(cfs)
TRANSCRIPT
3'-0"
6"
6" TOP SLAB
4'-0"
36"X36" ACCESS HATCH
ELEVATION VIEW
2'-0" 2'-0"
4'-0"
1'-0"
12'-0"
13'-0"
4'-0"5'-0"
ALTERNATE OUTLET
LOCATION
PLAN VIEW
LEFT END VIEW
1'-0"
INLET
Ø12" RCP MAX. OUTLET
18"X36" ACCESS HATCH
BYPASS WEIR/OUTLET BAY
OPENING TO BIOFILTRATION CHAMBER
INLET CONTOUR RACK WITH
PERFORATED FLOOR
24"x7" OPENING
FOR CURB INLET
8'-0"
ALTERNATE INLET
LOCATIONS AVAILABLE
ALTERNATE INLET
LOCATIONS AVAILABLE
2"
MULCH
1'-6"
StormMix™ MEDIA
6" DRAIN ROCK
UNDERDRAIN PIPE
SEE CURB INLET DETAIL
THIS SHEET
CURB INLET DETAIL
CURB INLET WITH
6" NOSING
CAST-IN PLACE CURB &
GUTTER BY OTHERS
7"
4"-6" RECOMMENDED
CURB INLET THROAT
OPENING
Bioretention/
Biofiltration
Ph: 800.579.8819 | www.oldcastleinfrastructure.com/stormwater
THIS DOCUMENT IS THE PROPERTY OF OLDCASTLE INFRASTRUCTURE, INC.
IT IS CONFIDENTIAL, SUBMITTED FOR REFERENCE PURPOSES ONLY AND
SHALL NOT BE USED IN ANY WAY INJURIOUS TO THE INTERESTS OF, OR
WITHOUT THE WRITTEN PERMISSION OF OLDCASTLE INFRASTRUCTURE, INC.
COPYRIGHT © 2021 OLDCASTLE INFRASTRUCTURE, INC. ALL RIGHTS RESERVED.
SHEET NAME REVISION SHEET
REV DATE
-
BioPod™ Biofilter System
CUSTOMER
PROJECT NAME
-
-
-
(STANDARD)
1 OF 1
Specifier Drawing
BPS-412IB
Surface Vault with Internal Bypass
PERFORMANCE SPECIFICATIONS
Treatment Flow Capacities:
NJDEP 80% Removal, 75 micron0.179 cfs
WA Ecology GULD - Basic,
Enhanced & Phosphorus
0.160 cfs
*Contact Oldcastle for alternative treatment flow capacities.
Bypass Capacity
2.0 cfs
NOTES:
1. DESIGN LOADINGS:
A. 300 PSF PEDESTRIAN LOADING
B. DESIGN SOIL COVER: 0' MAXIMUM
C. ASSUMED WATER TABLE: BELOW BASE OF
PRECAST
(ENGINEER-OF-RECORD TO CONFIRM SITE
WATER TABLE ELEVATION)
D. LATERAL EARTH PRESSURE: 45 PCF
(DRAINED)
E. LATERAL LIVE LOAD SURCHARGE: 80 PSF
(APPLIED TO 8'-0" BELOW GRADE)
F. NO LATERAL SURCHARGE FROM ADJACENT
BUILDINGS, WALLS, PIERS, OR FOUNDATIONS.
2. CONCRETE 28-DAY MINIMUM COMPRESSIVE
STRENGTH: 5,000 PSI MINIMUM.
3. REINFORCING: REBAR, ASTM A615/A706, GRADE 60
4. CEMENT: ASTM C150
5. REQUIRED ALLOWABLE SOIL BEARING CAPACITY:
2,500 PSF
6. REFERENCE STANDARD:
A. ASTM C890
B. ASTM C913
C. ACI 318-14
7. THIS STRUCTURE IS DESIGNED TO THE
PARAMETERS NOTED HEREIN.
ENGINEER-OF-RECORD SHALL VERIFY THAT NOTED
PARAMETERS MEET OR EXCEED PROJECT
REQUIREMENTS. IF DESIGN PARAMETERS ARE
INCORRECT, REVIEWING ENGINEER/AUTHORITY
SHALL NOTIFY OLDCASTLE INFRASTRUCTURE UPON
REVIEW.
8. INLET AND OUTLET HOLES WILL BE FACTORY
CORED/CAST PER PLANS AND CUSTOMER
REQUIREMENTS. INLET AND OUTLET LOCATIONS
CAN BE MIRRORED.
9. CONTRACTOR RESPONSIBLE TO VERIFY ALL SIZES,
LOCATIONS, AND ELEVATIONS OF OPENINGS.
10. CONTRACTOR RESPONSIBLE TO ENSURE
ADEQUATE BEARING SURFACE IS PROVIDED (I.E.
COMPACTED AND LEVEL PER PROJECT
SPECIFICATIONS).
11. SECTION HEIGHTS, SLAB/WALL THICKNESSES, AND
KEYWAYS ARE SUBJECT TO CHANGE AS REQUIRED
FOR SITE REQUIREMENTS AND/OR DUE TO
PRODUCT AVAILABILITY AND PRODUCTION FACILITY
CONSTRAINTS.
12. MAXIMUM PICK WEIGHTS":
A. TOP: XX,XXX LBS
B. BASE: XX,XXX LBS*
(* COMBINED WEIGHT OF BASE INCLUDES
BYPASS WEIR, DIVIDER WALL, ROCK & MEDIA)
13. INTERNALS SHALL CONSIST OF UNDERDRAIN
PIPE, ROCK, STORMMIX™ MEDIA, MULCH, AND INLET
CONTOUR RACK.
Structure ID
Treatment Flow Rate (cfs)
Peak Flow Rate (cfs)
Rim Elevation
Pipe Data
Pipe
Size
Pipe
Type
Invert
Elevation
Outlet
Notes:
Pipe
Location
SITE SPECIFIC DATA
ID
-
-
-
- - --