electric power quality

37
Page 1 PSERC Elec tr i c Po w e r Qua li ty  Ward Jewell Professor, Electrical Engineering Director, Center for Energy Studies Wichita State University Consulting Electrical Engineer PSERC Hos pita l CT scanne r fa ilures  During a normal half-hour series of scans, a CT scanner records images on a microcomputer that also contr ols the scanner. As often as twice each day, this hospital's scanner would shut down  before a series wa s complete. The recorded images were lost, and the patient was subjected to a repeat of the entire series. Utility  personnel found one cause of the shutdowns to be momentary  power outages caused by trees brushing aga inst utility distribution lines. They cor rected this by trimming trees. Another ca use was then found to be voltage sags that occurred when the hospital's chiller starte d. An improper setting on the sc anner's power control was corrected, and this problem disappeared.

Upload: navidelec

Post on 12-Oct-2015

20 views

Category:

Documents


0 download

DESCRIPTION

Electric Power Quality

TRANSCRIPT

  • Page 1

    PSERC

    Electric Power Quality

    Ward Jewell

    Professor, Electrical EngineeringDirector, Center for Energy Studies

    Wichita State University

    Consulting Electrical Engineer

    PSERC

    Hospital CT scanner failures During a normal half-hour series of scans, a CT scanner recordsimages on a microcomputer that also controls the scanner. Asoften as twice each day, this hospital's scanner would shut downbefore a series was complete. The recorded images were lost, andthe patient was subjected to a repeat of the entire series. Utilitypersonnel found one cause of the shutdowns to be momentarypower outages caused by trees brushing against utility distributionlines. They corrected this by trimming trees. Another cause wasthen found to be voltage sags that occurred when the hospital'schiller started. An improper setting on the scanner's powercontrol was corrected, and this problem disappeared.

  • Page 2

    PSERC

    MEDIATE !!!

    me

    hospital

    manufacturer

    utility

    PSERC

  • Page 3

    PSERC

    Momentary outage when treelimbs contact distribution line

    PSERC

    Recloser operates

  • Page 4

    PSERC

    Time

    PSERC

    Voltage sags when chiller starts

    Time

    110 - 112 V

  • Page 5

    PSERC

    ... voltage setting should be+10% of supply voltage ...

    - CT scanner installation manual

    Nominal voltage 120 V: 108 - 132 V

    PSERC

    ... voltage setting should be+10% of supply voltage ...

    - CT scanner installation manual

    Nominal voltage 120 V: 108 - 132 V

    Measured voltage at installation 126 V:113 - 139 V

  • Page 6

    PSERC

    Solution:

    Trim trees

    Remove instantaneous recloser trip

    Reset CT scanner low voltage dropout to 108 V.

    PSERC

    Power Line Conditioners

    CTscanner

    Filter

    ElectricPower

  • Page 7

    PSERC

    Power Line Conditioners

    CTscanner

    Transientvoltagesurge

    suppressor

    Filter

    ElectricPower

    PSERC

    Power Line Conditioners

    CTscanner

    Transientvoltagesurge

    suppressor

    Filter

    VoltageRegulator

    ElectricPower

  • Page 8

    PSERC

    Power Line Conditioners

    CTscanner

    Transientvoltagesurge

    suppressor

    Filter

    UninterruptiblePower Supply

    VoltageRegulator

    ElectricPower

    PSERC

    Another option:Static transfer switch

    Transfers load to another source

    Electronic switch

    Fast; user notices no change

  • Page 9

    PSERC

    Our power systems were designedfor:

    IncandescentLights

    AC Motors

    PSERC

    High-efficiencylights

    Computers

    Adjustable-speed

    Motor Drives

    Now the power system serves

  • Page 10

    PSERC

    High-efficiencylights

    Adjustable-speed Motor Drives

    Disturbing loads

    PSERC

    Computers

    Sensitive Loads

    Microprocessor-controlledequipment

  • Page 11

    PSERC

    POWER QUALITY

    IS

    PSERC

    A POWER QUALITY PROBLEM

    IS

    when something doesn't work because of

    the electric power supplied to it.

  • Page 12

    PSERC

    Power quality problems

    PSERC

    Radio transmitter damage

    A commercial FM radio station experienced repeatedfailure of its transmitter. Utility engineers determinedthat each failure coincided with switching of capacitorsat the distribution substation. Capacitor switchingtransients were recorded at the radio station serviceentrance. An electrical snubber was designed to reducethe frequency and damp oscillations in the transmitter.The snubber was installed, and no further rectifierfailures occurred.

  • Page 13

    PSERC

    PSERC

    Voltage goes to zero when feedercapacitor is switched on

  • Page 14

    PSERC

    Capacitor switching

    Distribution feeder

    Initial capacitorvoltage is zero

    When switch is closed,feeder voltage is zerountil capacitor charges.

    PSERC

    Transmitter dc power supply

    4 H

    20 uF 9000 Vdc480 Vac

  • Page 15

    PSERC

    Diode ratings

    Reverse voltage

    Forward voltage drop

    Forward current

    Turn off time: ~0.3 ms

    PSERC

    Transmitter dc power supply

    4 H

    20 uF 9000 Vdc480 Vac

    Reactance,stray capacitance

  • Page 16

    PSERC

    Transformer high voltagewhen capacitor switched

    20 kHzringing

    PSERC

    Solution: call someone whoknows what to do!!!

    4 H

    20 uF 9000 Vdc480 Vac

    Transmitter design engineerrecommended RC snubber

    No more failures!

  • Page 17

    PSERC

    Metal fabrication plantequipment failures

    An industrial plant where sheet metal is fabricatedexperienced various machinery failures. An initialsurvey revealed adjustable speed dc motor drives, acommon disturbing load, in use in the plant. Powerquality measurements confirmed that one of the driveswas causing severe "notching," a transient voltagedisturbance. This was corrected using series reactors. Agrounding error on a transformer was also found andcorrected.

    PSERC

    Voltage notching

  • Page 18

    PSERC

    DC motor adjustable speed drive

    +-

    ACsupply

    DCmotor

    Rectifierswitches

    Two switches closed causesmomentary short circuit and notch

    PSERC

    Voltage notching

    DC motordrive

    MainServicePanel

    Winder subpanel

    Drivesubpanel

    Numerically-controlledspring winder

    480 V

    420 V

    380 V

  • Page 19

    PSERC

    Spring winder counting circuitDC power

    supply

    AC50/60 Hz

    4-digitcounter

    andprocessor

    RESET

    up/downdisable

    count

    modes

    output 2

    output 1

    +5 Vdc

    10 k

    Pushbuttonreset Notch on

    ac resets counter

    PSERC

    Series Reactors

    DC motordrive

    MainServicePanel

    Winder subpanel

    Drivesubpanel

    Numerically-controlledspring winder

    48 V

    38 V

    42 VREACTOR

    480 V

  • Page 20

    PSERC

    The CBEMA curveComputer Business Equipment Manufacturers Association

    PSERC

    The ITIC CurveInformation Technology Industry Council

  • Page 21

    PSERC

    PSERC

    Distorted current waveform to PCs

    0 2 4 6-20

    0

    20

    Radians

    Cur

    rent

  • Page 22

    PSERC

    Fourier series - spectrum -of pc current waveform

    0

    0.2

    0.4

    0.6

    0.8

    1

    Harmonic

    Rel

    ativ

    e va

    lue

    1 3 5 7 9 11 13 15 17 19

    PSERC

    Total Harmonic Distortion (THD)

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    1

    0.737

    0.399

    0.115

    0.083

    0.082

    0.029

    0.029

    0.029

    0.012

    Harmonicnumber

    fundamental

    IhI1

    1

    0.543

    0.159

    0.013

    6.88910 -3

    6.72410 -3

    8.4110 -4

    8.4110 -4

    8.4110 -4

    1.4410 -4

    IhI1

    2

    2

    19

    h =

    0.732=IhI1

    2

    2

    19

    h =

    0.855=IhI1

    2

    THD = 85.5%

  • Page 23

    PSERC

    What causes harmonics?

    Saturated transformers

    Arcs Arc furnaces, fluorescent lights

    RectifiersMicroprocessors, motor drives,

    any electronic load

    PSERC

    Three-phase full wave rectifier

    Vdc

    +

    _

    Va Vb Vc

  • Page 24

    PSERC

    AC current to 6-pulse battery charger

    PSERC

    AC current to 6-pulse battery charger

  • Page 25

    PSERC

    Harmonics cause

    Transformers to overheat Transformer secondary voltage distortion Increased power system losses Telephone and wired communication systems

    noise Neutral overloads

    PSERC

    Other harmonic issues

    Watt-hour meters May read high or low

    Protective relays May not sense RMS values Nuisance trip or fail to trip

    Digital clocks May run fast

  • Page 26

    PSERC

    Solutions

    Use full sized or oversized neutral conductors Oversize or harmonic rate transformers Detune system (move capacitors, install reactors) Filter (install passive or active harmonic filters

    PSERC

    Power Quality Disturbances Voltage transients

    One time; impulse or oscillatory; shorter than half cycle

    Voltage variations One time; sag, swell or interruption; longer than half cycle

    Voltage imbalance Steady state

    Waveform distortion (voltage or current) Steady state; dc offset, harmonics, interharmonics, notching, noise

    Voltage fluctuations Intermittent

    Frequency variations Shorter than ten seconds

  • engr.wichita.edu/ces/PSERC www.psserc.wisc.edu

    Power Quality ReferencesIEEE Recommended Practice for Powering and Grounding Sensitive ElectronicEquipment, IEEE Emerald Book (IEEE Std. 1100-1992), IEEE, 345 E. 47th St., New York,NY, 10017-2394, 1992.

    Guideline on Electrical Power for ADP Installations, Federal Information ProcessingStandards Publication 94 (FIPS PUB 94), NTIS, US Dept. of Commerce, Springfield,Virginia, 22161.

    The IAEI Soares Book on Grounding, 4th Edition, International Association of ElectricalInspectors, 930 Busse Highway, Park Ridge, Illinois, 60068, 1991.

    Jerry C. Whitaker, AC Power Systems Handbook, CRC Press, 2000 Corporate Blvd., BocaRaton, Florida, 33431, 1991.

    Power Quality Assurance Magazine, Intertec International, 2472 Eastman Ave., Bldgs. 33 and34, Ventura, California, 93003-5792.

    Roger R. Block, The "Grounds" for Lightning and EMP Protection, Second Edition,Polyphaser Corporation, 1993.

    Agricultural Wiring Handbook, National Food and Energy Council, 409 Vandiver West, Suite202, Columbia, Missouri, 65202, 1990.

    Power Line Interference, A Practical Handbook, National Rural Electric CooperativeAssociation, 1800 Massachusetts Ave, NW, Washington, DC 98501, 1992.

    Recommended Practice for Establishing Transformer Capability When SupplyingNonsinusoidal Load Currents (ANSI/IEEE C57.110-1986), IEEE, 345 E. 47th St., New York,NY, 10017-2394, 1988.

    IEEE Recommended Practice for Harmonic Control in Electric Power Systems (IEEE 519),IEEE, 345 E. 47th St., New York, NY, 10017-2394, 1992.

    National Electrical Code 1993 (ANSI/NFPA 70), NFPA, Batterymarch Park, Quincy,Massachusetts, 02269, 1992.

    National Electrical Safety Code 1990 (ANSI C2-1990), IEEE, 345 E. 47th St., New York, NY,10017-2394, 1989.

    The Dranetz Field Handbook for Power Quality Analysis, Dranetz Technologies Inc., 1000New Durham Road, Edison, New Jersey, 08818, 1991.

    Alexander McEachern, Handbook of Power Signatures, Basic Measuring Instruments, 335Lakeside Drive, Foster City, California, 94404, 1989.

  • Page 1

    PSERC

    Site Surveys

    PSERC

    Power quality is suspected when:

    Someone elsecant figure outwhats wrong

    Lightsflicker

    ???

    or

  • Page 2

    PSERC

    Talk to everyone

    Users

    Maintenancepersonnel

    PlantEngineers

    Workers

    Electrician

    Repairpersonnel

    Technicians FieldEngineers

    PSERC

    Acknowledge frustration!!!!!

    Wastedtime

    Reducedproductivity

    Failure to resolve problemsafter many attempts

  • Page 3

    PSERC

    Determine exactly what is wrong

    Whats not working?

    Whats it doing?

    PSERC

    When does it happen?

    Time of day?

    Time of week, month, year?

    How often?

    When did it start?

  • Page 4

    PSERC

    What changedbefore the problem started?

    Changes to electric power system?

    New equipment?

    Equipment relocated?

    PSERC

    Have user keep a log

    Date Time Equipment Problem Observations, notes

    Compare with utilityoperation and service logs

  • Page 5

    PSERC

    Walk through the facility

    List disturbing loads

    List susceptible loads

    Talk with people as you go

    PSERC

    Inspect feeder

    Trim trees

    Check recorders for activity

    Transformers

    Capacitors Fuses

    Connections

  • Page 6

    PSERC

    Get wiring diagrams

    Identify connections amongdisturbing and affected loads

    MainPanel

    ExteriorLighting

    InteriorLighting

    RooftopHVAC Unit

    Elevators

    Transformer45 kVA

    Transformer75 kVA

    OfficeEquipment

    OfficeEquipment

    Heating

    OfficeEquipment

    PSERC

    Inspect and repairfacility wiring and grounding

    National Electrical Code Correct safety problems first

    Powering and Grounding SensitiveElectronic Equipment (IEEE 1100, theEmerald Book) Use Figure 6-1 forms

  • Page 7

    PSERC

    Replace equipment with duplicateif possible

    If replacement works, the problem isnt power quality.

    PSERC

    Ask for help fromequipment design engineer

    Describe problemfirst by phone

    then fax or e-mail

  • Page 8

    PSERC

    Most problemswill be solved

    by now.

    PSERC

    Still no solution?

    Measure power quality Digital multimeter (true rms reading)

    Wiring and grounding survey equipment

    Oscilloscope

    Power quality monitor

    Field strength meter

    Spectrum analyzer

  • Page 9

    PSERC

    Power quality analysis technique

    Begin at affected equipment

    Move away from affected equipment to locatesource

    Measure at service entrance to determine ifsource is inside facility

    Measure on transformer primary (distributionfeeder) to determine if utility or another customeris source

    Connect monitor to phone line for long-termremote operation if no disturbance is detected

    PSERC

    n Duplicate disturbance and effects to verify cause

    n Safely test various solutions before implementing

    Simulate if necessary

    Actual Simulated

  • Page 10

    PSERC

    Specify solution

    Do not allow a vendor to specify equipment(you may get something you dont need)

    Instead:

    Specify the equipment needed,then request quotes from several vendors

    PSERC

    Summary

    Mediate - people will be frustrated

    Talk to the people using the equipment

    Fix NEC problems - power quality will improve

    Call equipment designers for help

    Specify the needed solution