flecs ct manual v12-1 (1)

96
1 FLECS CT Users Manual Software Version 1.2

Upload: rodolfo-santesqui

Post on 13-May-2017

225 views

Category:

Documents


2 download

TRANSCRIPT

1

FLECS CT Users Manual

Software Version 1.2

2

1 FLECS Concepts ......................................................................................................... 5

1.1 FLECS System Concepts .................................................................................... 5

1.2 FLECS Display ................................................................................................... 5

1.2.1 FLECS Display Screen ............................................................................... 5

1.2.2 FLECS Display Touch-screen .................................................................... 6

1.2.3 FLECS Display Keypad .............................................................................. 6

1.2.4 FLECS Display Power Indicator ................................................................ 7

2 FLECS CT Concepts................................................................................................... 8

2.1 FLECS CT Interface Organization ..................................................................... 8

2.2 Constantly Visible Display ................................................................................. 8

2.3 Context Dependent Display ................................................................................ 9

2.4 Context Menu...................................................................................................... 9

3 Keypad Navigation ................................................................................................... 10

3.1 FLECS CT Desktop .......................................................................................... 10

3.2 Key Hints .......................................................................................................... 10

3.2.1 Desktop Key Hints .................................................................................... 10

3.2.2 Key Hints in Menus .................................................................................. 11

3.3 CTRL Key ......................................................................................................... 12

4 Entering Calibration Points ....................................................................................... 12

4.1 Add Calibration Point ....................................................................................... 12

4.1.1 mA Value Entry ........................................................................................ 12

4.1.2 Value Entry ............................................................................................... 15

4.2 Delete Calibration Point .................................................................................... 17

5 Sensor and Actuator Connection Selection............................................................... 18

5.1 Overview ........................................................................................................... 18

5.1.1 Current Selection ...................................................................................... 18

5.1.2 Changing the Selection ............................................................................. 19

6 Weight Display ......................................................................................................... 20

6.1 FLECS CT Weight Measurement ..................................................................... 20

6.2 Current Weight.................................................................................................. 20

6.3 Limiting System Status ..................................................................................... 21

6.4 Weight Display Configuration .......................................................................... 21

6.4.1 Load Pin Setup .......................................................................................... 21

6.4.2 Load Pin Status ......................................................................................... 25

6.4.3 Zero Weight .............................................................................................. 26

6.4.4 Weight Unit Selection ............................................................................... 28

6.4.5 Limiting System ........................................................................................ 28

6.4.6 Close ......................................................................................................... 28

7 Depth & Speed Display ............................................................................................ 28

7.1 FLECS CT Depth Measurement ....................................................................... 29

7.2 Current Depth.................................................................................................... 29

7.3 Speed ................................................................................................................. 30

7.4 Direction Indicator ............................................................................................ 30

7.5 Limiting System Status ..................................................................................... 31

7.6 Depth & Speed Display Configuration ............................................................. 31

7.6.1 Encoder Setup ........................................................................................... 32

3

7.6.2 Depth Unit Selection ................................................................................. 33

7.6.3 Speed Unit Selection ................................................................................. 34

7.6.4 Zero Depth ................................................................................................ 34

7.6.5 Set Depth ................................................................................................... 35

7.6.6 Limiting System ........................................................................................ 36

7.6.7 Close ......................................................................................................... 36

8 Pressure Display........................................................................................................ 36

8.1 FLECS CT Pressure Measurement ................................................................... 37

8.2 Tubing Pressure ................................................................................................ 37

8.3 Wellhead Pressure ............................................................................................. 38

8.4 Pressure Display Configuration ........................................................................ 38

8.4.1 Tubing Pressure Transducer Status ........................................................... 39

8.4.2 Tubing Pressure Display Unit ................................................................... 39

8.4.3 Tubing Pressure Zero ................................................................................ 40

8.4.4 Tubing Pressure Transducer Configuration .............................................. 42

8.4.5 Close ......................................................................................................... 44

9 Limiting System ........................................................................................................ 44

9.1 Limit States ....................................................................................................... 45

9.1.1 Off ............................................................................................................. 45

9.1.2 On .............................................................................................................. 46

9.1.3 Warn .......................................................................................................... 47

9.1.4 System Disabled........................................................................................ 47

9.1.5 Tripped ...................................................................................................... 48

9.2 Weight Limits ................................................................................................... 49

9.2.1 Pull Limit .................................................................................................. 49

9.2.2 Snub Limit ................................................................................................ 50

9.2.3 Tag Limit .................................................................................................. 50

9.3 Depth & Speed Limits ...................................................................................... 51

9.3.1 Pull Out Limit ........................................................................................... 51

9.3.2 Speed Out of Hole Limit ........................................................................... 51

9.3.3 Speed In Hole Limit .................................................................................. 52

9.4 Limit Setup........................................................................................................ 53

9.4.1 Output Tab ................................................................................................ 53

9.4.2 Weight Tab................................................................................................ 54

9.4.3 Depth/Speed Tab ....................................................................................... 58

9.5 Resetting Tripped Limits .................................................................................. 61

9.5.1 Reset Pull Limit ........................................................................................ 61

9.5.2 Reset Snub Limit....................................................................................... 61

9.5.3 Reset Tag Detect Limit ............................................................................. 61

9.5.4 Reset Pull Out Limit ................................................................................. 61

9.5.5 Reset Speed Out of Hole Limit ................................................................. 62

9.5.6 Reset Speed In Hole Limit ........................................................................ 62

9.6 Limit System Test ............................................................................................. 62

10 System Menu ........................................................................................................ 64

10.1 Shutdown .......................................................................................................... 64

10.2 KIPS Calibration ............................................................................................... 66

4

10.3 Serial Setup ....................................................................................................... 68

10.3.1 CT60079_B ............................................................................................... 69

10.3.2 Port Settings .............................................................................................. 69

10.4 Version Information .......................................................................................... 69

10.5 Set Time and Date ............................................................................................. 70

10.6 Start RTD Job ................................................................................................... 71

11 Display Backlight Brightness ............................................................................... 72

12 Custom Inputs ....................................................................................................... 73

12.1 Custom Input Number....................................................................................... 74

12.2 Configure New Custom Input ........................................................................... 74

12.3 Custom Current ................................................................................................. 75

12.4 Custom Frequency and Mag-Pickup ................................................................. 78

12.5 Custom Encoder ................................................................................................ 81

12.6 Custom Total – Frequency or Mag-Pickup ....................................................... 84

12.7 Custom Total - Encoder ................................................................................... 88

12.8 Zero Custom Total ............................................................................................ 92

12.9 Modify Custom Input ........................................................................................ 92

12.10 Disable Custom Input ................................................................................... 92

13 Latest Software ..................................................................................................... 92

5

1 FLECS Concepts This section describes Halliburton’s FLECS system and how the FLECS CT application

relates to the FLECS System.

1.1 FLECS System Concepts

The FLECS system consists of two primary components. The FLECS display and the

FLECS card stack. The FLECS display has a 6.3 inch color display, a touch screen and a

keypad. The FLECS card stack contains a computer and hardware for interfacing with

instrumentation such as pressure transducers and optical encoders.

Software is written to run on the FLECS system. The software for coiled tubing is called

“FLECS CT”. This manual discusses the operational aspects of the FLECS CT

application.

1.2 FLECS Display

This section describes the components of the FLECS display and general information on

how to use the components.

There are two version of the FLECS Display deployed on Halliburton Coiled Tubing

equipment. The most common is the safe area display, used primarily for land units. The

safe area display is illustrated in this document. The second display is a modified version

of the safe area display, for use in hazardous area equipment.

The hazardous area display does not have a touch screen. Operation of the hazardous area

display is accomplished with keypad navigation. The same keypad navigation

functionality is implemented on the safe area display. Refer to Section 3 of this document

for more information on using Keypad Navigation.

1.2.1 FLECS Display Screen

The FLECS display has three major components. The display contains a color screen.

This screen is similar to the monitor on a desktop computer.

Figure 1 - FLECS Display with Screen Highlighted

6

1.2.2 FLECS Display Touch-screen

The safe area display has a touch-screen. A touch-screen enables the operator to take

action by pressing directly on the screen with a finger. The touch-screen is much like a

mouse found on desktop computers. Using a mouse one moves the cursor over objects on

screen and clicks to take some action. Touching an object illustrated on the FLECS

screen has the same effect as moving the mouse over an object and clicking.

Figure 2 - FLECS Display with Touch-Screen Highlighted

1.2.2.1 FLECS Display Touch-screen Extended Touchable Area

The touch-screen is slightly larger than the screen. To the left and right of the screen are

what appears to be five buttons. These buttons are part of the touch-screen. Touching in

these areas is like pressing a button on the FLECS keypad. This part of the touch-screen

is called the extended touchable area.

Figure 3 - FLECS Display with Extended Touchable Area Highlighted

1.2.3 FLECS Display Keypad

The FLECS display has a keypad for entering information and for operation without the

touch screen. The keys are located below and to the right of the screen.

7

Figure 4 - FLECS Display with Keypad Highlighted

Most of the keys on the keypad have two functions. The primary function of the button is

the larger character printed in the center of the button. The secondary function of the

buttons is printed in smaller text on the lower right corner of the button.

Figure 5 – Key with Primary and Shifted Function Illustrated

The secondary function of the button is called the “shifted” function. The keypad has a

shift button labeled “SHIFT LOC”. When the shift function is enabled the red dot on the

lower right corner of the shift button will be illuminated. When shift is enabled pressing a

button will cause the secondary character to be entered. Pressing the shift button changes

the state of the shift.

1.2.4 FLECS Display Power Indicator

To the left of the screen is a red light which indicates power is being supplied to the

FLECS Display.

8

Figure 6 – Power Indicator, Illuminated

2 FLECS CT Concepts This section describes fundamental concepts of operating a FLECS CT system. These

concepts apply throughout the FLECS CT application.

2.1 FLECS CT Interface Organization

The interface for FLECS CT is divided into two primary sections. These two parts are

called the “constantly visible” and the “context dependent” sections.

2.2 Constantly Visible Display

The right one third of the screen is called the constantly visible section of the screen. This

part of the screen provides information that is critical for coiled tubing operations. This

information will always be visible on screen. Figure 7 highlights the constantly visible

section of the display.

The constantly visible section of the display is divided into three parts. The top third

provides information related to the tubing weight. The middle third provides information

related to the depth, speed and direction of tubing movement. The bottom third provides

the tubing and wellhead pressure.

Figure 7 – FLECS CT Display with Constantly Visible Display Highlighted

9

2.3 Context Dependent Display

The left two thirds of the screen is called the context dependent section of the screen.

Figure 8 highlights the context dependent section of the display. This part of the screen

provides information from additional sensors. This section of the screen is also used to

display menus for configuring the FLECS CT system.

The information from additional sensors is only displayed when all configuration menus

are closed. This part of the screen works similar to a Microsoft Windows desktop

computer. On a computer running Windows, when all applications (Word, Outlook, etc)

are closed you see the “desktop”. The “desktop” for FLECS CT displays information

from additional sensors. The information from these additional sensors is covered up

when a menu is opened for another reason.

Figure 8 – FLECS CT Display with Context Dependent Display Highlighted

2.4 Context Menu

In the FLECS CT application there are some operations which are infrequently

performed. Because of the limited space available on the FLECS screen, infrequently

used operations are hidden in what is called a context menu.

Throughout the FLECS CT application the context menu is accessed by pressing the

lower left most part of the touch screen or by pressing the F1 key. The area which opens

the context menu in FLECS CT is highlighted in Figure 9. This is called the context

menu button.

10

Figure 9 – FLECS CT with Context Menu Button Highlighted

When a context menu is open, a second press to the context menu button closes the

context menu.

When using a desktop computer running Microsoft Windows a right click on an object

causes a context menu to be displayed. For example if you right click on a folder in

Windows, a menu with options specific to that folder is displayed.

One can think of the context menu in FLECS CT like a right click in Windows. When

you press the context menu button in FLECS CT relevant options will be presented.

3 Keypad Navigation The FLECS CT software can be operated using either the touch screen or buttons on the

keypad. For hazardous area units keypad navigation is the only method of interacting

with the FLECS CT system. For safe area units the operator may use both the touch

screen and keypad navigation.

3.1 FLECS CT Desktop

The term “FLECS CT Desktop” refers to the state in which all menus are closed and the

six custom inputs are visible in the context dependent section of the screen. The custom

inputs are visible only when all other menus are closed. See Section 2.3 for more

information on the context dependent section of the screen.

3.2 Key Hints

FLECS CT uses key hints to show the operator what button on the keypad is the same as

touching an item on screen.

3.2.1 Desktop Key Hints

In Figure 10 the FLECS CT desktop is illustrated. In this illustration key hints are turned

on. The square with the four arrows and the word “Enter” in the top right is the currently

selected square. When an arrow key is pressed the selected square moves in the direction

of the arrow. Pressing the enter key has the same effect as touching in the selected square.

11

In the bottom right of Figure 10 there are two small squares. The upper square contains

the text “F7” and a symbol. The lower square contains the text “F8” and a symbol. These

tabs indicate that touching the extended touchable area buttons to the right of the tab will

have some effect. They also indicate that a press of the F7 key is the same as touching on

the touch screen in the extended touchable area. See Section 1.2.2.1 for more information

on the Extended Touchable Area.

While at the desktop as illustrated in Figure 10, if key hints are not enabled pressing an

arrow key or the enter key does not have any effect. However, the function keys F7 and

F8 are operational even if key hints are not displayed.

Desktop key hints are automatically hidden from view if no key is pressed for 15

seconds.

Figure 10 - Desktop Key Hint Label Illustration

3.2.2 Key Hints in Menus

When a menu is opened and key hints are enabled a hint appears over each part of the

screen which could be pressed with the touch screen. Pressing the key indicated by the

key hint is the same as touching on the item with the touch screen.

In Figure 11 the button labeled “Load Pin Setup” has a key hint in the top right

containing the text “F6”. This key hint indicates that pressing the F6 key is the same as

touching on the Load Pin Setup button.

Keypad navigation works for menus even if key hints are disabled. Key hints are always

numbered beginning with F2. Generally the items on screen are assigned keys left to

right, then top to bottom.

12

Figure 11 - Key Hint Label Illustration

3.3 CTRL Key

The CTRL key is used to enable and disable key hints. Each press of the CTRL key

changes the state of key hints. If key hints are off and CTRL is pressed key hints will be

turned on. If key hints are on and CTRL is pressed key hints will be turned off.

4 Entering Calibration Points The FLECS CT application uses a common process for adding calibration points for load

pins and the pressure transducers. The process of deleting existing calibration points is

also common.

Beginning in version 1.1 it is no longer possible to modify an existing calibration. The

incorrect calibration point must be deleted and then a new point added.

This section discusses the process of adding and deleting calibration points.

4.1 Add Calibration Point

After pressing the “Add Point” button from either the Load Pin Setup or transducer setup

screen, the Add Calibration Point mA screen is displayed. The first screen, illustrated in

Figure 12, prompts for the mA value of the calibration point.

4.1.1 mA Value Entry

Enter the mA value of the new calibration point in the text field. This field accepts

numeric values with up to two decimal places. The field will not allow numbers which

are out of the valid range indicated by the Range Bar.

After entering the mA value touch the Next button. The Next button will not be enabled

unless a valid value is entered in the mA field. To cancel the Add Calibration Point

process, touch the Cancel button.

13

Figure 12 – Add Calibration Point mA

4.1.1.1 mA Valid Range Bar

The center of the Add Calibration Point screen displays the valid range for a calibration

point mA value. This range is displayed by the green bar. This bar is called the Range

Bar. The Range Bar is surrounded by a blue oval in Figure 13.

Figure 13 – Add Calibration Point mA – Range Bar Detail – No Existing Points

4.1.1.1.1 Minimum mA Value

In Figure 13 the minimum mA value which can be entered is indicated below the left end

of the Range Bar. This value is enclosed in a red rectangle.

4.1.1.1.2 Maximum mA Value

In Figure 13 the maximum mA value which can be entered is indicated below the right

end of the Range Bar. This value is enclosed in a green triangle.

4.1.1.1.3 Existing Point Ranges

14

The mA value of any existing calibration points will be illustrated on the Range Bar with

an Existing Point Range. An Existing Point Range is illustrated with a red bar. The

Existing Point Range will be illustrated on top of the green Range Bar.

For some sensors a minimum spacing between the mA values of calibration points is

required. In this case the red Existing Point Range illustrates the range of mA values not

allowed because they are too close to an existing calibration point.

Figure 14 illustrates the Add Calibration Point mA screen with one existing point at 6.0

mA. The red Existing Point Range is detailed by a green triangle.

Figure 14 – Add Calibration Point mA – Existing Point

4.1.1.1.4 Entered Point Indicator

When a value is entered in the mA field a representation of that value is illustrated on the

Range Bar. This is called the Entered Point Indicator. The Entered Point Indicator is

illustrated with a tall, orange bar. The Entered Point Indicator bar moves each time a new

mA value is entered. In Figure 15 the Entered Point Indicator is highlighted with a blue

oval.

15

Figure 15 – Add Calibration Point mA – Entered Point Indicator

If a mA value is entered which overlaps the Existing Point Range of another calibration

point a message will be displayed under the mA field. The Next button will be disabled.

This situation is illustrated in Figure 16.

Figure 16 – Add Calibration Point mA– Invalid Point Entered

4.1.2 Value Entry

After confirming the mA value FLECS CT prompts for the value corresponding to the

entered mA value. For load pins the requested value will be a weight. For pressure

transducers the requested value will be a pressure. The display value is requested in the

selected units for the sensor.

After entering a value press the Finish button. Press cancel to exit the add calibration

point process without changing the sensor calibration.

The display value field will not allow entry of a value outside the valid range.

16

Figure 17 illustrates the screen used to enter the display value corresponding to the mA

value previously entered. In this example the calibration point is being added for a

pressure transducer.

Figure 17 – Add Calibration Point Value

4.1.2.1 Value Range Bar

The center of the Add Calibration Point screen displays the valid range for a calibration

point value. This range is displayed by the green bar. This bar is called the Display Value

Range Bar. The Display Value Range Bar is surrounded by a blue oval in Figure 18.

Figure 18 – Add Calibration Point Value

4.1.2.1.1 Minimum Display Value

In Figure 18 the minimum display value which can be entered is indicated below the left

end of the Range Bar. This value is enclosed in a red square.

4.1.2.1.2 Maximum Display Value

In Figure 18 the maximum display value which can be entered is indicated below the

right end of the Range Bar. This value is enclosed in a green triangle.

17

4.1.2.1.3 Existing Points

The valid range indicated by the range bar is calculated with respect to other existing

calibration points. The example in Figure 18 illustrates the display range bar for a

pressure transducer which had no existing calibration points. Because no other calibration

points existed the display value corresponding to the mA value could be anywhere

between 0 and 20,000 PSI.

4.1.2.1.4 Entered Point Indicator

When a value is entered in the display value field a representation of that value is

illustrated on the Range Bar. This is called the Entered Point Indicator. The Entered Point

Indicator is illustrated with a tall orange bar. The Entered Point Indicator bar moves each

time a new mA value is entered. In Figure 19 the Entered Point Indicator is highlighted

with a blue oval.

Figure 19 – Add Calibration Point Value – Entered Point Indicator

4.2 Delete Calibration Point

After touching on an existing calibration point the Delete Point button will be enabled.

Press the Delete Point button to delete the point. Press cancel to exit this screen without

modifying the sensor calibration.

18

Figure 20 - Delete Calibration Point Confirmation

5 Sensor and Actuator Connection Selection The FLECS CT system uses a common interface for setting where a sensor or actuator is

connected to the FLECS controller. Because this screen is common to all of the devices,

it is discussed generally in this section rather than duplicating the information several

times.

This section describes how to use the connection screens found in FLECS CT.

5.1 Overview

The connection selection page is divided into two parts. The top part indicates the

currently selected input or output. The bottom part enables the operator to change which

input or output the device is connected to.

5.1.1 Current Selection

When the FLECS CT software is initially installed the inputs and outputs used for sensors

and outputs used for actuators will not be set. Under this condition the input selection

screen will look similar to Figure 21.

19

Figure 21 - Connection Selection - Input Not Set

The top half of the display indicates that an input has not been assigned to the sensor yet.

Once an input has been selected the top half of the connection selection screen will show

which input is selected. This is illustrated in Figure 22.

Figure 22 - Connection Selection - Input Selected

5.1.2 Changing the Selection

To change which input or output is used use the arrow buttons to increase or decrease the

selection. The newly selected input or output is in the box between the two arrow buttons.

If the new selected input is already in use by this or another device, the apply button will

be disabled and the message “Analog Input Is In Use” will appear.

When the desired input is selected and it is available, press the apply button to make the

change effective. When the change is made, the top half of the screen will change to

show the newly selected input.

20

6 Weight Display The Weight display is the top one third of the Constantly Visible section of the screen.

The Weight display provides the current weight, the units the weight is displayed in and

the status of the load limiting system.

This section discusses general capabilities of the weight display system in FLECS CT

and describes the interface used for managing all aspects of the weight display.

Figure 23 – Weight Display

6.1 FLECS CT Weight Measurement

The FLECS CT system supports measurement of tubing weight using either one or two

load pins. Each configured load pin has an independent calibration table1. A load pin

calibration table must have at least two calibration points to be a valid calibration. A load

pin calibration table can consist of up to fifteen points.

When only one load pin is configured the force applied to the single load pin is doubled

to calculate the display weight. This is based on the assumption that exactly fifty percent

of the load is applied to the single installed pin.

When two load pins are configured the sum of the force applied to each pin is used for

the display weight.

6.2 Current Weight

The majority of the Weight display is used for display of the current tubing weight. In

Figure 24 the current weight has a red box around surrounding it. The weight is displayed

in the units selected on the Weight Display Configuration screen. The currently selected

unit has a blue oval around it in Figure 24.

Figure 24 – Weight Display, Current Weight & Units Highlighted

1 A calibration table relates the signal from a transducer to a display value. For example the most basic

calibration for a load pin might consist of two points: (4.00 mA, -17000 lbs) & (20.00 mA, 53000 lbs).

21

A value for the weight is displayed only if one or two load pins are configured and each

configured load pin has an input selected and a valid calibration table.

6.3 Limiting System Status

Just below the Current Weight display is the Load Limiting Status. The Load Limiting

status area is circled with a blue oval in Figure 25. The Load Limiting system is

discussed in Section 9 - Limiting System (Page 44).

Figure 25 – Weight Display – Load Limiting Status Highlighted

6.4 Weight Display Configuration

A touch in the Weight constantly visible area will open the Weight Display Configuration

menu. The Weight Display Configuration menu is displayed in the context dependent

section of the screen.

Figure 26 - Weight Display Configuration Menu

6.4.1 Load Pin Setup

The Load Pin Setup button opens the Load Pin Setup menu. From the Load Pin Setup

menu the number of pins to be used, the input each pin is connected to and the calibration

tables for each pin are configured.

6.4.1.1 No Pins Configured

When the FLECS CT software is initially installed or after all existing load pins are

deleted the load pin setup screen displays a message indicating no pins exist. Use the

22

context menu to add one or two load pins as appropriate. See Section 2.4 for more

information on the context menu.

Figure 27 - Load Pin Setup - No Pins Configured

6.4.1.2 Pin Selection

After one load pin has been added the load pin setup screen changes to look like that in

Figure 28. There is a single tab on the left side of the screen labeled “Pin 1”. Because

there is not a second side tab labeled “Pin 2” we know only one pin has been added to the

system.

All of the information in the Calibration and Input tabs applies to Pin 1.

Figure 28 - Load Pin Setup - Single Pin

When a second load pin has been added a second side tab appears. The new tab is labeled

“Pin 2”. The currently selected load pin has a white background. In Figure 29 Pin 1 is

selected. The information in the Calibration and Input tabs applies to Pin 1.

23

Figure 29 - Load Pin Setup - Two Pins - Pin 1 Selected

In Figure 30 Pin 2 is selected. The information in the Calibration and Input tabs applies to

Pin 2.

Figure 30 - Load Pin Setup - Two Pins - Pin 2 Selected

6.4.1.3 Add Load Pin

To add a pin to the system, select the Add Pin button from the Load Pin Setup context

menu.

When a pin is added the pin does not have an input selected and no calibration points

exist for the pin.

6.4.1.4 Input Tab

Use the input tab of the load pin setup screen to see the currently selected input and

change the selected input. See Section 5 for more information on how to use this screen.

The information on the input tab applies to the currently selected load pin.

24

6.4.1.5 Calibration Tab

The calibration tab of the load pin setup screen displays the currently entered calibration

points. Also it provides buttons to add new calibration points and delete existing points.

Figure 31 illustrates the calibration tab before any calibration points have been entered.

Figure 31 - Load Pin Setup - Calibration Tab

In Figure 32 the calibration tab is illustrated with several calibration points entered. The

points in the table are for illustration only and are not necessarily the calibration points to

be used on a unit. Note that when there are more points in the list than can be displayed

on the screen, there will be a scroll bar on the right of the calibration point list.

The Add New Point button is only enabled if there are less than 15 points in the list. The

delete button is only enabled when a point is selected. Touch on a point in the list to

select it.

Figure 32 - Load Pin Setup - Calibration Tab with Points

25

6.4.1.6 Add Load Pin Calibration Point

Touch on the Add Point button to add a calibration point to the currently selected pin.

Refer to Section 4.1 - Add Calibration Point (Page 12) for instructions on adding

calibration points.

When 15 calibration points already exist the Add Point button will be disabled.

6.4.1.7 Delete Existing Calibration Point

To delete an existing calibration point, touch on the row of the calibration point to be

deleted in the calibration point list. This will select the point to be deleted. Press the

delete point button, read and acknowledge the confirmation screen.

6.4.1.8 Delete Load Pin

Select the pin to be deleted using the Pin Selection buttons on the left of the Load Pin

Setup menu. From the context menu press the Delete Pin button. Read and acknowledge

the confirmation screen.

When a pin is deleted from the system the calibration table is cleared, the input is made

available for use by other sensor setup menus and the pin is removed from the system.

Note: Once a pin has been deleted the information deleted with the pin cannot be

recovered.

6.4.2 Load Pin Status

The top section of the Weight Display Configuration menu provides the status of

configured load pins. There is a button for each pin which may be configured. These

buttons are called the pin status selection buttons. The pin status selection buttons are

labeled Pin 1 and Pin 2. Below the pin status selection buttons is an area where messages

related to the state of the selected pin will be displayed; this is referred to as the pin

status.

When no pins have been added to the system or all existing pins have been deleted both

buttons will be gray. The pin status below the buttons will read “NO PINS

CONFIGURED”.

After a pin has been added to the system one of the pin status selection buttons will

appear with black text. When two pins have been added to the system both buttons will

appear with black text.

The pin status information applies to the selected pin. If the input has not been selected

for the sensor the pin status will read “INPUT NOT CONFIGURED”. When the input

has been selected for a sensor the pin status area will display the signal currently being

received from the load pin.

26

Figure 33 illustrates the Load Pin Status area with no load pins configured. Note that

neither Pin 1 nor Pin 2 is selected and the text for each pin is grayed out. The text in the

pin status area reads “NO PINS CONFIGURED”.

Figure 33 – Load Pin Status, No Pins Configured

In Figure 34 one load pin has been added to the system but the no input has been

specified.

Figure 34 – Load Pin Status, One Pin Configured, Pin Input Not Configured

In Figure 35 one load pin has been added to the system and the input has been specified.

The signal being received from the pin is displayed.

Figure 35 – Load Pin Status, One Pin Configured, Pin Signal Displayed

Figure 36 illustrates the load pin status area with two pins configured and Pin 2 selected.

Figure 36 – Load Pin Status, Two Pins Configured, Pin Signal Displayed

6.4.3 Zero Weight

In the center of the Weight Display Configuration screen is a button labeled “Zero

Weight”. This button begins the process of applying an offset to the weight display. An

offset is used to hide forces associated with the system that are not applied to the tubing.

To zero the weight display, touch the Zero Weight button. After touching the Zero

Weight button a confirmation screen will be displayed. This screen displays information

regarding the action that will be taken on confirmation. Dependent upon the conditions of

the injector, reel and tubing this confirmation will display different messages. Always

carefully read the zero weight confirmation.

27

To confirm that the offset should be applied press the Confirm button from the context

menu. Alternately to cancel the Zero Weight process, press the Cancel button.

Figure 37 illustrates the Zero Weight Confirmation screen under normal conditions. The

weight to be offset was less than 2,000 pounds and the depth was not more than 50 feet.

Figure 37 – Zero Weight Confirmation - Normal

Figure 38 illustrates the Zero Weight Confirmation screen under the conditions that the

offset to be applied is greater than 2000 pounds. A large deviation from zero at the

surface may cause problems during the job if an offset is used to temporarily cover up a

problem. Verify all equipment is ready for operation before proceeding.

Figure 38 - Zero Weight Confirmation - Large Offset

Figure 39 illustrates the Zero Weight Confirmation screen under the conditions that the

depth was greater than 50 feet. Attempting to zero the weight with tubing in hole may

cause the weight display to hide some the weight of some tubing in the hole. Additionally

an offset sampled with tubing in hole may not be accurate due to well conditions.

28

Figure 39 - Zero Weight Confirmation - Depth Warning

6.4.4 Weight Unit Selection

Just below the load pin status area is the Weight Unit Selection area. The display for

weight will match whichever button is selected. Figure 40 illustrates the weight unit

selection area.

The FLECS CT application stores the selected display unit during the shutdown process.

When the FLECS CT application starts, the display unit setting is restored. See Section

10.1 - Shutdown for information on the FLECS CT shutdown process.

Figure 40 - Weight Unit Selection Area

6.4.5 Limiting System

The button labeled “Limiting System” on the Weight Display Configuration screen opens

the Limiting System configuration menu. See Section 9 - Limiting System for Limiting

System documentation.

6.4.6 Close

In the context menu for the Weight Display Configuration screen is a button labeled

Close. This button closes the Weight Display Configuration menu. When the Weight

Display Configuration menu is closed the Custom Inputs will be displayed.

7 Depth & Speed Display The Depth & Speed display is the middle (vertically) one third of the Constantly Visible

section of the screen. The Depth & Speed display provides the current depth, speed and

direction of tubing movement. Also provided by the Depth & Speed display is the status

of the speed and depth limiting systems.

29

This section discusses general capabilities of the Depth & Speed display system in

FLECS CT and describes the interface used for managing all aspects of the Depth &

Speed display.

Figure 41 – Depth & Speed Display

7.1 FLECS CT Depth Measurement

The FLECS CT system measures depth using an encoder. The encoder is connected to a

wheel which contacts the tubing. The FLECS CT system is capable of using encoders of

different resolutions and wheels of different circumferences.

The Halliburton standard encoder has a resolution of 500 pulses per revolution. The

Halliburton standard wheel has a circumference of 2.000 feet.

7.2 Current Depth

The large number in the top half of the Depth & Speed display indicates the current

depth. Depth increases as the direction of tubing movement is in hole. The depth will

become negative when tubing moves above the point at which the depth was set to zero.

The unit the depth is currently displayed in is indicated in the above and right of the

current depth.

The depth is not displayed if the encoder does not have a valid calibration.

In Figure 42 the current depth is circled by a blue oval. The current units indicator is

enclosed in a green triangle.

Figure 42 – Depth & Speed Display – Depth & Units Highlighted

30

7.3 Speed

The speed indicator is in the lower right corner of the Depth & Speed display. The speed

is always a positive number. The direction of pipe movement is indicated by the

Direction Indicator.

At speeds less than 10 ft/min in either direction the speed will be displayed to one-tenth

of a foot per minute accuracy. When the speed is greater than 10 ft/min the speed is

displayed to one foot per minute accuracy.

7.4 Direction Indicator

The direction of tubing movement is indicated by a graphic just under the speed label in

the lower left corner of the Depth & Speed display. This is called the Direction Indicator.

When the tubing is moving out of hole the Direction Indicator appears as an upward

pointing arrow. In Figure 43 the Direction Indicator is highlighted by a red rectangle and

the direction of tubing movement is out of hole.

Figure 43 – Depth & Speed Display – Out of Hole

When the tubing is moving in hole the Direction Indicator appears as a downward

pointing arrow. In Figure 44 the Direction Indicator is highlighted by a blue oval and the

direction of movement is in hole.

Figure 44 – Depth & Speed Display – In Hole

In Figure 45 the tubing is not moving and the Direction Indicator is a flat bar. The

Direction Indicator is highlighted by a green triangle.

31

Figure 45 – Depth & Speed Display – No Movement

7.5 Limiting System Status

There are three limits related to the depth and speed. The two areas highlighted by blue

ovals in Figure 46 indicate the state of limits. The Limiting System is discussed in

Section 9 - Limiting System (Page 44).

Figure 46 - Depth & Speed Display - Limit Status Area

7.6 Depth & Speed Display Configuration

A touch in the Depth & Speed display will open the Depth & Speed Display

Configuration screen. The Depth & Speed Display Configuration menu is displayed in

the context dependent section of the screen.

Figure 47 – Depth & Speed Display Configuration Menu

32

7.6.1 Encoder Setup

Located in the context menu of the Depth & Speed Display Configuration menu is a

button labeled “Encoder Setup”. The Encoder setup button is used to configure which

input the Encoder is connected to, set the resolution of the encoder and set the wheel

circumference.

7.6.1.1 Input Tab

The input tab is used to specify where the encoder is connected to the FLECS controller.

See Section 5 for details on this screen.

Note that FLECS frequency inputs not configured as Quadrature type will show as “In

Use” on this screen.

Figure 48 - Encoder Setup - Input Tab

7.6.1.2 Calibration Tab

The calibration tab is used to apply a calibration for the encoder. This calibration is used

to calculate depth and speed.

When the FLECS CT software is initially installed there will not be a calibration for the

encoder. The calibration tab will appear with message indicating the calibration is not yet

set. To set a new calibration or modify an existing calibration press the “Set/Modify

Calibration” button.

Once a calibration has been set, the calibration tab will appear as illustrated in Figure 49.

33

Figure 49 – Encoder Setup – Calibration Tab

7.6.2 Depth Unit Selection

Near the top of the Depth & Speed Display Configuration menu are two buttons labeled

“ft” and “m”. These two buttons are used to select the units for display of the depth. The

currently selected unit is illustrated with a darkened circle on the left side of the button.

The abbreviation “ft” represents feet. The abbreviation “m” represents meters.

The FLECS CT application stores the selected display unit during the shutdown process.

When the FLECS CT application starts, the display unit setting is restored. See Section

10.1 - Shutdown for information on the FLECS CT shutdown process.

In Figure 50 the Depth Unit Selection buttons are enclosed in a red rectangle. The

currently selected unit is “ft”.

Figure 50 – Depth & Speed Configuration – Depth Unit Buttons Highlighted

34

7.6.3 Speed Unit Selection

Near the center of the Depth & Speed Display Configuration menu are two buttons

labeled “ft/min” and “m/min”. These two buttons are used to select the units for display

of the speed. The currently selected unit is illustrated with a darkened circle on the left

side of the button.

The abbreviation “ft/min” represents feet per minute. The abbreviation “m/min”

represents meters per minute.

The FLECS CT application stores the selected display unit during the shutdown process.

When the FLECS CT application starts, the display unit setting is restored. See Section

10.1 - Shutdown for information on the FLECS CT shutdown process.

In Figure 51 the Speed Unit Selection buttons are enclosed in a blue oval. The currently

selected unit is “ft/min”.

Figure 51 – Depth & Speed Configuration – Speed Unit Buttons Highlighted

7.6.4 Zero Depth

Just below the Depth Unit Selection buttons is a button labeled “Zero Depth”. This button

is used to set the current depth to zero. In Figure 52 the Zero Depth button is enclosed in

a red rectangle.

To set the depth display to zero, press the Zero Depth button. A confirmation screen will

be displayed indicating what action will be taken upon confirmation. To proceed and set

the depth to zero press the confirm button. To cancel the zero depth process, press the

cancel button.

35

Figure 52 – Depth & Speed Configuration – Zero Depth

When the tubing is in motion the Zero Depth button will be disabled. This is a safety

feature related to the load limiting system. When the Zero Depth button is disabled the

text in the center of the button appears in a light gray color and pressing the button has no

effect.

7.6.5 Set Depth

The Set Depth feature is used to set the current depth display to a value specified by the

operator. In the context menu of the Depth & Speed Display Configuration screen is a

button labeled “Set Depth”. In Figure 53 the Set Depth button is highlighted by a blue

oval.

Figure 53 – Depth & Speed Configuration Context Menu – Set Depth

To set the depth display to a new value press the Set Depth button. The Set Current Depth

screen will be displayed. The Set Current Depth display is illustrated in Figure 54.

The Set Current Depth screen has a field in the center for entering a new depth. In Figure

54 the New Depth field is enclosed in a red rectangle. The depth is entered in the

36

currently selected units for depth display. The selected unit is indicated to the right of the

New Depth field.

Enter the new depth for the depth display then press the apply button. The apply button is

disabled until a valid value is entered in the New Depth field.

Figure 54 – Set Current Depth

After pressing the apply button a confirmation screen will be displayed indicating the

action that will take place upon confirmation. Read the information on this screen. To

implement the change touch on the Confirm. To cancel the set depth operation press the

cancel button.

When the tubing is in motion the Set Depth button will be disabled. This is a safety

feature related to the load limiting system. When the Set Depth button is disabled the text

in the center of the button appears in a light gray color and pressing the button has no

effect.

7.6.6 Limiting System

The button labeled “Limiting System” at the bottom of the Depth & Speed Display

Configuration screen opens the Limiting System configuration menu. See Section 9 -

Limiting System (Page 44) for Limiting System documentation.

7.6.7 Close

In the context menu for the Depth & Speed Display Configuration screen is a button

labeled Close. This button closes the Depth & Speed Display Configuration menu. When

the Depth & Speed Display Configuration menu is closed the Custom Inputs will be

displayed.

8 Pressure Display The pressure display is the bottom one third of the constantly visible section of the

screen. The pressure display provides the tubing and wellhead pressures. In Figure 55 the

pressure display is highlighted in a red rectangle.

37

This section discusses the general capabilities of the pressure display and describes the

interface used for managing all aspects of the pressure display.

Figure 55 – Pressure Display

8.1 FLECS CT Pressure Measurement

The FLECS CT system measures pressure using pressure transducers. The standard

pressure transducer is a 0 – 15,000 PSI transducer with a 4-20 mA output. The FLECS

CT system is capable of using analog output pressure transducers with other pressure

ranges, up to 20,000 PSI.

8.2 Tubing Pressure

The top half of the pressure display provides the tubing pressure. The current pressure is

displayed in large black text in the top half of the pressure display. The selected unit for

the tubing pressure is displayed above the tubing pressure on the right side of the pressure

display.

In Figure 56 the tubing pressure is enclosed in a blue oval. The selected unit is

highlighted by a green triangle.

38

Figure 56 – Pressure Display – Tubing Pressure

8.3 Wellhead Pressure

The bottom half of the pressure display provides the wellhead pressure. The current

pressure is displayed in large black text in the bottom half of the pressure display. The

selected unit for the wellhead pressure is displayed above the wellhead pressure on the

right side of the pressure display.

In Figure 57 the wellhead pressure is enclosed in a red rectangle. The selected unit is

highlighted by a blue oval.

Figure 57 – Pressure Display – Wellhead Pressure

8.4 Pressure Display Configuration

A touch in the pressure display opens the Pressure Display Configuration menu. The

Pressure Display Configuration screen is displayed in the context dependent section of

the screen. Figure 58 illustrates the Pressure Display Configuration menu.

Configuration of the tubing and wellhead pressure transducers use similar screens. Only

configuration of the tubing pressure transducer is illustrated in this document.

39

Figure 58 – Pressure Display Configuration

8.4.1 Tubing Pressure Transducer Status

Just below the Tubing Pressure text at the top of the screen the tubing pressure transducer

status is displayed. In Figure 59 the Tubing Status area is circled by a blue oval.

Figure 59 – Pressure Display Configuration – Tubing Status

If the input has not been selected for the tubing transducer the status area will display

“Input Not Configured”.

8.4.2 Tubing Pressure Display Unit

In the top left quarter of the Pressure Display Configuration menu are three buttons

labeled “PSI”, “kPa” and “MPa”. These three buttons are surrounded by a red rectangle

in Figure 60.

A touch on one of these three buttons changes the units for the tubing pressure value.

40

Figure 60 – Pressure Display Configuration – Tubing Display Unit

8.4.3 Tubing Pressure Zero

In the top right of the Pressure Display Configuration menu is a large button labeled

“Zero”. This button is used to apply an offset to the tubing pressure. The zero button is

highlighted by a green triangle in Figure 61.

Figure 61 – Pressure Display Configuration – Zero

Before performing the zero process for a pressure transducer ensure that the transducer is

exposed to atmospheric pressure. Touch on the zero button to begin the zero process. The

Confirm Zero Transducer screen will be displayed indicating what action is going to take

place upon confirmation. The Confirm Zero Transducer screen is illustrated in Figure 62.

Read the message carefully. To confirm and execute the zero process, press Zero

Pressure. To cancel press the Cancel button.

41

Figure 62 – Confirm Zero Pressure

A safety feature is integrated into FLECS CT which prevents the pressure display from

differing from the actual pressure on the transducer because of a large offset. This

condition could occur if the transducer was exposed to pressure when a zero process was

executed. This feature also prevents the zero process from being executed if the

transducer signal is below the reasonable operating range for the transducer.

When the signal from a pressure transducer is more than 4.50 mA the Cannot Zero

Transducer message will be displayed. The only option is to touch Cancel and correct the

condition causing the high transducer signal. Figure 63 illustrates the message displayed

under these conditions.

Figure 63 – Cannot Zero Pressure – High Signal

When the signal from a pressure transducer is less than 3.5 mA but greater than 0.5 mA

the Cannot Zero Transducer message will be displayed. The only option is to touch

Cancel and correct the condition causing the low transducer signal. Figure 64 illustrates

the message displayed under these conditions.

42

Figure 64 – Cannot Zero Pressure – Low Signal

When the signal from a pressure transducer is less than 0.5 mA Cannot Zero Transducer

message will be displayed. The only option is to touch Cancel and correct the condition

causing the low transducer signal. Figure 65 illustrates the message displayed under these

conditions.

Figure 65 – Cannot Zero Pressure – No Signal

8.4.4 Tubing Pressure Transducer Configuration

Located in the context menu of the Pressure Display Configuration menu is a button

labeled “Set Up Tubing Transducer”. A touch on this button opens the Transducer Setup

menu illustrated in Figure 66.

43

Figure 66 – Tubing Pressure Setup – Calibration Tab

8.4.4.1 Input Selection Tab

Use the input tab to see the currently selected input and change the selected input. See

Section 5 for more information on how to use this screen.

8.4.4.2 Point List

A table providing the list of currently configured calibration points is illustrated on the

Transducer Setup screen. Figure 67 shows the Load Pin Setup menu with a red box

around the Calibration Point List. Two calibration points exist in Figure 67.

Figure 67 – Transducer Setup - Calibration Point List

Note: A pressure transducer must have two calibration points for a valid configuration.

8.4.4.3 Add Calibration Point

At the bottom of the Transducer Setup menu is a button labeled “Add Point”. The Add

Point button is illustrated with a blue oval in Figure 68. In the illustration the button is

44

disabled. A pressure transducer has a maximum of two calibration points. If two points

have already been added the button will be disabled.

Figure 68 – Transducer Setup – Add Point Button

Touch on the Add Point button to add a calibration point. Refer to Section 4.1 - Add

Calibration Point (Page 12) for instructions on adding calibration points for sensors with

current outputs.

8.4.4.4 Delete Existing Calibration Point

To delete an existing calibration point, touch on the row of the calibration point to be

deleted in the calibration point list. Press the delete point button then read and confirm

the point should be deleted.

8.4.5 Close

In the context menu for the Pressure Display Configuration screen is a button labeled

Close. This button closes the Pressure Display Configuration menu. When the menu is

closed the Custom Inputs will be displayed.

9 Limiting System The Limiting System monitors several aspects of the coiled tubing unit. When conditions

exceed a predefined threshold the CT unit is stopped.

The Limiting System consists of three components. The first component is the set of

sensors used to measure the state of the CT unit. The load pin(s) are used to measure the

state of the forces applied to the tubing. The encoder is used to measure the depth, speed

and direction of the tubing.

The second component of the Limiting System is the FLECS controller. The FLECS

controller observes the state of the system using the sensors described above. Ten times

per second the FLECS controller evaluates each limit to determine if the state of the CT

unit is still within the limits established by the operator.

45

If the FLECS controller determines the CT unit has exceeded the limits the third

component of the Limiting System is used to stop the injector. A pair of electrically

controlled valves simultaneously stop the injector and set the injector brake.

The Limiting System is designed to quickly react to an emergency situation. The

Limiting System is not designed to reduce operator workload. The injector experiences

high loads when rapidly stopping the motion of tubing. Configuration of the Limiting

System resulting in frequently exceeded limits will reduce the lifespan of some

components of the injector.

The Limiting System consists of six individual limits. The operation of each individual

limit is described in Sections 9.2 and 9.3.

9.1 Limit States

The way the FLECS CT controller conveys information about each limit is by displaying

the state of the limit. Each of the limits moves between one of the five states as a result of

actions taken by the operator and signals received by sensors.

The remainder of this section describes what each of the five states means and how the

state is illustrated on the FLECS display. Also discussed are the actions the FLECS CT

controller takes when a limit is in the state.

The information in this section is generalized. For details specific to each limit see the

section discussing the relevant limit.

The state of each limit is illustrated in the constantly visible display related to the limit. In

each section describing a limit state an illustration of each limit in the described state is

provided.

9.1.1 Off

The Off state indicates the operator has turned the limit off. While off the limit state will

be illustrated with black text on a red background. The text for the limit will contain the

word “Off”.

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

46

Figure 69 – All Limits Off

9.1.2 On

The On state will be illustrated with green text on a white background. The text for the

limit state will contain the word “On”.

The FLECS CT application monitors the sensors associated with the limit. The signal

from the sensor indicates that the limit is within the currently established threshold.

Figure 70 – All Limits On

47

9.1.3 Warn

The Warn state will be illustrated with black text on a yellow background. The yellow

background will fill the entire constantly visible display associated with the limit. The

text for the limit state will contain the word “Warn”.

The FLECS CT application monitors the sensors associated with the limit. The FLECS

CT application has determined that the limit is close to the established threshold. Action

should be taken to prevent the limit from tripping.

Not all limits will enter the warning state before enter the tripped state. If the conditions

of the CT unit are changing rapidly even limits with a warning state may move directly

from On to Tripped without warning.

Figure 71 – Warn State

9.1.4 System Disabled

The System Disabled state is illustrated with black text on a white background. The text

for the limit state will contain the word “Off”.

The FLECS CT application monitors the sensors associated with the limit. The FLECS

CT application has determined that a rapid shutdown of the injector would be unsafe

under current conditions. The limit will not trip even if the threshold for the limit is

exceeded.

All limits will exit System Disabled state regardless of the speed if the depth is less than

100 feet.

If the limit is turned on the limit will be restored to On or Warn state when system

conditions indicate that a rapid shutdown of the injector is safe. If the FLECS CT

48

application determines that the potential consequences of a rapid shutdown of the injector

are less serious than not taking this action the FLECS CT application will restore the

limits to the On or Warn state.

All limits which are on when a limit system test begins will be set to System Disabled

state until the test is ended.

Figure 72 – System Disabled State

9.1.5 Tripped

The Tripped state is illustrated with black text on a red background. The red background

will fill the entire constantly visible display associated with the limit. The text for the

limit state will contain the word “Limit”.

The FLECS CT application determined that the threshold for the limit has been exceeded.

The FLECS CT application uses the limiting system valves to dump injector pressure and

set the injector brake.

See Section 9.5 - Resetting Tripped Limits (Page 61) for details on resetting tripped

limits.

49

Figure 73 – Tripped State

9.2 Weight Limits

There are three limits related to the weight. This section provides details on the operation

of each limit.

Each of the Weight Limits requires all components of the Load Limiting system to be

operating correctly to be effective.

9.2.1 Pull Limit

The Pull Limit compares the current weight to a threshold set by the operator. When the

weight is within 1500 pounds of the threshold the limit will enter Warn state. When the

weight exceeds the threshold the limit will enter Tripped state.

The Pull Limit will enter System Disabled state if the out of hole speed exceeds 50 feet

per minute. When the out of hole speed drops below 50 feet per minute the Pull Limit

will exit System Disabled State. When the depth is less than 100 feet the Pull Limit will

exit System Disabled State regardless of tubing speed.

FLECS CT will not allow the Pull Limit to be enabled if the load pin configuration is

invalid or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin

Setup (Page 21) for more information on configuring load pins. See Section 7.6.1 -

Encoder Setup (Page 32) for more information on the primary encoder setup.

All calculations related to the Pull Limit are performed in pounds regardless of the

display unit.

50

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

9.2.2 Snub Limit

The Snub Limit compares the current weight to a threshold set by the operator. When the

weight is within 1500 pounds of the threshold the limit will enter Warn state. When the

weight exceeds the threshold the limit will enter Tripped state.

The Snub Limit will enter System Disabled state if the out of hole speed exceeds 50 feet

per minute. When the out of hole speed drops below 50 feet per minute the Snub Limit

will enter the relevant state based on the comparison of current weight to Snub Limit

threshold. When the depth is less than 100 feet the Snub Limit will exit System Disabled

State regardless of tubing speed.

FLECS CT will not allow the Snub Limit to be enabled if the load pin configuration is

invalid or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin

Setup (Page 21) for more information on configuring load pins. See Section 7.6.1 -

Encoder Setup (Page 32) for more information on the primary encoder setup.

All calculations related to the Snub Limit are performed in pounds regardless of the

display unit.

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

9.2.3 Tag Limit

The Tag Limit monitors the rate of change of the current weight. If the weight changes by

more than 800 pounds in one tenth of a second the Tag Limit enters the Tripped state.

There is no Warn state for the tag limit.

The Tag Limit will enter System Disabled state if the out of hole speed exceeds 50 feet

per minute. When the out of hole speed drops below 50 feet per minute the Tag Limit

will enter the relevant state based on the comparison of current weight to Tag Limit

threshold. When the depth is less than 100 feet the Tag Limit will exit System Disabled

State regardless of tubing speed.

FLECS CT will not allow the Tag Limit to be enabled if the load pin configuration is

invalid or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin

Setup (Page 21) for more information on configuring load pins. See Section 7.6.1 -

Encoder Setup (Page 32) for more information on the primary encoder setup.

All calculations related to the Tag Limit are performed in pounds regardless of the

display unit.

51

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

9.3 Depth & Speed Limits

There are three limits related to the depth and speed. This section provides details on the

operation of each limit.

Each of the Depth & Speed Limits requires all components of the Load Limiting system

to be operating correctly to be effective.

9.3.1 Pull Out Limit

The Pull Out Limit monitors the current depth and speed. The Pull Out limit will enter

System Disabled state when the direction is out of hole and the speed exceeds 50 feet per

minute.

The Pull Out Limit exits System Disabled state regardless of speed when the depth is less

than 100 ft.

The Pull Out Limit enters the Warn state under two conditions. The Warn state will be

entered when the time to zero depth is less than sixty seconds and the direction is out of

hole. The Warn state will also be entered when the depth is 25 feet or less and the

direction is out of hole, regardless of the speed.

The Pull Out Limit enters the Tripped state under two conditions. The Tripped state will

be entered when the time to zero depth is less than 10 seconds and the direction is out of

hole. The Tripped state will also be entered when the depth is 10 feet or less and the

direction is out of hole, regardless of the speed.

FLECS CT will not allow the Pull Out Limit to be enabled if the load pin configuration is

invalid or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin

Setup (Page 21) for more information on configuring load pins. See Section 7.6.1 -

Encoder Setup (Page 32) for more information on the primary encoder setup.

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

FLECS CT will not allow the Pull Out Limit to be enabled if the load pin configuration is

invalid or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin

Setup (Page 21) for more information on configuring load pins. See Section 7.6.1 -

Encoder Setup (Page 32) for more information on the primary encoder setup.

9.3.2 Speed Out of Hole Limit

The Speed Out of Hole limit compares the current speed to a threshold set by the

operator. When the direction is out of hole and the speed is within 15 feet per minute of

52

the threshold the limit will enter Warn state. When the direction is out of hole and the

speed exceeds the threshold the limit will enter Tripped state.

The Speed Out of Hole Limit will enter System Disabled state if the out of hole speed

exceeds 50 feet per minute. When the out of hole speed drops below 50 feet per minute

the limit will enter the relevant state based on the comparison of current speed to limit

threshold. When the depth is less than 100 feet the Speed Out of Hole Limit will exit

System Disabled State regardless of tubing speed.

FLECS CT will not allow the limit to be enabled if the load pin configuration is invalid

or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin Setup

(Page 21) for more information on configuring load pins. See Section 7.6.1 - Encoder

Setup (Page 32) for more information on the primary encoder setup.

All calculations related to the Speed Out of Hole Limit are performed in feet per minute

regardless of the display unit.

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

9.3.3 Speed In Hole Limit

The Speed In Hole limit compares the current speed to a threshold set by the operator.

When the direction is in hole and the speed is within 15 feet per minute of the threshold

the limit will enter Warn state. When the direction is in hole and the speed exceeds the

threshold the limit will enter Tripped state.

The Speed In Hole Limit will enter System Disabled state if the out of hole speed exceeds

50 feet per minute. When the out of hole speed drops below 50 feet per minute the limit

will enter the relevant state based on the comparison of current speed to limit threshold.

When the depth is less than 100 feet the Speed In Hole Limit will exit System Disabled

State regardless of tubing speed.

FLECS CT will not allow the limit to be enabled if the load pin configuration is invalid

or if the primary encoder has not been configured. See Section 6.4.1 - Load Pin Setup

(Page 21) for more information on configuring load pins. See Section 7.6.1 - Encoder

Setup (Page 32) for more information on the primary encoder setup.

All calculations related to the Speed In Hole Limit are performed in feet per minute

regardless of the display unit.

The FLECS CT application does not evaluate the limit when in the off state. The FLECS

controller will not automatically turn a limit on under any conditions. Limits must be

turned on by the operator.

53

9.4 Limit Setup

The Limit Setup menus can be accessed with two different methods. Both the Weight

Display Configuration and Depth & Speed Display Configuration menus have a Limiting

Setup button. See Sections 6.4.5 (Page 28) and 7.6.6 (Page 36) for more information on

accessing the Limit Setup screen.

There are four sections in Limit Setup menu. The sections of the Limit Configuration

menu are referred to as “tabs.” Each tab of the Limit Setup menu provides options for

configuration a specific part of the Limiting System.

Figure 74 illustrates the tabs with Output tab currently selected. The currently selected

tab has a white background. The other two tabs are illustrated with a gray background.

To change to another tab touch the desired tab. Not all tabs are visible on the screen. Use

the left and right arrow buttons to scroll through the available tabs.

FLECS CT will not allow changing from the output tab until the digital output has been

configured.

Figure 74 – Limiting System Tabs

9.4.1 Output Tab

The Output Tab is used to select the digital output controlling the two load limiting

valves. When FLECS CT is installed there is not a digital output selected. Until a digital

output is selected no other tabs are accessible. Figure 75 illustrates the Output tab. In

Figure 75 the output has not yet been configured.

54

Figure 75 – Limiting System Configuration – Output Configuration

9.4.1.1 Output Selection

See Section 5 (Page 18) for details on using the output selection screen.

9.4.2 Weight Tab

The Weight Tab is used to enable or disable the Pull, Snub and Tag limits and to set the

thresholds for the Pull and Snub limits. The Weight tab is divided into three sections, one

for each of the limits. The labels on the left side of the screen indicate which limit the

information displayed in the section applies to. Figure 76 illustrates the Weight tab.

Notice the three blue squares to the right of each limit name. Each of these is called a

checkbox. A checkbox is much like an on off switch. When a limit is turned on a check

mark will appear in the middle of each box. In Figure 76 the Snub Limit is on because

there is a check mark in the box. When a limit is off there is no check mark in the

checkbox. In Figure 76 the Pull Limit is off. To change the state of a check box touch on

the checkbox.

Figure 76 – Limiting System Configuration - Weight Tab

55

9.4.2.1 Pull Limit

The Pull Limit section of the Weight tab is enclosed in a red rectangle in Figure 77.

Figure 77 – Limiting System Configuration - Weight Tab – Pull Limit

9.4.2.1.1 Pull Limit Enable / Disable Checkbox

This checkbox is used to turn the Pull Limit on or off. The Pull Limit Enable / Disable

Checkbox is contained in a green triangle in Figure 77. Touch the checkbox to change the

state of the limit.

9.4.2.1.2 Pull Limit Threshold

The box to the right of the Enable/Disable Checkbox contains a number. This number is

the current threshold for the Pull Limit. This value is displayed in the display units

selected for the weight display. In Figure 77 the Pull Limit Threshold is in a blue oval.

To change the Pull Limit Threshold touch on the box containing the current threshold.

The Pull Limit Threshold menu will be displayed as illustrated in Figure 78.

Figure 78 – Pull Limit Threshold

56

Enter the new limit value in the new limit value field.

Just below the new limit field the valid range for a new limit is displayed. The FLECS

CT application will not allow a new limit value to be entered which would cause the

system to immediately go to Warn or Tripped state. The number in the new limit field

must be within this range before the Set Limit button will be enabled.

After entering a value in the New Limit field press the Set Limit button to implement the

change.

9.4.2.2 Snub Limit

The Snub Limit section of the Weight tab is enclosed in a red rectangle in Figure 79.

Figure 79 – Limiting System Configuration - Weight Tab – Snub Limit

9.4.2.2.1 Snub Limit Enable / Disable Checkbox

This checkbox is used to turn the Snub Limit on or off. The Snub Limit Enable / Disable

Checkbox is contained in a green triangle in Figure 79. Touch the checkbox to change the

state of the limit.

9.4.2.2.2 Snub Limit Threshold

The box to the right of the Enable/Disable Checkbox contains a number. This number is

the current threshold for the Snub Limit. This value is displayed in the display units

selected for the weight display. In Figure 79 the Snub Limit Threshold is in a blue oval.

To change the Snub Limit Threshold touch on the box containing the current threshold.

The Snub Limit Threshold menu will be displayed as illustrated in Figure 80.

57

Figure 80 – Snub Limit Threshold

Enter the new limit value in the new limit value field.

Just below the new limit field the valid range for a new limit is displayed. The FLECS

CT application will not allow a new limit value to be entered which would cause the

system to immediately go to Warn or Tripped state. The number in the new limit field

must be within this range before the Set Limit button will be enabled.

After entering a value in the New Limit field press the Set Limit button to implement the

change.

9.4.2.3 Tag Limit

The Tag Limit section of the Weight tab is enclosed in a red rectangle in Figure 81.

Figure 81 – Limiting System Configuration - Weight Tab – Tag Limit

9.4.2.3.1 Tag Limit Enable / Disable Checkbox

58

This checkbox is used to turn the Tag Limit on or off. The Tag Limit Enable / Disable

Checkbox is contained in a green triangle in Figure 81. Touch the checkbox to change the

state of the limit.

9.4.3 Depth/Speed Tab

The Depth/Speed Tab is used to enable or disable the Pull Out, Speed Out of Hole and

Speed In Hole limits. The thresholds for the Speed Out of Hole and Speed In Hole limits

are also configured from the Depth/Speed Tab. The tab is divided into three sections, one

for each of the limits. The labels on the left side of the screen indicate which limit the

information displayed in the section applies to. Figure 82 illustrates the Depth/Speed tab.

Figure 82 – Limiting System Configuration - Depth/Speed Tab

9.4.3.1 Pull Out Limit

The Pull Out Limit section of the Depth/Speed tab is enclosed in a red rectangle in Figure

83.

Figure 83 – Limiting System Configuration - Depth/Speed Tab – Pull Out Limit

9.4.3.1.1 Pull Out Limit Enable / Disable Checkbox

59

This checkbox is used to turn the Pull Out Limit on or off. The Pull Out Limit Enable /

Disable Checkbox is contained in a green triangle in Figure 83. Touch the checkbox to

change the state of the limit.

9.4.3.2 Speed Out of Hole Limit

The Speed Out of Hole Limit section of the Depth/Speed tab is enclosed in a red

rectangle in Figure 84.

Figure 84 – Limiting System Configuration - Depth/Speed Tab – OOH Limit

9.4.3.2.1 Speed Out of Hole Limit Enable / Disable Checkbox

This checkbox is used to turn the Speed Out of Hole Limit on or off. The Speed Out of

Hole Limit Enable / Disable Checkbox is contained in a green triangle in Figure 84.

Touch the checkbox to change the state of the limit.

9.4.3.2.2 Speed Out of Hole Limit Threshold

The box to the right of the Enable/Disable Checkbox contains a number. This number is

the current threshold for the Speed Out of Hole Limit. This value is displayed in the

display units selected for the speed display. In Figure 84 the Speed Out of Hole Limit

Threshold is in a blue oval.

To change the Speed Out of Hole Limit Threshold touch on the box containing the

current threshold. The Speed Out of Hole Limit Threshold menu will be displayed.

Enter the new limit value in the new limit value field.

Just below the new limit field the valid range for a new limit is displayed. The FLECS

CT application will not allow a new limit value to be entered which would cause the

system to immediately go to Warn or Tripped state. The number in the new limit field

must be within this range before the Set Limit button will be displayed.

After entering a value in the New Limit field press the Set Limit button to implement the

change.

60

9.4.3.3 Speed In Hole Limit

The Speed In Hole Limit section of the Depth/Speed tab is enclosed in a red rectangle in

Figure 85.

Figure 85 – Limiting System Configuration - Depth/Speed Tab – IH Limit

9.4.3.3.1 Speed In Hole Limit Enable / Disable Checkbox

This checkbox is used to turn the Speed In Hole Limit on or off. The Speed In Hole Limit

Enable / Disable Checkbox is contained in a green triangle in Figure 85. Touch the

checkbox to change the state of the limit.

9.4.3.3.2 Speed In Hole Limit Threshold

The box to the right of the Enable/Disable Checkbox contains a number. This number is

the current threshold for the Speed In Hole Limit. This value is displayed in the display

units selected for the speed display. In Figure 85 the Speed In Hole Limit Threshold is in

a blue oval.

To change the Speed In Hole Limit Threshold touch on the box containing the current

threshold. The Speed In Hole Limit Threshold menu will be displayed.

Enter the new limit value in the new limit value field.

Just below the new limit field the valid range for a new limit is displayed. The FLECS

CT application will not allow a new limit value to be entered which would cause the

system to immediately go to Warn or Tripped state. The number in the new limit field

must be within this range before the Set Limit button will be displayed.

After entering a value in the New Limit field press the Set Limit button to implement the

change.

61

9.5 Resetting Tripped Limits

This section describes the process of resetting the limiting system after a limit has been

exceeded. Failure to reset a limit using correct procedure can result in injury to personnel

and damage to equipment.

After a limit has tripped immediately reduce injector maximum pressure adjust to

minimum setting and set the injector brake. This is always the first step in resetting a

limit.

9.5.1 Reset Pull Limit

1. Set Injector Maximum Pressure to zero.

2. Set Injector Brake.

3. Note event in job log.

4. Determine why the limit tripped.

5. Verify equipment and wellhead ready to return to service.

6. Touch in the Weight constantly visible display to reset limit.

7. Turn Pull Limit On.

8. Resume Operations.

9.5.2 Reset Snub Limit

1. Set Injector Maximum Pressure to zero.

2. Set Injector Brake.

3. Note event in job log.

4. Determine why the limit tripped.

5. Verify equipment and wellhead ready to return to service.

6. Touch in the Weight constantly visible display to reset limit.

7. Turn Snub Limit On.

8. Resume Operations.

9.5.3 Reset Tag Detect Limit

1. Set Injector Maximum Pressure to zero.

2. Set Injector Brake.

3. Note event in job log.

4. Determine why the limit tripped.

5. Verify equipment and wellhead ready to return to service.

6. Touch in the Weight constantly visible display to reset limit.

7. Resume Operations.

9.5.4 Reset Pull Out Limit

1. Set Injector Maximum Pressure to zero.

2. Set Injector Brake.

3. Note event in job log.

4. Determine why the limit tripped.

5. Verify equipment and wellhead ready to return to service.

6. Touch in the Depth / Speed constantly visible display to reset limit.

62

7. Turn Pull Out Limit On.

8. Resume Operations.

9.5.5 Reset Speed Out of Hole Limit

1. Set Injector Maximum Pressure to zero.

2. Set Injector Brake.

3. Note event in job log.

4. Determine why the limit tripped.

5. Verify equipment and wellhead ready to return to service.

6. Touch in the Depth / Speed constantly visible display to reset limit.

7. Resume Operations.

9.5.6 Reset Speed In Hole Limit

1. Set Injector Maximum Pressure to zero.

2. Set Injector Brake.

3. Note event in job log.

4. Determine why the limit tripped.

5. Verify equipment and wellhead ready to return to service.

6. Touch in the Depth / Speed constantly visible display to reset limit.

7. Resume Operations.

9.6 Limit System Test

The fourth tab of the Limit Setup screen is the Test tab. This tab enables maintenance

personnel to energize the limiting system valves. The purpose of this is to verify the

valves are operating properly.

The Test tab is illustrated in Figure 86. The test tab simply has a button for beginning the

test. To begin a test press the button, read the confirmation screen and confirm or cancel.

All limits turned on will enter the system disabled state and remain in that state until the

test is ended.

Figure 86 - Limit System – Test

63

FLECS CT will not allow the limit system to be tested while the tubing is in motion. If

tubing motion is detected the Begin Test button will be disabled. The begin test button

will remain disabled until the tubing stops.

Figure 87 - Limit System - Test with Tubing in Motion

When a test is in progress the button on the Test tab will read “End Test.” To end the test

press the end test button.

Figure 88 - Limit System - End Test

64

10 System Menu The Operator uses the System Menu to perform the five functions described in detail in

the following sections: System Shutdown, KIPS Gauge Calibration, Serial Setup, Set

Time and Date, and Start/Stop RTD File.

The Operator opens the System Menu by touching in the lower right corner of the FLECS

touch screen, in the extended touchable area. See Section 1.2.2 - FLECS Display Touch-

screen (Page 6) for details on the touch-screen and extended touchable area. In addition,

the F8 key will also open the System Menu.

The unit displays the System Menu in the Context Dependent section of the FLECS

screen. The System Menu is illustrated in Figure 89.

System Setup

Close

Shutdown Set Time

KIPS

CalibrationStart Job

Serial Setup

1.2.0 Build 3 1.2.0 Build 3

Figure 89 – System Menu

To close the System Menu touch on the button labeled “Close”.

10.1 Shutdown

Prior to turning the power to the FLECS controller off the Shutdown process must be

performed. The shutdown process allows the FLECS CT application to properly prepare

for the power to be switched off. Failure to perform a System Shutdown prior to

switching the power off can cause the FLECS CT application to malfunction and cause

damage FLECS hardware.

To begin the System Shutdown process press the System Shutdown button on the System

Menu.

After a touch on the System Shutdown button the FLECS CT application displays a

confirmation dialog. When the FLECS CT application begins the shutdown process the

FLECS Controller discontinues any services it normally provides.

65

To cancel the System Shutdown process touch on the Cancel button. To confirm the

System Shutdown process touch on the Shutdown button.

The System Shutdown takes up to a minute to complete. It is critical that the power to the

FLECS controller never be interrupted while the FLECS CT application is shutting down.

Interruption of the power while shutting down can cause the FLECS CT application to

become inoperative and damage FLECS hardware. When the System Shutdown process

begins the FLECS display will indicate that the Shutdown Process is in progress.

Figure 90 – System Shutdown In Progress

After the System Shutdown process completes FLECS CT will show the message

illustrated in Figure 91. Do not turn off the power to the FLECS controller until this

message is displayed.

Figure 91 – System Shutdown Complete

In the event a problem occurs during the System Shutdown process a different message

will be displayed. This message is illustrated in Figure 92. This message indicates a

problem with the FLECS controller. The controller must be repaired before used on

another job.

66

Figure 92 – Shutdown Did Not Complete

10.2 KIPS Calibration

The KIPS calibration process enables the FLECS CT application to set the KIPS gauge to

the same value displayed on the FLECS display.

To begin the KIPS calibration process touch on the button labeled “KIPS”. This button is

in a red rectangle in Figure 93.

System Setup

Close

Shutdown Set Time

KIPS

CalibrationStart Job

Serial Setup

1.2.0 Build 3 1.2.0 Build 3

Figure 93 – System Menu – KIPS Button

The first of two KIPS calibration menus will be displayed. The objective of these two

screens is to use the up and down arrows to move the needle on the KIPS gauge until it

rests on the target weight.

The target weight is surrounded by a blue oval in Figure 94. This is the weight the needle

on the KIPS gauge should point to before continuing.

67

The up arrows make the needle move in the clockwise direction, towards a higher pull

value. The down arrows make the needle move in the counter-clockwise direction,

towards a higher snub value.

The arrows on the left side of the menu make the needle move a large amount with one

touch. Use these two arrows to get the needle close to the target weight. The arrows on

the right side of the menu move the needle a small amount. Use these arrows to make

small adjustments to the needle until it rests on the target weight.

When the needle is as close to the target weight as possible touch on the Next button to

move to the second KIPS calibration menu. Use the up and down arrows to move the

needle to the target weight. Then touch the Done button to complete the process.

Figure 94 – KIPS Calibration

68

10.3 Serial Setup

The FLECS CT application provides serial data on up to three serial ports. By default all

serial ports 1, 2 and 3 transmit the CT60079_B program.

There are no user configurable options for the serial ports in FLECS CT. The Serial Setup

screen only contains information.

System Setup

Close

Shutdown Set Time

KIPS

CalibrationStart Job

Serial Setup

1.2.0 Build 3 1.2.0 Build 3

Figure 95 – System Menu – Serial Setup Button

Touching the Serial Setup button opens the Serial Setup menu illustrated in Figure 96.

Figure 96 – Serial Setup

69

10.3.1 CT60079_B

This section compares the output from the UNIPRO CT60079_B program to the output

from the FLECS CT application.

UNIPRO FLECS

Seconds since January 1, 1970

Seconds since January 1, 1970

Events (0-99) 0

Speed Speed

Depth Depth

Tubing Pressure Tubing Pressure

Flow Rate Custom 1 Value

Flow Total Custom 1 Total

Spare Weight Spare Weight

Wellhead Pressure Wellhead Pressure

N2 Rate Custom 2 Value

N2 Total Custom 2 Total

Weight Weight

Spare Pressure Custom 3 Value

N2 Temp Custom 4 Value

Spare Flow Custom 5 Value

Spare Total Custom 5 Total

Depth Depth

Depth Depth

Flow Total 0

CRC CRC

10.3.2 Port Settings

FLECS CT outputs serial data using the following serial port settings.

9600 bps

8 data bits

Parity: None

Stop Bits: 1

Flow control: None

10.4 Version Information

At the bottom of the System Menu the interface software version and controller software

version are displayed. The interface software version is on the left. The controller

software version is on the right.

70

10.5 Set Time and Date

The Set Time process enables the FLECS CT application to set the Time and Date for the

display and the FLECS controller stack.

To begin the Set Time process, touch on the button labeled “Set Time”. This button is in

a red rectangle in Figure 97 - System Menu - Set Time Button.

System Setup

Close

Shutdown Set Time

KIPS

CalibrationStart Job

Serial Setup

1.2.0 Build 3 1.2.0 Build 3

Figure 97 - System Menu - Set Time Button

Pressing the Set Time button opens the set time and date dialog shown in Figure 98.

7

Hour

2

Minute

18

Day

8

Month

9

Year

7:02 pm

18 Aug 2009 Set Exit

PM

Figure 98 – Set Time Menu

The screen displays the current time in the lower left hand corner. The Hour, Minute,

Day, Month, and Year are adjusted up or down with the arrows to the right of each entry.

Pressing the button in the upper right, currently “PM” will change the value to “AM.”

Once the operator has set the desired values, he or she will press Set to set the entered

values or Exit to exit without saving. The clock will be set in both the local display and

the FLECS hardware stack. After a few seconds, the display will update the current time

in the lower left hand corner.

71

10.6 Start RTD Job

The Start Job process results in the FLECS logging the data sent out the serial stream to a

local RTD file.

To begin the Start Job process, touch on the button labeled “Start Job”. This button is in a

red rectangle in Figure 99.

System Setup

Close

Shutdown Set Time

KIPS

CalibrationStart Job

Serial Setup

1.2.0 Build 3 1.2.0 Build 3

Figure 99– System Menu – Set Time Button

Once the operator enables RTD logging, the system will log the data sent out the serial

stream to a local RTD file. The operator can retrieve the file with a pen drive configured

to load the CT or Cementing software. While logging data, the display will be as shown

in Figure 100:

System Setup

Close

Shutdown RTD Running

KIPS

CalibrationEnd Job

Serial Setup

1.2.0 Build 3 1.2.0 Build 3

Figure 100 – System Menu – Set Time Button

The Set Time function is disabled and the button now states RTD Running. Likewise,

the Start Job button now states End Job. Pressing the End Job button causes the data

logging to stop and the screen reverts to the screen shown in Figure 99.

72

11 Display Backlight Brightness The Display Brightness screen enables the operator to control the intensity of the display

backlight.

The Display Brightness screen is accessible only when all other screens are closed. The

Extended Touchable Area (See 1.2.2.1, Page 6) button on the right side, second from the

bottom opens the Display Brightness screen. The screen can also be accessed by pressing

the F7 key while at the FLECS desktop (See 3.1, Page 10).

The Display Brightness screen is illustrated in Figure 101. The screen provides two preset

brightness settings, one for day use and the second for night use. Touching on one of the

two preset buttons will cause the display brightness to change to a predefined setting

which should be acceptable for most operations.

The screen also provides a control on the left side of the screen offering more precise

control of the backlight if desired.

When satisfied with the brightness level press Done. This will exit the Display Brightness

menu. The display brightness is saved at the time the screen is closed. The next time the

FLECS CT system is powered on the same brightness level will be applied.

Figure 101 - Display Brightness

73

12 Custom Inputs Custom Inputs are used for displaying inputs from additional sensors connected to the

FLECS controller. FLECS CT supports four types of sensors: Current (4-20 mA) inputs,

frequency inputs, magnetic pickup inputs, and encoders. The FLECS application can also

display the totalized values for frequency, mag-pickup and encoder inputs.

When all menus and context dependent menus are closed, the context dependent section

of the screen is divided into six parts. The operator can configure each of the six parts as

any of the four supported custom input types. The red rectangle encloses the six custom

inputs in Figure 102.

Figure 102 - Custom Inputs Highlighted

When configured, the Custom Input will display either three or six information fields

related to the Custom Input. In Figure 103 the Custom Input on the left has been

configured as a Current and the units have been selected as MPa. The operator has

configured the screen on the right as a Total, so it includes a rate in the upper half and the

totalized rate in the lower half.

CURRENT 1 MPa

100.2

FREQ 1 BBl/m

10.00Total gal

10.00

Figure 103 - Custom Input Display Detail

The text in upper left is the custom input label. The operator uses the label to describe

what value the custom input is displaying. The operator selects the unit of display on the

right as described in the discussions below.

74

12.1 Custom Input Number

The systems refers to custom inputs individually as Custom Input 1, Custom Input 2, etc.,

and numbers them starting with one from left to right then top to bottom. In Figure 101

each custom input is illustrated with its number in large red text. The Custom Input used

for displaying a sensor affects if the value from the sensor will be included in the serial

output, see Section 10.3 – Serial Setup for details.

Figure 101 - Custom Inputs with Input Numbering

12.2 Configure New Custom Input

To configure a new custom input, touch on the custom input display. For example to

begin the configuration of a new sensor, touch the area in the red rectangle shown in

Figure 102. This opens the Select Type window shown in Figure 103 that allows

selecting what type of signal will feed the Custom Input. The following sections will

outline the procedure for each custom type.

Figure 102 - Custom 1 Touch Area Figure 103 - Custom Input Setup

1 2

3 4

5 6

Select Type

Current

Frequency

Encoder

Total

Mag-Pickup

Cancel Next

Custo

m Inp

ut 1

75

12.3 Custom Current

Begin by pressing the Current button in the Select Type window and press the Next

button to proceed. The system will not enable the Next button until the operator selects a

signal type.

Select Type

Current

Frequency

Encoder

Total

Mag-Pickup

Cancel Next

Custo

m Inp

ut 1

Figure 104 - Custom Input Setup

Custom Input Label Screen:

Enter up to 13 characters for the label displayed at the top of the custom input using the

FLECS display keypad and press Next.

Custom Input Label

New Label

Current 1

Remaining Characters: 4

Cancel Next

Custo

m Inp

ut 1

Figure 105 - Custom Input Label

76

Input Select Screen:

Use the left and right arrow buttons to scroll through the available signals. The system

will display the “Analog Input # Is In Use” (where # is equal to 1 through 8) message if

the channel is in use or is not configured for the desired signal type. The system will not

enable the Apply button until the operator selects an available input. Once the Apply

button is pressed, the system will advance to the next screen. The operator only uses the

Next button when modifying an existing Custom Current input.

Input Not Set

New Input

Analog Input 1

Is In Use

Cancel Next

1 Apply

Cu

sto

m In

pu

t 1

Figure 106 - Custom Analog Input

Calibration Point 1 Screen:

The custom current input uses a two-point calibration. Enter the lower calibration point

and press the Next button. The example uses a 0-500-psi pressure transducer with a

range of

4-20mA.

Calibration Point 1

mA:

4

Cancel Next

Value:

0

Cu

sto

m In

pu

t 1

Figure 107 - Custom Analog Cal Point 1

77

Calibration Point 2 Screen:

Enter the upper calibration point and press the Next button.

Calibration Point 2

mA:

20

Cancel Next

Value:

500C

usto

m In

pu

t 1

Figure 108 - Custom Analog Cal Point 2

Units Screen:

Select the desired units and press the Done button.

Select Units

Cancel Done

PSI

kPa

MPa

DegF

DegC

Cu

sto

m In

pu

t 1

Figure 109 - Custom Analog Select Units

78

After pressing the Done button the FLECS CT application will implement the new

configuration for the custom input and begin displaying the value from the sensor. The

values entered in this example result in the display shown in Figure 110. Note the label

on the left and the units on the right.

Current 1 MPa

100.2

Figure 110 - Custom Analog Displayed Values

12.4 Custom Frequency and Mag-Pickup

Begin by pressing the Frequency button in the Select Type window and press the Next

button to proceed. The system will not enable the Next button until the operator selects a

signal type.

Select Type

Current

Frequency

Encoder

Total

Mag-Pickup

Cancel Next

Cu

sto

m In

pu

t 1

Figure 111 - Select Type Frequency

79

Custom Input Label Screen:

Enter up to 13 characters for the label displayed at the top of the custom input using the

FLECS display keypad and press Next.

Custom Input Label

New Label

FREQ 1

Remaining Characters: 9

Cancel Next

Cu

sto

m In

pu

t 1

Figure 112 - Custom Input Label - Frequency

Input Select Screen:

This screen is the only difference between the Frequency and Mag-Pickup setup. A

FLECS configuration file determines what signals are configured for each type. Use the

left and right arrow buttons to scroll through the available signals. The system will

display the “Input Q# Is In Use” (where # is equal to 1 through 8) message if the channel

is in use or is not configured for the desired signal type. The system will not enable the

Apply button until the operator selects an available input. Once the Apply button is

pressed, the system will advance to the next screen. The operator only uses the Next

button when modifying an existing Custom Frequency input.

Input Not Set

New Input

Input Q1 Is In Use

Cancel Next

1 Apply

Cu

sto

m In

pu

t 1

Figure 113 - Input Select - Frequency

80

Calibration Screen:

Enter the meter factor for the desired flow meter in Pulses per Gallon. The FLECS will

display the value in the units selected on the next screen. Press the Next button.

Calibration Point 1

Conversion Factor

100

Cancel Next

Enter the conversion

factor in

Pulses Per Gallon PPG

Cu

sto

m In

pu

t 1

Figure 114 - Custom Frequency Setup - Units Per Pulse

Units Screen:

Select the desired units and press the Done button.

Select Units

Cancel Done

Gallons

Liters

Barrels

Cubic Meters

Cu

sto

m In

pu

t 1

Figure 115 - Custom Frequency Units Per Pulse

81

After pressing the Done button the FLECS CT application will implement the new

configuration for the custom input and begin displaying the value from the sensor.

The values entered in this example result in the display shown in Figure 116. Note the

label on the left and the units on the right.

FREQ 1 BBl/m

10.00

Figure 116 - Custom Frequency Setup – Displayed Values

12.5 Custom Encoder

Begin by pressing the Encoder button in the Select Type window and press the Next

button to proceed. The system will not enable the Next button until the operator selects a

signal type.

Select Type

Current

Frequency

Encoder

Total

Mag-Pickup

Cancel Next

Cu

sto

m In

pu

t 1

Figure 117 - Select Type Encoder

82

Custom Input Label Screen:

Enter up to 13 characters for the label displayed at the top of the custom input using the

FLECS display keypad and press Next.

Custom Input Label

New Label

ENCODER 1

Remaining Characters: 4

Cancel Next

Cu

sto

m In

pu

t 1

Figure 118 - Custom Encoder Label

Input Select Screen:

Use the left and right arrow buttons to scroll through the available signals. The system

will display the “Input Q# Is In Use” (where # is equal to 1 through 8) message if the

channel is in use or is not configured for the desired signal type. The system will not

enable the Apply button until the operator selects an available input. Once the Apply

button is pressed, the system will advance to the next screen. The operator only uses the

Next button when modifying an existing Custom Encoder input.

Input Not Set

New Input

Cancel Next

7 Apply

Cu

sto

m In

pu

t 1

Figure 119 - Custom Encoder Setup - Input

83

Calibration Screen:

Enter the counts per revolution (typically 500) of the encoder and the number of feet per

revolution of the depth counter (typically 2 ft). The FLECS will display the value in the

units selected on the next screen. Press the Next button.

Calibration

Count Per Revolution

500

Cancel Next

Feet Per Revolution

2

Cu

sto

m In

pu

t 1

Figure 120 - Custom Encoder Setup - PPR & UPR

Units Screen:

Select the desired units and press the Done button.

Select Units

Cancel Done

Feet

Meters

Cu

sto

m In

pu

t 1

Figure 121 - Custom Encoder Displayed Units

84

After pressing the Done button the FLECS CT application will implement the new

configuration for the custom input and begin displaying the value from the sensor.

The values entered in this example result in the display shown in Figure 122. Note the

label on the left and the units on the right.

ENCODER 1 m/min

10.00

Figure 122 - Custon Encoder Display Value

12.6 Custom Total – Frequency or Mag-Pickup

Begin by pressing the Total button in the Select Type window and press the Next button

to proceed. The system will not enable the Next button until the operator selects a signal

type.

Select Type

Current

Frequency

Encoder

Total

Mag-Pickup

Cancel Next

Cu

sto

m In

pu

t 1

Figure 123 - Custom Total Selection

85

Custom Input Label Screen:

Enter up to 13 characters for the label displayed at the top of the custom input using the

FLECS display keypad and press Next.

Custom Input Label

New Label

TOTAL 1

Remaining Characters: 6

Cancel Next

Cu

sto

m In

pu

t 1

Figure 124 - Custom Total Label

Total Select Input Type

Select either the Frequency or the Mag-Pickup button; the system will advance to the

next screen as soon as the operator selects a button.

Select Input Type

Cancel

Frequency

Encoder

Mag-Pickup

Cu

sto

m In

pu

t 1

Figure 125 - Custom Total Input Type

86

Input Select Screen:

This screen is the only difference between the Frequency and Mag-Pickup setup. A

FLECS configuration file determines what signals are configured for each type. Use the

left and right arrow buttons to scroll through the available signals. The system will

display the “Input Q# Is In Use” (where # is equal to 1 through 8) message if the channel

is in use or is not configured for the desired signal type. The system will not enable the

Apply button until the operator selects an available input. Once the Apply button is

pressed, the system will advance to the next screen. The operator only uses the Next

button when modifying an existing Custom Frequency input.

Input Not Set

New Input

Input Q1 Is In Use

Cancel Next

1 Apply

Cu

sto

m In

pu

t 1

Figure 126 - Custom Total Input Select

Calibration Screen:

Enter the meter factor for the desired flow meter in Pulses per Gallon. The FLECS will

display the value in the units selected on the next screen. Press the Next button.

Calibration Point 1

Conversion Factor

100

Cancel Next

Enter the conversion

factor in

Pulses Per Gallon PPG

Cu

sto

m In

pu

t 1

Figure 127 – Custom Total Frequency Calibration

87

Rate Units Screen:

Select the desired units and press the Done button.

Select Units

Cancel Done

Gallons

Liters

Barrels

Cubic MetersC

usto

m In

pu

t 1

Figure 128 - Custom Total Rate Units

Totalizer Units Screen:

Select the desired units and press the Done button.

Select Totalizing Units

Done

Gallons

Liters

Barrels

Cubic Meters

Cu

sto

m In

pu

t 1

Figure 129 - Custom Total Totalizing Units

88

After pressing the Done button the FLECS CT application will implement the new

configuration for the custom input and begin displaying the value from the sensor.

The values entered in this example result in the display shown in Figure 130. Note the

labels on the left and the units on the right.

FREQ 1 BBl/m

10.00Total gal

10.00

Figure 130 - Custom Units Frequency Display

12.7 Custom Total - Encoder

Begin by pressing the Total button in the Select Type window and press the Next button

to proceed. The system will not enable the Next button until the operator selects a signal

type.

Select Type

Current

Frequency

Encoder

Total

Mag-Pickup

Cancel Next

Cu

sto

m In

pu

t 1

Figure 131 - Custom Total

89

Custom Input Label Screen:

Enter up to 13 characters for the label displayed at the top of the custom input using the

FLECS display keypad and press Next.

Custom Input Label

New Label

ENCODER 1

Remaining Characters: 4

Cancel Next

Cu

sto

m In

pu

t 1

Figure 132 - Custom Total Label

Select Signal Type

Select the Encoder button; the system will advance to the next screen as soon as the

operator selects a button.

Select Input Type

Cancel

Frequency

Encoder

Mag-Pickup

Cu

sto

m In

pu

t 1

Figure 133 - Custom Total Input Type

90

Input Select Screen:

Use the left and right arrow buttons to scroll through the available signals. The system

will display the “Input Q# Is In Use” (where # is equal to 1 through 8) message if the

channel is in use or is not configured for the desired signal type. The system will not

enable the Apply button until the operator selects an available input. Once the Apply

button is pressed, the system will advance to the next screen. The operator only uses the

Next button when modifying an existing Custom Encoder input.

Input Not Set

New Input

Input Q1 Is In Use

Cancel Next

1 Apply

Cu

sto

m In

pu

t 1

Figure 134 - Custom Total Input Select

Calibration Screen:

Enter the counts per revolution (typically 500) of the encoder and the number of feet per

revolution of the depth counter (typically 2 ft). The FLECS will display the value in the

units selected on the next screen. Press the Next button.

Calibration

Count Per Revolution

500

Cancel Next

Feet Per Revolution

2

Cu

sto

m In

pu

t 1

Figure 135 - Custom Total Encoder Calibration

91

Units Screen:

Select the desired units and press the Next button.

Select Units

Cancel Done

Feet

Meters

Cu

sto

m In

pu

t 1

Figure 136 - Custom Total Encoder Units

Totalized Units Screen:

Select the desired units and press the Done button.

Select Totalizing Units

Done

Feet

Meters

Cu

sto

m In

pu

t 1

Figure 137 - Custom Total Totalizing Units

92

After pressing the Done button the FLECS CT application will implement the new

configuration for the custom input and begin displaying the value from the sensor.

The values entered in this example result in the display shown in Figure 130. Note the

label on the left and the units on the right.

ENCODER 1 m/m

10.00Total feet

10.00

Figure 138 - Custom Total Encoder Display

12.8 Zero Custom Total

To zero a Custom Total input touch on the custom input. The Modify Custom Input

screen will be displayed. If the custom input touched on was a total there will be a button

labeled “Zero”. Press the zero button to zero the custom total.

12.9 Modify Custom Input

To modify the setup of a custom input touch on the custom input to be modified. The

Custom Input Modify screen is displayed. Press the button labeled “Modify” to modify

the existing configuration.

12.10 Disable Custom Input

To disable a custom input touch on the custom input to be disabled. The Custom Input

Modify screen is displayed. Press the button labeled “Disable” to disable the custom

input.

13 Latest Software The latest release of the FLECS CT application can be obtained from the FLECS Systems

page on HalWorld. This page can be accessed from either the PE Electronic Technicians

portal or the Coiled Tubing / HWO portal. From the links sections of the portal look for

the FLECS Systems link.

93

Table of Figures

Figure 1 - FLECS Display with Screen Highlighted 5

Figure 2 - FLECS Display with Touch-Screen Highlighted 6

Figure 3 - FLECS Display with Extended Touchable Area Highlighted 6

Figure 4 - FLECS Display with Keypad Highlighted 7

Figure 5 – Key with Primary and Shifted Function Illustrated 7

Figure 6 – Power Indicator, Illuminated 8

Figure 7 – FLECS CT Display with Constantly Visible Display Highlighted 8

Figure 8 – FLECS CT Display with Context Dependent Display Highlighted 9

Figure 9 – FLECS CT with Context Menu Button Highlighted 10

Figure 10 - Desktop Key Hint Label Illustration 11

Figure 11 - Key Hint Label Illustration 12

Figure 12 – Add Calibration Point mA 13

Figure 13 – Add Calibration Point mA – Range Bar Detail – No Existing Points 13

Figure 14 – Add Calibration Point mA – Existing Point 14

Figure 15 – Add Calibration Point mA – Entered Point Indicator 15

Figure 16 – Add Calibration Point mA– Invalid Point Entered 15

Figure 17 – Add Calibration Point Value 16

Figure 18 – Add Calibration Point Value 16

Figure 19 – Add Calibration Point Value – Entered Point Indicator 17

Figure 20 - Delete Calibration Point Confirmation 18

Figure 21 - Connection Selection - Input Not Set 19

Figure 22 - Connection Selection - Input Selected 19

Figure 23 – Weight Display 20

Figure 24 – Weight Display, Current Weight & Units Highlighted 20

Figure 25 – Weight Display – Load Limiting Status Highlighted 21

Figure 26 - Weight Display Configuration Menu 21

Figure 27 - Load Pin Setup - No Pins Configured 22

Figure 28 - Load Pin Setup - Single Pin 22

Figure 29 - Load Pin Setup - Two Pins - Pin 1 Selected 23

Figure 30 - Load Pin Setup - Two Pins - Pin 2 Selected 23

Figure 31 - Load Pin Setup - Calibration Tab 24

Figure 32 - Load Pin Setup - Calibration Tab with Points 24

Figure 33 – Load Pin Status, No Pins Configured 26

Figure 34 – Load Pin Status, One Pin Configured, Pin Input Not Configured 26

Figure 35 – Load Pin Status, One Pin Configured, Pin Signal Displayed 26

Figure 36 – Load Pin Status, Two Pins Configured, Pin Signal Displayed 26

Figure 37 – Zero Weight Confirmation - Normal 27

Figure 38 - Zero Weight Confirmation - Large Offset 27

Figure 39 - Zero Weight Confirmation - Depth Warning 28

Figure 40 - Weight Unit Selection Area 28

Figure 41 – Depth & Speed Display 29

Figure 42 – Depth & Speed Display – Depth & Units Highlighted 29

Figure 43 – Depth & Speed Display – Out of Hole 30

Figure 44 – Depth & Speed Display – In Hole 30

Figure 45 – Depth & Speed Display – No Movement 31

94

Figure 46 - Depth & Speed Display - Limit Status Area 31

Figure 47 – Depth & Speed Display Configuration Menu 31

Figure 48 - Encoder Setup - Input Tab 32

Figure 49 – Encoder Setup – Calibration Tab 33

Figure 50 – Depth & Speed Configuration – Depth Unit Buttons Highlighted 33

Figure 51 – Depth & Speed Configuration – Speed Unit Buttons Highlighted 34

Figure 52 – Depth & Speed Configuration – Zero Depth 35

Figure 53 – Depth & Speed Configuration Context Menu – Set Depth 35

Figure 54 – Set Current Depth 36

Figure 55 – Pressure Display 37

Figure 56 – Pressure Display – Tubing Pressure 38

Figure 57 – Pressure Display – Wellhead Pressure 38

Figure 58 – Pressure Display Configuration 39

Figure 59 – Pressure Display Configuration – Tubing Status 39

Figure 60 – Pressure Display Configuration – Tubing Display Unit 40

Figure 61 – Pressure Display Configuration – Zero 40

Figure 62 – Confirm Zero Pressure 41

Figure 63 – Cannot Zero Pressure – High Signal 41

Figure 64 – Cannot Zero Pressure – Low Signal 42

Figure 65 – Cannot Zero Pressure – No Signal 42

Figure 66 – Tubing Pressure Setup – Calibration Tab 43

Figure 67 – Transducer Setup - Calibration Point List 43

Figure 68 – Transducer Setup – Add Point Button 44

Figure 69 – All Limits Off 46

Figure 70 – All Limits On 46

Figure 71 – Warn State 47

Figure 72 – System Disabled State 48

Figure 73 – Tripped State 49

Figure 74 – Limiting System Tabs 53

Figure 75 – Limiting System Configuration – Output Configuration 54

Figure 76 – Limiting System Configuration - Weight Tab 54

Figure 77 – Limiting System Configuration - Weight Tab – Pull Limit 55

Figure 78 – Pull Limit Threshold 55

Figure 79 – Limiting System Configuration - Weight Tab – Snub Limit 56

Figure 80 – Snub Limit Threshold 57

Figure 81 – Limiting System Configuration - Weight Tab – Tag Limit 57

Figure 82 – Limiting System Configuration - Depth/Speed Tab 58

Figure 83 – Limiting System Configuration - Depth/Speed Tab – Pull Out Limit 58

Figure 84 – Limiting System Configuration - Depth/Speed Tab – OOH Limit 59

Figure 85 – Limiting System Configuration - Depth/Speed Tab – IH Limit 60

Figure 86 - Limit System – Test 62

Figure 87 - Limit System - Test with Tubing in Motion 63

Figure 88 - Limit System - End Test 63

Figure 89 – System Menu 64

Figure 90 – System Shutdown In Progress 65

Figure 91 – System Shutdown Complete 65

95

Figure 92 – Shutdown Did Not Complete 66

Figure 93 – System Menu – KIPS Button 66

Figure 94 – KIPS Calibration 67

Figure 95 – System Menu – Serial Setup Button 68

Figure 96 – Serial Setup 68

Figure 97 - System Menu - Set Time Button 70

Figure 98 – Set Time Menu 70

Figure 99– System Menu – Set Time Button 71

Figure 100 – System Menu – Set Time Button 71

Figure 101 - Custom Inputs with Input Numbering 74

Figure 102 - Custom 1 Touch Area Figure 103 - Custom Input Setup 74

Figure 104 - Custom Input Setup 75

Figure 105 - Custom Input Label 75

Figure 106 - Custom Analog Input 76

Figure 107 - Custom Analog Cal Point 1 76

Figure 108 - Custom Analog Cal Point 2 77

Figure 109 - Custom Analog Select Units 77

Figure 110 - Custom Analog Displayed Values 78

Figure 111 - Select Type Frequency 78

Figure 112 - Custom Input Label - Frequency 79

Figure 113 - Input Select - Frequency 79

Figure 114 - Custom Frequency Setup - Units Per Pulse 80

Figure 115 - Custom Frequency Units Per Pulse 80

Figure 116 - Custom Frequency Setup – Displayed Values 81

Figure 117 - Select Type Encoder 81

Figure 118 - Custom Encoder Label 82

Figure 119 - Custom Encoder Setup - Input 82

Figure 120 - Custom Encoder Setup - PPR & UPR 83

Figure 121 - Custom Encoder Displayed Units 83

Figure 122 - Custon Encoder Display Value 84

Figure 123 - Custom Total Selection 84

Figure 124 - Custom Total Label 85

Figure 125 - Custom Total Input Type 85

Figure 126 - Custom Total Input Select 86

Figure 127 – Custom Total Frequency Calibration 86

Figure 128 - Custom Total Rate Units 87

Figure 129 - Custom Total Totalizing Units 87

Figure 130 - Custom Units Frequency Display 88

Figure 131 - Custom Total 88

Figure 132 - Custom Total Label 89

Figure 133 - Custom Total Input Type 89

Figure 134 - Custom Total Input Select 90

Figure 135 - Custom Total Encoder Calibration 90

Figure 136 - Custom Total Encoder Units 91

Figure 137 - Custom Total Totalizing Units 91

Figure 138 - Custom Total Encoder Display 92

96