dräger regard 3910 control system - draeger web...

4
The Dräger REGARD 3910 is a modular control panel for cabinet construction, based upon the Dräger REGARD 3900. Multiple systems can be installed into new or existing cabinets providing a unique solution to gas detection control. With a panel mounted display and new backplane, to allow the input and output cards to be installed into a cabinet, the REGARD 3910 is a flexible and expandable option for the gas detection control market. The Dräger REGARD 3910 allows the mounting of multiple systems into one control panel. Each system is controlled by a display board which can operate a mixture of up to four input and output boards. In addition, two repeat 4-20 mA boards can also be installed. As each system works independently there is no limit as to how many system are utilised. Each control system is fully configurable between 1 and 16 channels, depending upon the type and quantity of input and output boards installed. Developed with an innovative modular design, this allows the entire system to be suitable for the most stringent of budgets. With the flexibility of the system this allows changes and upgrades to accommodate with ease any plant expansions that are made. ANALOGUE INPUT BOARD Each analog input board caters for one to four, 2 or 3 wire, 4 to 20 mA transmitters. Each transmitter connects to dedicated field terminals. Up to a total of four analogue input boards can be installed in to a single Dräger REGARD 3910, thus giving a maximum input count of sixteen transmitters. Each individual input board is populated with three relays. These relays offer common Fault, Alarm 1 and Alarm 2 SPCO outputs. The two alarm levels are fully configurable and be set as rising or falling, latching or non-latching. To differentiate between each input board a simple mechanical link is required. RELAY OUTPUT BOARD Each relay output board is populated with eight additional SPCO relays. Relay 1 on each relay board is a dedicated Fault relay and cannot be reconfigured. The remaining seven relays can be configured as Single, Common, Voting, Inhibit or Non-operational. An additional Alarm 3 level is offered by the relay board along with a second Fault threshold. All configurable relays can be Rising/Falling, Dräger REGARD 3910 Control System Dräger REGARD 3910 Control System D-4258-2010 D-2519-2010

Upload: others

Post on 14-Apr-2020

44 views

Category:

Documents


0 download

TRANSCRIPT

The Dräger REGARD 3910 is a modular control panel for cabinet construction, based upon the Dräger REGARD 3900.Multiple systems can be installed into new or existing cabinetsproviding a unique solution to gas detection control.

With a panel mounted display and newbackplane, to allow the input and outputcards to be installed into a cabinet, theREGARD 3910 is a flexible and expandableoption for the gas detection control market.

The Dräger REGARD 3910 allows themounting of multiple systems into onecontrol panel. Each system is controlledby a display board which can operate amixture of up to four input and outputboards. In addition, two repeat 4-20 mAboards can also be installed. As each system works independently there is nolimit as to how many system are utilised.

Each control system is fully configurablebetween 1 and 16 channels, dependingupon the type and quantity of input andoutput boards installed.

Developed with an innovative modulardesign, this allows the entire system tobe suitable for the most stringent ofbudgets. With the flexibility of the systemthis allows changes and upgrades toaccommodate with ease any plant expansions that are made.

ANALOGUE INPUT BOARD

Each analog input board caters for one tofour, 2 or 3 wire, 4 to 20 mA transmitters.Each transmitter connects to dedicatedfield terminals. Up to a total of four analogue input boards can be installed into a single Dräger REGARD 3910, thusgiving a maximum input count of sixteentransmitters. Each individual input boardis populated with three relays. Theserelays offer common Fault, Alarm 1 andAlarm 2 SPCO outputs. The two alarm levels are fully configurable and be set asrising or falling, latching or non-latching.To differentiate between each input boarda simple mechanical link is required.

RELAY OUTPUT BOARD

Each relay output board is populated witheight additional SPCO relays. Relay 1 oneach relay board is a dedicated Fault relayand cannot be reconfigured. The remaining seven relays can be configuredas Single, Common, Voting, Inhibit orNon-operational. An additional Alarm 3level is offered by the relay board alongwith a second Fault threshold. All configurable relays can be Rising/Falling,

Dräger REGARD 3910Control System

Dräger REGARD 3910 Control System

D-4258-2010

D-2519-2010

9046827_PI_Regard_3910_engl_2 16.03.10 17:35 Seite 1

DRÄGER REGARD 3910 CONTROL SYSTEM02 |

Latching/Non Latching and NormallyEnergised/Energised on alarm. Alarmrelays are acknowledged via the push button located on the front panel of the instrument housing. A maximum of tworelay boards can be installed in a singleDräger REGARD 3910 control system.

REPEAT BOARD

Each 4-20mA output board repeats thesignal of up to eight inputs. This allows

indication or recording of gas levels byother units. A maximum of two analogueoutput boards can be installed in a singleDräger REGARD 3910 control system.

SYSTEM CONFIGURATION

The Dräger REGARD 3910 is fully configurable via a Laptop PC. The configuration software, Config 3900,allows quick and easy set-up. For newinstallations the configuration can be

ORDER INFORMATION

Dräger REGARD 3910 Order Code

Dräger REGARD 3910 Display Assembly 42 08 830

Dräger REGARD 3910 Mounting Plate for I/O Boards 42 08 831

Dräger REGARD 3900/3910/3920 4-20 Module 42 08 782

Dräger REGARD 3900/3910/3920 Relay Module 42 08 784

Dräger REGARD 3900/3910/3920 4-20mA Repeat Output Board 42 08 797

Dräger REGARD 3900/3910/3920 CAN Interface 42 08 785

performed off-line and then uploaded during commissioning. Or during a Serviceroutine, the system configuration can bedownloaded from the Dräger REGARD3910 to the PC for verification. All calibration routines, zero and span areperformed using the Config 3900 configuration software. A simple interfacecable is required to connect the PC to theDräger REGARD 3910 control unit.

9046827_PI_Regard_3910_engl_2 16.03.10 17:35 Seite 2

DRÄGER REGARD 3910 CONTROL SYSTEM | 03

TECHNICAL DATA

Type Control unit for location in a non-hazardous area

Gas and ranges Toxic, oxygen and combustible gases with user definable measuring ranges. Refer to transmitter type for ranges, name and engineering units. All configurations by Laptop computer.

Inputs 2 or 3 wire 4-20 mA transmittersRemote reset24 VDC supply

Outputs Alarm 1, Alarm 2 and Fault as standardWarning and Inhibit relays on optional relay board Single, common or voted alarms on optional relay board Acknowledgeable relays on optional relay board Repeat 4-20 mA via optional Repeat Board

Display 4 line, 40 character back-lit LCDActive, Fault, Alarm 1 and Alarm 2 LED’s per inputDC and AC power LED’sInhibit LED

Power supply External 24 VDC

Internal 2.5 A, 5 A or 10 A power supply at 110/240 VAC

Dimensions Display: approx. 300 x 225 x 20mm (W x H x D)I/O Mounting Plate: 480 x 180mm (W x H x D)

Weight approx. 3 kg / 6.6 lbs, depending upon installed power supply

Ambient conditions Temperature 0 to 55 °C / 32 to 130 °FPressure 700 to 1300 hPa / 20.6 to 38.3 inch HgHumidity 0 to 100 %RH, non condensingIngress Protection IP 65, ABS – OV material of construction

Approvals ATEX EX II(2)GSIL SIL 1CE-mark Electromagnetic Compatibility (89/336/EEC)

Low Voltage Directive (72/23/EEC, 93/68/EEC)

9046827_PI_Regard_3910_engl_2 16.03.10 17:35 Seite 3

90 46 827 | 03.10-1 | M

arketing Com

munications | C

S | PR | LE | Printed

in Germany | C

hlorine-free – environ

mentally com

patib

le | Sub

ject to mod

ificatio

ns | ©

2010 Dräge

r Safety AG & C

o. KGaA

HEADQUARTERSDräger Safety AG & Co. KGaARevalstrasse 123560 Lübeck, Germany

www.draeger.com

FRANCEDräger Safety France SAS3c route de la Fédération, BP 8014167025 Strasbourg Cedex 1Tel +33 3 88 40 59 29Fax +33 3 88 40 76 67

SINGAPOREDraeger Safety Asia Pte Ltd67 Ayer Rajah Crescent #06-03Singapore 139950Tel +65 68 72 92 88Fax +65 65 12 19 08

UNITED KINGDOMDraeger Safety UK Ltd.Blyth Riverside Business ParkBlyth, Northumberland NE24 4RGTel +44 1670 352 891Fax +44 1670 544 475

USADraeger Safety, Inc.505 Julie Rivers, Suite 150Sugar Land, TX 77478Tel +1 281 498 1082Fax +1 281 498 5190

SYSTEM CENTERS

P. R. CHINABeijing Fortune Draeger SafetyEquipment Co., Ltd.A22 Yu An Rd, B Area, Tianzhu Airport Industrial Zone,Shunyi District, Beijing 101300Tel +86 10 80 49 80 00Fax +86 10 80 49 80 05

GERMANYDräger Safety AG & Co. KGaARevalstrasse 123560 LübeckTel +49 451 882-2794Fax +49 451 882-4991

9046827_PI_Regard_3910_engl_2 16.03.10 17:35 Seite 4