4009951 further information webcode: GW-1242 GEMÜ 1242 Electrical position indicator Features Fieldbus connection AS-Interface and DeviceNet (optional) Communication and programming interface IO-Link Adjustable switch point tolerances Speed -AP function for fast mounting and initialisation High visibility position indicator by LED Can be fitted to GEMÜ valves or third-party actuators On-site or remote end position programming via programming input Description The GEMÜ 1242 electrical position indicator is suitable for mounting to pneumatically operated linear actuators. Secure con- nection to valve spindle means reliable feedback signal. Intelligent microprocessor controlled functions make commissioning and support during operation easier. The current position of the valve is displayed via high visibility LEDs and fed back via electrical signals. The GEMÜ 1242 has been specially designed for valves with a stroke of 2 to 46 mm. Technical specifications Ambient temperature: 0 to 60 °C Stroke: 2 to 46 mm Communication modes: 24 V with IO-Link | AS-Interface | DeviceNet Protection class : IP 67

Upload: others

Post on 26-Oct-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: db 1242 gb - gemu-group.com

4009951

further informationwebcode: GW-1242

GEMÜ 1242Electrical position indicator

Features• Fieldbus connection AS-Interface and DeviceNet (optional)• Communication and programming interface IO-Link• Adjustable switch point tolerances• Speed-AP function for fast mounting and initialisation• High visibility position indicator by LED• Can be fitted to GEMÜ valves or third-party actuators• On-site or remote end position programming via

programming input

DescriptionThe GEMÜ 1242 electrical position indicator is suitable for mounting to pneumatically operated linear actuators. Secure con-nection to valve spindle means reliable feedback signal. Intelligent microprocessor controlled functions make commissioningand support during operation easier. The current position of the valve is displayed via high visibility LEDs and fed back viaelectrical signals. The GEMÜ 1242 has been specially designed for valves with a stroke of 2 to 46 mm.

Technical specifications• Ambient temperature: 0 to 60 °C• Stroke: 2 to 46 mm• Communication modes: 24 V with IO-Link | AS-Interface | DeviceNet• Protection class : IP 67

Page 2: db 1242 gb - gemu-group.com

www.gemu-group.com2 / 20GEMÜ 1242

Product description

1

2

4

3

5

Item Name Materials1 Housing cover - standard version: PC2 Housing base Anodised aluminium or SS3 Electrical connection SS, PP4 Adapter piece SS5 Mounting kit, valve specific SS

Seals EPDM and NBR

Product description

Page 3: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 3 / 20

Status LEDsAs well as the electrical position feedback and error analysis a visual signal is emitted by LEDs that can be seen from above.

24 V / AS-Interface / IO-Link version DeviceNet version

LED Colour FunctionStandard 1) Inversed 2)

CLOSED green orange Process valve in CLOSEDposition

ERROR red red ErrorOPEN orange green Process valve in OPEN

positionMNS green green Communication existing

red red Communication errorPWR/FAULT green green Communication existing

red red Communication errorHigh visibility LED green orange Process valve in CLOSED

positionorange green Process valve in OPEN

positiongreen / orange green / orange Programming mode

1) OptionCode 00: Without

2) OptionCode 40: Inversed LED feedback

For order codes see chapter "Order data"

AvailabilityOption Code 24 V / IO-Link

Code 000AS-Interface

Code A2, A3, A4DeviceNetCode DN

Housing material 1) 07 X X X14 X X X

Option 2) 00 X X X40 X X X

Electrical connection 3) 01 X X X02 X - -

1) Housing materialCode 07: Stainless steel base, PC coverCode 14: Aluminium base, PC cover

2) OptionCode 00: WithoutCode 40: Inversed LED feedback

3) Electrical connectionCode 01: M12 plug, 5-pinCode 02: M12 plug, 8-pin

Availability

Page 4: db 1242 gb - gemu-group.com

www.gemu-group.com4 / 20GEMÜ 1242

Overview of available functionsFunction Version

24 V / IO-Link AS-Interface DeviceNetA2 A3 A4

Optical high visibility position indicator X X X X XDeactivation high visibility positionindicator

X - - X X

On-site programming X X X X XDeactivation of on-site programming X - - X XPosition feedback Open X X X X XPosition feedback Closed X X X X XFeedback for operating mode X X X X XLocation function X - - X XInversion of LED colours X - - X XInversion of feedback signals X - - X XSwitch point setting (tolerance) X X X X XSetting stroke reduction alarm X - - - XFeedback stroke reduction alarm X - - X XFeedback programmed positions X - - - XFeedback current positions X - - - XFeedback internal error X X X X XFeedback sensor error X X X X XFeedback programming error X X X X XFeedback over-temperature X - - - -Counter Powerfail X - - - -Counter Power on X - - - -Programming counter X - - - -Counter programming error X - - - -Counter sensor error X - - -Counter over-temperature X - - - -Cycle counter (on-site) X - - - XTotal cycle counter X - - - XDefault X - - - Via

DeviceNet

Overview of available functions

Page 5: db 1242 gb - gemu-group.com

Order dataThe order data provide an overview of standard configurations.

Please check the availability before ordering. Other configurations available on request.

Note: A valve specific mounting kit is required for assembly. For designing the mounting kit, the valve type, nominal size, con-trol function and actuator size must be stated.

Order codes1 Type CodeElectrical position indicator 1242

2 Fieldbus CodeWithout, 24 V version, with IO-Link 000AS-Interface, 31 slaves, 4I/4O A2AS-Interface, 62 slaves, 4I/3O A3AS-Interface, 62 slaves, 8I/8O A4DeviceNet DN

3 Accessory CodeAccessory Z

4 Housing material CodeStainless steel base, PC cover 07Aluminium base, PC cover 14

5 Function CodePosition feedback Open / Closed 00

6 Electrical connection CodeM12 plug, 5-pin 01M12 plug, 8-pin 02

7 Option CodeWithout 00Inversed LED feedback 40

8 Switch CodeElectronics E0

9 Connection diagram CodeM12 plug, 5-pin 01M12 plug, 8-pin 02

10 Special version CodeWithoutNEC 500 and UL/CSA approval YATEX (2014/34/EU) X

Order exampleOrder option Code Description

1 Type 1242 Electrical position indicator2 Fieldbus 000 Without, 24 V version, with IO-Link3 Accessory Z Accessory4 Housing material 14 Aluminium base, PC cover5 Function 00 Position feedback Open / Closed6 Electrical connection 01 M12 plug, 5-pin7 Option 00 Without8 Switch E0 Electronics9 Connection diagram 01 M12 plug, 5-pin10 Special version Without

Order data

GEMÜ 1242www.gemu-group.com 5 / 20

Page 6: db 1242 gb - gemu-group.com

www.gemu-group.com6 / 20GEMÜ 1242

Technical dataTemperatureAmbient temperature: 0 to 60 °C

Storage temperature: 0 to 40 °C

Product complianceEMC Directive: 2014/30/EU

24 V / IO-Link AS-Interface DeviceNetInterferenceemission

EN 61000-6-3 acc. to AS-InterfaceSpec. 3.0

EN 61000-6-3

Interferenceresistance

EN 61000-6-2 acc. to AS-InterfaceSpec. 3.0

EN 61000-6-2

Explosion protection: ATEX (2014/34/EU), order code special version XNEC 500 (ISA 12.12.01), order code for special version Y

ATEX marking: Gas: II 3G Ex ec nC IIC T4 Gc XDust: II 3D Ex tc IIIC T 80 °C Dc XType examination certificate: IBExU18ATEXB008 X

NEC marking: Class I, Division II, Groups C & D, T4

Mechanical dataInstallation position: Optional

Weight: 320 g (aluminium version)600 g (stainless steel version)

Protection class: IP 67IP NEMA 4X (UL 61010-1, UL 50E), only available as special version code YIP64, only as special version code X

Travel sensor: Minimum stroke: 2 mmMaximum stroke: 46 mmHysteresis: 0.2 mmAccuracy: 0.2 Full Scale

Technical data

Page 7: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 7 / 20

Electrical dataSupply voltage Uv: 24 V / IO-Link AS-Interface DeviceNet

24 V DC(18 to 30 V DC)

26.5 to 31.6 V DC 24 V DC (11 to 25 V DC)

Duty cycle: Continuous duty

Reverse batteryprotection:

yes

Line fuse: 630 mA medium time lag, for order code Fieldbus 000

Current consumption: 24 V / IO-Link AS-Interface DeviceNettypically 40 mA typically 50 mA typically 30 mA

Electrical connectiontype:

1 x 5-pin M12 plug (A-coded)

Switching characteristic:

100%

0%

td1 td1

td1 td2td1

tat/ms

t/ms

t/ms

Stroke %

Switch point "Open"Switching hysteresis

Switching hysteresis

Switching output "Open"

Switch point "Closed"

active

inactive

active

inactive

Switching output "Closed"

td1: Signal delaytd2: Signal delayta: Signal interval

Switch points: The data in percent refers to the programmed stroke, before each end position

Switch points: Default setting switch point CLOSED 12 %Default setting switch point OPEN 25 %Min. switch point CLOSED 0.8 mmMin. switch point OPEN 0.5 mm

If the percentage switch points dependent on the programmed stroke are smaller than the per-missible min. switch points, the min. switch points apply automatically.

Electrical protectionclass:

III

Technical data

Page 8: db 1242 gb - gemu-group.com

www.gemu-group.com8 / 20GEMÜ 1242

Dimensions

98

Ø57

X

1316,647

WAF 20 for mounting kit M12x1,x = 9 mm WAF 24 for mounting kit M16x1,x = 11 mm dependent on valve usedDimensions in mm

Dimensions

Page 9: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 9 / 20

Electrical connection24 V / IO-Link, ordering option Fieldbus, code 000Pin assignment

1

4

3

2

5

Pin Signal name1 U, 24 V DC, supply voltage2 24 V DC, Open end position output3 U, GND4 24 V DC, Closed end position output, C/Q IO-Link5 24 V DC, programming input

Pin 5 is highly active. If not used, connect to GND or leave open.

Inputs (pin 5)Input impedance: min. 27 kΩ

Input voltage: max. 30 V DC

High level: ≥ 18 V DC

Low level: ≤ 5 V DC

Outputs (pin 2, 4)Internal wiring:

Push-Pull

Max. switching current: ± 100 mA

Max. voltage drop Vdrop: 3 V DC at 100 mA

Switching voltage: +Uv - Vdrop push high-Uv + Vdrop pull low

AS-Interface, ordering option Fieldbus, code A2, A3, A4Pin assignment

1

4

3

Pin Signal name1 AS-Interface +2 -3 AS-Interface -

Electrical connection

Page 10: db 1242 gb - gemu-group.com

www.gemu-group.com10 / 20GEMÜ 1242

Pin Signal name4 n.c.5 -

Carry out potential equalisation via pre-assembled earthing kit.Connect yellow/green stranded wire H07 V-K 4.0 on site.

DeviceNet, ordering option Fieldbus, code DNNet topology - DeviceNet systemTo avoid malfunction the trunk cable is fitted with resistors on both sides. The drop cables do not require bus ends.

V+V-

CAN_H120 Ω 1/4 W

CAN_LShield

Protectiveearth

Protectiveearth

Drop cable

120 Ω 1/4 W

Trunk cable

Maximum cable lengthBaud rate [kBaud] Trunk cable Drop cable

Thick cable Thin cable Max. cable length perdrop cable

Max. drop cable accu-mulated length

125 500 m 100 m 6 m 156 m250 250 m 100 m 6 m 78 m500 100 m 100 m 6 m 39 m

Electrical connection

Page 11: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 11 / 20

Pin assignment

1

4

3

2

5

Pin Signal name1 Shield2 V+3 V-4 CAN_H5 CAN_L

Specific data IO-Link (pin 4)Frame type in Operate: 2.5

Transmission rate: 38400 baud

Min. cycle time: 2.3 ms

Physics: Physics 2 (3-wire design)

Port configuration: Port type A

Vendor-ID: 401

Device-ID: 124201

Product-ID: 1242 IO-LINK

ISDU support: yes

SIO operation: yes

IO-Link specification: V1.1

InputsBit Default Designation Function Logic0 0 Valve position Feedback OPEN position 0 = process valve not in OPEN position

1 = process valve in OPEN position1 0 Valve position Feedback CLOSED position 0 = process valve not in CLOSED position

1 = process valve in CLOSED position2 0 Programing mode Indication of operating mode 0 = normal operation

1 = programing mode3...7 not used

OutputsBit Default Designation Function Logic0 not used1 0 Programing mode Selection of operating mode 0 = normal operation

1 = programing mode2 0 Location function Location function 0 = not active

1 = active3 … 7 not used

Specific data IO-Link (pin 4)

Page 12: db 1242 gb - gemu-group.com

www.gemu-group.com12 / 20GEMÜ 1242

ParameterIndex[Hex]

Su-bindex

Parameter Length

Datatype

Ac-cess

Standardvalue

Value range

0x10 0 Vendor Name 6 byte StringT ro GEMUE -0x12 0 Product Name 13

byteStringT ro 1242 IO-Link -

0x13 0 Product ID 8 byte StringT ro 1242 IO-LINK -0x15 0 Serial number 9 byte StringT ro 0 –

4294967296-

0x16 0 Hardware Revision 8 byte StringT ro Rev. xx -0x17 0 Firmware Revision 10

byteStringT ro V x.x.x.x -

0x50 1 Inversion of LED colours 1 bit Boolean rw 0 0 = standard1 = inversed

2 Inversion of feedback signals 1bit Boolean rw 0 0 = standard1 = inversed

3 Function of high visibility 3 bit UIntegerT rw 3 0 = off1 = open/closed (33 %)2 = open/closed (66 %)3 = open/closed (100 %)

4 Programming mode 1 bit Boolean rw 0 0 = automatic1 = manual

5 On site programming 1 bit Boolean rw 0 0 = enabled1 = disabled

6 Inversion of Outputs 1 bit Boolean rw 0 0 = standard1 = inversed

0x51 1 Switch Point OPEN request 8 bit UIntegerT rw 25 % 3 % - 97 %2 Switch Point CLOSED request 8 bit UIntegerT rw 12 % 3 % - 97 %3 Switch Point OPEN real 8 bit UIntegerT ro 25 % Display of values

3 % - 97 %4 Switch Point CLOSED real 8 bit UIntegerT ro 12 % Display of values

3 % - 97 %0x52 1 Alarm Stroke reduction OPEN 4 bit UIntegerT rw 1 0 = disabled

1 = 25 % of Switch Point2 = 50 % of Switch Point3 = 75 % of Switch Point

2 Alarm Stroke reduction CLOSED 4 bit UIntegerT rw 1 0 = disabled1 = 25 % of Switch Point2 = 50 % of Switch Point3 = 75 % of Switch Point

3 Alarm opening time 8 bit UIntegerT rw 0 0 = disabled1-255 s

4 Alarm closing time 8 bit UIntegerT rw 0 0 = disabled1-255 s

0x53 1 Programmed position OPEN 16 bit UIntegerT ro 0 Display of numerical values0 - 40922 Programmed position CLOSED 16 bit UIntegerT ro 0

3 Programmed position STROKE 16 bit UIntegerT ro 00X54 1 Last position OPEN 16 bit UIntegerT ro 0

2 Last position CLOSED 16 bit UIntegerT ro 03 Last position STROKE 16 bit UIntegerT ro 0

0X56 1 Valve cycles user 24 bit UIntegerT rw 0 Resettable to 0, display of numerical values0 - 16777215

Specific data IO-Link (pin 4)

Page 13: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 13 / 20

Index[Hex]

Su-bindex

Parameter Length

Datatype

Ac-cess

Standardvalue

Value range

2 Valve cycles total 24 bit UIntegerT ro 0 Display of numerical values 0 - 16777215

0x57 1 Counter Powerfail 16 bit UIntegerT ro 0 Display of numerical values0 - 655352 Counter Power on 16 bit UIntegerT ro 0

3 Counter Programming 16 bit UIntegerT ro 04 Counter Sensor calibration 16 bit UIntegerT ro 05 Counter Prog error no stroke 16 bit UIntegerT ro 06 Counter Prog error less stroke 16 bit UIntegerT ro 07 Counter Prog error after sensor

error16 bit UIntegerT ro 0

11 Counter Sensor error open 16 bit UIntegerT ro 012 Counter Sensor error closed 16 bit UIntegerT ro 016 Counter Over temperature 16 bit UIntegerT ro 0

0X60 0 Actual AD-value 16 bit UIntegerT ro 0 Display of numerical values0 - 4092

Specific data - AS-InterfaceA2 version A3 version A4 version

AS-Interface specification 3.0; max. 31 slaves 3.0; max. 62 slaves 3.0; max. 62 slavesAS-Interface profile S 7.F.E (4I/4O) S 7.A.E (4I/3O) S 7.A.A (8I/8O)I/O configuration 7 7 7ID code F A AID2 code E E AAS-Interface approval AS-Interface certificate No. 96002

InputsBit Default Function Version Logic

A2 A3 A4DI0 0 Indication of OPEN position X X X 0 = process valve not in OPEN position

1 = process valve in OPEN positionDI1 0 Indication of CLOSED position X X X 0 = process valve not in CLOSED position

1 = process valve in CLOSED positionDI2 0 Indication of operating mode X X X 0 = normal operation

1 = programming modeDI3 0 Error 2 X X X see error analysisDI4 0 Error 3 - - XDI5 0 Error 4 - - XDI6,DI7

not used - - X

PF 0 Error 1 X X X see error analysis

OutputsBit Default Function Version Logic

A2 A3 A4DO0,DO1

not used X X X

DO2 0 Setting slave in programming mode X X X 0 = normal operation1 = programming mode

DO3 0 Programming mode X - - 0 = manual programming1 = automatic programming

Specific data - AS-Interface

Page 14: db 1242 gb - gemu-group.com

www.gemu-group.com14 / 20GEMÜ 1242

Bit Default Function Version LogicA2 A3 A4

0 Function of high visibility positionindicator

- - X 0 = activated1 = deactivated

DO4 0 Inversion of feedback signals - - X 0 = standard1 = inversed

DO5 0 Inversion of LED colours - - X 0 = standard1 = inversed

DO6 0 Location function - - X 0 = deactivated1 = activated

DO7 0 On-site programming - - X 0 = enabled1 = disabled

Specific data - AS-InterfaceA2 version A3 version A4 version

AS-Interface specification 3.0; max. 31 slaves 3.0; max. 62 slaves 3.0; max. 62 slavesAS-Interface profile S 7.F.E (4I/4O) S 7.A.E (4I/3O) S 7.A.A (8I/8O)I/O configuration 7 7 7ID code F A AID2 code E E AAS-Interface approval AS-Interface certificate No. 96002

InputsBit Default Function Version Logic

A2 A3 A4DI0 0 Indication of OPEN position X X X 0 = process valve not in OPEN position

1 = process valve in OPEN positionDI1 0 Indication of CLOSED position X X X 0 = process valve not in CLOSED position

1 = process valve in CLOSED positionDI2 0 Indication of operating mode X X X 0 = normal operation

1 = programming modeDI3 0 Error 2 X X X see error analysisDI4 0 Error 3 - - XDI5 0 Error 4 - - XDI6,DI7

not used - - X

PF 0 Error 1 X X X see error analysis

OutputsBit Default Function Version Logic

A2 A3 A4DO0,DO1

not used X X X

DO2 0 Setting slave in programming mode X X X 0 = normal operation1 = programming mode

DO3 0 Programming mode X - - 0 = manual programming1 = automatic programming

0 Function of high visibility positionindicator

- - X 0 = activated1 = deactivated

DO4 0 Inversion of feedback signals - - X 0 = standard1 = inversed

DO5 0 Inversion of LED colours - - X 0 = standard1 = inversed

Specific data - AS-Interface

Page 15: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 15 / 20

Bit Default Function Version LogicA2 A3 A4

DO6 0 Location function - - X 0 = deactivated1 = activated

DO7 0 On-site programming - - X 0 = enabled1 = disabled

Specific data - DeviceNetCommunication modes: Function, Polling, Change of state, Cyclic, Bit strobe

IdentityClass Inst. Attr. Function Value

1h 1h 1h Vendor ID 8692h Product Type 433h Product Code 12424h Rev. 2.2 1)

5h Status Device status according to DeviceNet specifications6h Series No. Continuous serial number7h Name 1242 DN position indicator

1) Use EDS file in accordance with revision status of the device

Note: Download EDS files from www.gemu-group.com

InputsBit Default Designation Function Logic

0, 1 not used2 0 Programmingmode Operating mode 0 = normal operation

1 = programming mode3 0 Position Closed CLOSED position 0 = process valve not in CLOSED position

1 = process valve in CLOSED position4 0 Position Open OPEN position 0 = process valve not in OPEN position

1 = process valve in OPEN position5 0 Calibrationmode Calibration mode 0 = normal operation

1 = calibration mode6 0 Global warnings Warning 0 = warning not active

1 = warning active7 0 Global errors Error 0 = error not active

1 = error active

As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h

OutputsBit Default Designation Function Logic

0 … 2 not used3 0 Location function Location function 0 = location function not active

1 = location function active4 not used5 0 Manual

programmingManual programming mode 0 = manual programming mode not

active1 = manual programming mode active

6 0 Automaticprogramming

Automatic programming mode: 0 = automatic programming mode notactive1 = automatic programming mode active

7 not used

As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h

Specific data - DeviceNet

Page 16: db 1242 gb - gemu-group.com

www.gemu-group.com16 / 20GEMÜ 1242

ParameterClass Inst. Attr. Parameter Lengt

hDatatype

Ac-cess

Stand-ard

value

Value range

Fh 1h 1h Inversion of LED colours 1 byte Boolean Get/Set 0 0 = standard1 = inversed

Fh 2h 1h Inversion of signals 1 byte Boolean Get/Set 0 0 = standard1 = inversed

Fh 3h 1h Function of high visibility 1 byte USINT Get/Set 3 0 = OFF1 = 33 %2 = 66 %3 = 100 %4 = Closed 100%; Open OFF5 = Closed OFF; Open 100%

Fh 4h 1h On site programming 1 byte Boolean Get/Set 0 0 = enabled1 = disabled

Fh 5h 1h Switch Point OPEN request 1 byte USINT Get/Set 25 3 % – 97 %Fh 6h 1h Switch Point OPEN real 1 byte USINT Get 0 Display of values 0 % – 100 %Fh 7h 1h Switch Point CLOSED request 1 byte USINT Get/Set 12 3 % – 97 %Fh 8h 1h Switch Point CLOSED real 1 byte USINT Get 0 Display of values 0 % – 100 %Fh 9h 1h Alarm stroke reduction OPEN 1 byte USINT Get/Set 1 0 = disabled

1 = 25 %2 = 50 %3 = 75 %

Fh Ah 1h Alarm stroke reductionCLOSED

1 byte USINT Get/Set 1 0 = disabled1 = 25 %2 = 50 %3 = 75 %

Fh Bh 1h Alarm opening time 1 byte USINT Get/Set 0 0 - 255 (0 = off)Fh Ch 1h Alarm closing time 1 byte USINT Get/Set 0 0 - 255 (0 = off)Fh Fh 1h Programmed position OPEN 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 10h 1h Programmed position CLOSED 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 11h 1h Programmed stroke 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 12h 1h Last position OPEN 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 13h 1h Last position CLOSED 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 14h 1h Last stroke 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 15h 1h Valve position 2 byte UINT Get 0 Display of numerical values 0 -

4092Fh 16h 1h Sensor error 1 byte USINT Get 0 0 = Sensor OK

1 = Sensor error positionclosed2 = Sensor error position open

Fh 17h 1h Programming error 1 byte USINT Get 1 0 = Programming OK1 = not calibrated2 = no stroke3 = stroke < min. stroke4 = Sensor error positionclosed

Specific data - DeviceNet

Page 17: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 17 / 20

Class Inst. Attr. Parameter Length

Datatype

Ac-cess

Stand-ard

value

Value range

5 = Sensor error position open6 = Sensor error positionclosed + open

Fh 19h 1h Internal error 1 byte USINT Get 0 0 = Device OK1 = un-valid crc-check2 = un-valid serial number3 = Memory error

Fh 1Ah 1h Stroke reduction warning 1 byte USINT Get 0 0 = Stroke OK1 = Stroke reduction positionclosed2 = Stroke reduction positionopen3 = Stroke reduction positionclosed + open

Fh 1Bh 1h Valve cycles user 4 byte UDINT Get/Set 0 Resettable to 0, display of numerical values 0 - 429496729

Fh 1Ch 1h Valve cycles total 4 byte UDINT Get 0 Display of numerical values 0 - 429496729

Specific data - DeviceNet

Page 18: db 1242 gb - gemu-group.com

www.gemu-group.com18 / 20GEMÜ 1242

AccessoriesGEMÜ 4242000ZMAProgramming magnet

Ordering information

Order number: 88377537

GEMÜ 1219Cable socket / cable plug M12The GEMÜ 1219 is a connector (cable socket / cable plug) M12, 5-pin. Straight and/or 90° angled plugtype. Defined cable length or with threaded connection without cable. Various materials available for thefixing nut.

Ordering information

Description Length Order number5-pin, angle without cable 88205545

2 m cable 882055345 m cable 8820554010 m cable 8821091115 m cable 88244667

5-pin, straight without cable 882055442 m cable 882055425 m cable 8820554310 m cable 8827097215 m cable 88346791

8-pin, angle 5 m cable 883745748-pin, straight without cable 88304829

GEMÜ 4150AS-Interface extension plugThe AS Interface Extension Plug serves to extend the network cable length from the current 100 m to 200m without a repeater. This is a passive component without an address in the AS-Interface fieldbus sys-tem. At the same time, the extension plug serves as a voltage monitor. Low voltages are signalled by theintegrated LED. The extension plug can also be employed in a standard network in order to improve thesignal quality and to reduce possible existing telegram error rate.Ordering information

Order number: 88262994

Accessories

Page 19: db 1242 gb - gemu-group.com

GEMÜ 1242www.gemu-group.com 19 / 20

GEMÜ 4160AS-Interface I/O moduleThe AS-Interface I/O module 4160 is designed as a compact, robust field module. It is composed of anelectronic module and a coupler module. Connectors for sensors / actuators can be found on the elec-tronic module. The coupler module serves to accommodate the AS-Interface flat cable and to assemblethe module. The type 4160 modules have binary inputs / outputs. The status of the inputs/outputs andthe power supply are signalled by the LEDs located on the front.Ordering information

Order number: 88317542

GEMÜ 4170AS-Interface cable, 100 mAS-Interface cable, 100 m yellow

Ordering information

Order number: 88073528

GEMÜ 4180AS-Interface connectorAS-Interface connector (M12 on AS-Interface, flat cable)

Ordering information

Order number: 88073531

GEMÜ SERVICE-IO-LINK-KITProgramming setProgramming kit, comprising IO-Link master, adapter and cable gland.The programming kit is suitable forall GEMÜ IO-Link interfaces.

Ordering information

Order number: 99072365

Accessories