gaza electricity distribution corporation ltd. technical ... a...gaza electricity distribution...
TRANSCRIPT
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Rated Voltage (Uo/U) kV 0.6/1
5 Clamp Bushing Material
Weather and UV resistant Elastomer
(EPDM)
6 Clamp Body MaterialHot Galvanized
Steel
7Clamp Butterfly End Nut Material (Die Cast Wing Nut)
Hot Galvanized Steel
8 DesignSuspension
Clamp for Four Core Cable
9Phase Conductor Cross Sectional Area mm2 50
10 Clamp Breaking Load KN 7.5
11 Bundle Diameter mm 26 - 30
12 Hole Diameter mm 25
13 Attached DrawingDrawing No.
ABS_50
Technical Guarantees No. ABS_50
Suspension Clamp for ABC Aluminium Cable 4*50 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards
4 Description
Buckle to hold wrapped band
for cable bundling
5 Construction
with teeth and ears provide for
maximum clamping strength
6 Material201 Stainless
Steel
7 Width mm 12.7
8 Attached DrawingDrawing No
STB_254
Tenderer’s Signature : ……………………..… Date: ………………………………
Technical Guarantees No. STB_254
Stainless Steel Ear-Lokt Buckle
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards
4 Descriptionfor cable bundling
5 Material201 Stainless
Steel
6 Width mm 12.7
7 Thickness mm 0.76
8 Length m 30
9 Attached DrawingDrawing No
STB_204
Tenderer’s Signature : ……………………..… Date: ………………………………
Technical Guarantees No. STB_204
Stainless Steel Band
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards ANSI
4 Material Porcelain
5 Creepage distance mm 57
6 Dimensions as Drawing
7 Mechnical failing load kN 89
8 Transverse holes (Slots) each 2
a) Dry kv 35
b) Wet kv 18
10 Attached DrawingDrawing No
SSI_01
Technical Guarantees No. SSI_01
Stay Strain Insulator
Tenderer’s Signature : ……………………..… Date: ………………………………
Power frequency flashover voltage
9
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Design Standards BS
4 Test Standards IEC
5.1 a) Shackle Insulator Porcelain
5.2 b) U - BracketHot-Dip
Galvanized Steel
5.3 c) NailHot-Dip
Galvanized Steel
5.4 d) Buckle Copper Plated
5.4e) Steel Bolt with Nut and Washers (for Connectting with the Pole)
Hot Galvanized 5/8"
6 Dimensions As Drawing
7 Insulator Mechanical Failing Load KN 13
8 Bracket Ultimate Tensile Strength KN 20
9.1 a) Dry kV 25
9.2 b) Wet kV 12
10 Accessories U - Bracket ,
Nail & Buckle , Steel Bolt
11 Attached DrawingDrawing No
SPI_01
Technical Guarantees No. SPI_01
Low Tension Shackle Porcelain Insulator for Earth line
5- Material
9- Insulator Power Frequency withstand Voltage (1min)
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
H D d d1 R76 89 48 17.5 10
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Description Stay Rod
4 Rod and Accessories MaterialHot Dip
Galvanized
5 Rod Diameter mm 16
6 Rod Total Length mm 1400
a) first SideWelded with Steel Angle
b) Another Side
made into a round
eye with best quality welding
8 Round eye Inner Diameter mm 25
9 Steel Angle Length mm 150
10 Steel Angle Size mm 40x40x4
11 Another Dimensions as drawing
12 Attached DrawingDrawing No.
SE_16
Technical Guarantees No. SE_16
Stay Electrode, 16 mm
Tenderer’s Signature : ……………………..… Date: ………………………………
7
Stay Rod Construction
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Material Concrete B300
4 Dimensions as Drawing
5 Attached DrawingDrawing No
SCB_300
Technical Guarantees No. SCB_300
Stay Concrete Base
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Design StandardsIEC 61109 , IEC 60815
4 Nominal System Voltage kV 24
5 Type Pin Type
6 Insulating Material Composite
Polymer
7 Housing Silicon
8 Metal PartsHot Dip
Galvanized
9 Number of Sheds
10 Total High mm
11 Shed Diameter mm
12 Min. Creepage Distance mm 1050
13 Cantilever Strength KN 12.5
14 Weight Kg
15.1 a) Dry kV 125
15.2 b) Wet kV 95
15.3 c) Impulse +VE & -VE kV
Technical Guarantees No. PPYI_1050
22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 1050 mm
15- Power Frequency withstand Voltage (1 min)
Studies and Documentation Branch
1/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
Technical Guarantees No. PPYI_1050
22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 1050 mm
16.1 a) Power Frequency (Dry) kV 140
16.2 b )Power Frequency (Wet) kV 110
16.3 c) Impulse +VE & -VE kV r+220/-245
17.1 Pin Diameter (stud) mm 25
17.2 Pin AccessoriesNut and Washers
17.3 Pin Toothed Part Length mm 120
18 Attached DrawingDrawing No. PPYI_1050
16- Flashover Voltage
17- Fittings
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
2/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Design StandardsIEC 61109 , IEC 60815
4 Nominal System Voltage kV 24
5 Type Pin Type
6 Insulating Material Composite
Polymer
7 Housing Silicon
8 Metal PartsHot Dip
Galvanized
9 Number of Sheds
10 Total High mm
11 Shed Diameter mm
12 Min. Creepage Distance mm 800
13 Cantilever Strength KN 12.5
14 Weight Kg
15.1 a) Dry kV 125
15.2 b) Wet kV 95
15.3 c) Impulse +VE & -VE kV
Technical Guarantees No. PPYI_800
22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 800 mm
15- Power Frequency withstand Voltage (1 min)
Studies and Documentation Branch
1/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
Technical Guarantees No. PPYI_800
22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 800 mm
16.1 a) Power Frequency (Dry) kV 140
16.2 b )Power Frequency (Wet) kV 110
16.3 c) Impulse +VE & -VE kV r+220/-245
17.1 Pin Diameter (stud) mm 25
17.2 Pin AccessoriesNut and Washers
17.3 Pin Toothed Part Length mm 120
18 Attached DrawingDrawing No.
PPYI_800
16- Flashover Voltage
17- Fittings
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
2/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Design StandardsIEC 61109 ,
IEC 60815 , BS 3288
4 Nominal System Voltage kV 24
5 Insulating Material Composite
Polymer
6 Housing Silicon
7 Metal PartsHot Dip
Galvanized
8 Number of Sheds
9 Total Length mm
10 Shed Diameter mm
11 Min. Creepage Distance mm 1050
12 Min. Mechanical Failing Load kN 70
13 Socket and Ball Size mm Ф16
14 Weight Kg
15.1 a)Dry kV 130
15.2 b)Wet kV 120
Technical Guarantees No. PDI_1050
22kv Overhead Line Tension Polymeric Composite Insulator , with Ball and Socket with Creepage Distance 1050 mm
15- Power Frequency withstand Voltage ( 1min)
Studies and Documentation Branch
1/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
Technical Guarantees No. PDI_1050
22kv Overhead Line Tension Polymeric Composite Insulator , with Ball and Socket with Creepage Distance 1050 mm
15.3 c)Positive Dry Impulse +VE kV 235
15.4 d)Negative Dry Impulse -VE kV 320
16Power Frequency Flashover Voltage (Wet)
kV 130
17 Attached DrawingDrawing No.
PDI_1050
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
2/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-2
4 Description Copper Parallel Groove Clamps
a) Body High Strength Copper Alloy (Cu Ni 2 Si)
b) BoltsHigh Strength
Copper Alloy, F-60, DIN 933
c) NutsCopper, DIN
934
d) Conical WashersSteel, DIN
6796, Copper Plated
6 Surface Uncoated
7Copper Conductor Cross Sectional Area mm2 6-50
8 Conductor Diameter mm 2.7-9
9 Bolts (No. x Length) 2 x 30
10 Bolt Torque Moments 7Nm
11 Attached DrawingDrawing No.
NTC_650
Technical Guarantees No. NTC_650
Non-Tension Clamp 35 mm2 Copper
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
BS 2874 -CZ 112
4 Description Split-Bolt
Connector with hexagonal head
5 Material Brass (CuZn)
6 SurfaceUncoated or
Tin-Plated
7 Conductor Diameter mm 5.3-8.12
8 Attached DrawingDrawing No.
NTC_635
Technical Guarantees No. NTC_635
Non-Tension Clamp 6/35 mm2 Copper
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross-Section
sq. mm
Conductor Diameter Ø mm
Dimensions mm
Min Max A C D
35 5.30 8.12 31 18.00 23.30
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-2
4 Description Copper Parallel Groove Clamps
a) Body High Strength Copper Alloy (Cu Ni 2 Si)
b) BoltsHigh Strength
Copper Alloy, F-60, DIN 933
c) NutsCopper, DIN
934
d) Conical WashersSteel, DIN
6796, Copper Plated
6 Surface Uncoated
7Copper Conductor Cross Sectional Area mm2 16-150
8 Conductor Diameter mm 4.5-15.7
9 Bolts (No. x Length) 2 x 50
10 Bolt Torque Moments 39Nm
11 Attached DrawingDrawing No.
NTC_150
Technical Guarantees No. NTC_150
Non-Tension Clamp 16/150 mm2 Copper
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Dimensions Dimension mm.
Bolts Cross Section
mm2 Ø Diameter
mm L B D
16-150 4.5-15.7 52 50 27 2XM10x50
Torque Moments:
M8 : 39Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-2
4 Description Copper Parallel Groove Clamps
a) Body High Strength Copper Alloy (Cu Ni 2 Si)
b) BoltsHigh Strength
Copper Alloy, F-60, DIN 933
c) NutsCopper, DIN
934
d) Conical WashersSteel, DIN
6796, Copper Plated
6 Surface Uncoated
7Copper Conductor Cross Sectional Area mm2 10-95
8 Conductor Diameter mm 3.5-12.5
9 Bolts (No. x Length) 2 x 45
10 Bolt Torque Moments 20Nm
11 Attached DrawingDrawing No.
NTC_95
Technical Guarantees No. NTC_95
Non-Tension Clamp 10/95 mm2 Copper
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Dimensions Dimension mm.
Bolts Cross Section
mm2 Ø Diameter
mm L B D
10-95 3.5-12.5 42.5 42 22.5 2xM8x45
Torque Moments:
M8 : 20Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-2
4 Description Copper Parallel Groove Clamps
a) Body High Strength Copper Alloy (Cu Ni 2 Si)
b) BoltsHigh Strength
Copper Alloy, F-60, DIN 933
c) NutsCopper, DIN
934
d) Conical WashersSteel, DIN
6796, Copper Plated
6 Surface Uncoated
7Copper Conductor Cross Sectional Area mm2 6-70
8 Conductor Diameter mm 2.7-10.5
9 Bolts (No. x Length) 2 x 40
10 Bolt Torque Moments 20Nm
11 Attached DrawingDrawing No.
NTC_70
Technical Guarantees No. NTC_70
Non-Tension Clamp 6/70 mm2 Copper
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Dimensions Dimension mm.
Bolts Cross Section
mm2 Ø Diameter
mm L B D
6-70 2.7-10.5 36 40 20 2xM8x40
Torque Moments:
M8 : 20Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48201, DIN 48204
4 Description Bimetallic
Parallel Groove Clamp
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1) with
hot forged bimetallic sheet, for
copper tap-off
b) BoltsSteel 8.8, DIN 933, hot-dip galvanized
c) NutsSteel 8, DIN 934 hot-dip galvanized
d) Conical Washers
According to DIN 6796 corrosion-protected
Technical Guarantees No. NTAC_300
Non-Tension Clamp 35-300/35-240 mm2 Aluminium/Copper
5
Material
Studies and Documentation Branch
1/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
Technical Guarantees No. NTAC_300
Non-Tension Clamp 35-300/35-240 mm2 Aluminium/Copper
6ACSR or Aluminium Conductor Diameter
mm 7.5-23
7 Copper Conductor Diameter mm 7.5-20.3
8 Bolts (No. x Length) 3 X 70
9 Bolt Torque Moments 46Nm
10 Attached DrawingDrawing No. NTAC_300
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
2/2
Conductor Cross Section sq. mm
Conductor Diameter Ø mm
Dimension mm. Bolts
Al ACSR Cu Al Cu L B D
35-300 35/6-265/35 35-240 7.5-23.0 7.5-20.3 105 65 33 3xm10x70
Torque Moments: M10 : 46Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48201, DIN 48204
4 Description Bimetallic
Parallel Groove Clamp
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1) with
hot forged bimetallic sheet, for
copper tap-off
b) BoltsSteel 8.8, DIN 933, hot-dip galvanized
c) NutsSteel 8, DIN 934 hot-dip galvanized
d) Conical Washers
According to DIN 6796 corrosion-protected
Technical Guarantees No. NTAC_12
Non-Tension Clamp 16-120/10-95 mm2 Aluminium/Copper
5
Material
Studies and Documentation Branch
1/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
Technical Guarantees No. NTAC_12
Non-Tension Clamp 16-120/10-95 mm2 Aluminium/Copper
6ACSR or Aluminium Conductor Diameter
mm 5.1-14
7 Copper Conductor Diameter mm 3.5-12.5
8 Bolts (No. x Length) 2 x 45
9 Bolt Torque Moments 23Nm
10 Attached DrawingDrawing No.
NTAC_12
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
2/2
Conductor Cross Section sq. mm
Conductor Diameter Ø mm
Dimension mm. Bolts
Al ACSR Cu Al Cu L B D
16-120 16/2.5-95/15 10-50 5.1-14.0 3.5-12.5 47.7 48.0 28.0 2xM8x45
Torque Moments: M8 : 23Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-1
4 Description Aluminium
Parallel Groove Clamps
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1)
b) BoltsDIN 933, steel
8.8, hot-dip galvanized
c) Conical Washers DIN 6796, corrosion-protected
7Aluminium or/and ACSR Conductor Cross Sectional Area mm2
35/240 (for AL) & 35/6-210/35
(for ACSR)
8 Conductor Diameter mm 7.5-20.3
9 Bolts (No. x Length) 3 x 70
10 Bolt Torque Moments 46Nm
11 Attached DrawingDrawing No.
NTA_240
Technical Guarantees No. NTA_240
Non-Tension Clamp 35/240 mm2 Aluminium
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross sq. mm Conductor
DiameterØmm
Dimension mm. Bolts
Al ACSR L B D
35-240 35/6-210/35 7.5-20.3 67 100 35 3xM10x70
Torque Moments: M10 : 46Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-1
4 Description Aluminium
Parallel Groove Clamps
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1)
b) BoltsDIN 933, steel
8.8, hot-dip galvanized
c) Conical Washers DIN 6796, corrosion-protected
7Aluminium or/and ACSR Conductor Cross Sectional Area mm2
16/120 (for AL) & 16/2.5 -95/15
(for ACSR)
8 Conductor Diameter mm 5.1-14
9 Bolts (No. x Length) 2 x 50
10 Bolt Torque Moments 23Nm
11 Attached DrawingDrawing No.
NTA_120
Technical Guarantees No. NTA_120
Non-Tension Clamp 16/120 mm2 Aluminium
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Torque Moments: M8 : 23Nm
Conductor Cross sq. mm Conductor
DiameterØmm
Dimension mm. Bolts
Al ACSR L B D
16-120 16/2.5-95/15 5.1-14.0 45 50 25 2xM8x50
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48072-1
4 Description Aluminium
Parallel Groove Clamps
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1)
b) BoltsDIN 933, steel
8.8, hot-dip galvanized
c) Conical Washers DIN 6796, corrosion-protected
7Aluminium or/and ACSR Conductor Cross Sectional Area mm2
16/70 (for AL) & 16/2.5-70/12
(for ACSR)
8 Conductor Diameter mm 5.1-11.7
9 Bolts (No. x Length) 2 x 40
10 Bolt Torque Moments 23Nm
11 Attached DrawingDrawing No.
NTA_70
Technical Guarantees No. NTA_70
Non-Tension Clamp 16/70 mm2 Aluminium
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Torque Moments: M8 : 23Nm
Conductor Cross sq. mm Conductor
DiameterØmm
Dimension mm. Bolts
Al ACSR L B D
16-70 16/2.5-70/12 5.1-11.7 36 40 20 2xM8x40
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 57295
4 Description
Copper Non-Tension
Compression Joint
5 MaterialElectrolytic
Copper
6 Surface Uncoated
7 Conductor Diameter mm 7.5
8 Hole Diameter mm 8.2
9 Joint Length mm 50
10 Dimensions As Drawing
11 Attached DrawingDrawing No.
NJ35
Technical Guarantees No. NJ_35
22Kv Copper Non Tension Compression Joint for Conductor 35 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Connecting Dimensions Standards
DIN 48064
4 Material Standards DIN 1692
5 Surface Standards DIN 50976
6 MaterialMalleable cast
iron GTS-45
7 SurfaceHot-dip
Galvanized
8 Nominal Load KN 110
9 Construction and Dimensions mm As Drawing
10 Attached DrawingDrawing No.
HMC_01
Technical Guarantees No. HMC_01
Strain Thimbles with Socket (Half Moon Clamp)
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
IEC243 , IEC251
4 Description
Environment friendly flame retardant heat shrinkable tube for Low Voltage
Cable
5 MaterialHigh Quality
Polymer
6 Cable Outer Diameter 32
7 Dielectric strength KV/mm ≥20
8 Tensile strength Mpa ≥13
9 Elongation at breek % ≥300
Technical Guarantees No. HIS_240
Shrinck Insulator for Lugs 240 mm2 (Color)
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Design StandardsBS137& IEC60120
4 Test Standards IEC
5 Insulator material Glass
6 Min. Mechanical Failing Load kN 80
7Min. Mechanical Residual Strength
kN 42
8 Weight Kg
9 Creepage Distance mm 320
10 Diameter mm 255
11 Ball Size mm Ф16
12 Dimensions as Drawing
13.1 a)Dry kV 70
13.2 b)Wet kV 40
13.3 c)Positive Dry Impulse +VE kV 100
13.4 d)Negative Dry Impulse -VE kV 103
Technical Guarantees No. GDI_320
22kv Overhead Line Toughened Tension Glass Disk Insulator with Ball and Socket
13- Power Frequency withstand Voltage ( 1min)
Studies and Documentation Branch
1/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
Technical Guarantees No. GDI_320
22kv Overhead Line Toughened Tension Glass Disk Insulator with Ball and Socket
14 Min Puncture Voltage in Oil kV 130
15Phosphorous Bronze Security Clip (BS 3288 Part 4)
W-CLIP
16 Accessories Hot Galvanized Ball and Socket
17 Attached DrawingDrawing No.
GDI_320
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
2/2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Connecting Dimensions Standards
DIN 48064
4 Material Standards DIN 1692
5 Surface Standards DIN 50976
6 MaterialMalleable cast
iron GTS-45
7 SurfaceHot-dip
Galvanized
8 Nominal Load KN 160
9 Construction and Dimensions mm As Drawing
10 Attached DrawingDrawing No.
FBH_16
Technical Guarantees No. FBH_16
Fork Ball Hook 16mm (SOCKET EYES-TYPE-A)
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
KEMA standard 83-C
4 Material Cooper
5 CoatingCopper shrink
jacket
6 Length mm
7 Diameter mm 15
Technical Guarantees No. ERJ_15
Earth Rod Joint 15 mm Diameter
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Material Brass
5 Design
Suitable for earth rod 15
mm Dia to used for connection between Rod
and cable
6 Earth Rod Diameter mm 15
7 Copper Cable Diameter mm 10.7
8 Attached DrawingDrawing No.
ERC_15
Technical Guarantees No. ERC_15
Earth Rod Connection Clamp
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
KEMA standard 83-C
4 Material Steel St-60
5 CoatingCopper shrink
jacket
6 Length mm 1500
7 Diameter mm 15
Technical Guarantees No. ER_15
Earth Rod 15 mm Diameter , 1.5 m
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation
No Description Unit RequirementsOffered
Data
Notes, Remarks , Ref to
Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Reference Manufacturing Standards
4 Description Elastomeric End
Cap for ABC Cable 150 mm2
5 MaterialThermoplastic ,
UV Resistant
6 Voltage Test mm
6 kv Under_water
According NFC 33020
7 Recommended Cross Section mm2 150
8Nominal Cable Diameter over Insulation (Min. - Max)
mm 17.6 - 18
9 Cap Diameter mm 19
10 Attached Drawing Drawing No. EC
Technical Guarantees No. EC_150
Sealing Cap for ABC Cable 150 mm2 (Elastomeric End Cap)
Tenderer’s Signature : ……………………..… Date: ………………………………
1/1
Gaza Electricity Distribution Corporation
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Reference Manufacturing Standards
4 Description
Elastomeric End Cap for
ABC Cable 95 mm2
5 MaterialThermoplastic ,
UV Resistant
6 Voltage Test mm
6 kv Under_water
According NFC 33020
7 Recommended Cross Section mm2 95
8Nominal Cable Diameter over Insulation (Min. - Max)
mm 15.5-16
9 Cap Diameter mm 16.5
10 Attached Drawing Drawing No. EC
Technical Guarantees No. EC_95
Sealing Cap for ABC Cable 95 mm2 (Elastomeric End Cap)
Tenderer’s Signature : ……………………..… Date: ………………………………
1/1
Gaza Electricity Distribution Corporation
No Description Unit RequirementsOffered
Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Reference Manufacturing Standards
4 Description
Elastomeric End Cap for
ABC Cable 50 mm2
5 MaterialThermoplastic ,
UV Resistant
6 Voltage Test mm
6 kv Under_water
According NFC 33020
7 Recommended Cross Section mm2 50
8Nominal Cable Diameter over Insulation (Min. - Max)
mm 11.5-12
9 Cap Diameter mm 12.5
10 Attached Drawing Drawing No. EC
Technical Guarantees No. EC_50
Sealing Cap for ABC Cable 50 mm2 (Elastomeric End Cap)
Tenderer’s Signature : ……………………..… Date: ………………………………
1/1
Gaza Electricity Distribution Corporation
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Reference Manufacturing Standards
4 Description Elastomeric End
Cap for ABC Cable 25 mm2
5 MaterialThermoplastic ,
UV Resistant
6 Voltage Test mm
6 kv Under_water
According NFC 33020
7 Recommended Cross Section mm2 25
8Nominal Cable Diameter over Insulation (Min. - Max)
mm 8.3-8.7
9 Cap Diameter mm 9.5
10 Attached Drawing Drawing No. EC
Technical Guarantees No. EC_25
Sealing Cap for ABC Cable 25 mm2 (Elastomeric End Cap)
Tenderer’s Signature : ……………………..… Date: ………………………………
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards
4 MaterialSolid Copper Coated Steel
5 Tie TypeTop groove of
insulators
6 Conductor Type Copper
7 Conductor Diameter (Min. - Max.) 7.4 - 14.3
8 Length mm 1500
Tenderer’s Signature : ……………………..… Date: ………………………………
Technical Guarantees No. DTCT_01
Distribution Ties Performed , Copper (Top)
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards
4 MaterialSolid Copper Coated Steel
5 Tie TypeSide groove of
insulators
6 Conductor Type Copper
7 Conductor Diameter (Min. - Max.) 7.4 - 14.3
8 Length mm 1500
Tenderer’s Signature : ……………………..… Date: ………………………………
Technical Guarantees No. DTCS_01
Distribution Ties Performed , Copper (Side)
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards
4 MaterialSolid Aluminum
Coated Steel
5 Tie TypeTop groove of
insulators
6 Conductor Type ACSR
7 Conductor Diameter (Min. - Max.) 9.5 - 17.2
8 Length mm 1500
Tenderer’s Signature : ……………………..… Date: ………………………………
Technical Guarantees No. DTAT_01
Distribution Ties Performed , AL (Top)
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered DataNotes, Remarks
, Ref to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Standards
4 MaterialSolid Aluminum
Coated Steel
5 Tie TypeSide groove of
insulators
6 Conductor Type ACSR
7 Conductor Diameter (Min. - Max.) 9.5 - 17.2
8 Length mm 1500
Tenderer’s Signature : ……………………..… Date: ………………………………
Technical Guarantees No. DTAS_01
Distribution Ties Performed , AL (Side)
Studies and Documentation Branch1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48201
4 Description Copper Dead
End Clamp
a) BodyHigh strength copper alloy
(CuNi2Si)
b) BoltsDIN 933, high
strength copper alloy (F60)
c) Nuts
DIN 934, copper. Option
to stainless steel
6 Surface Uncoated
7 Conductor Cross Sectional Area mm2 25-35
8 Conductor Diameter mm 6.3-7.5
9 Bolts (No. x Length) 2 x 30
10 Bolt Torque Moments 20Nm
11 Attached DrawingDrawing No.
DEC_25
Technical Guarantees No. DEC_25
Dead End Clamp , 25/35 mm2 Copper
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross Section
sq. mm
Conductor Diameter
Ømm
Dimension mm. Bolts
L B D
25-35 6.3-7.5 47 47 30 2xM8x30
Torque Moments:
M8 : 20Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48201, DIN 48204
4 Description Aluminium Dead End
Clamp
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1)
b) BoltsSteel, 8.8,DIN
933 hot-dip galvanized
c) NutsSteel, 8, DIN 934 hot-dip galvanized
7Aluminium or/and ACSR Conductor Cross Sectional Area mm2
95/120 (for AL) & 95/15 (for
ACSR)
8 Conductor Diameter mm 12.5-13.6
9 Bolts (No. x Length) 2 x 45
10 Bolt Torque Moments 80Nm
11 Attached DrawingDrawing No.
DEA_120
Technical Guarantees No. DEA_120
Dead End Clamp , 95/120 mm2 Aluminium
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 48201, DIN 48204
4 Description Aluminium Dead End
Clamp
a) Body
High strength, corrosion-resistant,
aluminium alloy (AlMgSi1)
b) BoltsSteel, 8.8,DIN
933 hot-dip galvanized
c) NutsSteel, 8, DIN 934 hot-dip galvanized
7Aluminium or/and ACSR Conductor Cross Sectional Area mm2
50/70 (for AL) & 50/8-70/12 (for ACSR)
8 Conductor Diameter mm 9-11.7
9 Bolts (No. x Length) 2 x 35
10 Bolt Torque Moments 46Nm
11 Attached DrawingDrawing No.
DEA_70
Technical Guarantees No. DEA_70
Dead End Clamp , 50/70 mm2 Aluminium
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross-Section sq. mm
Conductor Diameter
Ømm
Dimension mm. Bolts
Al ACSR L B D
50-70 50/8-70/12 9.0-11.7 60 64 42 2xM10x35
Torque Moments: M10 : 46Nm
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 46235
4 Description
Copper Compression
Lug with 13mm Hole
5 MaterialE-Cu, DIN
40500/2, F-25
6 Surface Tin-plated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 240
9 Conductor Diameter mm 20.2
10 No of Compression 5
11 Dimensions as Drawing
12 Barrel
Capped and Filled with Grease to
Avoid Oxidation
13 Attached DrawingDrawing No.
CLC_240
Technical Guarantees No. CLC_240
Compression Terminal Lug with 13 mm Hole for 240 mm2 Copper Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
mm
Dimensions
d1 l b d2
240 20.2 21.5 92 42 13
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 46235
4 Description
Copper Compression
Lug with 13mm Hole
5 MaterialE-Cu, DIN
40500/2, F-25
6 Surface Tin-plated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 120
9 Conductor Diameter mm 14
10 No of Compression 4
11 Dimensions as Drawing
12 Attached DrawingDrawing No.
CLC_120
Technical Guarantees No. CLC_120
Compression Terminal Lug with 13 mm Hole for 120 mm2 Copper Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
mm
Dimensions
d1 l b d2
120 14 15.5 70 32 13
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 46235
4 Description
Copper Compression
Lug with 13mm Hole
5 MaterialE-Cu, DIN
40500/2, F-25
6 Surface Tin-plated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 95
9 Conductor Diameter mm 12.6
10 No of Compression 4
11 Dimensions as Drawing
12 Attached DrawingDrawing No.
CLC_95
Technical Guarantees No. CLC_95
Compression Terminal Lug with 13 mm Hole for 95 mm2 Copper Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
mm
Dimensions
d1 l b d2
95 12.6 13.5 65 28 13
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 46235
4 Description
Copper Compression
Lug with 13mm Hole
5 MaterialE-Cu, DIN
40500/2, F-25
6 Surface Tin-plated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 70
9 Conductor Diameter mm 10.7
10 No of Compression 3
11 Dimensions as Drawing
12 Attached DrawingDrawing No.
CLC_70
Technical Guarantees No. CLC_70
Compression Terminal Lug with 13 mm Hole for 70 mm2 Copper Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
mm
Dimensions
d1 l b d2
70 10.7 11.5 55 24 13
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 46235
4 Description
Copper Compression
Lug with 13mm Hole
5 MaterialE-Cu, DIN
40500/2, F-25
6 Surface Tin-plated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 35
9 Conductor Diameter mm 7.5
10 No of Compression 2
11 Dimensions as Drawing
12 Attached DrawingDrawing No.
CLC_35
Technical Guarantees No. CLC_35
Compression Terminal Lug with 13 mm Hole for 35 mm2 Copper Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
mm
Dimensions
d1 l b d2
35 7.5 8 42 21 13
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Description Bimetallic
Compression Lug
a) Barrel Part
Aluminium of Purity Equal to or Greater than
99.5%
b) Palm PartElectrolytic
Copper
6 Surface Uncoated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 400
9 Hole Diameter mm 13
10 Barrel
Capped and Filled with Grease to
Avoid Oxidation
11 Attached DrawingDrawing No. CLAC_400
Technical Guarantees No. CLAC_400
Aluminium / Copper Compression Terminal Lug
with 13 mm Hole for 400 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
Ø mm
Dimensions mm.
No. of compressionsd1 d2 b L2 L1
400 24.5 26 13.0 36 85 117.5 6-3
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Description Bimetallic
Compression Lug
a) Barrel Part
Aluminium of Purity Equal to or Greater than
99.5%
b) Palm PartElectrolytic
Copper
6 Surface Uncoated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 185
9 Hole Diameter mm 13
10 Barrel
Capped and Filled with Grease to
Avoid Oxidation
11 Attached DrawingDrawing No. CLAC_185
Technical Guarantees No. CLAC_185
Aluminium / Copper Compression Terminal Lug
with 13 mm Hole for 185 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
Ø mm
Dimensions mm.
No. of compressionsd1 d2 b L2 L1
185 17 17 13.0 35 66 97.5 6-3
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Description Bimetallic
Compression Lug
a) Barrel Part
Aluminium of Purity Equal to or Greater than
99.5%
b) Palm PartElectrolytic
Copper
6 Surface Uncoated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 150
9 Hole Diameter mm 13
10 Barrel
Capped and Filled with Grease to
Avoid Oxidation
11 Attached DrawingDrawing No. CLAC_150
Technical Guarantees No. CLAC_150
Aluminium / Copper Compression Terminal Lug
with 13 mm Hole for 150 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
Ø mm
Dimensions mm.
No. of compressionsd1 d2 b L2 L1
150 15.5 15.5 13.0 30 66 100 6-3
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Description Bimetallic
Compression Lug
a) Barrel Part
Aluminium of Purity Equal to or Greater than
99.5%
b) Palm PartElectrolytic
Copper
6 Surface Uncoated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 120
9 Hole Diameter mm 13
10 Barrel
Capped and Filled with Grease to
Avoid Oxidation
11 Attached DrawingDrawing No. CLAC_120
Technical Guarantees No. CLAC_120
Aluminium / Copper Compression Terminal Lug
with 13 mm Hole for 120 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
Ø mm
Dimensions mm.
No. of compressionsd1 d2 b L2 L1
120 13.7 13.7 13.0 30 66 100 6-3
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Description Bimetallic
Compression Lug
a) Barrel Part
Aluminium of Purity Equal to or Greater than
99.5%
b) Palm PartElectrolytic
Copper
6 Surface Uncoated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 95
9 Hole Diameter mm 13
10 Barrel
Capped and Filled with Grease to
Avoid Oxidation
11 Attached DrawingDrawing No.
CLAC_95
Technical Guarantees No. CLAC_95
Aluminium / Copper Compression Terminal Lug
with 13 mm Hole for 95 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
Ø mm
Dimensions mm.
No. of compressionsd1 d2 b L2 L1
95 12.5 12.5 13.0 25 49 77.5 5-2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Description Bimetallic
Compression Lug
a) Barrel Part
Aluminium of Purity Equal to or Greater than
99.5%
b) Palm PartElectrolytic
Copper
6 Surface Uncoated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 70
9 Hole Diameter mm 13
10 Barrel
Capped and Filled with Grease to
Avoid Oxidation
11 Attached DrawingDrawing No.
CLAC_70
Technical Guarantees No. CLAC_70
Aluminium / Copper Compression Terminal Lug
with 13 mm Hole for 70 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
5
Material
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
Ø mm
Dimensions mm.
No. of compressionsd1 d2 b L2 L1
70 10.5 11.0 13.0 25 49 77.5 5-2
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
DIN 46329
4 Description
Aluminium Compression
Lug with 13mm Hole
5 Material Al 99.5
6 Surface Tin-plated
7 TypeCompression, Longitudinally
Sealed
8 Conductor Cross Section mm2 70
9 Conductor Diameter mm 10.5
10 Dimensions as Drawing
11 Barrel
Capped and Filled with Grease to
Avoid Oxidation
12 Attached DrawingDrawing No.
CLA_70
Technical Guarantees No. CLA_70
Compression Terminal Lug with 13 mm Hole for 70 mm2 Aluminium Conductor
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Conductor Cross
Section mm2
Conductor Diameter
mm
Dimensions
d1 l b d2
70 10.5 11.5 83 28 13
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Description Cable Clamps
4 Cable Outer Diameter mm 36-53
5 No. of Cables 1
6 MaterialPolyamide, Glass Fiber Reinforced
7 Tensile strength N/mm2 120
8 Flexural Strength N/mm2 200
9 Thermal Expansion 0.02% / 1°C
10 Fire ResistanceUL 94 , VDE 0304, Part 3
11 Accessories
2 Hot Galvanized Bolt with nuts and
washers
12 Dimensions As Drawing
13 Attached DrawingDrawing No.
CC_52
Technical Guarantees No. CC_52
Clamp to Holder the Cable (Single , Large )
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Cable Out Side Diameter (D)
Ø mm
No. of Cables
Dimensions mm Weight Kg. L B I Ød H
36-53 1 108 60 75 12.4 40-57 .17
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3 Description Cable Clamps
4 Cable Outer Diameter mm 26-38
5 No. of Cables 1
6 MaterialPolyamide, Glass Fiber Reinforced
7 Tensile strength N/mm2 120
8 Flexural Strength N/mm2 200
9 Thermal Expansion 0.02% / 1°C
10 Fire ResistanceUL 94 , VDE 0304, Part 3
11 Accessories
2 Hot Galvanized Bolt with nuts and
washers
12 Dimensions As Drawing
13 Attached DrawingDrawing No.
CC_51
Technical Guarantees No. CC_51
Clamp to Holder the Cable (Single , Small )
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Cable Out Side Diameter (D)
Ø mm
No. of Cables
Dimensions mm Weight Kg. L B I Ød H
26-38 1 92 60 60 12.4 32-44 .11
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Rated Voltage (Uo/U) kV 0.6/1
5Clamp Wedges and Thimble Material
Weather and UV resistant
Glass Reinforced
Polymer
6 Clamp Body Material (Straps)Corrosion Resistant
Aluminium Alloy
7 Stay wire
Galvanized steel stranded
wire with insulation
wear_resistant Saddle
8 Designto Tension Messenger Cable only
9Messenger Conductor Cross Sectional Area mm2 95
10 Clamp Breaking Load KN
11 Attached DrawingDrawing No.
ABT_150
Technical Guarantees No. ABT_150
Tension Clamp for ABC Aluminium Cable 3*150+1*95+2*25 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
VDE0211
4 Rated Voltage (Uo/U) kV 0.6/1
5 Wedges Material
weather and UVResistant Glass
Fibre Reinforced
Polymer
6 All ferrous partsHot Galvanized
Steel
7 Design
to anchor self supporting 4
Cores LV-ABC lines
8 Constructionwith movable
arm
9 Conductor Cross Sectional Area mm2 4x95
10 Clamp Breaking Load KN 43
11 Attached DrawingDrawing No.
ABT_95
Technical Guarantees No. ABT_95
Tension Clamp for ABC Aluminium Cable 4*95 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
VDE0211
4 Rated Voltage (Uo/U) kV 0.6/1
5 Wedges Material
weather and UVResistant Glass
Fibre Reinforced
Polymer
6 All ferrous partsHot Galvanized
Steel
7 Design
to anchor self supporting 4
Cores LV-ABC lines
8 Constructionwith movable
arm
9 Conductor Cross Sectional Area mm2 4x50
10 Clamp Breaking Load KN 30
11 Attached DrawingDrawing No.
ABT_50
Technical Guarantees No. ABT_50
Tension Clamp for ABC Aluminium Cable 4*50 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Rated Voltage (Uo/U) kV 0.6/1
5 Clamp and Movable Link Material
Weather and UV resistant Glass Fibre Reinforced
Polymer
6 Design
Suspension Clamp for
Messenger Cable only
7Phase Conductor Cross Sectional Area mm2 150
8Messenger Conductor Cross Sectional Area mm2 95
9 Clamp Breaking Load KN 30
10 Bundle Diameter mm 15 - 17.5
11 Hole Diameter mm 22
12 Attached DrawingDrawing No.
ABS_150
Technical Guarantees No. ABS_150
Suspension Clamp for ABC Aluminium Cable 3*150+1*95+2*25 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1
Gaza Electricity Distribution Corporation LTD.
No Description Unit Requirements Offered Data
Notes, Remarks , Ref
to Documentation
Evaluation Committee Comments
1 Name of Manufacturer
2 Country of Origin
3Reference Manufacturing Standards
4 Rated Voltage (Uo/U) kV 0.6/1
5 Clamp Bushing Material
Weather and UV resistant Elastomer
(EPDM)
6 Clamp Body MaterialHot Galvanized
Steel
7Clamp Butterfly End Nut Material (Die Cast Wing Nut)
Hot Galvanized Steel
8 DesignSuspension
Clamp for Four Core Cable
9Phase Conductor Cross Sectional Area mm2 95
10 Clamp Breaking Load KN 7.5
11 Bundle Diameter mm 36 - 40
12 Hole Diameter mm 25
13 Attached DrawingDrawing No.
ABS_95
Technical Guarantees No. ABS_95
Suspension Clamp for ABC Aluminium Cable 4*95 mm2
Tenderer’s Signature : ……………………..… Date: ………………………………
Studies and Documentation Branch
1/1