHS): EN 50581
The EU Declaration of conformity (DoC), which is obtainable via Detectortesters (No Climb Products Limited)
DoC No.: Solo 461 (Solo 460-770-727) New Framework EU Declaration of Conformity-M
RE7T-C1Detectortesters (No Climb Products Limited), Edison House,
163 Dixons Hill Road, Welham Green, Hertfordshire, AL9 7JE United KingdomTechnical data: see doc. A6V10252901
-
19Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Applicable documents
Document ID NameA6V10229261 List of compatibility (for 'Cerberus™ PRO' product line)A6V10201731 Installation Detector exchanger DX791, adapter for detector
exchanger FDUD491A6V10254740 Operating instructions Solo461 heat detector tester kit RE7TA6V10387053 Installation RE8ST Testifire 1001-101 ST test kit, RE8STCO
Testifire 2001-101 STCO test kitA6V10260320 Operation RE7T-C Solo726 charger for RE7T-BA6V11432110 Operation RE7T-C1 Solo727 charger for RE7T-B1 Solo770008250 Technical Manual Line tester FDUL221A6V10395483 Line tester – operating instructions for electricians007016 Technical manual Linear smoke detector FDL241-9000257 Operating instructions Test lamp LE3Safety data sheetsA5Q00011687D Safety data sheet REF8A5Q00011688D Safety data sheet REF8-SA5Q00035329C Safety data sheet REF8-C
MCL-USB adapter (radio) FDUZ227, see data sheet A6V10355605.
-
20Building Technologies A6V10203222_k_en_--Fire Safety 2018-08-24
Issued bySiemens Switzerland LtdBuilding Technologies DivisionInternational HeadquartersTheilerstrasse 1aCH-6300 ZugTel. +41 58 724 2424www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2008Technical specifications and availability subject to change without notice.
Document ID A6V10203222_k_en_-- Manual FD720Edition 2018-08-24 Register 9