    Linda Morrison

    Jesse StanleyApril 16th 2010

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    2/36

    Energy efficiency

    Renewable energy

    Net zero buildings

    Envelope

    HVAC systems

    Water efficiency and metering

    Rating system, codes, best practice

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    3/36

    LEED-NC Version 3 [RATING SYSTEM]

    Labs 21 [RATING SYSTEM SUPPLEMENT]

    CO-CHPS [RATING SYSTEM]

    ASHRAE 90.1-2007 [STANDARD]

    ASHRAE 189.1-2009 [STANDARD]

    PNNL 50% Energy Savings Design TechnologyPackage Medium Office[GUIDELINE]

    Architecture 2030 [GUIDELINE]

    Living Building Challenge [RATING SYSTEM]

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    4/36

    ASHRAE 189.1

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    5/36

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    6/36

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    7/36

    http://www.architecture2030.org/2030_challenge/targets.html

    http://www.architecture2030.org/2030_challenge/targets.html
  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    8/36

    Energy Star / Energy Use Index (kBTU/sf/yr)

    Compares building performance to average building

    Average building determined by Commercial Building Energy

    Consumption Survey (CBECS) 2003Energy Star Target Finder score of 50 is average

    Target Finder score of 75+ is qualified for Energy Star

    Performance Rating Method 90.1

    Compares design to baselineAll areas modeled as heated and cooled

    Natural ventilation is an exceptional calculation

    Limits on unmet hours

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    9/36

    Reduction fromASHRAE 90.1-2007

    Energy Star

    LEED -NCv3 Mandatory10%

    Points up to 48%

    NA

    CO-CHPS Mandatory 25%Points up to 60%

    Minimum 75Energy StarTarget Finder

    ASHRAE189.1-2009

    Comply with 189 NA

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    10/36

    Living Building Challenge:100% of a projects energy needs must be supplied by on-siterenewable energy on a net annual basis

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    11/36

    Renewables Green Power

    LEED -NCv3 Not mandatory1 point for 1% energy cost

    7 points for 13% energy cost

    1 point for 35% of electrical

    use for 2 years

    CO-CHPS Mandatory Flex EnergySolar Ready7 points for 50+% annual site energywith monitoring system

    after 40% reduction from 90.1-2007:Grid Neutral (electric, site)

    Zero Net Energy (site)ASHRAE

    189-2009Mandatory renewable ready for

    minimum of 3.7 W/sf x roof area

    Prescriptive:

    Requires 6.0 kBtu/sf of conditioned space

    Prescriptive Exception:

    less than 4.0 kW/m2 dailyaverage incident radiation

    AND

    purchase 7 kWh/sf of Green

    Power for 10 yrs

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    12/36

    Design to cost-effectively adapt:

    PV 100% annual electric usage

    Ground Source Heat Pumps 100% of heat / cool

    Thermal Energy Storage 8 hours of heat / coolElectric Vehicles 50% of parking spaces

    Biomass 80% of heating

    Solar HW Heating 50% of pool

    MER for future off-site district energy

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    13/36

    Flex Energy for Buildings

    High-level overview of key systems and technologies

    Checklist of design suggestions

    Online calculator to estimate system capacities and sizerequirements

    Simple electronic workbook to document design decisions

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    14/36

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    15/36

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    16/36

    Climate Zone ASHRAE 90.1 07 ASHRAE 189.1 09* PNNL 50% 90.1 04

    Steel Framed Steel Framed Steel Framed

    C. Z. 4 R-15.6 R-18.2 R-15.6

    C. Z. 5 R-15.6 R-18.2 R-23.8

    C. Z. 6 R-15.6 R-18.2 R-27.0

    C. Z. 7 R-15.6 R-18.2 R-27.0

    *Requires air barrier

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    17/36

    Climate Zone ASHRAE 90.1 07 ASHRAE 189.1 09 PNNL 50% 90.1 04

    Insulation above Deck Insulation above Deck Insulation above Deck

    C. Z. 4 R-20 c.i. R-25 c.i. R-30 c.i.

    C. Z. 5 R-20 c.i. R-25 c.i. R-30 c.i.

    C. Z. 6 R-20 c.i. R-30 c.i. R-30 c.i.C. Z. 7 R-20 c.i. R-35 c.i. R-35 c.i.

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    18/36

    Climate Zone ASHRAE 90.1 07 ASHRAE 189.1 09 PNNL 50% 90.1 04

    U Factor SHGC U Factor SHGC U Factor SHGC

    C. Z. 4 0.40 0.40 0.30 0.35 0.44 0.26

    C. Z. 5 0.35 0.40 0.25 0.35 0.44 0.26

    C. Z. 6 0.35 0.40 0.25 0.40 0.42 0.35

    C. Z. 7 0.35 0.45 0.25 0.45 0.31 0.40

    Nonmetal framing

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    19/36

    Rating System Shading Requirements

    LEED-NCv3 NA

    CO-CHPS NA

    ASHRAE189.1-2009

    Climate Zones 1-5:Fenestration on west, south, and eastshaded by permanent projections

    with Projection Factor of 0.50 ormore

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    20/36

    Shading Requirements

    LEED-NCv3 NA

    CO-CHPS Shade (15 years of growth) to at least 30% of allSW, S, and SE surfaces with 80 ft of building.

    ASHRAE189.1-2009

    Shade 30% of east and west above grade wallsgrade to 20 ft within 5 years of growth

    10 am for east and3 pm for west on summer solstice

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    21/36

    Fan EnergyASHRAE 90.1-2007

    Constant Volume hp

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    22/36

    Economizer

    ASHRAE 90.1-2007Economizers required for units above 65,000 Btu/h to 135,000 Btu/h

    depending on climate zoneHigh Limit Shut offs depend on climate zone and control type

    ASHRAE 189.1-2009Economizers required for units above 33,000 Btu/h for most ClimateZones 3-8

    Rooftop units under a certain size must have a two stage capacity foruse with the outside air economizer

    Fixed leaving air temperature systems must be capable of resettingsupply temperature during economizer operation

    Economizer can be eliminated if cooling efficiency is high enough

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    23/36

    Heat RecoveryStandard Requirements MinimumEffectiveness

    90.1 2007 Systems with 5000 cfm an d 70% or more outside air 50%

    189.1 2009 Depends on Climate Zone, Supply flow, and % Outside Air 60%

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    24/36

    Standard Fume Hoods

    90.1 2007 Fume Hood exhaust over 15,000 cfm must be either :Variable Air Volume

    Dedicated Outside Air System

    Or Heat Recovery

    Labs 21 Consider not using Fume Hoods

    Develop fume hood sash management planFume hood monitoring and control

    Fume hood commissioning

    Fume Hoods

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    25/36

    Building Automation Systems

    Building Automation

    CO-CHPS BAS RequiredIncludes recommended Sensors, Points Matrix, Trend

    Capabilities, and System Architecture

    HVAC and domestic hot water

    Lighting

    189.1 2009 7.3.3 Energy Consumption ManagementRequires measurement and data collection for various systems given

    a certain connected load is met

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    26/36

    Emissions

    CO-CHPS Mandatory Calculate,report, and verify annual GHG emissions tothe Climate Action Registry

    189.1 2009 Emissions to air accounted for in LifeCycle Assessment of

    material components and energy consumption

    Green House Gas Emissions

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    27/36

    Living Building Challenge:

    Net Zero Water

    LBC allows initial water purchase only

    Would require on site water treatment including black water100% of storm water and building water must be handled on sitefor reuse

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    28/36

    Indoor Water Sewer Conveyance Process Water

    Reduction Reduction Efficiency

    LEED-NCv3 Mandatory 20%

    Points for 30%-40%

    50% Reduction

    Treat 50% on-site

    Schools:

    20% reductionNo garbage disposals

    No once-throughcooling

    CO-CHPS Mandatory 20%

    Points for up to 50%Includes process

    35% reduction

    through efficiencyor reclaimed or

    recycled water

    See Indoor

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    29/36

    Fixture LEED-NCv3CO-CHPS

    ASHRAE 189.1-2009

    Toilets 1.6 gpf 1.28 gpf

    Urinals 1.0 gpf 0.5 gpfFaucets 0.5 gpm

    0.25 g metering

    0.5 gpm

    0.25 g metering

    Kitchen Faucets 2.2 gpm 2.2 gpm

    Showerheads 2.5 gpm 2.0 gpm

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    30/36

    Process Water

    Efficiency

    ASHRAE 189.1-

    2009

    No once-though cooling w/potable

    Cooling tower drift:0.002% counterflow

    0.005% cross-flow

    Cycles of concentration

    Recover condensate

    SteamA/C units > 65,000 kBTU/hr

    Labs 21 No domestic water once-through cooling at a flow rate

    greater than 2 gallons per minute

    20% process water reduction

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    31/36

    Metering

    LEED-NCv3 NA

    CO-CHPS WE3.1.1 1 point:

    Separately meter domestic water, exterior irrigation and equipment

    exceeding 20% of total and provide maintenance plan

    WE3.1.21 point:

    Water Management System with pulse output water meters

    Indoor water

    Gyms with showers

    Landscaping

    Recreational fields

    Swimming pool

    Cooling towers

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    32/36

    Metering

    ASHRAE

    189.1-2009

    Water Consumption Management for potable > 1000 gal/day and

    reclaimed water > 1000 gal/day

    Cooling towers > 500 gpm through tower

    Evaporative coolersmakeup water > 0.6 gpm

    Steam and hot water boilers > 500,000 BTU/hr

    Submeters for tenants

    Irrigation > 25,000 sf

    Labs 21 Document annual process water use and wastewater

    Meters for process water

  • 7/29/2019 1 Rmashrae Rating Systems 0416 10

    33/36

    Living Building Challenge:

    First two projects to be certified in May 2010

    Colorado:

    1 not confidential The Lindholm Residence, Snowmass, CO

    3 confidential Carbondale, Telluride (commercial/medical), other

    Elsewhere:

    70 officially registered projects in N. America

    4 International (France, Ireland, Australia, Colombia)