Page 1: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

GESTRA Steam Systems

NRG 16-4Installation Instructions 818596-00Level Electrode NRG 16-4

Page 2: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Contents

Page

Important Notes

Usage for the intended purpose...............................................................................................................4Safety note..............................................................................................................................................4Danger note ............................................................................................................................................4ATEX (Atmosphères Explosibles)..............................................................................................................4

Explanatory Notes

Scope of supply.......................................................................................................................................5Description..............................................................................................................................................5Function..................................................................................................................................................5System components................................................................................................................................5Design ....................................................................................................................................................5

Technical Data

NRG 16-4................................................................................................................................................6Corrosion resistance................................................................................................................................7Sizing......................................................................................................................................................7Name plate .............................................................................................................................................7Dimensions .............................................................................................................................................8Key .........................................................................................................................................................9

Functional Elements

NRG 16-4................................................................................................................................................9Key .........................................................................................................................................................9

Installation

Cutting electrode tip to length ...............................................................................................................10Mounting electrode ...............................................................................................................................10Tools.....................................................................................................................................................11Examples of Installation.........................................................................................................................12Key .......................................................................................................................................................13

Wiring

Terminal box .........................................................................................................................................14Wiring diagram......................................................................................................................................15Tools.....................................................................................................................................................15

Commissioning

Check wiring .........................................................................................................................................15Apply mains voltage ..............................................................................................................................15

2

Page 3: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Contents

Page

Malfunctions

Fault finding list for troubleshooting ...................................................................................................... 16

Decommissioning

Danger note.......................................................................................................................................... 17Disposal ............................................................................................................................................... 17

3

Page 4: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

4

Important Notes

Usage for the intended purpose

The level electrode NRG 16-4 is exclusively designed for detecting and signalling levels in liquids with a minimum electrical conductivity.

The equipment must only be used within the admissible pressure and temperature ratings.

Any type of use differing from the usage described above must be considered as improper. The resulting risk will have to be borne by the user alone. The manufacturer hereby expressly rejects any claims for any damage resulting from improper usage.

Safety note

The equipment must only be installed and commissioned by qualified and competent staff.

Retrofitting and maintenance work must only be performed by qualified staff who - through adequate train-ing - have achieved a recognised level of competence.

For installation, removal, commissioning and operation of the equipment every person who works with the equipment must have read and understood the complete installation manual. Furthermore, responsibilities must have been defined clearly and unambiguously and must be adhered to.

Usage of the equipment for the intended purpose includes compliance with the rules and notes in these installation instructions for installation, removal, commissioning and operation.

The operating company must ensure that, whenever the equipment is being operated, it is in perfect condition.

Working methods that jeopardise safety must not be used!

Danger note

When loosening the level electrode steam or hot water might escape. This presents the dan-ger of severe scalds to the whole body.

It is essential not to mount or dismantle the electrode unless the boiler pressure is verified to be zero!

The level electrode becomes hot during operation. Touching the hot equipment presents the risk of severe burns to hands and arms. All installation, removal and maintenance work must only be performed when the equipment is cold.

ATEX (Atmosphères Explosibles )

The equipment is a simple item of electrical equipment according to DIN EN 50020 section 5.4. According to the European Directive 94/9 /EC the equipment must be equipped with approved Zener barriers if used in potentially explosive areas.

Applicable in Ex zones 1, 2 (1999/ 92/EC). The equipment does not bear an Ex marking. The suitability of the Zener barriers is certified in a separate document.

Danger

Page 5: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

5

Explanatory Notes

Scope of supply

■ 1 Level electrode type NRG 16-4

■ 1 Joint ring 17x 21 form D to DIN 7603, made from 1.4301, bright annealed

■ 1 Installation manual

Description

The level electrode NRG 16-4 is designed for detecting and signalling levels in liquids with a minimum electrical conductivity.

Depending on the type of level switch used the electrode can detect the highest or lowest (max./min.) liquid level.

The level electrode NRG 16-4 can be used in conjunction with level switches NRS 1-1, 1-2, 1-3 and 1-5 as part of a water level control, high level alarm or water level limiting system (without SMART function) in steam boilers and pressurised hot water plants.

Function

For the correct functioning of the level electrode NRG 16-4 together with level switch NRS 1-... a minimum electrical conductivity of 0.5 µS/cm at 25°C of the water is required.

The switching signal is triggered off as soon as the electrode tip submerges or is exposed.The electrode tip is simply cut to length to give the required switching level.

System components

Level switch NRS 1-1, Level switch NRS 1-2, Level switch NRS 1-3, Level switch NRS 1-5,

Design

NRG 16-4: Electrode with screwed connection 3/ 8" BSP, ISO 228-1.

Page 6: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

6

Technical Data

NRG 16-4

Type approval no. TÜV. WR/WB. 03-302

Service pressure 32 barg at 238°C

Connection Screwed 3/8" BSP, ISO 228-1

Materials Screw-in body: 1.4571, CrNiMoTi17122Electrode tip: 1.4571, CrNiMoTi17122Electrode insulation: PTFETerminal box and connector: Plastic

Electrode tip Lengths supplied: 500, 1000, 1500 mmDiameter: 5 mm

Sensitivity (at 25°C) > 0.5 µS/cm (depending on level switch)

Wiring Four-pole connector with screw terminals, cable strain relief and cable gland PG 11

Protection IP 65 to EN 60529

Ambient temperature at terminal box Max. 70°C

Weight Approx. 0.5 kg

Page 7: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Technical Data – continued –

7

Corrosion resistance

If the level electrode NRG 16-4 is used for its intended purpose, its safety is not impaired by corrosion.

Sizing

The housing must not be subjected to sharp increases in pressure. Welds and flanges are designed to with-stand dynamic loading (bending and alternative stress). The dimensional allowances and additives for cor-rosion reflect the latest state of technology.

Name plate

TÜV . WR / WB . 03-30232 bar (464psi)238°C (460°F)T amb = 70°C (158 °F)

Betriebsanleitung beachtenSee installation instructionsVoir instructions de montage

GESTRA AG Münchener Straße 77 D-28215 Bremen

PmaxTmax

/3 8

Equipment designation

Pressure/ temperature rangeManufacturer

Pressure rating, thread type, materialnumber, protection

Page 8: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Technical Data – continued –

8

Dimensions

70

190

Leng

th s

upp

lied

50

A. F. 22

A

B

C

0.5

Screwed 3/8" BSP,

Ø 23

Fig. 1 Fig. 2

D30

Ra

12.5

Ra 3.2

Page 9: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

9

Functional Elements

NRG 16-4

Key

Thermal insulation

Seating surface

Joint ring 17x 21 form D to DIN 7603 , made from 1.4301, bright annealed

Electrode screwed to 3/8" BSP, ISO 228-1

Screw M4

Cover

Upper part of the terminal box

Connecting plate

Insulating plate

Contact plate of level electrode

Cable strain relief

Cable gland M16 (PG 11)

Fig. 3

E

F

G

I

H

J

K

L

MAX 70 °C

MAX 95 %

%

IP 65

A

B

C

D

E

F

G

H

I

J

K

L

Page 10: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

10

Installation

Cutting electrode tip to length

1. Carefully determine the required length of the electrode tip in accordance with the level-dependent switchpoint (the length should be measured from the gasket face of the screwed connection). In steam boilers operating at full load arching of the water level may occur. This phenomenon should be taken into account when determining the length of the electrode tip.

2. Cut the electrode tip to length using a bolt cutter or a metal cutting saw.

3. Deburr the face of electrode tip end.

4. Strip off 50 mm of PTFE insulation from the end of the electrode tip (see Fig. 1). Make sure that the re-maining insulation is at least 30 mm long, measured from the lower edge of the screwed connection.

Mounting electrode

In steam or (pressurised) hot water boilers the level electrode can be installed vertically or with an inclina-tion of 45°.

1. Check seating surfaces of threads or mounting flange provided on vessel or boiler standpipe (see Fig.1 and Fig.2). If necessary rework the surfaces according to the specifications indicated in the drawing.

2. Place supplied joint ring onto the seating surface of the level electrode.

3. Apply a light smear of silicone grease to the electrode thread.

4. Screw electrode into threads or flange provided on vessel (see Fig.2) and tighten with a 22 mm open-end spanner. The torque required when cold is 63 Nm.

■ The seating surfaces and threads on the vessel and mounting flange must be accurately machined.

■ Do not bend the electrode tip when cutting.

■ Do not subject electrode to physical shocks.

■ Use only the supplied ring joint 17 x21 form D to DIN 7603, made from 1.4301, bright an-nealed!

■ Do not insulate the threads with hemp or PTFE tape!

■ Do not lag the electrode body above the hexagonal part.

■ Make sure that there is an air gap of > 14 mm around the electrode rod. Note that the air distance between the electrode rod and earth (flange, vessel wall) must not be less than 14mm.

■ Be sure that the electrode insulation is at least 30 mm long.

■ The specified torques must be strictly observed.

B

C B

Attention

Page 11: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Installation – continued –

11

Mounting electrode – continued –

Observe TÜV (German Technical Supervisory Association) regulations when using the level electrode in steam boilers or (pressurised) hot water plants.

■ For the approval of the boiler standpipe the relevant local and national regulations must be observed.

■ Several examples of installation are given on page 12.

■ The angle of installation of the electrode must not exceed 45° and the length of the elec-trode rod is limited to 500mm!

■ If installed outdoors the level electrode must be equipped with a GESTRA weather pro-tection cover.

Tools

■ Open-end spanner 22 mm A. F.

■ Bolt cutter or metal cutting saw

■ Flat file, medium cut

Note

Page 12: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

12

Examples of Installation

4

3/8"BSP3/8"BSP

12

3

5

7

8

11

DN50

12

3

Ø20

20

4

5

6

9

<90°

Ø20

>10

8

3/8"BSP

DN50

12

3

Ø20

20

5

6

9

<90°

Ø 20

>10

<15

00

Fig. 4 Fig. 5

3/8"BSP

1

DN20

DN20

DN20

4

5

9

>10

>20

9

<90°

Ø20

>10

3/4"BSP

DN100

24.5 24.5

<15

00

4

Ø20

20

10 10

Fig. 7Fig. 6

4

8

12

>88.9

Page 13: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Key

Flange PN 40, DN 50 to DIN 2501-1 Flange PN 40, DN 100 to DIN 2501-1

For the approval of the boiler standpipe with connecting flange the relevant regulations must be considered

Provide vent hole as close to the boiler wall as possible!

High water (HW)

Electrode rod d = 5 mm

Protection tube > DN 80

Protection tube > DN 100

Electrode distance >14 mm

Low water NW

Reducer DIN 2616-2, K88.9x 3.2-42.4x 2.6 W

Reducer DIN 2616-2, K114.3x 3.6 -48.3 x2.9 W

Centre distance of connecting flanges

1

2

3

4

5

6

7

8

9

10

11

12

13

Page 14: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

14

Wiring

Terminal box

Use screened cable type I–Y (St) Y2x 2x0.8mm² or LIYCY 4x 0.5mm² for wiring.

1. Unscrew screw . Fig.3

2. Remove terminal box from level electrode, leaving the insulating rubber plate on the contact plate .

3. Remove cover .

4. Press connecting plate out of the upper part of the terminal box .

The electrode terminal can be turned in steps of 90°.

5. Detach cable gland and cable strain relief from the upper part of the terminal box .

6. Run cable through cable gland and upper part of the terminal box and wire the terminal of the connecting plate according to the wiring diagram (see Fig. 8).

7. Press connecting plate into the upper part of the terminal box and align the cable.

8. Fix cable with cable strain relief and cable gland firmly into position.

9. Replace cover and insert screw .

10.Put upper part of the terminal box onto the level electrode and fix it with screw .

If several level electrodes are to be installed in one steam boiler or vessel we recommend labelling the terminal box with the electrode type.

E

I

J

F

H G

L K G

L G

H

H G

K L

F E

E

Page 15: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

Wiring – continued –

15

Wiring diagram

Key

Level switch NRS...

For wiring of level switch see installation instructions NRS ...

Electrode tip

Tools

■ Screwdriver for slotted screws, size 2.5, completely insulated according to DIN VDE 0680-1

■ Crimping pliers for end sleeves

■ Wire stripper

Commissioning

Check wiring

Check that the level electrode NRG 16-4 and the associated level switch are connected in accordance with the wiring diagram (see Fig. 8).

Apply mains voltage

Apply mains voltage to the level switch.

3

Fig. 8

1

2

3

1

2

3

Page 16: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

16

Malfunctions

Fault finding list for troubleshooting

Level electrode immersed - no function

Fault: Mains voltage is not applied to the level switch.

Remedy: Switch on mains voltage. Connect electrode according to wiring diagram.

Fault: The electrode body does not have earth connection to the boiler.

Remedy: Clean seating surfaces and screw in the equipment together with the supplied joint ring 17x 21, form D to DIN 7603 (made from 1.4301), bright annealed. Do not insulate level elec-trode with hemp or PTFE tape!

Level electrode exposed - no function

Fault: The internal insulation of the electrode rod is damaged.

Remedy: Replace level electrode.

Fault: The electrode tip has earth contact.

Remedy: Check and, if necessary, change position of installation.

Fault: The vent hole in the protection tube does not exist, is obstructed or flooded.

Remedy: Check protection tube and, if necessary, provide vent hole.

For more information see the Installation Instructions of the level switch.

If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country.

Page 17: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

17

Decommissioning

Danger note

Risk of severe burns and scalds to the whole body! Before installing the level electrode make sure that the vessel or the external pot are depressurised (0 bar) and cooled down to room temperature (20°C).

Disposal

Dismantle the level electrode and separate the waste materials, using the specifications in the table "Ma-terials" as a reference. Electronic component parts such as the circuit board must be disposed of sepa-rately! For the disposal of the level electrode observe the pertinent legal regulations concerning waste disposal.

Danger

Page 18: NRG 16-4 - Flowservepreview.flowserve.com/files/Files/Literature/ProductLiterature/... · 5 Explanatory Notes Scope of supply 1 Level electrode type NRG 16-4 1 Joint ring 17x21 form

818596-00/905 agt ©2005 GESTRA AG Bremen Printed in Germany

www.gestra.de

GESTRA AG

Postfach 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Telefon +49 (0) 421 35 03 -0 Telefax +49 (0) 421 35 03-393E-Mail [email protected] Internet www.gestra.de

España

GESTRA ESPAÑOLA S.A.Luis Cabrera, 86-88E-28002 MadridTel. 00 34 91 / 51 52 032Fax 00 34 91 / 41 36 747; 51 52 036E-mail: [email protected]

Great Britain

Flowserve Flow Control (UK) Ltd.Burrel Road, Haywards HeathWest Sussex RH 16 1TLTel. 00 44 14 44 / 31 44 00Fax 00 44 14 44 / 31 45 57E-mail: [email protected]

Italia

Flowserve S.p.A.Flow Control DivisionVia Prealpi, 30 I-20032 Cormano (MI)Tel. 00 39 02 / 66 32 51Fax 00 39 02 / 66 32 55 60E-mail: [email protected]

Portugal

Flowserve Portuguesa, Lda.Av. Dr. Antunes Guimarães, 1159Porto 4100-082Tel. 0 03 51 22 / 6 19 87 70Fax 0 03 51 22 / 6 10 75 75E-mail: [email protected]

Poland

GESTRA POLONIA Spolka z.o.o.UI. Schuberta 104PL - 80-172 GdanskTel. 00 48 58 /306 10-02 od 10Fax 00 48 58 /306 33 00E-mail: [email protected]

USA

Flowserve DALCO Steam Products2601 Grassland DriveLouisville, KY 40299Tel. 00 15 02 / 4 95 01 54, 4 95 17 88Fax 00 15 02 / 4 95 16 08E-mail: [email protected]