water-cooled series r(tm) - china product report
TRANSCRIPT
![Page 1: Water-Cooled Series R(TM) - China Product Report](https://reader038.vdocument.in/reader038/viewer/2022100506/5531bb79550346dd568b4b3f/html5/thumbnails/1.jpg)
Water-Cooled Series R (TM) - China
Job Information
Job01
Tag CRTHD-1 Compressor configuration E3 Compressor
Evaporator configuration G2 EvaporatorQuantity 1
Condenser configuration G1 Condenser
Product Version 1.8
Unit Information
Capacity Efficiency 0.686 kW/ton349.40 tons
NPLV Refrigerant charge (HFC-134a) 318 kg0.165 kW/kW
Pressure vessel code
Refrigerant isolation valvesRefrigeration isolation valves
Oil cooler With oil cooler
Operating weights include refrigerant, oil, and water charges.
Sound pressure measured in accordance with AHRI Standard 575-94.
Evaporator Information
Evap leaving temp 2.00 C Evap flow rate 59.72 L/s
Evap entering temp 7.00 C Evap pressure drop 6498.51 mm H2O
Minimum evap flow rate 31.04 L/s Evap fouling factor 0.00010 hr-sq ft-deg F/Btu
Number of evaporator passes 4 pass -3.61 CEvap fluid freeze point
Evap fluid type Ethylene Glycol Evap fluid concentration 10.00 %
Condenser Information
Cond entering temp 30.00 C Cond flow rate 88.33 L/s
Cond leaving temp 34.00 C Cond pressure drop 7047.68 mm H2O
Number of cond passes 2 pass condenser Cond fouling factor 0.00025 hr-sq ft-deg F/Btu
Cond fluid concentration 0.00 %Cond fluid type Water
Condenser tube type Enhanced fin - copper
Electrical Information
Unit voltage 415 Volt 3 phase Unit hertz 50 Hertz
Unit power 239.70 kW Starter type Wye-delta closed transition starter
Maximum overcurrent protection 857.30 AMinimum circuit ampacity 476.30 A
Starter expected inrush 776.00 A Motor locked rotor amps 2515.00 A
381.00 ARun load amps
This unit complies with the efficiency requirements of ASHRAE Standard 90.1-1999
Performance for above conditions is rated in accordance with AHRI Standard 550/590. The
following are outside the scope of AHRI Standard 550/590: Glycol, 50 Hz units below 200
tons.
Page 1 of 2
6/27/2011 Product Version 1.8
![Page 2: Water-Cooled Series R(TM) - China Product Report](https://reader038.vdocument.in/reader038/viewer/2022100506/5531bb79550346dd568b4b3f/html5/thumbnails/2.jpg)
Water-Cooled Series R (TM) - China
Job Information
Job01
Tag CRTHD-2 Compressor configuration E3 Compressor
Evaporator configuration G2 EvaporatorQuantity 1
Condenser configuration G1 Condenser
Product Version 1.8
Unit Information
Capacity Efficiency 0.616 kW/ton392.90 tons
NPLV Refrigerant charge (HFC-134a) 318 kg0.146 kW/kW
Pressure vessel code
Refrigerant isolation valvesRefrigeration isolation valves
Oil cooler Without oil cooler
Operating weights include refrigerant, oil, and water charges.
Sound pressure measured in accordance with AHRI Standard 575-94.
Evaporator Information
Evap leaving temp 5.00 C Evap flow rate 65.74 L/s
Evap entering temp 10.00 C Evap pressure drop 7261.24 mm H2O
Minimum evap flow rate 25.93 L/s Evap fouling factor 0.00010 hr-sq ft-deg F/Btu
Number of evaporator passes 4 pass 0.00 CEvap fluid freeze point
Evap fluid type Water Evap fluid concentration 0.00 %
Condenser Information
Cond entering temp 30.00 C Cond flow rate 97.65 L/s
Cond leaving temp 34.00 C Cond pressure drop 8451.11 mm H2O
Number of cond passes 2 pass condenser Cond fouling factor 0.00025 hr-sq ft-deg F/Btu
Cond fluid concentration 0.00 %Cond fluid type Water
Condenser tube type Enhanced fin - copper
Electrical Information
Unit voltage 415 Volt 3 phase Unit hertz 50 Hertz
Unit power 242.00 kW Starter type Wye-delta closed transition starter
Maximum overcurrent protection 865.30 AMinimum circuit ampacity 480.70 A
Starter expected inrush 776.00 A Motor locked rotor amps 2515.00 A
384.60 ARun load amps
This unit complies with the efficiency requirements of ASHRAE Standard 90.1-1999
Certified in accordance with the AHRI Water-Chilling Packages using the Vapor
Compression Cycle Certification Program, which is based on AHRI Standard 550/590.
Page 2 of 2
6/27/2011 Product Version 1.8