Visit our website at www.appletonelec.com or contact us at (800) 621-1506. © December 2011
260
FNES LED Series Self-Contained Emergency Lighting with Self-Test SystemZone 2 - 21 and 22
Applications• Providesadequatelightingand/orvisualindicationof
accessandexitroutesduringanevacuationinahazardousenvironment.
• CanbeinstalledinhazardousareasdesignatedasZone2,21and22.
• Typicalapplicationsincludeoilrefineries,petrochemicalplants,pulp,papermillsandsilos.
Features• Powersupply230Vac50/60Hz.• 1hourduration(emergency).• Non-maintained.• Operatesinanyposition.• Batterypack. —Escaperoutelighting:2.4V-1.5Ah(2cells-Nicd).
—Spacelighting:7.2V-2.2Ah(6cells-NiMh).• OpenandcloseusinganAllenkey(size10)ora6mmflat
screwdriver.• Connectiontoplug-interminalblockvia2x5x2.5mm2
terminals.• TwoM20clearanceholessuppliedwithonecablegland(dia.
6.5to14.5mm),oneblankingplugandtwolocknuts.• ChargeindicatorbygreenLED(lifetimeover10years).• Automaticbuilt-inself-testsystem(SATI)withmemorizationof
testsindicatedbyLEDs.• Usingamicroprocessorandaninternalclock,theunitwillcarry
outautomatictests.• Weeklytest:Lampcheckduration6seconds.• Quarterlytest:Emergencyoperationandlampcheckfor1hour.• Canberemotelycontrolledandcheckedwithoutswitching
themainsoffwithremotecontrolunitfromLegrand(CatalogNumber03901)orURA(CatalogNumber095448and095450)manufacturers.
• Theremotecontrolunitinstalledinasafeareaorinsideaflameproofboxallowsmanualignitionofalltheunits(max.300units)forvisualinspectionoftheiroperation.
• Escaperoutelighting:55lumens,0.50wattage.• Spacelighting:540lumens,0.95wattage.
Standard Materials• Body:fiberglassreinforcedpolyester• Diffuser(hingedtobody):polycarbonate• Gasket:elastomer• Fixingbrackets:zincplatedsteel,graypaintedaluminumor316
stainlesssteel• Cableglandandblankingplug:polyamide• Locknut:nickel-platedbrass
Options• Addressableversions:
—Providingtheregulatorycontroloftheemergencylightingunitsandcentralizinginformationcomingfromthoseunitsonacomputerizedmanagementsystem.
—Operatingwithoutanyspecialline,communicationbetweenunitsandthecontrolsystemisrealizedviamains-bornesignalsontheremotecontrolline.
—Capacity:onecontrolsystemfor200emergencylightingunits.—Max.capacity:1000emergencylightingunitswithboosters.
• Addressablemonitoringsoftware,pleaseconsultfactory.• Lowtemperatureapplication,pleaseconsultfactory.
Certifications and Compliances• CertificationType:FLn• Zone2 —ConformingtoATEX94/9/CE:CE0081 II3G —ATEX/IECProtection:ExnRII —TRating:T6• Zone21-22 —ConformingtoATEX94/9/CE:CE0081 II2D —ATEX/IECProtection:ExtDA21andExtDA22 —SurfaceTemperature:T167°F/T75°C• AmbientTemperature:-40°F/-40°Cto131°F/55°C• CEDeclarationofConformity:50212(Zone2-22)and50227
(Zone21)• ATEXCertificate:LCIE03ATEX6072(Zone2-22),LCIE02ATEX
6067(Zone21)• IECExCertificate:IECExLCI04.0021(Zone2-22)• OtherCertifications:GOST• IndexofProtection(solidandliquid):IP66/67• ImpactResistance(shock):IK10• Exstandards:EN/IEC60079-0;60079-15/61241-0;61241-1• Productstandards:EN/IEC60598-1;60598-2-22• EMCstandards:EN/IEC55015;61547• Otherstandards:EN/IEC60529(IP);62262(IK)
FNES LED
Zone 2 - 21 and 22 II 2 D and II 3 GD
ATEX / IECEx IP66/67 - IK10
Optimum operating temperature for battery is 23 °F/-5 °C to 86 °F/+30 °C.
LightingLighting: increased safety/fLameproof — BuLkhead
Visit our website at www.appletonelec.com or contact us at (800) 621-1506. © December 2011
261
Catalog Numbering Guide
FNES LED XX A A
Series:FNES
Zone2,21and22ATEX/IECCertified
LampType:LED
CableEntry:A-ArmoredM20U-UnarmoredM20N-Unarmored
SL-SpaceLightingE-EscapeRouteLighting
Options:A-AddressableW-WithSwitch(Automaticmainscut-off)
Unswitched Version – 1 hour duration - Non-maintained - Two M20 clearance entries
Type Power and Lamp Lumen Output Weight (kg) Volume (dm3) Pack Catalog Number
SpaceLightingLEDArray
540lm 7.2 32.3 1 FNESLEDSLU
EscapeRouteLighting 55lm 7.2 32.3 1 FNESLEDEU
Accessories
Description Catalog Number
Half Clamps Brackets - Set of Two
1-1/4"(dia.42mm)to1-1/2"(dia.49mm)
Zincplatedsteel FEHC49Z
316stainlesssteel FEHC49S
2"(dia.60mm)
Zincplatedsteel FEHC60Z
316stainlesssteel FEHC60S
M8 Ring Bolts - Set of Two
Zincplatedsteel FERBM8Z
Hinged Brackets - Set of two brackets for adjusting luminaire when wall-mounted
Aluminum(graypainted) FEHBA
316stainlesssteel FEHBS
Brackets for Surface Mounting - Set of two
Aluminum(graypainted) FESBA
316stainlesssteel FESBS
Fixing Brackets - Set of two brackets for ease of surface installation
Zincplatedsteel FEFBZ
316stainlesssteel FEFBS
FNES LED Series Self-Contained Emergency Lighting with Self-Test SystemZone 2 - 21 and 22
Zone 2 - 21 and 22 II 2 D and II 3 GD
ATEX / IECEx IP66/67 - IK10
CableEntry:A-ArmoredM20U-UnarmoredM20N-Unarmored
Series:FNES
Zone2,21and22ATEX/IECCertified
Ligh
ting
Light
ing:
incr
ease
d sa
fety
/fLa
mepr
oof
— Bu
Lkhe
ad
Visit our website at www.appletonelec.com or contact us at (800) 621-1506. © December 2011
262
FNES LED Series Self-Contained Emergency Lighting with Self-Test SystemZone 2 - 21 and 22
Zone 2 - 21 and 22 II 2 D and II 3 GD
ATEX / IECEx IP66/67 - IK10
Electrical Wiring Diagram
PE N L (B) (A)
Non-MaintainedEmergency
Lighting Unit
U
N
PE
-(B)
+(A)
Mains Remote (Optional)- +
LED Indicator
Battery not Connected or Faulty
Dimensions (in/mm)
15.8/400
31.0/785
2 x M8
8.54/217
5.71
/145
LightingLighting: increased safety/fLameproof — BuLkhead
Visit our website at www.appletonelec.com or contact us at (800) 621-1506. © December 2011
263
LED Indicator
FNES LED Series Self-Contained Emergency Lighting with Self-Test SystemZone 2 - 21 and 22
Zone 2 - 21 and 22 II 2 D and II 3 GD
ATEX / IECEx IP66/67 - IK10