title of presentation enhancement of the coefficient of performance in air conditioning systems by...
TRANSCRIPT
Title of Presentation
ENHANCEMENT OF THE COEFFICIENT OF PERFORMANCE IN AIR CONDITIONING SYSTEMS BY
UTILIZING FREE COOLING
A. Al-Salaymeh1, M. Al-Salaymeh2, M. Rabah3, M. Abdelkader1
1Mech. Eng. Dept., University of Jordan, Amman, Jordan2Jordan Telecommunication Company, Zarka, Jordan
3Mech. Eng. Dept., Al-Balqa Applied University, Amman, Jordan
1
2nd International Conference on Thermal Engineering Theory and ApplicationsJanuary 3 - 6, 2006, Al Ain, United Arab Emirates
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Contents of Presentation 2
INTRODUCTION
BASIC DEFINITIONS
ELEMENTS OF REFRIGERATION AND AIR CONDITIONING SYSTEMS
COMPRESSORS
REFRIGERANT AND REFRIGERANT FLOW CONTROL
FREE COOLING
ECONOMIC STUDY OF USING FREE COOLING
CONCLUSIONS
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Introduction 3
All sources of energy may be grouped into two general categories:
Income energy, which is the energy reaching the earth from outer space,
Capital energy, which is the energy that already exists on or within the earth.
The utilization of income energy sources is very attractive because they are nondepletable sources of energy and they are relatively pollution free.
Jordan is relatively poor in conventional resources and is basically a non-oil-producing country, i.e. about 95% of its needs being supplied from abroad as crude oil and refined products.
It is therefore unlikely that any future energy scenario for Jordan will not include a significant proportion of its energy coming from Renewable Energy.
It is clear that the government’s plan requires consideration of the increased energy demands of the country and the undertaking of research and development efforts towards solutions of current problems.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Energy Policy in Jordan 4
The energy demand in Jordan has doubled during the last 20 years, and is expected to continue at the same rate, or even higher.
All recent energy forecast scenarios have shown that national energy consumption might double between 2015 and 2020.
Such a rapid increasing demand is due to the high growth rate of the population and the expansion of economical activities in various fields.
By high oil prices, the government is undertaking new measures to improve the situation in the energy sector by formulating and implementing an adjustment plan.
The demand for primary energy in Jordan is 4.8 million tons of oil equivalents (toe), showing a 3% annual growth
The primary energy consumption that was required for electricity generation in 2000 was equivalent to 1.8 million toe.
The average energy consumption per inhabitant is 970 kg oil equivalent.
It is predicted that electricity generation of Jordan will be around 12500 and 15000 GWh in 2010 and 2015, respectively.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
5Existing Knowledge & Aim of the Work
The share of solar energy in the total energy mix in Jordan is estimated to be around 1.7% during the year 2002.
The expected share of solar energy in the total energy mix in the year 2007 is estimated to be around 2.1%.
All the above-mentioned attempts to ensure Jordan’s energy supply do not eliminate the need to search for new energy sources in the country.
In order to reduce dependence on the imported oil, Jordan has pursued programs for promoting solar energy involving systematic monitoring and assessment of technological developments combined with the implementation of appropriate technologies, demonstrations and pilot projects.
Free cooling technique in air conditioning system can be utilized to save the energy consumption.
The present work shows the economics study of utilizing free cooling in air conditioning system.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Elements of Air Conditioning 6
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Phases in the Cooling Circuit 7
•Compressor makes up the pressure in the discharge line to the condenser coil.
• Due to the cooling effect of the air flow across the condenser the refrigerant vapour will condense to liquid form and heat will be released to the condenser air flow.
• The refrigerant liquid will run into the receiver, which the liquid line to the thermostatic valve, always will be full of refrigerant.
• The filter dryer obtain impurities and humidity.
• The solenoid valve is operating ON/OFF and is an important part in the “Pump down” system.
• The thermostatic expansion valve is located just before the evaporator. The valve releases sufficient amount of refrigerant to the give a little superheat of 4-6C ensuring that all liquid has evaporated.
• The evaporation of refrigerant takes place at low pressure in the evaporator and because the refrigerant has a low boiling temperature, the evaporation process needs heat energy. Heat is taken from the air passing through the evaporator coil, the result will be that the air flow is cooled.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Free Cooling (1) 8
Free cooling take place when the external ambient air temperature is less than the indoor air temperature
Air conditioning systems either provide supply air using:
A mixture of outside air and recirculated (return) air from the shiltter room.
100% outside air systems which are generally used in the cases of hospitals, densely occupied areas such as theatres etc.
Free cooling may be used with mixed outside air and recirculation systems by the use of modulating dampers.
Dampers are provided on the outside air intake ductwork, exhaust air ductwork and the recirculation ductwork.
In the event of cool outside air the quantity of outside air is increased and the quantity of recalculated air is reduced to provide the required supply air temperature. In this way cooling by means of refrigeration equipment is avoided altogether at certain times of year and often at night times.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Free Cooling (1) 9
During cool weather, the outside ambient temperature can help save energy in Air conditioning systems.
The low temperature of the cooling ambient air supply enables free cooling of computer rooms.
Free cooling can be used to save energy whenever the outside wet-bulb temperature drops below the required cooling air set-point.
This energy-efficiency measure can save enough compressor electric power to pay for damper installation costs in less than 2 years.
When the outside air temperature is higher than the room temperature in Summer the dampers will modulate to the minimum outside air position to keep the load on the refrigeration equipment to a minimum.
The free cooling version has a motorized damper that conducts the two flows of internal and external air. When the damper is open it takes the air necessary for cooling directly from the exterior, excluding compressor operation as shown in Figure.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Principle Operation 10
Free cooling offFree cooling on
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Economic Study of Using Free Cooling
11
The air conditioning system (small shiltter) uses “free” cooling techniques to reduce energy costs.
COP which is the ratio of cooling energy provided divided by the amount of energy used to run the refrigeration plant, has typical values between 3 and 5.
The 4 ton cooling load in JTC buildings represents about 13.69 kW of cooling load, which is effectively provided with about 3.75 of electrical consumption for a COP of 3.65.
However there are periods of the year where (in the case of JTC cooling ambient temperature can be utilized to provide nearly free cooling (COP > 90 – where the only energy consumption is from the use of evaporative fans.
The compressor of A/C is shut off during this period, thereby saving energy
The compressor of A/C can be shut down form 1 to as may as 4 months a year (from November until February).
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Case Study 12
Small equipment room containing telecommunication racks, file servers or a midrange computer and it needs cooling. The hardware manufacturer recommends controlled conditions of 22C 2C and a relative humidity of 50% 5%.
Usually, a package air conditioning system is used in order to cool the room to the desired condition.
The cost of electrical energy is increasing because of the increasing prices of the oil and the high demand on the oil and the shortest resources of energy.
This fact was the main motivation for many researchers and scientific people to look for a method for saving energy. The new scientific work was resulted developing the free cooling technology in air conditioning system.
This method is based on using the outside air when the ambient temperature decreases below the desired inside temperature. Since the equipment room contains some telecommunication devices such as servers and computers, its temperature is usually high.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Technical Data (1) 13
Model
Evaporator DataAMBIENT TEMEATURE F
75 85 95 100 105 115
Air Flow Rate
On CoilTotal
Capacity
Sensible Capacit
y
Total Capacity
Sensible Capacity
Total Capacity
Sensible Capacity
Total Capacity
Sensible Capacity
Total Capacity
Sensible Capacity
Total Capacity
Sensible CapacityD
BWB
CFM F F MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH
PWM 20
750
76 63 22.1 16.0 21.1 15.6 20.1 15.2 19.6 15.0 19.2 14.8 18.1 14.4
78 65 22.9 15.9 21.9 15.5 20.9 15.1 20.4 14.9 19.9 14.8 18.7 14.3
80 67 23.9 15.9 23.0 15.6 22.0 15.2 21.4 15.0 20.9 14.8 19.8 14.4
PWM 25
900
76 63 26.2 19.2 25.1 18.8 23.9 18.3 23.2 18.0 22.7 17.8 21.4 17.3
78 65 27.1 19.1 25.9 18.7 24.7 18.2 24.1 18.0 23.5 17.8 22.2 17.3
80 67 28.3 19.2 27.1 18.7 25.9 18.3 25.3 18.0 24.7 17.8 23.4 17.3
PWM 33
1060
76 63 34.2 25.0 32.5 24.2 30.7 23.5 29.7 23.1 28.8 22.7 26.8 21.9
78 65 35.4 24.8 33.6 24.1 31.8 23.4 30.9 23.1 30.0 22.7 27.9 21.9
80 67 37.1 24.9 35.3 24.2 33.4 23.5 23.5 23.1 31.5 22.8 29.4 22.0
PWM 42
1600
76 63 44.4 31.5 42.3 30.6 40.1 29.7 38.8 29.2 37.6 28.7 35.1 27.7
78 65 45.9 31.3 43.9 30.5 41.6 29.6 40.3 29.1 39.1 28.7 36.5 27.7
80 67 48.2 31.4 46.0 30.5 43.6 29.7 24.4 29.2 41.1 28.8 38.4 27.8
PWM 48
2000
76 63 49.4 36.1 47.3 35.2 45.0 34.3 44.0 33.9 42.8 33.5 40.6 32.6
78 65 51.1 35.9 48.9 35.1 46.7 34.2 45.6 33.8 44.5 33.4 42.3 32.6
80 67 53.4 35.9 51.1 35.1 48.9 34.3 47.9 33.9 46.7 33.5 44.4 32.7
PWM 58
2100
76 63 57.6 43.7 55.2 55.2 52.8 41.7 51.5 41.2 50.2 40.7 47.7 39.8
78 65 59.6 43.5 57.1 57.1 54.6 41.6 53.4 41.1 52.1 40.6 49.5 39.6
80 67 62.3 43.5 59.8 59.8 57.4 41.7 56.0 41.2 54.6 40.7 51.8 39.7
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Technical Data (2) 14
PWM Model
Power Supply
Compressor CFM EFM
Nominal Motor Power
HP(Kw)
No.
LRA(Each
)(AMP
)
RLA(Each
)(AMP
)
Motor (Kw)
No.
FLA(Each
)(AMP
)
Motor (Kw)
No.
FLA(Each
)(AMP
)
PWM 20
220-240 V/1 ph/50 Hz
2(1.49) 1 46 11.9 0.165 1 0.8 0.147 1 1.7
PWM 25 2.5(1.87) 1 58 15 0.165 1 0.8 0.147 1 1.7
PWM 33 3(2.24) 1 87 19.1 0.165 1 0.8 0.147 1 1.7
PWM 42
280-420 V/3 ph/50 Hz
3.5(2.61) 1 42 8.2 0.245 1 1.1 0.147 1 1.7
PWM 48 4.5(3.36) 1 55 10.4 0.245 1 1.1 0.147 1 1.7
PWM 58 5(3.73) 1 65 9.6 0.245 1 1.1 0.147 2 1.7
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Technical Data (3) 15
The electrical data for power supply are:1.Compressor: Nominal Motor Power = 4.5 HP = 3.36 kW.2.Condenser for Motor = 0.245 kW.3.Evaporator for Motor = 0.147 kW.
Total electrical Input power = Motor Power for Compressor + Condenser + Evaporator
= 3.36 + 0.245 + 0.147 = 3.75 KW.
The Coefficient of Performance = COP = 13.69/3.75 = 3.65
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Room Volume = 3.0 m 2.5 m 2.5 m
Air flow rate for evaporator = 2000 cfm.
Cooling capacity of air conditioning system = 4.0 ton cooling load.
The outside ambient temperature at Zarka city was taken as 95F (35C)
Ambient Temperature 16
0
5
10
15
20
25
30
35
40
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
Tem
pe
ratu
re C
Tmin °CTmax °C
A comparison between the monthly average of minimum and maximum temperature values of Zarka city as a function of months
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
0
5
10
15
20
25
30
35
40
0 2 4 6 8 10 12
Month
Tem
per
atu
re C
Tmin °C
Tmax °C
The Cost of Operating A/C Without Free Cooling
17
0
5
10
15
20
25
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
No
. o
f O
pe
rati
ng
Ho
urs
Compressor
• Cost of 1 kWh electricity = 0.05 JD
• Number of operating hours for A/C in April day is 12 hours.
•Total number of operating hours in April for A/C is 30 * 12 = 360 hours
• The cost of 360 hours per 1 kWh power = 360 * 0.05 = 18 JD
• Since our selected A/C has a total input electrical power of 3.75 kW,
Cost in April month = 30 days * 12 hours * 0.05 JD * 3.75 kW= 67.5 JD
0
20
40
60
80
100
120
140
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
Co
st
(JD
)
Compressor Cost
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Cost of Operating Evaporator Fan Without Free Cooling
18
Normally, the air conditioning unit in JTC is permanently operated and therefore the evaporator fan will continue work during the time which the compressor is not working.
The electrical power for evaporator motor = 0.147 kW.The evaporator fan will be worked 12 hours more in April month,
therefore:Cost in April for evaporator fan = 30 days* 12 hours*0.05 JD*0.147
kW = 2.64 JD
0
2
4
6
8
10
12
14
16
18
20
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
No
. of
Op
era
tin
g H
ou
rs
Evaporator Fan
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Jan. Feb. March April May June July August Sept. Oct. Nov. Dec.Month
Co
st
(JD
)Evaporator Cost
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Total Cost of A/C Without Free Cooling
19
0
20
40
60
80
100
120
140
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
Co
st (
JD)
Evaporator CostCompressor CostTotal Cost
Total cost of A/C in April month that operates 24 hours per day (12 hours complete operation and 12 hours evaporator fan only) is: 67.5+2.64 = 70.14 JD
Total yearly cost = Sum of total electricity cost during 12 months = 948.5 JD
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
•Total electricity cost of the selected A/C in addition to the cost of the evaporator fan at different months.
Cost of Operating A/C with Free Cooling
20
No. of operating hours for A/C in April in the presence of free cooling is 5 hrs/day
Total number of operating hours in April for A/C is 30 * 5 = 150 hours
The cost of 360 hours per 1 kWh power = 150 * 0.05 = 7.5 JD
Since our selected A/C has a total input electrical power of 3.75 kW, therefore the total cost of operating such a unit during April is
Cost in April month = 30 days * 5 hours * 0.05 JD * 3.75 kW= 28.125 JD
0
2
4
6
8
10
12
14
16
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
No
. of
Op
erat
ing
Ho
urs
Compressor
0
10
20
30
40
50
60
70
80
90
100
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
Co
st
(JD
)
Compressor Cost
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Cost of Operating Evaporator Fan with Free Cooling
21
The electrical power for evaporator motor = 0.147 kW.
The evaporator fan will be worked 19 hours more in April month, therefore
Cost in April for evaporator fan = 30 days * 19 hours * 0.05 JD * 0.147 kW = 4.19 JD
0
5
10
15
20
25
30
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
No
. of
Op
era
tin
g H
ou
rs
Evaporator Fan
0
1
2
3
4
5
6
Jan. Feb. March April May June July August Sept. Oct. Nov. Dec.Month
Co
st
(JD
)Evaporator Cost
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Total Cost of A/C without Free Cooling
22
The total cost of A/C in April month that operates 24 hours per day (5 hours complete operation and 19 hours evaporator fan only) is 28.125 JD + 4.19 JD = 32.135 JD
Total yearly cost = Sum of total electricity cost during 12 months = 543.92 JD
0
10
20
30
40
50
60
70
80
90
100
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
Co
st (
JD)
Evaporator Cost
Compressor Cost
Total Cost
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Total electricity cost of the selected A/C in addition to the cost of the evaporator fan at different months
Total Cost With & Without Free Cooling
23
Total cost of operating A/C without free cooling = 948.50 JD/ year.
Total cost of operating A/C unit with free cooling = 543.92 JD/year.
The difference in the cost = 948.50 – 543.92 = 404.58 JD.
% of money saving = 404.85/948.50 = 42.6%
This result means that 42.6% from the total cost of electricity can be saved each year in the case of using free cooling technique.
The capital cost of the A/C system with dampers for free cooling is higher than the normal A/C by about 500 JD.
This means that the difference in the Capital Cost can be recovered after one year from operation because the running cost of operating A/C with free cooling is 400-500 JD less than the normal A/C
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Total Cost With & Without Free Cooling
24
0
20
40
60
80
100
120
140
Jan.
Feb.
Mar
chApr
ilM
ayJu
ne July
Augus
t
Sept.
Oct.Nov
.Dec
.
Month
Co
st (
JD)
Total Cost with Free Cooling
Total Cost without Free Cooling
A comparison between the total electricity cost for operating air conditioning unit in the case of presence or absence of free cooling at the
desired location and the required cooling capacity.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
0
20
40
60
80
100
120
140
0 2 4 6 8 10 12
Month
Co
st
(JD
)
Total Cost with Free Cooling
Total Cost without Free Cooling
Poly. (Total Cost with FreeCooling)Poly. (Total Cost without FreeCooling)
Total Cost With & Without Free Cooling
25
• The Coefficient of Performance (COP) can be reached a very high value in the case of free cooling.
• As it is known, the coefficient of performance is defined as the ratio between the output cooling load and input electrical power.
• The output cooling load is the same in the two cases which are the presence of free cooling air conditioning unit and in the absence of free cooling.
• But, the electrical input power is reduced in the case of free cooling and the input power is only the power needed for evaporator fan.
• Therefore, the calculated value of the coefficient of performance in the presence of free cooling is:The Coefficient of Performance = COP = 13.69/0.147 = 93.13 While in the absence of free cooling
The Coefficient of Performance = COP = 13.69/3.75 = 3.65
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Conclusions 26
• The main purpose of this project to study the utilizing of free cooling in the A/C system especially for the rooms which contains some heat generating sources and they needs to be cooled all days around the year. •During cool weather, the outside ambient temperature can help save energy in A/C systems. • The 4 ton cooling load in JTC buildings represents about 13.69 kW of cooling load, which is effectively provided with about 3.75 kW of electrical consumption for a COP of 3.65. • However there are periods of the year where cooling ambient temperature can be utilized to provide nearly free cooling and the COP > 90 – where the only energy consumption is from the use of evaporative fans.• The A/C system uses “free” cooling during cold weather without the requirement to run a compressor. The compressor of A/C is shut off during this period, thereby saving energy. •The cost for damper installation can be recovered in less than two years.
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
End of presentation 27
2nd ICTEA, January 3 - 6, 2006, Al Ain, UAE
Everything should be made as simple as possible, but not simpler. Albert Einstein (1879 - 1955) A theory is something nobody believes, except the person who made it. An experiment is something everybody believes, except the person who made it. Albert Einstein (1879 - 1955)
It is a capital mistake to theorize before one has data. Insensibly one begin to twist facts to suit theories instead of theories suit facts. C. Doyle
Thanks for you attention,
استماعكم لحسن جزيلا شكرا
The Final Conclusion !