ORDERING SPECIFICATION 00 22-11-2017 First Submission Sanjeev Kunal Satyam Rev. No. Date Description Prepared Checked Approved Title On Load Tap Changer Product Code SFPSZ-100000/200TH Indent No. 14108 Doc No. ACC.20010.OLTC Page No. 1 of 4 R2.TBEAEI/PDD-F-10/2015 ON LOAD TAP CHANGER TRANSFORMER DATA RATED POWER (MVA) OVERLOADING 100 110% overloading continuous, IS 2026 Part 7 RATED VOLTAGE (kV) NO. OF PHASE FREQUENCY (Hz) TRANSFORMER TYPE 220/66/11 3 50 Power Transformer TAPPING RANGE TAPPING LOCATION +5% to -15 % in 1.25% variation in each step Neutral End of HV Winding TEST VOLTAGES Operating and Test Voltages Max. Operating Voltage (kV) One Minute PF Voltage (kVrms) Impulse (kVp) Winding front end 231 395 950 OLTC 123 230 550 Voltage Stress in kV during High Voltage Transformer Test One Minute PF Voltage (kVrms) Impulse (kVp) Across Fine Tap Winding a 82 350 Across One Step a0 30 150 Fine Tap Winding between Phases b -- -- Across Coarse & Fine Tap Winding c1 -- -- Coarse & Fine Tap Winding between Phases c1 -- -- Across Coarse Tap Winding d -- -- SERVICE Generation Network Constant Induction o Furnace o Electrolysis o Variable induction Notes : 1) Tie-in-Resistor is not required as per Easun-MR confirmation vide e-mail TAP WINDING CONNECTION Figure Attached Below Potential Connection of Tap winding Only in case of coarse/fine tap winding

Upload: vuongkhanh

Post on 22-Jun-2018

250 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

ORDERING SPECIFICATION

00 22-11-2017 First Submission Sanjeev Kunal Satyam

Rev. No. Date

Description Prepared

Checked

Approved

Title On Load Tap Changer Product Code SFPSZ-100000/200TH

Indent No. 14108

Doc No. ACC.20010.OLTC .

Page No. 1 of 4

R2.TBEAEI/PDD-F-10/2015

ON LOAD TAP CHANGER

TRANSFORMER DATA

RATED POWER (MVA) OVERLOADING

100 110% overloading continuous, IS 2026 Part 7

RATED VOLTAGE (kV) NO. OF PHASE FREQUENCY (Hz) TRANSFORMER TYPE

220/66/11 3 50 Power Transformer

TAPPING RANGE TAPPING LOCATION

+5% to -15 % in 1.25% variation in each step Neutral End of HV Winding

TEST VOLTAGES

Operating and Test

Voltages

Max. Operating Voltage (kV) One Minute PF Voltage

(kVrms)

Impulse (kVp)

Winding front end 231 395 950

OLTC 123 230 550

Voltage Stress in kV during High Voltage Transformer Test One Minute PF Voltage

(kVrms)

Impulse (kVp)

Across Fine Tap Winding a 82 350

Across One Step a0 30 150

Fine Tap Winding between

Phases

b -- --

Across Coarse & Fine Tap

Winding

c1 -- --

Coarse & Fine Tap Winding

between Phases

c1 -- --

Across Coarse Tap Winding d -- --

SERVICE Generation Network Constant Induction

o Furnace o Electrolysis o Variable induction

Notes :

1) Tie-in-Resistor is not required as per Easun-MR confirmation vide e-mail

TAP WINDING CONNECTION

F Figure Attached Below

Potential Connection of Tap

winding

Only in case of coarse/fine

tap winding

Page 2: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

ORDERING SPECIFICATION

00 22-11-2017 First Submission Sanjeev Kunal Satyam

Rev. No. Date

Description Prepared

Checked

Approved

Title On Load Tap Changer Product Code SFPSZ-100000/200TH

Indent No. 14108

Doc No. ACC.20010.OLTC .

Page No. 2 of 4

R2.TBEAEI/PDD-F-10/2015

Winding arrangement MV-HV-TV-LV The recovery voltage without Tie

in measures between changeover

selector contacts Is

__________kV. Supplier to

furnish the recovery voltage

calculations for tie in resistor,

enclosed the following:

a. Winding connection diagram

b. Capacitance of tap winding to

earth

c. Capacitance of tap winding to

its adjacent HV/other winding

or winding parts

Value of stray impedance

between coarse and fine

tap winding:

X=_________Ohms

Capacitance of tap winding to

earth (Pico Farad)

LV-TAP: 2001 pF

Capacitance of tap winding to

its adjacent HV/other winding

or winding parts (Pico Farad)

TAP-COMMON: 4660 pF

ON LOAD TAP CHANGER DATA

OLTC type Poles Max.

rated

through

current

connection

(Y/D)

Voltage

Class

(voltage

to ground)

Tap

selector

size

Basic

connection

diagram

operating

positions

Type of

connection

(Linear/

coarse-

fine/

reversing)

Bell

mounting

facility

required

Yes/No

Tie-in

resistors

required

Yes/No

potential

switch

required

Yes/No

Step voltage in

the phase

Ust 1587.71 V

if variable

Ust max__---____

Ust min ___---___

M III 500 Y 123 C 10.19.3W 17 Reversing Yes No No Max. Tapping

current

Imax 308.74 A

DESIGNATION OF OPERATING POSITIONS

Max. No. of effective turns Mid position(s) Min. No. of effective turns “Raise” means control towards

Position: 1 Position: 9a, 9b, 9c Position: 17 Position: 17

MOTOR DRIVE UNIT

Motor Circuit Heater Circuit Control Circuit Dial Switch Details

Motor Drive

Unit Type

Supply

Voltage

(V)

Position

3~N, 3~

Rated

Frequency

Supply

Voltage

(V)

DC /

AC

Voltage

(volts)

DC / AC Potentiometer

contact range

Ohms

No. of

Additional

Dial Switch

required

Make

before/

make after

break

MA-2

415 V 3~N 50 Hz 240 V AC 110 V AC 16 X 1K

ohms

Refer

schematic

drawing

Make

before

break

DRIVE SHAFT DETAILS

Page 3: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

ORDERING SPECIFICATION

00 22-11-2017 First Submission Sanjeev Kunal Satyam

Rev. No. Date

Description Prepared

Checked

Approved

Title On Load Tap Changer Product Code SFPSZ-100000/200TH

Indent No. 14108

Doc No. ACC.20010.OLTC .

Page No. 3 of 4

R2.TBEAEI/PDD-F-10/2015

a. Horizontal Drive shaft dimension

Refer Attached Drawing

b. Vertical Drive shaft dimension

c. Suction Arrangement (for D type)

d. Drive shaft arrangement (refer our drawing)

e. Head variant (for M type)

f. Swiveling range of gear unit (for M type)

LIST OF ADDITIONAL FEATURES

Provisions required in the DM suitable for RTCC

(Please fill in) Control schematic drawing will be furnished later

Control provision required (for reference)

OTHER DETAILS

Oil Surge Relay Required Yes

Pressure Relief Valve Yes

Paint shade 631 of IS:5 PU

Important: Provision required for mounting PT-100 sensor for OLTC temperature indication

Notes:

1. Dimension drawings of tap changer and type test reports shall be submitted for approval. 2. OLTC shall be suitable for bell mounting & VPD drying. 3. One No. oil surge relay type RS 2001 shall be included per pole. 4. Tie in resistors and / or Potential Switch, if required, shall be included and shall be mounted on a cylinder fitted

below the selector switch. Drawings and 3D model of the same shall be submitted with the offer. Total length of the tap changer after assembly of Tie-in-resistor and /or potential switch shall be clearly marked in the drawing.

5. Degree of protection for motor drive unit IP 55 as per IS 2147. 6. Overloading conditions cl. 2.3.2 of IEC 542 / IS 8478- As per IS 6600. 7. Provision for earthing at Tap changer head and motor drive unit. 8. Safety diaphragm for over pressure release in diverter switch. 9. Spark gap for protection against transient over voltages between diverter switch contacts. 10. Requirements in respect of earthing arrangements, pressure relief device, and oil surge relay as per Indian

Electricity rules are in-built in the standard design. 11. Motor drive unit motor shall operate at 85% of rated voltage. 12. OLTC to comply with IS 8468 amended up to date. 13. Phase diagram to be submitted along with the offer. 14. Shield cap shall be provided for each bolted connection. Extra shield caps shall be provided for connection on

bridge if applicable. 15. 3D Model of the selected model shall submitted with the offer if possible. 16. If parallel bridges are used, mark the outermost dimension of live contact in the drawing.

Voltage Table and Circuit Diagram

Page 4: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

ORDERING SPECIFICATION

00 22-11-2017 First Submission Sanjeev Kunal Satyam

Rev. No. Date

Description Prepared

Checked

Approved

Title On Load Tap Changer Product Code SFPSZ-100000/200TH

Indent No. 14108

Doc No. ACC.20010.OLTC .

Page No. 4 of 4

R2.TBEAEI/PDD-F-10/2015

Page 5: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
Page 6: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

Easun - MR Tap Changers (P) Ltd., Tiruninravur - 602024 Chennai , INDIA

DRG.NO: AM 0023 / R1

ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
Page 7: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

DRG.NO:

M 0011/R1TECHNICAL DATA

TYPE 'M'

TECHNICAL DATA

Easun-MR Tap Changers (P) Ltd., Thiruninravur - 602024 Chennai , INDIA

Motor drive unit MA2 / MA9 , Protective housing in outdoor design,motor data: 415 V, 3-ph, 50Hz, 1.0 Hp / 0.75 Hp,step by step operation with local and remote control, mechanical and electrical position limitation, facility for remote position indication, hand crank operation for emergency and adjustment purpose.

M I 1203 M I 1503 M I 1803 M III 350 D M III 600 D

ST0064
Rectangle
ST0064
Rectangle
Page 8: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
st0064
Rectangle
Page 9: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
st0064
Rectangle
st0064
Rectangle
st0064
Rectangle
Page 10: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

125

120

205

25

25 145

18

190

PA

SS

ING

ON

, AS

WE

LL A

S D

UFL

ICA

TIN

G T

HIS

DO

UC

ME

NT,

UTI

LIS

ATI

ON

AN

D R

EP

RIN

T O

F IT

S C

ON

TEN

T A

RE

FU

RB

IDD

EN

,IF

NO

T E

XP

RE

SS

LY P

ER

MIT

TED

OFF

EN

CE

S A

RE

PO

SS

IIBLE

.ALL

RIG

HTS

FO

R T

HE

PA

TTE

RN

,MO

DE

L A

ND

DE

SIG

N A

RE

RE

SE

RV

E

12

34

56

87

A B C D E F

A B C D E

12

34

3D C

AD

D

RA

WIN

GN

O M

AN

UA

LC

OR

RE

CTI

ON

EASU

N -

MR

TAP

CH

ANG

ERSG

ENER

AL T

OLE

RAN

CE

WO

RKP

IEC

E ED

GE

SUR

FAC

E FI

NIS

H

MAT

ERIA

L:

SHEE

T:

1:5

SCAL

E

AP

PR

OV

ED

CH

EC

KE

DD

RA

WN

NA

ME

DA

TE

CH

AN

GE

NO

TIC

E

NU

MB

ER

RE

VIS

ION

IN

DE

X

DO

CU

ME

NT

NU

MB

ER

:

DW

G.

SIZE

PAR

T N

UM

BER

:

PR

OJE

CTI

ON

1/1

F

56

78

N.L

S.RS.K

14/0

7/20

15

D 1

4 01

4

TITL

E:

A3

BE

VE

L G

EA

R A

RR

AN

GE

ME

NT

(FIX

ED

AB

OV

E D

RIV

E M

EC

HA

NIS

M)

14/0

7/20

15

14/0

7/20

15

EN

ISO

130

2W

N 4

015

01IS

O 2

768m

H; I

SO

801

5

Page 11: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
Page 12: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
Page 13: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
Page 14: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor
Page 15: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

M 0039 / R2Easun - MR Tap Changers (P) Ltd., Thiruninravur - 602024 Chennai , INDIA

DRG.NO:

M I 1803 / 2103 / 2403 - 0 M I 1803 / 2103 / 2403- W M I 1803 / 2103 / 2403 - G

ST0064
Rectangle
ST0064
Rectangle
ST0064
Rectangle
Page 16: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor

Easun - MR Tap Changers (P) Ltd., Tiruninravur - 602024 Chennai , INDIA

DRG.NO: AM 0017

Page 17: ORDERING SPECIFICATION - TBEA Energy (India) …bidding.tbeaportal.com/userfiles/bidheader/1073.pdf · ORDERING SPECIFICATION ... IS 2026 Part 7 RATED VOLTAGE (kV) ... 1) Tie-in-Resistor