Page 1: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

1www.alltemp.ca

Refrigeration Monitoring And Controls Catalogue

Vol 2.0

Page 2: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

22

One Control

Evaporator Probe

Return Air Probe

Compressor

FanDefrost

7 ApplicationsParameter

tCType of Control

Models Replaced

Required Probes

1 On / Off thermostat - HeatingXR110C, XR01CX, XR10C, XR10CX

x 1

2 Off cycle defrost (timed)XR120C, XR02CX, XR20C, XR20CX

x 1

3Off Cycle defrost time initiated / temperature terminated

XR120C, XR02CX, XR20C-E

x 2

4Off Cycle defrost time initiated / temperature terminated, Alarm Relay

XR130C, XR03CX, XR30CX

x 2

5Electical / Hot gas defrost, time initiated / temperature terminated

XR140C, XR04CX, XR40CX

x 2

6Electical / Hot gas defrost, time initiated / temperature terminated + evap. Fan delay and control

XR160C, XR06CX, XR60CX

x 2

7Full open map of parameters,configure your own control

Your determination 1 to 3

Universal - XR ControllerU

NIV

ER

SA

L -

XR C

ON

TRO

LLE

RThe Universal-XR controller offers a 7 in 1 solution for Heating/Medium & Low Temperature/Defrost/Fans/Alarms etc. in just one control. Select one of the six preset maps in the application menu, and you now have a replacement of virtually any control. It’s the one control that is a must have on your service vehicle. Ultra simplified, one does it all. The Universal-XR Advanced Map (tC=7) allows total flexibility with inputs and outputs. Comes complete with two NTC probes, will work with existing PTC/NTC probes. TTL/Modbus communication capable with optional adapter.

Part # Description

14-XR60CX-AN1F1-UR 12/24 Volts

14-XR60CX-4N1F1-UR 120 Volts

14-XR60CX-5N1F1-UR 240 Volts

Dimensions:Frontal: 74x32mm,

70mm depth

Mounting: 71x29mm panel cutout

Page 3: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

33

tC = 2 Cooling, Off Cycle Defrost, Time Ended tC = 3 Cooling, Off Cycle Defrost, Time Ended

tC = 1 Heating

tC = 4 Cooling, Off Cycle Defrost, Time Ended, Alarm Relay tC = 5 Cooling, Electric or Hot Gas Defrost Temp.Ended

tC = 6 Low Temp, Elec. or Hot Gas Defrost, Temp. Ended, Fan Control tC = 7 Open Map to be Configured for any Application

The One . . . And Only CONTROL THAT SHOULD BE ON YOUR TRUCKUniversal-XR Replacement Controller for all Dixell, and many other

manufacturer's models.

Page 4: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

4

e-Class Controllers

Medium Temp Refrigeration

Low Temp Refrigeration

The e-Class series of controls are the OEM choice for economy, efficiency, and easiness. Designed for the North American market, the e-Class features high quality components built in a state-of-the-art factory in northern Italy. Simplified parameters, Hot Key programming for warming, medium, and low temp refrigeration. Extra large relays assure long life. 1/4" Fast-on Connectors ideal for OEM production assembly.

Specifications

Power: 120V / 230Vac 50/60HzOutputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference)Inputs: 1 NTC / PTCRange: -40 / 230 or 302°FProtection: IP65Digital Inputs: 0-1

Display: 2 or 3 DigitsIcons: 3Connections: Probes DisconnectableOutputs: 1/4" fast-onHot Key: YesTTL: No

E-C

LAS

S C

ON

TRO

LLE

RS

Part # Description

14-XR02CX-4N4FQ 120V, NTC, No Buzzer

14-XR02CX-4N5FQ 120V, NTC, w/ Buzzer

14-XR02CX-5N4FQ 240V, NTC, No Buzzer

Part # Description

14-XR06CX-4N4F7 120V, NTC, No Buzzer

14-XR06CX-4N5F7 120V, NTC, w/ Buzzer

14-XR06CX-5N4F7 240V, NTC, No Buzzer

Dimensions:Frontal: 74x32mm, 60mm depth

Mounting: 71x29mm panel cutout

Dimensions:Frontal: 74x32mm, 70mm depth

Mounting: 71x29mm panel cutout

14-C-BoxAvailable Enclosure

Page 5: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

5

Prime Series ControllersThe Dixell Prime Series configurable controllers provide digital solutions for both medium temperature and low temperature refrigeration units. Depending on the model the installer can adjust through the parameter menu such fields as set point, differential, short cycle protection, energy savings temperature differential, digital input configuration, fan cycling plus alarm levels and delays. Included TTL Modbus communications via Hot Key port.

PR

IME

SE

RIE

S C

ON

TRO

LLE

RS

Dimensions:Frontal: 74x32mm, 70mm depth

Mounting: 71x29mm panel cutout

SPECIFICATIONS:Power: 120V / 230Vac 50/60hzOutputs:16FLA/96LRA,10A, 5A(see model differences)Inputs: 1-3 NTC / PTCRange: -40 / 230 or 302 °F/CProtection: IP65Digital Inputs: 1

Display: 3 DigitsIcons: 8Connections: Probes disconnectableOutputs: 1/4" fast-onHot Key: YesCommunications: TTL / Modbus

4 5 6 7

9 10 11 12

Comp

Room

8Hot Key/IV Probe

TTL or X-REP output

20(8)A250V

Line

N.C.

1 2 3 4 5 6 7

9 10 11 12

CompLight/Alarm

Room

8Hot Key/IV probe

TTL or X-REP output

8(3)A250V 20(8)A250V

Line

Medium Temp Refrigeration(Off Cycle Defrost)

Low Temp RefrigerationComp/Def/Fan

Low Temp RefrigerationComp/Def/Fan/Alarm

Alarm / Defrost

N.C.Line

8(3)A250V~

1 2 3 4 5 66

9 10 11 12

5(1)A

Max20A

Comp Def

Evap

.

Room

7Hot Key/IV probe

TTL or. X-REP outputFan

8

20(8)A250V~

How to OrderPrime Series Voltage Sensor Options F/C Relay/Connectors

XR10CXXR20CXXR30CXXR40CXXR60CXXR70CX

0 = 15AC/DC1 = 24AC/DC4 = 120Vac5 = 230Vac

N = NTCP = PTC

P = PT1000(XR30 / 70 only)

0 = None1 = Buzzer

F = °FC = °C

7 = 16FLA / 1/4"Fast-ons

8 = 16/60A 1/4" Fast-ons

(XR70CX only)

Part #

14-XR20CX

Part #

14-XR60CX

Part #

14-XR70CX

Part #

14-XR30CX

14-XR40CX

Page 6: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

6

On-Demand®Defrost – Saves Energy

Electronic SetPoint – More Accurate

Hands Free Lights – Auto Off Feature

Energy Saver Mode – Nights and Weekends

Remote Communications – Monitor via XWEB

Remote Keypad – Monitor Temps and Alarms

XW Walk-In ControlThe Dixell XW60K Walk-in controller provides an electronic solution for both medium temperature and low temperature Walk-in units. The XW60K features On-Demand® Defrost, Energy Saver Mode, Hands Free auto-off lights, Fan Cycling, Remote Keypad, and includes digital inputs for door ajar switches and other interfaces. Alarms include high and low temps, door and condenser alarms. energy savings can be up to 20-25%.

XW60K Remote KeypadXW60K Remote Keypad

P3  Discharge  Air  Probe  

P1  Return  Air  Probe  

P2  Evap.  /  Def.  Probe  

On-­‐Demand®  Defrost    Output  

Evap.  Fan    Output  

Liq.  Solenoid  Output  

Light  or  Alarm  Output  

Door  Switch  Input  Remote  ConnecIon  to  100Ft.  

Replaces  all  this  

P4  Opt.  Condenser  Probe  

XW W

ALK

-IN

CO

NTR

OL

Page 7: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

7

Optional XW Superheat Controller

The Dixell XW Superheat controller provides an electronic solution for stepper electric expansion valves. Featuring pre-sets for all popular valves the XEV22 takes a 0/5V or 4...20mA pressure input plus a Pt1000 or NTC input to manage Superheat. Special defrost algorithm reduces defrost time. Add to the XW60K for an advanced walk-in control solution.

Medium Low Temp Refrigeration for Walk-insComp/ Def / Fan/ Light

Replaces all of these Mechanical Instruments

XW60K

Remote Keypad

Optional XEV Driver

SPECIFICATIONS:Power: 120V / 230Vac 50/60hzOutput: 16FLA/96LRA 2 x 16A 1 x 10AInputs: NTC / PTCRange: -58 /230°F PTCDisplay: 3 DigitsIcons: 8Panel Mount: 32 x 74MMConnections: Probe screw terminalsOutputs: 1/4” fast-onKeyPad: J-Box mount / IP65Communications: TTL Modbus

Part # Description

14-XW60K-4N2F0 115V Kit

14-XW60K-5N2F0 230V Kit

XW60KINCLUDES:XAW60K ControlRemote KeypadDoor SwitchUSB HotKey3 Probes8" Mounting BoxHardware

Page 8: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

8

• High/Low temperature alarms w/ delays

• Lighting management – Auto on/Auto off

• Door open alarm w/ magnetic door switch

• Range – 40/230°F• 8ft probe• Battery back-up• Loud buzzer• Pre-wired

XWA Walk-In AlarmOperators can be certain that the temperature inside their walk-in stays in the safe zone by indicating either a high or low temperature condition with a visual alarm and pulsing buzzer. An open door alarm keeps the cold inside where it belongs. A set of alarm contacts is included for outboard signaling. The light management system will automatically turn the lights ON when you open the door and the “AUTO-OFF” feature shuts off the light after an adjustable time delay. Optional 9Vdc battery back up will allow for visual alarms for up to 96 hours.

Part # Description

14-XWA11V-25-KIT Walk-in Alarm Kit

XWA

WA

LK-I

N A

LAR

M

Page 9: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

9

Alarm CodesHA High Temp AlarmdA Door open alarmLA Lo Temp AlarmPan Panic AlarmP1 Probe AlarmEA External Alarm

XWA11V-25-KITINCLUDES:Wall Mount EnclosureDoor SwitchExternal BuzzerPre-wired

iDial1Includes ext. relay to convert 8Aalarm relay to D.I.Includes 9/12Vdc transformerRJ11 wires and instructions9 Programmable phone no’sfor each channel

PANPushbutton backlight panicalarm. The XWA will display“Pan” and turn on alarmrelay for external buzzer orphone dialer

MGSGas leak detector for refrigerantleaks. Various gases/rangesavailable.

H300Current transformerto detect defrost.

MDSMagnetic door switch1/2” spacing magneticdoor switch to connectto digital input

STRStrobe light for visual alarmwarning

Accessories Available:iDial Phone DialerMGS Leak DetectorPAN Panic ButtonEXT/BUX External 85db buzzer

SPECIFICATIONS:Power: 120V / 230Vac 50/60hzOutput: 8A alarm / 15A LightInputs: NTCRange: -40 / 230°FDisplay: 3 DigitsIcons: 3J-Box Mount Connections: Probe 1/4" fast-onsOutputs: 1/4" fast-on

Page 10: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

10

Anti-Sweat ControllerThe XH55P measures temperature and Humidity and calculates Dew Point. The unit then turns on and off glass door heaters to eliminate condensation on the glass. The internal 16A relay can manage between 6 and 10 doors depending on amperage draw. The units has 3 LED indicators; ON / TX / Alarm, has one Digital Input, voltage free open / closed circuit that can initiate Energy Saver Mode (i.e. turn off when the cooler is in defrost).The adjustment knob offset is a + /- 6°F Dew Point Set Point adjustment to run the control on the “Dew Point Edge”, saving energy costs and offers seasonal adjustment. An analog output (0/10V) and RS485 Modbus interface allows the XH55P to communicate to BMS Systems and is XWEB Compatible.

Part # Description

14-XH55P Anit-Sweat Controller

+ + 10 11 12

8 or 16A

HOT KEY

0 – 10V RS485 PowerSupply

n.c. c. n.oDi

gital

Inp.

Rem

ote

1 2 3 4 5 6- -

7 8 9

• Walk-in Coolers & Freezers

• Glass doors• Temperature and

Humidity Monitoring• Energy Saving

SSR Box Solid State RelayXJ485USB Wall Bracket

MountingSPECIFICATIONS:Power: 24VAC, 3VA maxOutput: 16A internal/Optional 25A SSR outboard relay Kit, and one 0/10V Analog Output.Inputs:Digital Input (open/closed circuit) that is typically used to place the unit into Energy Saving Mode ( as defined by the HES parameter)

AN

TI-S

WE

AT C

ON

TRO

LLE

R

Page 11: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

11

XJDL Series Digital Data LoggerRecord up to 4 temperatures every 15 minutes and store up to 1 year with the XJDL Digital Data Logger. Operators can take the guesswork and human error out of HACCP recording. Record up to 4 temperatures and 4 events, such as door openings or defrost cycles on a single unit. Data transfer to a PC with ease using a standard USB drive to a .TXT file that can be uploaded to Excel. Dated security prohibits tampering. A built-in dry contact relay can be used for audible or visual alarms, phone dialer, BMS or security system interface.

Part # Description

14-XJDL40D Data Logger Kit

DIG

ITA

L D

ATA

LO

GG

ER

KIT INCLUDES:• (4) 8 ft. NTC probes included –40/230°F&C• Record every 15 minutes and store for up to 1 year• Download .TXT file to USB key/Upload to any PC & Excel®

• Hi & Low Alarm setpoints with dry contacts SPDT• 4 door switch inputs• 24V Plug-in transformer• Wall mounting enclosure

Page 12: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

12

PR

OB

E M

ON

ITO

RIN

G M

OD

ULE

SI/O Probe Monitoring ModulesXJP60D is an acquisition module that can read up to 6 analogue inputs and 3 inputs at 230Vac (110Vac or 24Vac opt.). By means of the serial output RS485, they can be connected to the XJ500 or a ModBUS-RTU compatible monitoring system. Modules XJP, DIN RAIL format, are without display and are programmable by means of a programming keyboard KB1 PRG. The analogue inputs can be PTC, NTC 4÷20mA or 0÷10V; when the inputs are PTC or NTC the choice can be made by a parameter.It is also possible to program them with with a programming "Hot Key" and to connect them to a display device calle XJP REP which shows the main temperature and input status.

13 14 15 16 17 18 19 20 21 22 23 24

10 11 125 6 7 8 93 41 2

Part # Description

14-XJP60D-2F0N3 Monitoring Module

SPECIFICATIONS:Housing: self extinguishing ABS.Case: 4 DIN modules 70x85mm; depth 61mm.Mounting: DIN RAIL mounted in an omega (3) din rail.Connections: Screw terminal block ≤ 2.5mm2 wiring.Power Supply: 230Vac, ± 10% 50/60Hz;24Vac, ± 10% 50/60Hz.Power Absorbtion: 3 VA max.Analogue Inputs: 6 probes PTC or NTC inputs 4÷20mA or 0÷10V.Inputs: 3 power supply inputs.RS485 Outputs: RS485 serial output with ModBUS-RTU protocol.Data Storing: on the non-volatile memory(EEPROM)Operating Temperature: 0÷60°CStorage Temperature: -30÷85°CRelative Humidity: 20÷85%Mesuring and Regulation Range: PTC: -50÷150°C (-58÷302°F) NTC: -40÷110°C (-58÷230°F) or according to the probe.Resolution: 0.1°C or 1°F (selectable)Accuracy of the Controller at 25°C: ±0.3°C ± 1 digit

Page 13: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

13

Part # Description

14-XJR40D Relay Module

SPECIFICATIONS:Housing: self extinguishing ABS.Case: 4 DIN modules 70x85mm; depth 61mm.Mounting: DIN RAIL mounted in an omega (3) din rail.Connections: Screw terminal block ≤ 2.5mm2 wiring.Power Supply: 230Vac, ± 10% 50/60Hz (opt. 115Vac, ± 10% 50/60Hz; 24Vac, ± 10% 50/60Hz.)Power Absorbtion: 6 VA.Digital Inputs: 4 free voltage contactRS485 Outputs: RS485 serial output with ModBUS-RTU protocol.Data Storing: on the non-volatile memory(EEPROM)Operating Temperature: 0÷60°CStorage Temperature: -30÷85°CRelative Humidity: 20÷85% ( no condensing)

LIG

HTI

NG

CO

NTR

OLL

ER

4 Zone Light ControllerXJR40D is a module with 4 on-board relays and 4 digital Input free voltage contact (DI). All the outputs can be switched by the local or remote keyboard. This module is equipped with the serial output RS485, so it can be connected to the XWEB series or to a ModBUS-RTU compatible monitoring system. XJR, DIN RAIL format, is without display and has to be programmed by means of the keyboard KB1 PRG. It is also possible to program it with a programming "Hot key”

PowerSupplyRS485

1917 18 22 2313 14 16 20 21

8(3)A/250Vac

1 2 3 4 5 8 976 11 12

15 24

8(3)A/250Vac 8(3)A/250Vac 8(3)A/250Vac

Load2 Load3 Load4Load1Line

Page 14: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

14

XC10CX Features:• Controls based on Suction Pressure, Cut

In/Cut Out• 0/150psi Brass transducer 1/4 SAE female

connection• PSI Display reading• High pressure switch input for safety (auto

& manual reset)• Optional temp input for high temp alarm• Bump Start function (after being idle for

over 4 years)

XC30CX Features:• Fan Management – up to 2 fans• Equalizes fan run time• 0/500psi SST transducer ¼ SAE female

connection• 0/150psi Brass transducer ¼ SAE female

connection

Alarm Recording• Number of high pressure alarms• Number of high temperature alarms• Number of manual restarts

SensorsXC10CX - W528-150-S-F2A 1/4 SAE (7/6-20UNF-2A) internal thread with Schrader deflator. Range 0-150psi. It has a three wire disconnectable metro-pack connector with 12" flying leads

SensorsXC30CX - W528-150-S-F2A 1/4 SAE (7/6-20UNF-2A). Additional ranges and material are available

Service Menu• Number of compressor starts• Compressor running hours• First fan working hours• Second fan working hours

CO

ND

ENSI

NG

UN

IT C

ON

TRO

LLER

XC Condensing Unit ControllerThe Dixell XC10 & 30CX Controls replace old mechanical pressure switches that are inaccurate, difficult and time consuming to set up.The XC Controls can directly control a compressor and up to 2 fans (XC30CX model).It is possible to control the pressure values of the suction and discharging lines by using a new low cost ratio-metric pressure sensor input. With the addition of a fixed pressure switch you can shut down (and save) the compressor on high pressure alarm conditions. The XC30CX will also control up to two condenser fans, rotating them for equal run times. A service menu records information on starts, run times, manual starts, and alarms.

Part # Description

14-XC10CX-4P00G Compressor Control

Part # Description

14-XC30CX-4P004HU Compressor + 2 fans, Control only

14-XC30CX-4P004H-KITXC30CX w/ 2 transducers, a box, harness and High

pressure switch

Page 15: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

15

XC10CX XC30CX

Circuits 1 1

Compressors 1 1

Fans 0 1-2

PSI Sensor 1 2

Ratio-Metric Transducer

SPECIFICATIONS:Housing: self extinguishing ABSCase: frontal 32x74 mm; depth 70mmMounting: panel mounting in a 71x29mm panel cut-outProtection: IP20Frontal protection: IP65Connections: spade on terminal blocks 6.2mmPower supply: according to the model: 230Vac 10%, 50/60Hz, 110Vac 10%, 50/60HzPower absorption: 3VA maxDisplay: 3 digits, red LED, 14.2 mm highInputs: up to 3 probesDigital input: free voltage contactRelay outputs: Compressor: SPST 20(8) A, 250VacData storing: on the non-volatile memory (EEPROM)Kind of action: 1BPollution degree: 2Software class: ARated impulsive voltage: 2500VOvervoltage Category: IIOperating temperature: -10 to 55°C (14 to 131°F)Storage temperature: -30 to 85°C (-22 to 185°F)Relative humidity: 20 to 85% (no condensing)Measuring and regulation range: NTC probe: -40 to 110°C (-40 to 230°F) PTC 990ohm probe: -50 to 150°C (-58 to 302°F)Resolution: 0.1°C or 1°C or 1°F (selectable)Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit

Page 16: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

16

XC650CX XC645CX XC1015D

Circuits 1 1 2

Compressors 2-5 2-5 2-15

Digital Scroll no yes opt.

Fans 1-3 1-3 1-15

Unloaders yes yes yes

XC Rack ControlsDixell offers a full line of Compressor Rack Controllers for systems of all sizes. Project specifications may include working with multiple stages, compressors of differing power, condenser fans, digital scroll management, proportional band or dead band adjustments. Options on certain models can include alarm relay and analog outputs. Tell us about your next project.

XC R

AC

K C

ON

TRO

LS

Part # Description

14-XC650C-1C02E Up to 5 comps and/or fans

Part # Description

14-XC645C-1C0F1 1 Digital Scroll + up to 4 comps and/or fans

Part # Description

14-XC1015D-1F01F Advanced Rack Control15 Relay outs + 4 analog outs

Page 17: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

17

MGS Gas Leak DetectorThe MGS is either a stand alone leak detector which utilizes a range of sensor types to detect most gases or as part of a remote monitoring system. The MGS detects most gases using a variety of sensor technologies: Semiconductor, Electrochemical or Infrared, depending on the type of gas monitoring required. The MGS continuously determines the gas level present in an area, room, zone, air space or airflow. A Universal gas detection solution interfaces with the XWEB using the XJP60D or any controller, BMS or SCADA system through selectable analogue outputs: 0-5V,1-5V, 0-10V, 2-10V or 4-20mA. A Relay Output rated at 1A SPDT is included along with an internal buzzer.

Part # Description

14-MGS-R404A Infared Gas Sensor - R404A

GA

S L

EA

K D

ETE

CTO

R

MODEL MGS OVERVIEWThe Sensor detects various gas leaks in PPM (parts per million) and will alarm at 50% of the range and send an analog out-put 0-5V, 1-5V, 0-10V, 2-10V or 4..20mA to a Monitoring system. Specify specific gas when ordering.MOUNTING: The product is wall mounted using multiple wall mounting options on the back of the 3.39" x 4.73" case.SENSORS: The product shall have Semi-conductor, Electromechanical or Infrared sensors, depending on the gas to be detected. POWER: The product shall be powered by 12 - 24Vac/dc - 91mA max.OUTPUTS: The MGS has one 1A SPDT relay output, and a 0/10V, 05V or 4...20Ma analog output. The MGS is compatible with the XJP60D and XWEB.

Applications include detection of:• Refrigerant gases including: Ammonia,

Carbon Dioxide, Hydrocarbons, Halocarbons HFCs, HCFCs, CFCs, for refrigeration, air-conditioning.

• Combustible gases such as Methane, LPG, Propane, Butane, and Hydrogen for industrial heating, landfills and power generation.

• Toxic gases such as: Carbon Dioxide and Ammonia in refrigeration, Hydrogen Sulphide in sewage treament plants and Carbon Monoxide in underground parking garages.

• Volatile Organic Compounds such as: Acetone, Benzene, Carbon Tetrachloride, Chloroform, Ethanol, Toluene, Trichloroethylene, for process and general industrial.

• Detect small leaks before they become big problems.

• Reduce costs of replacement refrigerant, service calls and product loss.

Other refrigerants available by replacing "R404A" with required refrigerant.

Page 18: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

18

iStat/ProThe HVAC system can represent up to 25% of an operators utility costs. The thermostat is the key component to save on heating or cooling system costs. The requirements are: First it must look good on the wall, be very easy to use and meet all the needs of the user and the equipment it is controlling. Second it must be able to adapt to all the different control variations required (single or multi stage heat/cool systems, single or multiple fan speed + Heat Pump and emergency heat applications. Initially the operator has to be able to “lock-out” local control in favor of remote control, while maintaining comfort and eliminate energy wasting adjustments.

The installer is able to configure the iStat/Pro to control Heat pump systems, (with auxiliary or emergency heating if necessary) gas/oil heating systems with add on cooling, plus control high and low balance points (using external sensors as well as the number of heating and cooling stages needing precise control. It can even adapt to manage the number of fan speeds it can control. The operator can choose The iStat/Pro to be in programmable or manual mode with single or multiple set points. By networking multiple iStat/Pro's with our XWEB Internet Monitoring and Control System, the iStat/Pro can be remotely Monitored and Controlled keeping HVAC costs under control.

Part # Description

iStat/pro Manual/Programmable Thermostat

Features:• Selectable as Manual or Programmable• Up to 2 stage Heat/Cool or heat pump• Single or 3 speed fan control• Keyboard and/or Temperature Locks• Occupancy sensor input• Economizer function• 24V powered with battery backup• Large backlit LCD Touch Screen Display• Remote temperature sensors available• Integrated Remote Communications• Replaces almost all 24V thermostats• XWEB Compatible

ISTA

T P

RO

Page 19: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

19

Installer Options: Wiring

Page 20: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

20

Model No.24DT0=Thermometer onlyS = SST CoverL = with Light SwitchPower0=12Vac./dc4=110Vac.5=230Vac.DisplayF = °F -40/230°FC = °C -40/110°CUpdate Time*0 = 1 Second1 = 1 Minute3 = 3 MinuteEx: 24DT-L-4F1Wall Plate Thermometer / 120 Vac / Light Switch / 1 Minute Update

How to Order LED Thermometers

Model No. Mounting20DT U = U-Clamp F = Front Flange

Power0 = 12 Vac/dc4 = 120 VacDisplayF = -40/230°FC = -40/110°CUpdate Time*0 = 1 Second1 = 1 Minute*3 = 3 Minute*Order Entry Example: 20DTF-4F12" Front Flange / 120 Vac / °F / 1 Second Update*Display changes 1° every 1 or 3 minutes on increase of temperature – on decreasing temperature, the display will change every second, regardless of time.

24DT 20DT 24DT-S 24DT-L

ThermometersThe New Generation LED Thermometers include our exclusive Direct Power Feature eliminating the need for an external transformer. Powered by 120Vac, (230Vac,12Vac, optional) not only makes the unit easier to install but adds reliability and life to the instrument. With UL and NSF Listing, both designs can be ordered with 1 second,1 minute or 3 minute display update times to eliminate temperature fluctuations from repeated door openings. Each unit has a detachable sensor and power fast-ons to speed up installation. With an extended range of –40 to 230°F our LED units are well suited to many applications. Includes Temperature Probe and Wiring Harness.*

THER

MO

MET

ERS

Page 21: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

21

APPLICATIONS FOR FOOD SAFETY AND ENERGY SAVINGSCHOOLS • FOOD WAREHOUSES • INSTITUTIONAL FOOD SERVICE • C-STORES

HOTEL KITCHENS • FOOD PROCESS • RESTAURANTS • SUPERMARKETSDixell Monitoring & Control Applications via the Internet

see diagram on back cover

SU

PE

RV

ISO

R A

ND

MO

NIT

OR

ING

SY

STE

MS

XWEB EVOThe XWEB EVO is the new system family for the optimum management of Retail field and HVAC/R applications. New innovative tools to improve the efficiency of both small and large applications are available such as the advanced graphical one to facilitate the data analysis. Furthermore, systems are provided with a customizable web user interface to make navigation easier and without any additional software. XWEB EVO is designed to obtain energy savings, thereby reducing running costs and helping to preserve the environment. Our solutions are synonymous with quality, user-friendliness and efficiency because they are focused to meet end user needs.

A powerful hardware platform with USB, Ethernet, RS485 ports, and more, offers the maximum level of connectivity.

HIGHCONNECTIVITY

The user interface is available for modern Web browsers without the need to install additional software. XWEB EVO is also compatible with HD and touch-screen technologies and tablets.

HIGHINTEGRATION

An effective alarm management system easily detects and signals alarm status so prompt intervention can restore optimum functioning of the application.

ALARMMANAGEMENT

Constant data recording, HACCP reports and timely alarm notifi cation guarantee high quality of fresh and frozen food and is in compliance with the UNI EN 12830 rule.

FOODQUALITY

Special algorithms and continuous tracking of energy usage optimizes the application’s effi ciency by increasing energy savings and reducing costs.

ENERGYSAVING

With our eco-friendly solutions, innovation and effi ciency means respecting the environment by optimizing consumption and reducing pollution, gas emission and waste.

ENVIRONMENTALLYFRIENDLY

Part # Description

XWEB300D EVO 6 or 18 device installations

XWEB500 EVO 20, 36, 50, or 100 device installations

XWEB500D EVO 20, 36, 50, or 100 device installations

Page 22: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

22

ProbesPR

OB

ES

Nickel Brass 1.8" x ¼" Molded / Potted Probe18NB-NTC-1.5M 05ft18NB-NTC-2.5M 08ft18NB-NTC-4.5M 15ft18NB-NTC-6.0M 20ft

Standard 10K Ohm NTC Thermistor -40/230°F

SST 3.0" x ¼" Molded / Potted Probe30SS-NTC-x.xM Lengths noted above, max length 300ft.Other lengths, NPT Fittings and Thermo-wells available.

Pipe Mount Condenser Molded ProbePMT6-67-1.5M 5ft. 1/8" to 11/8" Pipe PT-1000NT6-67-1.5M 5ft. 1/8" to 11/8" Pipe NTC

XH10P 30-90%RH +/- 5% 4…20mAXH20P 0-99%RH +/- 3% 4…20mA

PP11 0-160psi +/- 1% 4….20mAPP30 0-435psi +/- 1% 4….20mA

PPR15 0-218psi +/- 1.2% 0/5VPPR30 0-435psi +/- 1.2% 0/5V

W528-150 0-150psi +/- 1.5% 0/5VW528-500 0-500psi +/- 1.5% 0/5V

wall mount

7/16”-20 male

7/16”-20 female

7/16”-20 female

Nickle Brass Probes

Stainless Steel Probes

Humidity Probes

Pressure Transducers

Page 23: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

23

TEMPERATURE TO RESISTANCECHART NTC THERMISTOR

Temp C Temp F Resistance Ohms-50 -58 329.5-45 -50 247.7-40 -40 188.5-35 -31 144.1-30 -22 111.3-25 -12.5 86.43-20 -4 67.77-15 5 53.41-10 14 42.47-5 23 33.90 32 27.285 41 22.0510 50 17.9615 59 14.6920 68 12.0925 77 1030 86 8.31335 95 6.9440 104 5.82745 13 4.91150 122 4.1655 131 3.53660 140 3.0265 149 2.58870 158 2.22875 167 1.92480 176 1.66885 185 1.45190 194 1.26695 203 1.108100 212 0.9731105 221 0.8572110 230 0.7576

All Resistance is k or (x1000)

Page 24: 3FGSJHFSBUJPO.POJUPSJOHOE$POUS PMT$BUBMPHVF 7PM€¦ · Outputs: 16FLA / 96LRA, 16A Res. 10A DEF 5A FAN (see model difference) Inputs: 1 NTC / PTC Range: -40 / 230 or 302°F Protection:

Refrigeration Monitoring And Controls Catalogue

Vol 2.0