Variable Speed ModularMulti-position Air Handlers2-5 Tons

TAM7A0A24H21SATAM7A0B30H21SATAM7A0C36H31SATAM7A0C42H31SATAM7A0C48H41SATAM7A0C60H51SA

PUB. NO. 22-1847-02

Page 2: Trane Manual a-C 6209 Attic

2 Pub. No. 22-1847-02

Featuresand Benefits

© 2011 Trane

• Air-Tite II™ cabinet – 2% or less air leakage – Precision applied - durable door

seals – Specially designed air seal around

refrigerant, condensate and conduit connections

– Double wall foamed cabinet system – ≥ R-4.2 insulating value – No loose fiber design – Smooth cleanable interior design – Sweat eliminating design – Composite foamed cabinet doors – Water proof cabinet design – Integrated horizontal drain pans – Modular cabinet with 5/16" allen

wrench "quick latch" design • Multi-position up/down flow horizontal

left/right• Side return option (sold as accessory)• Control board protection pocket built

into cabinet wall• Alert port to view control board codes

without door removal

• Alert code notification• Low voltage terminal connection point• Quarter turn phillips head door fasten-

ers• Vortica® blower with polarized plug

connections and integrated slide deck for easy removal

• Aluminum coil with integrated slide deck for easy removal and polar-ized plug connections on coil EEV

• Patented enhanced coil fin• Electronic Expansion Valve (EEV) with

low ambient and low superheat compressor protection

• Dual refrigerant compatible as shipped• Slide in electric heaters with polarized

plug connections (sold as accessory)

• Slide in hot water coils with polarized plug connections (sold as accessory)

• UVC light kit with safety switch and polarized plug connections (sold as accessory)

• Labeled panels and connections• Molded in 1" standard filter rail• Variable speed ECM motor• Soft start fan motor operation• Comfort RTM mode• Built in fan delay modes• Maximum width of 23.5"• Compact 20.8" depth with doors

removed• Two tone color• Fused 24v power• Safety door switch• 1-year warranty • 10-year warranty registered• Optional extended warranty avail-

able

Page 3: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 3

Contents

Features and Benefits 2Optional Equipment 4

“Air-Tite II™” Features and Benefits 5

General Data 6TAM7A0A24H21SA 6TAM7A0B30H21SA 6TAM7A0C36H31SA 6TAM7A0C42H31SA 6TAM7A0C48H41SA 6TAM7A0C60H51SA 6

Performance Data 7Electrical Data 19

Field Wiring 26

Convertibility 30

Dimensions 31

Page 4: Trane Manual a-C 6209 Attic

4 Pub. No. 22-1847-02

Optional Equipment

Accessory Number Description Fits Cabinet Size

BAYEVAC05BK1AA Electric Heater, 5kW, Breaker, RS-485 Control, 1 Ph A to C

BAYEVAC05LG1AA Electric Heater, 5kW, Lugs, RS-485 Control, 1 Ph A to C

BAYEVAC08BK1AA Electric Heater, 8kW, Breaker, RS-485 Control, 1 Ph A to C

BAYEVAC08LG1AA Electric Heater, 8kW, Lugs, RS-485 Control, 1 Ph A to C

BAYEVAC10BK1AA Electric Heater, 10kW, Breaker, RS-485 Control, 1 Ph A to C

BAYEVAC10LG1AA Electric Heater, 10kW, Lugs, RS-485 Control, 1 Ph A to C

BAYEVBC15BK1AA Electric Heater, 15kW, Breaker, RS-485 Control, 1 Ph B to C

BAYEVBC20BK1AA Electric Heater, 20kW, Breaker, RS-485 Control, 1 Ph B to C

BAYEVCC25BK1AA Electric Heater, 25kW, Breaker, RS-485 Control, 1 Ph C

BAYEVAC10LG3AA Electric Heater, 10kW, Lugs, RS-485 Control, 3 Ph A to C

BAYEVBC15LG3AA Electric Heater, 15kW, Lugs, RS-485 Control, 3 Ph B to C

BAYSUPFLGAA Supply Duct Flange A A

BAYSUPFLGBA Supply Duct Flange B B

BAYSUPFLGCA Supply Duct Flange C C

BAYRETFLGAA Return Duct Flange A A

BAYRETFLGB Return Duct Flange B B

BAYRETFLGCA Return Duct Flange C C

TASB175 Plenum Stand A A

TASB215 Plenum Stand B B

TASB235 Plenum Stand C C

BAYSRKIT100A Side Return Kit A to C

BAYICSKIT01A Internal Condensate Switch Kit A to C

BAYHHKIT001A Horizontal Hanger Kit A to C

BAYUVCLK001A UVC Lights A to C

BAYLVKIT100A Low Voltage Conduit Entry Kit A to C

BAYSPEKT200A Single Power Entry Kit A to C

BAYWVAA05SC0AAA Hydronic Coil - 50,000 BTUH - Slide-in A to A

BAYWVBB07SCAAA Hydronic Coil - 70,000 BTUH - Slide-in B to B

BAYWVCC08SC1AAA Hydronic Coil - 80,000 BTUH - Slide-in C to C

BAYWVCC10SC1AAA Hydronic Coil - 100,000 BTUH - Slide-in C to C

BAYWACC11SC1AA Hydronic Coil - 110,000 BTUH - Add-on C to C

OPTIONAL EQUIPMENT FOR AIR HANDLERS

Page 5: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 5

“Air-Tite II™”Features and Benefits

5 Conduit Connections

r Integrated Horizontal Drain Pans

6 Quarter Turn Door Fasteners

7 Alert Code Viewport

e Compact 20.8” Depth with Doors Removed

1 AirTite IITM Cabinet

2 Precision Durable Door Seals

q Electronic Expansion Valve (EEV)

3 Refrigeration Connections

9 All Aluminum Coil

t Safety Door Switch

4 Condensate Connections

w Maximum width is 23.5”

8 VorticaTM Blower and Deck

0 Labeled Panels and Connections

1 AirTite IITM Cabinet - Double wall foamed cabinet system - Waterproof Cabinet Design - ≥ R-4.2 Insulating Value - Composite Foamed Cabinet Doors - Sweat Eliminating Cabinet Design - Loose Fiber Eliminating Design - Smooth Cleanable Cabinet Design2 Precision Durable Door Seals3 Refrigeration Connections4 Condensate Connections5 Conduit Connections - Conduit Connections on Left,

Right, and Top6 Quarter Turn Door Fasteners7 Alert Code Viewport - Alert Codes can be Viewed Without Door Removal - Control Protection Pocket

8 VorticaTM Blower and Deck - Polarized Plug on Blower

9 All Aluminum Coil - Integrated Slide Deck for Easy Removal - Polarized Plug connections on Coil EEV - Patented Enhanced Coil Fin0 Labeled Panels and Connectionsq Electronic Expansion Valve (EEV) - Low Ambient and Low Superheat Protection - Dual Refrigerant Compatible as Shippedw Maximum width is 23.5”e Compact 20.8” Depth with Doors Removedr Integrated Horizontal Drain Panst Safety Door Switch - Fused 24V Powery 5/16” Allen Wrench “Quick Latch” Modular

Cabinet

Page 6: Trane Manual a-C 6209 Attic

6 Pub. No. 22-1847-02

GeneralData

PRODUCT SPECIFICATIONSMODEL TAM7A0A24H21SARATED VOLTS/PH/HZ. 200-230/1/60RATINGS 1 See O.D. SpecificationsINDOOR COIL — Type Plate FinRows — F.P.I. 3 - 14Face Area (sq. ft.) 3.67Tube Size (in.) 3/8Refrigerant Control EEVDrain Conn. Size (in.) 2 3/4 NPTDUCT CONNECTIONS See Outline DrawingINDOOR FAN — Type CentrifugalDiameter-Width (In.) 11 X 8No. Used 1Drive - No. Speeds Direct - VariableCFM vs. in. w.g. See Fan Performance TableNo. Motors — H.P. 1 - 1/2Motor Speed R.P.M. Variable ECMVolts/Ph/Hz 208-230/1/60F.L. Amps 3.0FILTERFilter Furnished? NoType Recommended ThrowawayNo.-Size-Thickness 1 - 16 X 20 - 1 in.REFRIGERANT R-410ARef. Line Connections BrazedCoupling or Conn. Size — in. Gas 3/4Coupling or Conn. Size — in. Liq. 3/8DIMENSIONS H x W x DCrated (In.) 51-1/2 x 19 x 23-1/2Uncrated 49-7/8 x 17-1/2 x 21-3/4WEIGHTShipping (Lbs.) / Net (Lbs.) 127/116

TAM7A0B30H21SA200-230/1/60

See O.D. SpecificationsPlate Fin

3 - 145.043/8

EEV 3/4 NPT

See Outline DrawingCentrifugal

11 X 101

Direct - VariableSee Fan Performance Table

1 - 1/2Variable ECM208-230/1/60

3.0

NoThrowaway

1 - 20 X 20 - 1 in.R-410ABrazed

3/43/8

H x W x D56-1/2 x 23 x 23-1/2

55-11/16 x 21-5/16 x 21-3/4

150/138

TAM7A0C36H31SA200-230/1/60

See O.D. SpecificationsPlate Fin

3 - 145.503/8

EEV 3/4 NPT

See Outline DrawingCentrifugal

11 X 101

Direct - VariableSee Fan Performance Table

1 - 1/2Variable ECM208-230/1/60

3.0

NoThrowaway

1 - 22 X 20 - 1 in.R-410ABrazed

7/83/8

H x W x D57-1/4 x 25-1/4 x 23-1/2

56-15/16 x 23-1/2 x 21-3/4

157/146

PRODUCT SPECIFICATIONSMODEL TAM7A0C42H31SARATED VOLTS/PH/HZ. 200-230/1/60RATINGS 1 See O.D. SpecificationsINDOOR COIL — Type Plate FinRows — F.P.I. 4 - 14Face Area (sq. ft.) 5.04Tube (in.) 3/8Refrigerant Control EEV Drain Conn. Size (in.) 2 3/4 NPTDUCT CONNECTIONS See Outline DrawingINDOOR FAN — Type CentrifugalDiameter-Width (In.) 11 X 10No. Used 1Drive - No. Speeds Direct - VariableCFM vs. in. w.g. See Fan Performance TableNo. Motors — H.P. 1 - 1/2Motor Speed R.P.M. Variable ECMVolts/Ph/Hz 208-230/1/60F.L. Amps 3.0FILTERFilter Furnished? NoType Recommended ThrowawayNo.-Size-Thickness 1 - 22 X 20 - 1 in.REFRIGERANT R-410ARef. Line Connections BrazedCoupling or Conn. Size — in. Gas 7/8Coupling or Conn. Size — in. Liq. 3/8DIMENSIONS H x W x DCrated (In.) 57-1/4 x 25-1/4 x 23-1/2 Uncrated 56-15/16 x 23-1/2 x 21-3/4WEIGHTShipping (Lbs.) / Net (Lbs.) 162/151

TAM7A0C48H41SA200-230/1/60

See O.D. SpecificationsPlate Fin

4 - 145.963/8

EEV 3/4 NPT

See Outline DrawingCentrifugal

11 X 101

Direct - VariableSee Fan Performance Table

1 - 3/4Variable ECM208-230/1/60

4.2

NoThrowaway

1 - 22 X 20 - 1 in.R-410ABrazed

7/83/8

H x W x D62-3/4 x 25-1/4 x 23-1/2 61-3/4 x 23-1/2 x 21-3/4

175/163

TAM7A0C60H51SA200-230/1/60

See O.D. SpecificationsPlate Fin

4 - 145.963/8

EEV 3/4 NPT

See Outline DrawingCentrifugal

11 X 101

Direct - VariableSee Fan Performance Table

1 - 1Variable ECM208-230/1/60

5.5

NoThrowaway

1 - 22 X 20 - 1 in.R-410ABrazed

7/83/8

H x W x D62-3/4 x 25-1/4 x 23-1/2

61-11/16 x 23-1/2 x 21-3/4

175/163

1 These Air Handlers are AHRI. certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.

2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76)

Page 7: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 7

PerformanceData

TAM7A0A24 AIRFLOW PERFORMANCE TABLE - CONSTANT CFM

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0A24H21SAA 638/713 638/900 675/900 600/713 -- -- --

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

AIRFLOW PERFORMANCE - CONSTANT CFM*AM7A0A24 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE HEATING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9

1.5 tons

360 CFM/ton

CFMWatts

54238

54767

548101

547137

541175

390 CFM/ton

CFMWatts

58646

59980

600115

599153

595192

380 CFM/ton

CFMWatts

57443

58375

587110

588148

581185

410 CFM/ton

CFMWatts

61853

63388

636124

637163

629202

400 CFM/ton

CFMWatts

60549

61882

624119

625158

618196

430 CFM/ton

CFMWatts

65059

66596

669134

672174

660212

420 CFM/ton

CFMWatts

63655

65190

659128

660168

653207

450 CFM/ton

CFMWatts

68166

696104

703144

704185

696225

2 tons †

360 CFM/ton

CFMWatts

72375

743115

754158

756201

748242

390 CFM/ton

CFMWatts

78094

800137

809182

811227

802268

380 CFM/ton

CFMWatts

76186

782128

793172

796216

788259

410 CFM/ton

CFMWatts

818106

838151

848198

851244

842287

400 †CFM/ton

CFMWatts

79997

820141

832187

835233

827276

430 CFM/ton

CFMWatts

856119

876167

887215

889262

881307

420 CFM/ton

CFMWatts

836109

858155

870203

873250

866294

450 CFM/ton

CFMWatts

894134

913183

925233

927282

920327

2.5 tons

360 CFM/ton

CFMWatts

892130

914179

927229

930278

923324

390 CFM/ton

CFMWatts

964164

986218

997271

1000322

992370

380 CFM/ton

CFMWatts

939149

962201

974253

978304

971351

410 CFM/ton

CFMWatts

1013188

1034244

1045299

1049353

1040400

400 CFM/ton

CFMWatts

986170

1009225

1022279

1026332

1019380

430 CFM/ton

CFMWatts

1063214

1083273

1095331

1097385

1089434

420 CFM/ton

CFMWatts

1035194

1058251

1071308

1074362

1066411

450 CFM/ton

CFMWatts

1114243

1135305

1145365

1145420

1135469

3 tons

360 CFM/ton

CFMWatts

1065209

1088269

1101327

1103382

1095431

390 CFM/ton

CFMWatts

1160272

1181337

1190397

1189453

1157486

380 CFM/ton

CFMWatts

1126244

1149307

1160367

1161423

1151472

410 CFM/ton

CFMWatts

1225317

1244384

1249444

1230486

1146477

400 CFM/ton

CFMWatts

1190285

1211350

1220412

1218467

1164483

430 CFM/ton

CFMWatts

1291368

1305434

1298486

1217476

1135468

420 CFM/ton

CFMWatts

1255331

1273397

1278459

1237483

1151475

450 CFM/ton

CFMWatts

1355422

1361485

1285475

1206467

1124460

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

TAM7A0A24 MINIMUM HEATER CFM TABLE

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 8: Trane Manual a-C 6209 Attic

8 Pub. No. 22-1847-02

AIRFLOW PERFORMANCE - CONSTANT TORQUE MODE (See Switch S2-5)*AM7A0A24 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9

1.5 tons

360 CFM/ton

CFMWatts

65259

55971

40778

n/a n/a

380 CFM/ton

CFMWatts

67965

59378

46487

16794

n/a

400 CFM/ton

CFMWatts

70571

62685

51396

325101

n/a

410 CFM/ton

CFMWatts

73178

65893

556105

406112

n/a

2 tons †

360 CFM/ton

CFMWatts

809101

746118

666133

563144

428153

380 CFM/ton

CFMWatts

843113

784131

710146

617159

500168

400 †CFM/ton

CFMWatts

877125

821144

751161

666174

561183

410 CFM/ton

CFMWatts

911139

858158

792175

712189

615199

2.5 tons

360 CFM/ton

CFMWatts

979168

930189

869207

796222

709232

380 CFM/ton

CFMWatts

1024190

976211

918230

849244

766255

400 CFM/ton

CFMWatts

1070215

1023236

967255

901270

821280

410 CFM/ton

CFMWatts

1118242

1072264

1018282

953297

877307

3 tons

360 CFM/ton

CFMWatts

1148261

1102282

1048301

985315

910325

380 CFM/ton

CFMWatts

1209301

1164322

1111341

1050355

978364

400 CFM/ton

CFMWatts

1271347

1227368

1175386

1115399

1046408

410 CFM/ton

CFMWatts

1334397

1289418

1239435

1180448

1113455

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

TAM7A0A24 AIRFLOW PERFORMANCE TABLE - CONSTANT TORQUE MODE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0A24H21SAA 638/713 638/900 675/900 600/713 -- -- --

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

TAM7A0A24 MINIMUM HEATER CFM TABLE

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

PerformanceData

Page 9: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 9

TAM7A0B30 AIRFLOW PERFORMANCE TABLE - CONSTANT CFM

PerformanceData

TAM7A0B30 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0B30H21SAA 723/808 723/1020 765/1020 680/808 765/1063 850/1105 --

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

AIRFLOW PERFORMANCE - CONSTANT CFM*AM7A0B30 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE HEATING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9

1.5 tons

360 CFM/ton

CFMWatts

59130

56058

53387

509118

482150

390 CFM/ton

CFMWatts

63035

60965

58896

566128

540161

380 CFM/ton

CFMWatts

61833

59362

56993

547125

524158

410 CFM/ton

CFMWatts

65738

63970

621102

601136

578169

400 CFM/ton

CFMWatts

64537

62467

60499

584132

562166

430 CFM/ton

CFMWatts

68342

66975

653109

636143

614177

420 CFM/ton

CFMWatts

65938

63969

620102

602136

581170

450 CFM/ton

CFMWatts

70945

69880

685115

669151

649186

2 tons †

360 CFM/ton

CFMWatts

75051

74187

731125

719163

704200

390 CFM/ton

CFMWatts

80060

79799

791139

781180

766219

380 CFM/ton

CFMWatts

78457

77995

771134

762174

748213

410 CFM/ton

CFMWatts

83466

834107

830150

822192

810233

400 †CFM/ton

CFMWatts

81862

816103

811144

803186

792227

430 CFM/ton

CFMWatts

86873

871116

869161

864205

853248

420 CFM/ton

CFMWatts

83566

834107

831150

824192

813234

450 CFM/ton

CFMWatts

90280

908126

908172

905219

895263

2.5 tons

360 CFM/ton

CFMWatts

90480

908125

909172

907219

898264

390 CFM/ton

CFMWatts

96795

977145

982196

982247

974295

380 CFM/ton

CFMWatts

94789

955138

959188

958237

951285

410 CFM/ton

CFMWatts

1012106

1025160

1033214

1034268

1027318

400 CFM/ton

CFMWatts

991100

1002152

1009205

1010257

1003307

430 CFM/ton

CFMWatts

1057119

1074176

1084234

1087290

1078342

420 CFM/ton

CFMWatts

1013106

1026159

1034214

1036268

1029318

450 CFM/ton

CFMWatts

1104133

1124194

1136255

1139314

1128366

3 tons

360 CFM/ton

CFMWatts

1063120

1080177

1091236

1094292

1085344

390 CFM/ton

CFMWatts

1147147

1170211

1184276

1185336

1170389

380 CFM/ton

CFMWatts

1120137

1140199

1153262

1156321

1444374

410 CFM/ton

CFMWatts

1208168

1233238

1247306

1245367

1223418

400 CFM/ton

CFMWatts

1179157

1202224

1216290

1216351

1198403

430 CFM/ton

CFMWatts

1271193

1298267

1309337

1300398

1271446

420 CFM/ton

CFMWatts

1210168

1233237

1247305

1245306

1224417

450 CFM/ton

CFMWatts

1338221

1363299

1368369

1350427

1314472

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 10: Trane Manual a-C 6209 Attic

10 Pub. No. 22-1847-02

AIRFLOW PERFORMANCE - CONSTANT TORQUE MODE (See Switch S2-5)*AM7A0B30 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9

1.5 tons

360 CFM/ton

CFMWatts

68541

53856

29963

n/a n/a

380 CFM/ton

CFMWatts

71145

57260

35968

n/a n/a

400 CFM/ton

CFMWatts

73849

60565

41073

n/a n/a

420 CFM/ton

CFMWatts

75150

62167

43476

n/a n/a

2 tons †

360 CFM/ton

CFMWatts

84066

72685

57596

34499

n/a

380 CFM/ton

CFMWatts

87472

76492

622104

419107

n/a

400 †CFM/ton

CFMWatts

90879

802100

667113

484117

n/a

420 CFM/ton

CFMWatts

92483

820104

689118

513122

180132

2.5 tons

360 CFM/ton

CFMWatts

1017105

921129

804144

658150

454148

380 CFM/ton

CFMWatts

1061117

968142

856158

719165

538163

400 CFM/ton

CFMWatts

1106131

1016156

908174

779182

614180

420 CFM/ton

CFMWatts

1129138

1040164

934182

808190

650189

3 tons

360 CFM/ton

CFMWatts

1182156

1095182

993201

873211

727210

380 CFM/ton

CFMWatts

1241178

1157205

1059225

945235

809236

400 CFM/ton

CFMWatts

1304203

1221231

1127252

1018263

890265

420 CFM/ton

CFMWatts

1337217

1255246

1162267

1055279

931281

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

PerformanceData

TAM7A0B30 AIRFLOW PERFORMANCE TABLE - CONSTANT TORQUE MODE

TAM7A0B30 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0B30H21SAA 723/808 723/1020 765/1020 680/808 765/1063 850/1105 --

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 11: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 11

PerformanceData

TAM7A0C36 AIRFLOW PERFORMANCE TABLE - CONSTANT CFM

TAM7A0C36 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0C36H31SAA 876/979 876/1236 927/1236 824/979 927/1288 1030/1339 1236/1442

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

AIRFLOW PERFORMANCE - CONSTANT CFM*AM7A0C36 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE HEATING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9

2 tons

350 CFM/ton

CFMWatts

72444

70477

694111

695148

698185

400 CFM/ton

CFMWatts

81357

79794

794133

799174

806215

370 CFM/ton

CFMWatts

75949

74484

738120

740158

742197

420 CFM/ton

CFMWatts

84963

837102

835142

841185

849228

390 CFM/ton

CFMWatts

79554

78491

780129

783169

786209

440 CFM/ton

CFMWatts

88469

876110

876153

883197

891242

410 CFM/ton

CFMWatts

83060

82399

822139

824180

827222

450 CFM/ton

CFMWatts

90272

895114

897158

902203

912249

2.5 tons

350 CFM/ton

CFMWatts

87968

876110

877153

881197

884240

400 CFM/ton

CFMWatts

99291

991138

998188

1005237

1014287

370 CFM/ton

CFMWatts

92377

924121

927167

932213

936258

420 CFM/ton

CFMWatts

1036101

1040152

1048204

1057256

1064307

390 CFM/ton

CFMWatts

96886

971133

977181

983230

987277

440 CFM/ton

CFMWatts

1081113

1089167

1099221

1110277

1116330

410 CFM/ton

CFMWatts

101296

1020146

1028197

1034248

1039298

450 CFM/ton

CFMWatts

1105119

1113174

1125231

1136287

1141341

3 tons †

350 CFM/ton

CFMWatts

1036102

1044153

1053206

1060257

1064308

400 CFM/ton

CFMWatts

1175140

1189200

1203261

1214321

1215377

370 † CFM/ton

CFMWatts

1090116

1102171

1114227

1122282

1123334

420 CFM/ton

CFMWatts

1234159

1251223

1267288

1275351

1272406

390CFM/ton

CFMWatts

1145132

1161191

1176251

1184309

1184363

440 CFM/ton

CFMWatts

1295180

1315250

1331318

1335381

1325435

410 CFM/ton

CFMWatts

1204150

1223213

1238277

1246337

1242391

450 CFM/ton

CFMWatts

1327192

1348264

1362264

1364396

1350449

3.5 tons

350 CFM/ton

CFMWatts

1199149

1218211

1233274

1241335

1237389

400 CFM/ton

CFMWatts

1380214

1403289

1414360

1409422

1389472

370 CFM/ton

CFMWatts

1269172

1291240

1307307

1311370

1300423

420 CFM/ton

CFMWatts

1459248

1478327

1481397

1467456

1395476

390 CFM/ton

CFMWatts

1342200

1367273

1380343

1378405

1358456

440 CFM/ton

CFMWatts

1538287

1550366

1542433

1504478

1388472

410 CFM/ton

CFMWatts

1419232

1442309

1449380

1438440

1394478

450 CFM/ton

CFMWatts

1575307

1583385

1570450

1501477

1385470

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 12: Trane Manual a-C 6209 Attic

12 Pub. No. 22-1847-02

AIRFLOW PERFORMANCE - CONSTANT TORQUE MODE (See Switch S2-5)*AM7A0C36 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9

2 tons

350 CFM/ton

CFMWatts

85863

70677

53085

29790

19163

370 CFM/ton

CFMWatts

89269

74784

58593

38798

84135

390 CFM/ton

CFMWatts

92475

78791

635102

460107

213120

410 CFM/ton

CFMWatts

95782

82699

683111

524117

329123

2.5 tons

350 CFM/ton

CFMWatts

102697

905116

776130

639138

488143

370 CFM/ton

CFMWatts

1067107

952127

830142

702151

565157

390 CFM/ton

CFMWatts

1110118

999139

883155

762166

634172

410 CFM/ton

CFMWatts

1153130

1047153

935170

820181

700187

3 tons †

350 CFM/ton

CFMWatts

1175137

1070160

961177

848189

731196

370 †CFM/ton

CFMWatts

1229154

1129178

1024196

916209

805217

390CFM/ton

CFMWatts

1285173

1188198

1087218

984231

877240

410 CFM/ton

CFMWatts

1343195

1249221

1152241

1051256

948264

3.5 tons

350 CFM/ton

CFMWatts

1338193

1244219

1146239

1046254

942262

370 CFM/ton

CFMWatts

1408222

1317249

1223270

1126285

1025294

390 CFM/ton

CFMWatts

1481255

1393282

1301304

1206320

1108329

410 CFM/ton

CFMWatts

1555291

1468319

1379341

1286357

1189367

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

PerformanceData

TAM7A0C36 AIRFLOW PERFORMANCE TABLE - CONSTANT TORQUE MODE

TAM7A0C36 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0C36H31SAA 876/979 876/1236 927/1236 824/979 927/1288 1030/1339 1236/1442

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 13: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 13

TAM7A0C42 AIRFLOW PERFORMANCE TABLE - CONSTANT CFM

PerformanceData

TAM7A0C42 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0C42H31SAA 978/1093 978/1380 1035/1380 920/1093 1035/1438 1150/1495 1380/1610

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

AIRFLOW PERFORMANCE - CONSTANT CFM*AM7A0C42 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE HEATING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9

2.5 tons

330 CFM/ton

CFMWatts

85368

832108

820149

815191

813232

360 CFM/ton

CFMWatts

91282

897125

893170

895217

901264

350 CFM/ton

CFMWatts

89676

880119

870162

867162

866250

380 CFM/ton

CFMWatts

95692

945137

943185

946234

951283

370 CFM/ton

CFMWatts

93985

926130

920176

918222

918268

400 CFM/ton

CFMWatts

1000102

992151

992201

997253

1002304

390 CFM/ton

CFMWatts

98395

973143

969191

968240

969288

420 CFM/ton

CFMWatts

1044114

1040166

1042219

1047273

1052325

3 tons

330 CFM/ton

CFMWatts

99699

987147

984196

984246

983294

360 CFM/ton

CFMWatts

1071122

1069175

1072230

1078285

1082339

350 CFM/ton

CFMWatts

1049112

1043164

1044217

1045269

1045320

380 CFM/ton

CFMWatts

1126138

1127195

1132254

1139312

1142368

370CFM/ton

CFMWatts

1101127

1100183

1103239

1106294

1107348

400 CFM/ton

CFMWatts

1181157

1186218

1193280

1200341

1201399

390 CFM/ton

CFMWatts

1156144

1159203

1164264

1167322

1168379

420 CFM/ton

CFMWatts

1239177

1247243

1256309

1261373

1259432

3.5 tons †

330 CFM/ton

CFMWatts

1142140

1143198

1148257

1152315

1152370

360 CFM/ton

CFMWatts

1239177

1247243

1256309

1261373

1259432

350 CFM/ton

CFMWatts

1208162

1212224

1220288

1224350

1222407

380 CFM/ton

CFMWatts

1308205

1319276

1329346

1331412

1323470

370 † CFM/ton

CFMWatts

1274187

1283254

1293323

1295387

1289445

400 CFM/ton

CFMWatts

1381237

1394313

1401386

1398452

1332475

390 CFM/ton

CFMWatts

1344215

1357289

1366361

1364427

1345479

420 CFM/ton

CFMWatts

1456275

1468355

1471429

1443481

1323470

4 tons

330 CFM/ton

CFMWatts

1299196

1309266

1318336

1321401

1313459

360 CFM/ton

CFMWatts

1423258

1436337

1441410

1434475

1326472

350 CFM/ton

CFMWatts

1380232

1394307

1401381

1398447

1339477

380 CFM/ton

CFMWatts

1511304

1520386

1517459

1436477

1317466

370 CFM/ton

CFMWatts

1466273

1479354

1481428

1451482

1327470

400 CFM/ton

CFMWatts

1598356

1599437

1536472

1426470

1308461

390 CFM/ton

CFMWatts

1553320

1561403

1544470

1438475

1315465

420 CFM/ton

CFMWatts

1679409

1620451

1534471

1417464

1301456

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 14: Trane Manual a-C 6209 Attic

14 Pub. No. 22-1847-02

AIRFLOW PERFORMANCE - CONSTANT TORQUE MODE (See Switch S2-5)*AM7A0C42 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9

2.5 tons

330 CFM/ton

CFMWatts

98896

861114

712125

523128

208143

350 CFM/ton

CFMWatts

1030107

909126

768137

597141

353144

370 CFM/ton

CFMWatts

1072118

956139

823151

665155

458155

390 CFM/ton

CFMWatts

1115131

1003152

877165

729170

546169

3 tons

330 CFM/ton

CFMWatts

1128135

1017156

892170

748175

570174

350 CFM/ton

CFMWatts

1180152

1074174

956189

821196

662194

370CFM/ton

CFMWatts

1233171

1132195

1019210

893218

747217

390 CFM/ton

CFMWatts

1288192

1190217

1083234

964242

828242

3.5 tons †

330 CFM/ton

CFMWatts

1274187

1175211

1067228

946236

808236

350 CFM/ton

CFMWatts

1340214

1245239

1142257

1028267

901268

370 † CFM/ton

CFMWatts

1408245

1317272

1218291

1110301

991303

390 CFM/ton

CFMWatts

1479280

1390308

1295328

1192340

1080343

4 tons

330 CFM/ton

CFMWatts

1457268

1368296

1272316

1167327

1053330

350 CFM/ton

CFMWatts

1538312

1452340

1360361

1260374

1153378

370 CFM/ton

CFMWatts

1618359

1534389

1445411

1350425

1248429

390 CFM/ton

CFMWatts

1693409

1611439

1525462

1432476

1333481

NOTES: 1. * Models start with "A" or "T" 2. † Factory Setting 3. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 4. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

PerformanceData

TAM7A0C42 AIRFLOW PERFORMANCE TABLE - CONSTANT TORQUE MODE

TAM7A0C42 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA

*AM7A0C42H31SAA 978/1093 978/1380 1035/1380 920/1093 1035/1438 1150/1495 1380/1610

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 15: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 15

PerformanceData

TAM7A0C48 AIRFLOW PERFORMANCE TABLE - CONSTANT CFM

TAM7A0C48 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA BAYEVCC25BK1AA

*AM7A0C48H41SAA 1063/1188 1063/1500 1125/1500 1000/1188 1125/1563 1250/1625 1500/1750 1625/1813WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

AIRFLOW PERFORMANCE - CONSTANT CFM*AM7A0C48 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE HEATING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9

3 tons

330 CFM/ton

CFMWatts

110192

1017143

1015190

1006232

994270

380 CFM/ton

CFMWatts

1150128

1155184

1154237

1150286

1141330

350 CFM/ton

CFMWatts

1067106

1073158

1072208

1065252

1053292

400 CFM/ton

CFMWatts

1204145

1210203

1210259

1207310

1199356

370 CFM/ton

CFMWatts

1122120

1129175

1128227

1122274

1112315

420 CFM/ton

CFMWatts

1259162

1266224

1267282

1264335

1258384

390 CFM/ton

CFMWatts

1177136

1185194

1185248

1180297

1170341

440 CFM/ton

CFMWatts

1314182

1322246

1324307

1322363

1316413

3.5 tons

330 CFM/ton

CFMWatts

1164132

1171189

1171242

1165291

1156334

380 CFM/ton

CFMWatts

1323185

1331250

1333250

1331368

1325418

350 CFM/ton

CFMWatts

1228152

1235212

1236268

1232319

1224365

400 CFM/ton

CFMWatts

1388211

1398279

1400343

1399403

1395457

370 CFM/ton

CFMWatts

1292174

1300237

1302296

1299350

1292399

420 CFM/ton

CFMWatts

1455240

1465312

1468379

1469441

1463497

390 CFM/ton

CFMWatts

1356198

1366265

1369327

1367384

1361435

440 CFM/ton

CFMWatts

1523272

1534347

1538418

1538483

1534542

4 tons †

330 CFM/ton

CFMWatts

1315212

1324247

1326307

1323362

1316412

380 CFM/ton

CFMWatts

1502262

1514337

1518406

1518471

1514529

350 † CFM/ton

CFMWatts

1389212

1399280

1403343

1401402

1395455

400 CFM/ton

CFMWatts

1582302

1594382

1598454

1598522

1591581

370 CFM/ton

CFMWatts

1465245

1476317

1481384

1480446

1475502

420 CFM/ton

CFMWatts

1664348

1675421

1680508

1678577

1669638

390 CFM/ton

CFMWatts

1543283

1555359

1560430

1560495

1554553

440 CFM/ton

CFMWatts

1748400

1758486

1760565

1755634

1708668

4.5 tons **

330 CFM/ton

CFMWatts

1470247

1481319

1486387

1485449

1480505

380 CFM/ton

CFMWatts

1695367

1706451

1710528

1707598

1697659

350 CFM/ton

CFMWatts

1558290

1570367

1575439

1575505

1568563

400 CFM/ton

CFMWatts

1790428

1799515

1799594

1792664

1700661

370 CFM/ton

CFMWatts

1649340

1661422

1666497

1664565

1655625

420 CFM/ton

CFMWatts

1885496

1889584

1884662

1783656

1683648

390 CFM/ton

CFMWatts

1742397

1754483

1756561

1751630

1708666

440 CFM/ton

CFMWatts

1976568

1973655

1871652

1765643

1667636

NOTES: 1. * Models start with "A" or "T" 2. ** Not an actual OD size 3. † Factory Setting 4. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 5. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 16: Trane Manual a-C 6209 Attic

16 Pub. No. 22-1847-02

AIRFLOW PERFORMANCE - CONSTANT TORQUE MODE (See Switch S2-5)*AM7A0C48 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9

3 tons

330 CFM/ton

CFMWatts

1127117

1020143

907163

786173

654174

350 CFM/ton

CFMWatts

1180132

1078160

972180

859192

738194

370 CFM/ton

CFMWatts

1233149

1136177

1035199

929212

816215

390 CFM/ton

CFMWatts

1287167

1194196

1097219

996233

890238

3.5 tons

330 CFM/ton

CFMWatts

1274162

1179191

1082214

980227

872232

350 CFM/ton

CFMWatts

1336185

1246215

1153238

1056253

955259

370 CFM/ton

CFMWatts

1400210

1313241

1224265

1132281

1036288

390 CFM/ton

CFMWatts

1465238

1381270

1295295

1207312

1115320

4 tons †

330 CFM/ton

CFMWatts

1443228

1358260

1271284

1181301

1088308

350 †CFM/ton

CFMWatts

1517262

1436295

1352321

1266338

1177346

370 CFM/ton

CFMWatts

1594301

1516335

1435361

1352379

1267388

390 CFM/ton

CFMWatts

1673346

1597380

1519406

1439425

1356434

4.5 tons **

330 CFM/ton

CFMWatts

1599304

1521337

1440364

1357382

1272391

350 CFM/ton

CFMWatts

1688354

1613389

1535415

1455434

1373444

370 CFM/ton

CFMWatts

1780412

1707447

1632474

1554493

1475503

390 CFM/ton

CFMWatts

1873477

1801512

1728539

1653558

1576567

NOTES: 1. * Models start with "A" or "T" 2. ** Not an actual OD size 3. † Factory Setting 4. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 5. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

PerformanceData

TAM7A0C48 AIRFLOW PERFORMANCE TABLE - CONSTANT TORQUE MODE

TAM7A0C48 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA BAYEVCC25BK1AA

*AM7A0C48H41SAA 1063/1188 1063/1500 1125/1500 1000/1188 1125/1563 1250/1625 1500/1750 1625/1813WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 17: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 17

TAM7A0C60 AIRFLOW PERFORMANCE TABLE - CONSTANT CFM

PerformanceData

TAM7A0C60 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA BAYEVCC25BK1AA

*AM7A0C60H51SAA 1063/1188 1063/1500 1125/1500 1000/1188 1125/1563 1250/1625 1500/1750 1625/1813WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

AIRFLOW PERFORMANCE - CONSTANT CFM*AM7A0C60 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE HEATING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9

3.5 tons

370 CFM/ton

CFMWatts

1316194

1328258

1328314

1320364

1308406

400 CFM/ton

CFMWatts

1404205

1424275

1426337

1419391

1410440

380 CFM/ton

CFMWatts

1349207

1360272

1359329

1352380

1338422

410 CFM/ton

CFMWatts

1437218

1455289

1457351

1451407

1441456

390 CFM/ton

CFMWatts

1381220

1391286

1390344

1383396

1370439

420 CFM/ton

CFMWatts

1467230

1487303

1489367

1482423

1474474

400 CFM/ton

CFMWatts

1413234

1422300

1421360

1415412

1402456

430 CFM/ton

CFMWatts

1500244

1516317

1519382

1515441

1505491

4 tons

370 CFM/ton

CFMWatts

1485269

1493337

1493398

1486452

1475498

400 CFM/ton

CFMWatts

1586285

1600360

1604428

1601490

1592543

380 CFM/ton

CFMWatts

1521287

1529356

1528418

1522474

1511520

410 CFM/ton

CFMWatts

1622303

1636379

1640449

1638512

1629566

390 CFM/ton

CFMWatts

1557306

1564376

1564440

1559496

1548544

420 CFM/ton

CFMWatts

1659322

1672399

1677471

1675535

1667591

400 CFM/ton

CFMWatts

1593326

1600397

1600462

1595519

1585568

430 CFM/ton

CFMWatts

1695342

1708421

1713493

1712559

1705616

4.5 tons**†

370 †CFM/ton

CFMWatts

1652360

1659433

1660500

1655559

1646610

400 CFM/ton

CFMWatts

1769385

1782467

1789543

1788611

1783671

380 CFM/ton

CFMWatts

1694386

1701460

1701528

1697589

1688641

410 CFM/ton

CFMWatts

1811411

1826495

1831572

1832643

1827704

390 CFM/ton

CFMWatts

1736413

1742489

1744558

1740620

1732673

420 CFM/ton

CFMWatts

1854439

1869525

1875604

1877676

1872739

400 CFM/ton

CFMWatts

1778442

1785519

1786590

1783653

1776707

430 CFM/ton

CFMWatts

1898468

1913556

1919637

1921711

1918777

5 tons

370 CFM/ton

CFMWatts

1826475

1833555

1835627

1832692

1826748

400 CFM/ton

CFMWatts

1963515

1978606

1985689

1988766

1985833

380 CFM/ton

CFMWatts

1875512

1882593

1884667

1882733

1876791

410 CFM/ton

CFMWatts

2014554

2029647

2037733

2040811

2038880

390 CFM/ton

CFMWatts

1924551

1932634

1935710

1933777

1927836

420 CFM/ton

CFMWatts

2066595

2082691

2090779

2093859

2090928

400 CFM/ton

CFMWatts

1975593

1983678

1986755

1985824

1979884

430 CFM/ton

CFMWatts

2120640

2136738

2143828

2147909

2143980

NOTES: 1. * Models start with "A" or "T" 2. ** Not an actual OD size 3. † Factory Setting 4. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 5. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 18: Trane Manual a-C 6209 Attic

18 Pub. No. 22-1847-02

AIRFLOW PERFORMANCE - CONSTANT TORQUE MODE (See Switch S2-5)*AM7A0C60 WITH WET COIL, NO FILTER

OUTDOORMULTIPLIER

(TONS)

COOLING AIRFLOWSETTING

AirflowPower

EXTERNAL STATIC PRESSURE

0.1 0.3 0.5 0.7 0.9

3.5 tons

370 CFM/ton

CFMWatts

1404201

1330234

1244260

1146276

1033280

380 CFM/ton

CFMWatts

1435213

1362247

1278273

1183290

1074295

390 CFM/ton

CFMWatts

1466225

1394260

1312287

1220304

1115310

400 CFM/ton

CFMWatts

1496238

1426273

1346301

1256319

1154325

4 tons

370 CFM/ton

CFMWatts

1583278

1516314

1441342

1357362

1263370

380 CFM/ton

CFMWatts

1618295

1552331

1479360

1396380

1305389

390 CFM/ton

CFMWatts

1654313

1589350

1516379

1436400

1347409

400 CFM/ton

CFMWatts

1689332

1625369

1554399

1475420

1389430

4.5 tons**†

370 †CFM/ton

CFMWatts

1748365

1685403

1616433

1540454

1456465

380 CFM/ton

CFMWatts

1789390

1727427

1659458

1584480

1503491

390 CFM/ton

CFMWatts

1831416

1770454

1703484

1629506

1549518

400 CFM/ton

CFMWatts

1873443

1813481

1747512

1675534

1597546

5 tons

370 CFM/ton

CFMWatts

1921476

1862515

1797545

1726568

1650580

380 CFM/ton

CFMWatts

1971512

1912550

1848581

1778603

1703616

390 CFM/ton

CFMWatts

2021550

1963588

1900619

1832641

1758654

400 CFM/ton

CFMWatts

2073590

2015629

1953660

1886682

1814695

NOTES: 1. * Models start with "A" or "T" 2. ** Not an actual OD size 3. † Factory Setting 4. At continuous fan setting: Airflow values are approximately 50% of the listed cooling values 5. Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.

PerformanceData

TAM7A0C60 AIRFLOW PERFORMANCE TABLE - CONSTANT TORQUE MODE

TAM7A0C60 MINIMUM HEATER CFM TABLE

MODEL NO.BAYEVAC05BK1AABAYEVAC05LG1AA

BAYEVAC08BK1AABAYEVAC08LG1AA

BAYEVAC10BK1AABAYEVAC10LG1AA BAYEVAC10LG3AA BAYEVBC15BK1AA BAYEVCB15LG3AA BAYEVBC20BK1AA BAYEVCC25BK1AA

*AM7A0C60H51SAA 1063/1188 1063/1500 1125/1500 1000/1188 1125/1563 1250/1625 1500/1750 1625/1813WITHOUT HEAT PUMP / WITH HPSEE AIR HANDLER NAMEPLATE

MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX

NOTE: Minimum auxiliary heating airflow is automatically configured by the air handler model and the auxiliary heater model number. This is not field adjustable.

Page 19: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 19

ElectricalData

Notes:

1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters

2. Heater model numbers may have additional suffix digits.

kW BTUH kW BTUH

No Heater 0 - - 3.0** 4 15 - - 3.0** 4 15BAYEVAC05++1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25BAYEVAC08++1 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40BAYEVAC10++1 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30

*AM7A0A24H21SA

Note: * May be "A" or "T" Note: ** Motor Amps

208 Volt

Capacity Heater Amps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

Heater Model No. Capacity Minimum Circuit

Ampacity

MaximumOverload

Protection

240 Volt

HeaterAmps per

Circuit

No. of Circuits

Heater Attribute Data

kW BTUH kW BTUH

No Heater 0 - - 3.0** 4 15 - - 3.0** 4 15BAYEVAC05++1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25BAYEVAC08++1 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40BAYEVAC10++1 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30BAYEVBC15LG3 1-3 PH 14.40 42000 34.6 47 50 10.80 36900 30.0 41 45

9.60 32800 40.0 54 60 7.20 24600 34.6 47 504.80 16400 20.0 25 25 3.60 12300 17.3 22 25

208 Volt

Capacity Heater Amps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

Capacity

Note: * May be "A" or "T" Note: ** Motor Amps1 MCA and MOP for circuit 1 contains the motor amps

HeaterAmps per

Circuit

Heater Attribute Data

BAYEVBC15BK1 - Circuit 1 1BAYEVBC15BK1 - Circuit 2

MinimumCircuit

Ampacity

MaximumOverload

Protection

*AM7A0B30H21SA

Heater Model No. No. of Circuits

240 Volt

2

Page 20: Trane Manual a-C 6209 Attic

20 Pub. No. 22-1847-02

ElectricalData

kW BTUH kW BTUH

No Heater 0 - - 3.0** 4 15 - - 3.0** 4 15BAYEVAC05++1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25BAYEVAC08++1 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40BAYEVAC10++1 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30BAYEVBC15LG3 1-3 PH 14.40 42000 34.6 47 50 10.80 36900 30.0 41 45

9.60 32800 40.0 54 60 7.20 24600 34.6 47 50

4.80 16400 20.0 25 25 3.60 12300 17.3 22 25

9.60 32800 40.0 54 60 7.20 24600 34.6 47 50

9.60 32800 40.0 50 50 7.20 24600 34.6 43 45 Note: * May be "A" or "T" Note: ** Motor Amps1 MCA and MOP for circuit 1 contains the motor amps

BAYEVBC15BK1 - Circuit 1 1BAYEVBC15BK1 - Circuit 2

BAYEVBC20BK1 - Circuit 1 1BAYEVBC20BK1 - Circuit 2

HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

MaximumOverload

Protection

Capacity Heater Amps per

Circuit

Heater Attribute Data

MinimumCircuit

Ampacity

2

2

*AM7A0C36H31SA

Heater Model No. No. of Circuits

240 Volt 208 Volt

Capacity

kW BTUH kW BTUH

No Heater 0 - - 3.0** 4 15 - - 3.0** 4 15BAYEVAC05++1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25BAYEVAC08++1 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40BAYEVAC10++1 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30BAYEVBC15LG3 1-3 PH 14.40 42000 34.6 47 50 10.80 36900 30.0 41 45

9.60 32800 40.0 54 60 7.20 24600 34.6 47 50

4.80 16400 20.0 25 25 3.60 12300 17.3 22 25

9.60 32800 40.0 54 60 7.20 24600 34.6 47 50

9.60 32800 40.0 50 50 7.20 24600 34.6 43 45 Note: * May be "A" or "T" Note: ** Motor Amps1 MCA and MOP for circuit 1 contains the motor amps

Heater Attribute Data*AM7A0C42H31SA

Heater Model No. No. of Circuits

240 Volt 208 Volt

Capacity Heater Amps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

Capacity Heater Amps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

BAYEVBC15BK1 - Circuit 1 1BAYEVBC15BK1 - Circuit 2

BAYEVBC20BK1 - Circuit 1 1BAYEVBC20BK1 - Circuit 2 2

2

Notes:

1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters

2. Heater model numbers may have additional suffix digits.

Page 21: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 21

ElectricalData

kW BTUH kW BTUH

No Heater 0 - - 4.2** 5 15 - - 4.2** 5 15BAYEVAC05++1 1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30BAYEVAC08++1 1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40BAYEVAC10++1 1 9.60 32800 40.0 55 60 7.20 24600 34.6 49 50BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 34 35 7.20 24600 20.0 30 30BAYEVBC15LG3 1-3 PH 14.40 42000 34.6 48 50 10.80 36900 30.0 42 45

9.60 32800 40.0 55 60 7.20 24600 34.6 49 50

4.80 16400 20.0 25 25 3.60 12300 17.3 22 25

9.60 32800 40.0 55 60 7.20 24600 34.6 49 50

9.60 32800 40.0 50 50 7.20 24600 34.6 43 45

9.60 32800 40.0 55 60 7.20 24600 34.6 49 50

9.60 32800 40.0 50 50 7.20 24600 34.6 43 45

4.80 16400 20.0 25 25 3.60 12300 17.3 22 25

BAYEVCC25BK1 - Circuit 1 1BAYEVCC25BK1 - Circuit 2BAYEVCC25BK1 - Circuit 3

Note: * May be "A" or "T" Note: ** Motor Amps1 MCA and MOP for circuit 1 contains the motor amps

Heater Attribute Data*AM7A0C48H41SA

MinimumCircuit

Ampacity

MaximumOverload

Protection

Capacity Heater Amps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

BAYEVBC15BK1 - Circuit 1 1BAYEVBC15BK1 - Circuit 2

BAYEVBC20BK1 - Circuit 1 1BAYEVBC20BK1 - Circuit 2

Heater Model No. No. of Circuits

240 Volt 208 Volt

Capacity Heater Amps per

Circuit

2

2

3

Notes:

1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters

2. Heater model numbers may have additional suffix digits.

Page 22: Trane Manual a-C 6209 Attic

22 Pub. No. 22-1847-02

ElectricalData

kW BTUH kW BTUH

No Heater 0 - - 5.5** 7 15 - - 5.5** 7 15BAYEVAC05++1 1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30BAYEVAC08++1 1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40BAYEVAC10++1 1 9.60 32800 40.0 55 60 7.20 24600 34.6 49 50BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 34 35 7.20 24600 20.0 30 30BAYEVBC15LG3 1-3 PH 14.40 42000 34.6 48 50 10.80 36900 30.0 42 45

9.60 32800 40.0 55 60 7.20 24600 34.6 49 50

4.80 16400 20.0 25 25 3.60 12300 17.3 22 25

9.60 32800 40.0 55 60 7.20 24600 34.6 49 50

9.60 32800 40.0 50 50 7.20 24600 34.6 43 45

9.60 32800 40.0 55 60 7.20 24600 34.6 49 50

9.60 32800 40.0 50 50 7.20 24600 34.6 43 45

4.80 16400 20.0 25 25 3.60 12300 17.3 22 25

BAYEVCC25BK1 - Circuit 1 1BAYEVCC25BK1 - Circuit 2BAYEVCC25BK1 - Circuit 3

Note: * May be "A" or "T" Note: ** Motor Amps1 MCA and MOP for circuit 1 contains the motor amps

MinimumCircuit

Ampacity

MaximumOverload

Protection

BAYEVBC15BK1 - Circuit 1 1BAYEVBC15BK1 - Circuit 2

BAYEVBC20BK1 - Circuit 1 1BAYEVBC20BK1 - Circuit 2

Heater Model No. No. of Circuits

240 Volt 208 Volt

Capacity Heater Amps per

Circuit

Heater Attribute Data*AM7A0C60H51SA

Capacity Heater Amps per

Circuit

MinimumCircuit

Ampacity

MaximumOverload

Protection

2

3

2

Notes:

1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters

2. Heater model numbers may have additional suffix digits.

Page 23: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 23

AIR HANDLER ELECTRIC HEATER PRESSURE DROP

Air handler electric heater pressure drop is negligible for the heaters and is included in the airflow data for the Series 7 air handlers.

ElectricalData

Page 24: Trane Manual a-C 6209 Attic

24 Pub. No. 22-1847-02

TAM7 AIR HANDLER AND HEATER MATRIX - ALLOWBLE COMBINATIONS

ElectricalData

AIR HANDLER

MODEL NUMBER

AC05BK1AA4.80 Kw

BK

AC05LG1AA4.80 Kw

LG

AC08BK1AA7.68 Kw

BK

AC08LG1AA7.68 Kw

LG

AC10BK1AA9.60 Kw

BK

AC10LG1AA9.60 Kw

LG

BC15BK1AA14.40 Kw

BK

BC20BK1AA19.20 Kw

BK

CC25BK1AA24.00 Kw

BK*AM7A0A24H21SA Y Y Y Y Y Y ‐ ‐ ‐*AM7A0B30H21SA Y Y Y Y Y Y Y - ‐*AM7A0C36H31SA Y Y Y Y Y Y Y Y -*AM7A0C42H31SA Y Y Y Y Y Y Y Y -*AM7A0C48H41SA Y Y Y Y Y Y Y Y Y*AM7A0C60H51SA Y Y Y Y Y Y Y Y Y

APPROVED AIR HANDLER ‐ HEATER COMBINATIONSHEATER MODEL NUMBER BAYEV‐

AIR HANDLER

MODEL NUMBER

AC10LG3AA9.60 Kw

LG

BC15LG3AA14.4 Kw

LG*AM7A0A24H21SA Y ‐*AM7A0B30H21SA Y Y*AM7A0C36H31SA Y Y*AM7A0C42H31SA Y Y*AM7A0C48H41SA Y Y*AM7A0C60H51SA Y Y

APPROVED AIR HANDLER ‐ HEATER COMBINATIONS

HEATER MODEL NUMBER BAYEV‐

Page 25: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 25

ElectricalData

WIR

ING

DIA

GR

AM

FO

R T

AM

7 A

IR H

AN

DL

ER

S

No

te:

ET

sen

sor

wiri

ng m

ay b

e br

own

Page 26: Trane Manual a-C 6209 Attic

26 Pub. No. 22-1847-02

FieldWiring

Comfort Control

Air Handler

Air Conditioner

Neatly bundle all low voltage wires behind the service valve cover as shown.

Field wiring

Yellow

Blue

Red

Yellow

Green

White

Blue

B

B - Blue

WGY1

Y2

Y1 - Yellow

RO

ORB

YI

W1

YO

Y2

BKG

W2W3 *

(In)

(Out)

• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. • YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly. • Internally mounted condensate switch is optional and must be ordered separately. • If 3rd party condensate overflow switches are installed, they should be wired in series between YO and Y to the outdoor unit.

Single Stage Cooling

Page 27: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 27

FieldWiring

• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat • YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits

to work properly • Internally mounted condensate switch is optional and must be ordered separately • If a 3rd party condensate overflow switch is installed, it should be wired in series between YO and Y to the outdoor unit

Single Stage HP

Comfort Control

Air Handler

Heat Pump

Neatly bundle all low voltage wires behind the service valve cover as shown.

Field wiring

YellowBlue

Black(X2)

Red

Orange

Red

YellowOrange

Green

White

Blue

B

B - Blue

WX2

GY1

Y1 - Yellow

RO

ORB

YIY2

W1

YO

BKG

W2W3 *

R - RedO - Orange

(In)

(Out)

W1 - White

Page 28: Trane Manual a-C 6209 Attic

28 Pub. No. 22-1847-02

Two Stage Cooling

• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. • YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly. • Internally mounted condensate switch is optional and must be ordered separately. • If 3rd party condensate overflow switches are installed, they should be wired in series between YO and Y to the outdoor unit.

Comfort Control

Air Handler

Air Conditioner

Neatly bundle all low voltage wires behind the service valve cover as shown.

Yellow/Red

Field wiring

Yellow/Black

Blue

Red

YellowGreenWhite

BlueB

B - Blue

WGY1

BrownY2

Y1 - Yellow

Y2 - BrownRO

ORB

YI

W1

YO

Y2

BKG

W2W3 *

(In)

(Out)

FieldWiring

Page 29: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 29

• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat • YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits

to work properly • Internally mounted condensate switch is optional and must be ordered separately • If a 3rd party condensate overflow switch is installed, it should be wired in series between YO and Y to the outdoor unit

Comfort Control

Air Handler

Heat Pump

Neatly bundle all low voltage wires behind the service valve cover as shown.

Yellow/Red

Field wiring

Yellow

Blue

Black(X2)

RedOrange

Red

YellowOrange

GreenWhite

BlueB

B - Blue

WX2

GY1

BrownY2

Y1 - Yellow

Y2 - BrownRO

ORB

YI

W1

YO

Y2

BKG

W2W3 *

R - RedO - Orange

(In)

(Out)

W1 - White

Two Stage HP

FieldWiring

Page 30: Trane Manual a-C 6209 Attic

30 Pub. No. 22-1847-02

TAM7Convertibility

Multi-position Air Handler

Airflo

w

AirflowAirflow

Air

flo

w

Upflow Condensate Drains

Refrigerant Connections

Downflow Condensate Drains

Refrigerant Connections

Vertical Downflow*(as shipped)

Horizontal Left*

Vertical Upflow*

Horizontal Right*

Horizontal Left Condensate Drains

Refrigerant Connections

Horizontal Right Condensate Drains

Refrigerant Connections

* Note: No internal modifications required for any position.1 Badge rotation will keep brand in correct position

1

1

1

1

Page 31: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 31

Dimensions

TAM7 AIR HANDLER DIMENSIONAL DATA

Model No. H W

TAM7A0A24 49.9 17.5

TAM7A0B30 55.7 21.3

TAM7A0C36 56.9 23.5

TAM7A0C42 56.9 23.5

TAM7A0C48 61.7 23.5

TAM7A0C60 61.7 23.5

TAM7 AIR HANDLERS ARE ALL TWO PIECE CABINETS.

21.75”

H

W

Page 32: Trane Manual a-C 6209 Attic

32 Pub. No. 22-1847-02

TAM7 OUTLINE DRAWING

MODEL NO. A B C D E F H FLOWCONTROL

GAS LINE BRAZE

LIQ LINE BRAZE

*AM7A0A24H21SA 49.9 17.5 14.5 39.6 14.5 7.3 24.4 EEV 3/4 3/8

*AM7A0B30H21SA 55.7 21.3 18.4 45.5 18.4 9.2 24.8 EEV 3/4 3/8

*AM7A0C36H31SA 56.9 23.5 20.5 46.7 20.5 10.3 24.2 EEV 7/8 3/8

*AM7A0C42H31SA 56.9 23.5 20.5 46.7 20.5 10.3 24.5 EEV 7/8 3/8

*AM7A0C48H41SA 61.7 23.5 20.5 51.5 20.5 10.3 24.9 EEV 7/8 3/8

*AM7A0C60H51SA 61.7 23.5 20.5 51.5 20.5 10.3 24.9 EEV 7/8 3/8

* May be “A” or “T”

Page 33: Trane Manual a-C 6209 Attic

Pub. No. 22-1847-02 33

Page 34: Trane Manual a-C 6209 Attic

Trane6200 Troup HighwayTyler, TX 75707www.trane.com

04/11