generator capability verification
TRANSCRIPT
Generator Capability VerificationDaniel Leonard – Peregrine Engineering ConsultingSteve Barnes – Peregrine Engineering Consulting
Brian Hallett – ReliabilityFirstTechnical Talk with RF
June 21, 2021
Forward Together • ReliabilityFirst
Today’s Guest Speakers
2
Steven A. Barnes (BSEE Gannon University, MSEPE RPI) worked with Mitsubishi Electric Power Products, Inc. and GE Energy Consulting prior to joining Peregrine Engineering Consulting where he is a Technical Director.
Daniel J. Leonard, PE (BSEE, MSEE Clarkson University) worked with GE Energy Consulting prior to forming Peregrine Engineering Consulting where he is Business Owner and Chief Engineer.
Forward Together • ReliabilityFirst
Flow of Data from Interconnection > Test > Models > Studies
Differences between Unit Test and Capability Verification
Testing Requirements and Specifications
Overview of past Assist Visits and Questions regarding MOD-025
Forward Together
Agenda
3
Forward Together • ReliabilityFirst
Present the interconnectedness between the following:• Interconnection Agreements/Studies (FAC-001, FAC-002)• Development of Transmission Planning Cases (MOD-032)• Verification and Reporting of Real and Reactive Power Capability (MOD-025)
Share insight from Peregrine Engineering Consulting:• Benefits of good generator testing• Lessons Learned from the field• Specifications of Engineering Analysis
Objectives
4
Forward Together • ReliabilityFirst
Flow of Data from Interconnection > Test > Models > Studies
5
Forward Together • ReliabilityFirst
Consistent Data
6
Forward Together • ReliabilityFirst
Impact Project Timing
7
Forward Together • ReliabilityFirst
RF Maturity Model
8
Forward Together • ReliabilityFirst
Management Practices – Closer Look
EXID – Establishing key players and defining specifications
ACM – Change management and data integrity
VER – Ensure capabilities meet requirements and specifications
VAL – Ensure applications function as designed in environment9
Forward Together • ReliabilityFirst
Driving Improvement
Continuous improvement using Management Practices can mature processes beyond what is required in the NERC Standards
For example, through continuously improving specifications:• Identify whether Engineering Analysis has been completed
‒ No. Communication that this is raw test data. Consider additional analysis may be needed to determine true capability. Compare test results to interconnection studies/agreements.
‒ Yes. Consider in-depth analysis has been completed. This information could supersede FAC-001, FAC-002 info.
• Validate generator dispatch in interconnection-wide cases‒ Is the modeled dynamic reactive reserves/capability adequate in studies?‒ Units mostly likely should not be dispatches at 75% Q-max‒ May require analysis of load power factor and cap bank settings
10
Forward Together • ReliabilityFirst
Differences between Unit Test and Capability Verification
11
Forward Together • ReliabilityFirst
NATF Guide
Google “NATF Generator Reactive”• The distinction between the “Generator” reactive
power capability and the “Generating Unit” reactive power capability
• Tests performed under a single set of conditions may not be adequate to provide the full picture of a unit’s reactive power capability
• Does not provide a “one size fits all” approach to methods for determining “generating unit reactive power capability”
12
Forward Together • ReliabilityFirst
NATF Guide
13
Forward Together • ReliabilityFirst
Testing Requirements and Specifications
14
Forward Together • ReliabilityFirst
Lessons Learned – A Few Best Practices
Unit Tests• Identify Protection and Control Coordination Issues• Identify Issues with HMI screens, capability curves (or lack thereof)• Identify Measurement Errors
Plant Tests• Coordinate Real and Reactive Load among available units• If staged: can be more time efficient• If operational: ensure that all points are monitored in plant historian for
subsequent NERC MOD-025-2 Attachment 2 forms (or similar)
15
Forward Together • ReliabilityFirst
“Field” Example 1 – The Case for Pre-Work
Mis-coordinated Loss of Excitation Protection and Minimum Excitation Limiter
Site Test Reports Indicated Issue Had Been Noted, and Protection had been “Tested”
16
Strong Value in Independent Confirmation of Settings…and
Full Test
Forward Together • ReliabilityFirst
“Field” Example 2 – Even with Pre-Work…
Eastern Interconnect CCPP
Pre-Test PRC-019-1 studies indicated V/Hz limiter and protection at 105%. Note: customer left as-found due to OEM warranty.
Tester limited voltages to < 104.5%
GSU PT tolerances raised issue, led to ST GSU trip => Block trip.
17
Event uncovered latent cal/tolerance issues – during TEST vs. during Peak
Forward Together • ReliabilityFirst
Flow of Information
MOD-025-2 Attachment 2• Used to document test environment• Critical for engineering analysis, benchmark generator model• Variations in Other Regional Forms
WECC -- Excitation quantities documented• Additional information beyond standard
PJM -- AUX XFMR ratios, tap position not required• Format appropriate at BES modeling level
• TP data requests may be tailored to meet modeling needs
18
Forward Together • ReliabilityFirst
NERC MOD-025-2 Attachment 2
19
Forward Together • ReliabilityFirst
Identification of Limitations During Testing –Adapted NERC MOD-025-2 Attachment 2
20
Min-Lead Min-Lag Max-Lead Max-Lag
03/10/21 03/10/21 03/10/21 03/10/21
15:24 15:44 9:19 12:13
15:24 15:44 9:19 13:13
UEL 105% Vterm UEL 105% Vterm
64 65 51 62
36 35 38 31
67 66 52 63
98 96 106 106
44.2 44.0 45.6 45.3
Point Meas/Calc Min-Lead Min-Lag Max-Lead Max-Lag
M 17.33 18.90 17.46 18.90
M 110.0 111.0 232.0 227.0
M -76.7 85.6 -56.7 91.2
M 17.33 18.90 17.46 18.90
M 7.0 7.2 8.6 7.8
M 4.3 5.2 5.2 5.5
M 528.4 527.9 528.6 528.8
C 102.8 103.6 222.7 218.5
C -89.7 71.7 -89.1 57.7
-76.7 85.6 -56.7 91.2
4.3 5.2 5.2 5.5
-81.0 80.4 -61.9 85.7
110.0 111.0 232.0 227.0
7.0 7.2 8.6 7.8
103.0 103.8 223.4 219.2
--- --- --- ---
Net Real Power Capability (*MW)
GSU losses (only required if verification measurements are taken on the high side of the GSU - MVAr)
Comments
Note that during the maximum load testing, the CTG was in Peak Limit Control Mode.
Note that during the minimum load testing, the CTG was at its emmissions limited minimum output (110 MW).
Gross Reactive Power Capability (*MVAr)
Aux Reactive Power (*MVAr)
Net Reactive Power Capability (*MVAr)
Gross Real Power Capability (*MW)
Aux Real Power (*MW)
B(Aux)
Voltage (kV)
Real Power (MW)
Reactive Power (MVAR)
F(POI)
Voltage (kV)
Real Power (MW)
Reactive Power (MVAR)
Turbine Inlet Temperature (°F)
Cold Gas Temp (°F)
Hydrogen Pressure (PSIG)
Signal
A(Gen)
Voltage (kV)
Real Power (MW)
Reactive Power (MVAR)
Date
Start Time
End Time
Limit Reached
Ambient Temperature (°F)
Humidity (%):
Aux voltage ratio: 18 / 6.9 / 4.16 Aux tap setting: 18 / 6.9 / 4.16
Test
Unit: UNIT Sched voltage (kV): 500 kV to 550 kV
GSU voltage ratio: 18.0 / 525.0 GSU tap setting: 18.0 / 525.0
Company: CUSTOMER Reported by: Steven A. Barnes
Plant: SITE Report date: 04/09/21
NERC MOD-025 (Attachment 2) Reporting Form
Forward Together • ReliabilityFirst
Overview of Past Assist Visits and Questions Regarding MOD-025
21
Forward Together • ReliabilityFirst
New Questions
Questions from TPS and GS:• Required capability testing specific to wind and solar units
‒ What tests are required?‒ What tests are not required? ‒ Proper evidence to prove compliance
• NERC Reliability Guideline‒ Power Plant Model Verification for Inverter-Based Resources‒ Specific chapter called “MOD-025-2 Capability Testing”
• MRO Standard Application Guide ‒ MOD-025-2 I4 Dispersed Power Producing Resources
• NERC Standard One-Stop-Shop22
Forward Together • ReliabilityFirst
New Questions
Demonstration of how to use the Attachment 2 form• What information is expected• What information is optional
Details for Staged verification
Details for Operational verification • Identify what data could be used for testing
23
Forward Together • ReliabilityFirst
New Questions
The first verification for each applicable facility under this standard must be a staged test. Now that this isn’t our first verification, do we still need to do a staged test?
24
Forward Together • ReliabilityFirst
New Questions
The NERC PPMVTF put out a White Paper back in July 2019 “White Paper: Implementation of NERC Standard MOD-025-2” which essentially said that the data acquired during MOD-025-2 testing should NOT be used to represent the actual capability of the machine in power system models. Does RF have any recommendations as a result? • The purpose of the standard is that accurate Real and Reactive Power
capabilities are available for planning models.‒ White Paper points to capabilities being established in Interconnection Studies/Agreements‒ Tests look for errors, issues, damage that may impact unit performance less than capability‒ Corrective actions and/or additional analysis may be needed‒ Capability should not vary greatly between model series.
25
Forward Together • ReliabilityFirst
Past Assist Visits
Assist Visit Topic: MOD-025; Compliance; Attachment 2• Requestor Message: Data was collected on the TP form that differs from the
MOD‐025 standard and its Attachment 2 format. Below is what was identified as needing further review due to the format differences. ‒ GSU Tap Position is written in GSU step up format instead of an actual position. Ex 13.8 /
138.6 KV‒ Aux Transformer Tap Position is not on the TP form, therefore is not indicated.‒ Aux Transformer Voltage Ratio is not on the TP form, therefore is not indicated.
• Requestor Question: Should this be self-reported as a violation?• RF Guidance: Recommendation to complete MOD-025 Attachment 2 to
document test conditions and results, then populate applicable TP forms. This specific scenario did not require a self-report. In an on-site audit, this scenario would likely result in an Area of Concern.
26
Forward Together • ReliabilityFirst
Past Assist Visits
Assist Visit Topic: MOD-025 testing with modified Under-Excitation Limit (UEL)
• Requestor Message: I have a question regarding MOD‐025 testing we performed after we upgraded our Excitation systems on all 3 of our units. During the testing we ran our 3 units at the same time so that while we were testing a specific unit we could use the other 2 units to assist with maintaining our voltage schedule. While doing this we had the OEM (Siemens) temporarily remove a software limit for the UEL of the units to help with the balancing of our line voltage.
• Requestor Question: Do we need to re-test and self-report?• RF Guidance: In the future, review test plan for specific requirements. The UEL
is required to be in-place for the specific unit being tested.
27
Forward Together • ReliabilityFirst
Forward Together
28
Forward Together • ReliabilityFirst
Forward Together
Please continue to utilize the Assist Visit program• RF Staff coordination with OPCTF/CCTF• Reach-out if there are questions when developing test plans,
as opposed to after-the-fact
Collaborative participation on MOD-025 revision• Reach out to RF Staff if you have comments/concerns
Continued analysis and coordination between Engineering & System Performance (ESP) and Entity Engagement (EE)
29
Forward Together • ReliabilityFirst
Questions & AnswersForward Together ReliabilityFirst
30