Air Circuit Breakers Series 3SW68 1-1 www.sassin.com Power Distribution Electrics Body 1 Front drawer base Body 2 Shell Terminal block Busbar Back drawer base Arc chute Auxiliary switch Motor Current Transformer Contact system Release Operating mechanism Intelligent auxiliary switch Overview

Upload: others

Post on 24-Feb-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-1www.sassin.com

Power Distribution Electrics

Body 1

Front drawer base

Body 2

Shell

Terminal block

Busbar

Back drawer base

Arc chute

Auxiliary switch

Motor

Current Transformer

Contact system

Release

Operating mechanism

Intelligentauxiliary switch

Overview

Page 2: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-2 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Applications and functions

Incoming-feeder and outgoing-feeder function in distribution systems Switching and protecting large powers, motors, capacitors, generators, transformers, busbars and cables Overload protection Short-circuit protection with short delay Instantaneous short-circuit protection Used in building, industry, energy and infrastructure

Instruction of type code

Instruction of external structure

1. Terminal of secondary circuit

2. Drawer shelf

3.

4.

5. Switching-ON button

6. Indicator of energy-storage and energy-release

7. “Unlocking button” of the three positions (“separated”,

“test” and “connected”)

8. Safety padlock position

9. Cranking bar

10. Indicator of switching-on(I) and switching-off(O)

11.

12.

13. Release indicator and resetting button

Data label

Manual energy-storage and energy-release

Intelligent controller

Switching-OFF button

Breaking capacity: N; H ; S

Rated current (A)200, 400, 630, 800, 1000, 1250, 1600 (Frame A)1250, 1600, 2000, 2500 (Frame B)2000, 2500, 3200, 4000 (Frame C)4000, 5000, 6300 (Frame D)

Connection typeH: Horizontal terminal connectionV: Vertical terminal connection

Intelligent controller modelL: L typeM: M typeH: H type

Poles: 3: 3P; 4: 4P

Installation typeF: Fix typeD: Drawer type

FrameA: 3SW68-1600B: 3SW68-2500C: 3SW68-4000D: 3SW68-6300

Series code

N200HL3FAW68

12

987

10111213 4

3

56

Page 3: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Strength of former insulation materials.

Strength increased after adopting new insulation materials using nanotechnology.

Air Circuit BreakersSeries 3SW68

1-3www.sassin.com

Power Distribution Electrics

Low space requirements

3SW68 devices are very compact thus require very little space for installation. Frame A devices (up to 1600 A) fit into a 400 mm wide switchgear panel.Frame B,C,D devices (up to 6300 A) are the smallest of their kind and with their smallest construction width fits into a 800 mm wide switchgear panel.

3SW68-1600/1600 3SW8-2000/1600

60%

40%

100%

100%

80%

60%

40%

20%

0%

Communication

The use of modern communication-capable circuit breakers opens up completely new possibilities in terms of start-up, parameterization, diagnostics, maintenance and operation. This allows varieties of ways of reducing costs and improving productivity in industrial plants, buildings and infrastructure projects.

Strength of new material

55%

160140120100

80604020

0

20%

60

58

56

54

52

50

48

46

44

Four-pole circuit breaker with a drawer as an example

Strength of former insulation materials.

Strength increased after adopting new insulation materials using nanotechnology.

Former materials New materials

Actual body size Reduction of body size

Example of comparation with 3SW8 in measurement

Modular design

Components like auxiliary releases, motorized operating mechanisms,electronic releases, current sensors, auxiliary circuit signaling switches, automatic reset devices, interlocks and engagement operating mechanisms can all be exchanged or retrofitted in the back ground, thus allowing the circuit breaker to be adapted to new, changing required.

Impact strength(Mpa)

Bending strength(KI/m²)

Features and benefits

Former materials New materials

Page 4: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-4 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Complete current range and high-breaking capacity

Icu (kA)

Ics (kA)

Icw(kA/1s)9080706050403020100

AC400V-N AC400V-H AC690V-N AC690V-H

Icu (kA)

Ics (kA)

Icw(kA/1s)160

140

120

100

80

60

40

20

0

Icu (kA)

Ics (kA)

Icw(kA/1s)120

100

80

60

40

20

0

Icu (kA)

Ics (kA)

Icw(kA/1s)70

60

50

40

30

20

10

0AC400V-N AC400V-H AC690V-N AC690V-H

3SW68-1600 Rated current In(A)

3SW68-2500 Rated current In(A)

3SW68-4000 Rated current In(A)

3SW68-6300 Rated current In(A)

3SW68-1600 Breaking capacity

3SW68-2500 Breaking capacity

3SW68-4000 Breaking capacity

3SW68-6300 Breaking capacity

200

400

630

800

1000

1250

1600

1000

1250

1600

2000

2500

2000

2500

3200

4000

4000

5000

6300

65 42 42

30 30 30

35 35 35

65 65 65

85 85 85

50 50 50

65 65 65

85 85 85

100 100 100

120 100 100

85 85 85

65 65 65

100 100 100

100 100 100

120 120 120

150 150 135

65 55 50

AC400V-N AC400V-H AC400V-S AC690V-N AC690V-H

AC400V-N AC400V-H AC400V-S AC690V-N AC690V-H

85 85 85

Page 5: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-5www.sassin.com

Power Distribution Electrics

D63003,4

N H S4000 5000 6300

50/60400,690

100012

100%In

100 120 15085 100 100

100 120 15085 100 100

220 264 330187 220 220

100 120 13585 100 100

25-3070

1000800

500010000

Technical specifications:

30° 30°

3SW68-1600IEC60947-2

CEA

16003,4

N H200 400 630 800 1000 1250 1600

50/60400,690

100012

100%In

65 6530 35

42 5530 35

143 14363 73

42 50- -

25-3070

65003000

1500030000

30° 30° 30° 30° 30° 30°

-5 to +40℃, max. 95 % humidity-40 to +75℃

2000

Fixed /DrawerWxHxD

248x351x297318x351x597248x351x297318x351x297254x320x194324x320x194254x320x194324x320x194

B25003,4

N H1250 1600 2000 2500

50/60400,690

100012

100%In

65 8550 65

65 8550 65

143 187105 143

65 85- -

25-3070

50002500

1250025000

C40003,4

N H S2000 2500 3200 4000

50/60400,690

100012

100%In

85 100 12065 85 85

85 100 10065 85 85

187 220 264143 1 65 165

85 100 10065 85 85

25-3070

20001500

1000020000

Fixed /DrawerWxHxD

347x450x390442x450x390347x450x390442x450x390

367x403x308.5462x403x308.5367x403x308.5462x403x308.5

Fixed /DrawerWxHxD

440x450x390556x450x390440x450x390556x450x390

460x403x308.5586x403x308.5460x403x308.5586x403x308.5

Fixed /DrawerWxHxD

769x487x390995x487x390769x487x390995x487x390785x407x290

1010x407x290785x407x290

1010x407x290

TypeStandardApprovalFrame typeRated frame current In (A)Number of polesClass of breaking capacityRated current In(A)

Rated frequency (Hz)Rated voltage, Ue (V) Rated insulating voltage Ui (V)Rated impulsed withstand voltage, Uimp(kV)N-pole rated current Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 400V O-CO (kA)(AC) 50-60 Hz 690V O-CO (kA) Rated operating short-circuit breaking capacity,Ics(AC) 50-60 Hz 400V O-CO-CO (kA)(AC) 50-60 Hz 690V O-CO-CO (kA) Rated short-circuit making capacity (peak),Icm(AC) 50-60 Hz 400V (kA)(AC) 50-60 Hz 690V (kA) Rated short-time withstand current for 1s Icw (kA)(AC) 50-60 Hz 400V (kA/s)(AC) 50-60 Hz 690V (kA/s) Making time msMax breaking time msElectrical life (times) in 400V in 690VMechanical life (times) without maintenance with maintenanceMounting position

Installation typeDismension (mm)Drawer,horizontal, 3P Drawer,horizontal, 4PDrawer,Vertical, 3PDrawer,Vertical, 4PFixed,horizontal, 3PFixed,horizontal, 4PFixed,Vertical, 3PFixed,Vertical, 4PAmbient temperatureStorage temperatureAltitude( Max)

3SW68-2500IEC60947-2

CEIEC60947-2

CEIEC60947-2

CE

3SW68-4000 3SW68-6300

Page 6: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-6 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Basic protection

Overload protection

Short-time delayed short-circuit protection

Instantaneous short-circuit protection

Ground fault protection

Neutral pole protection

Additional functions

MCR Function

Thermal memory

Contact loss indicator

Self-diagnostic function

Fault memory

Test function

Zone Selective Interlocking

Closing counting

Parameter display

Fault trip display

Load monitoring display

Current display

Achieve communication through device net

Time display

Measurement

Current measurement

Voltage measurement

Frequency measurement

Power measurements

Power factor measurement

Phase sequence detection

Imbalance function

Energy measurement

Harmonic measurement

Protection

Overvoltage protection

Undervoltage protection

Imbalance protection

Over frequency protection

Under-frequency protection

Phase sequence protection

Inverse power protection

Communication

Communication Interface

Achieve communication through MODBUS

Achieve communication through PROFIBUS

L

S

I

G

N

Intelligent controller model

3SW68-L

Function

3SW68-H 3SW68-M

Intelligent controller characteristics

Note: “ ” available “ ” selectable ” ” unavailable

Page 7: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-7www.sassin.com

Power Distribution Electrics

Intelligent controller model and panel description

Intelligent controller model type 3SW68-L Basic 3SW68-M Standard 3SW68-H Communication

Introduction of intelligent controller panel

L type Intelligent controller panel(3SW68-1600)

Note: Parameter setting IR <Isd <II

1. RESET Button It pops up when fault tripping or test tripping. The circuit breaker can be switched on only when the button is pressed down. Meanwhile, the fault indicator resets.2. Indication of rated current (In)3. MCU indicator It remains lit when the controller is under normal working.4. Over-voltage indicator It lights up when current reaches 1.15IR.5. Current bar indicator To display the real time current as the percentage of IR; 10% each step.6. Fault reason indicator To show the fault reason after tripping occurs. If power supply works normally, it will indicate the fault reason after fault tripping. Press RESET to quit. If power supply is lost, press FAULT CHECK key to show the reason of last tripping when power recovers.7. Current settings adjustor8. Time settings adjustor9. FAULT CHECK key Press the key to enter fault check status when the controller is under normal working.10. TEST key Press TEST key, the breaker trips immediately, but no fault recorded. Press RESET and CLEAR after test. 11. CLEAR key

1

2 3

45

6

789

10

11

Page 8: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-8 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

M type and H type Intelligent controller panel for (3SW68-1600)

Indication1. RESET button It pops up when fault tripping or test tripping. The circuit breaker can be switched on only when the button is pressed down. Meanwhile, the fault indicator resets.2. LCD display3. Fault and alarm RESET key4. FAULT/ALARM LED indicator The indicator is out when normal working; it flashes quickly when maintenance; it turns on in red when alarm.5. NORMAL LED indicator It flashes in green always when the controller is power on and under normal working.6. LED curve Red LED indicators are equipped in the curve. The corresponding indicator flashes to indicate the fault reason when fault tripping. The corresponding indicator remains lit to indicate the current setting when protection settings.7. Test port A 16-pin test port is available on the bottom of front panel for plug-in portable power supply or inspection unit.

Keyboard 8. Function key 1 – Measurement: For measuring (In password input interface, the LEFT key) Press to enter the measurement default menu to measure current “I”, voltage “U’, frequency “F”, power “P”, energy “E”, and harmonic “H”.9. Function key 2 – Settings: For system parameter settings (In password input interface, the RIGHT key) Press to enter the setting default menu to set “Clock settings”, “Meter settings”, “Test & Lock”, “Communication settings”, “I/O settings”.10. Function key 3 – Protections: For protection parameter settings Press to set the parameters of “Current protection”, “Load monitor”, “Voltage protection”, and “Other protections”. 11. Function key 4 – Information: For history record and maintenance Press to check “Current alarm”, “Operation times”, “Contact wear”, “Product information”, “Tripping record”, “Alarm record”, “Transposition record”.12. UP – To move up or change the parameters upwards13. DOWN – To move down or change the parameters downwards.14. Esc – To exit and return to previous menu or cancel the current setting selection.15. ENTER – To enter the next menu, select the current parameter, or save the updates.

ESC

IR

Is

IsdIg

Ii

3SW68Intelligent controller

Reset

Fault/Alarm

Normal

8 9 10 11

12 13 14 15

1

2

3

45

6

7

ESC

Page 9: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-9www.sassin.com

Power Distribution Electrics

L type Intelligent controller panel(3SW68-2500、4000、6300)

1. Mechanical RESET button It pops up after tripping. Manual reset is required.2. Indication of intelligent controller model3. Operation indicator It remains flashing when the controller is under normal working.4. IR% 40%~100% indicator: To display the real time current as the percentage of IR.5. Indication of rated current (In)6. Simulation test area 6.1.Query key: check the last fault record (Record is shown as: one of the four fault indicators, IR, Isd, Ii, and Ig, becomes lighting. Press Clear button to clear indication). 6.2.Test key: When press Test Key under normal working status of controller, the breaker, commanded by the controller, trips instantaneously. Meanwhile, Ii fault indicator lights up, but no fault recorded. 6.3.Check key: self-diagnosis of inner working, each light will automatically scan, and will show a menu in one minute. 6.4.Clear button: clear the fault indicator7. Protect characteristic parameter setting area 7.1. IR (time-lapse protection) original setting is IR = 1.0 I n, t R = 480s. 7.2. I sd (short delay protection) original setting is I sd = 8 IR t sd = 0.4s (NO, OFF means inverse switch status default setting is OFF). 7.3. I i (instantaneous protection) original setting Ii =10In. 7.4. I g (ground fault protection) original setting I g = 0.8 I ntg = 0.4s.8. Fault indicator: Lighting when fault occurs.

运行 通信 遥控 故障

Electronic Controller

3SW68 L-

I R% Load current

40 60 80 100

In= A 4000

0.6

1.00.9

0.50.40.30.2

0.80.7

1.0

0.70.60.50.4 1.0

0.950.9

0.850.8

OFF

OFF

0.6

0.80.75

0.50.40.30.2

0.70.65

OFF

10864

321.5

1215

432

1512108

OFF

6

1

90604530 480

360240180120

15

0.10.2

0.40.30.20.1

0.30.4

2I t OFFON @8IR

@1.5 IR

Isd

Ii

Ig

tR S

tsd s

tg s

In

In

In

IR

IR

2

4

6

8

3

5

7

1

Operation

Quary Test Check Clear

Page 10: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-10 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

M type Intelligent controller panel (3SW68-2500、4000、6300)

1. Mechanical RESET button It pops up after tripping. Manual reset is required.2. Indication of intelligent controller model3. Power indicator: It keeps flashing when power on.4. LCD display5. Indication of rated current (In)6. Simulation test area

6.1. ENTER key: To enter or confirm menu.

6.2. ESC key: To return to previous menu or exit menu

6.3. UP DOWN key: To scroll up or down the menu

7. Protection characteristic parameter setting area7.1. IR ( long-time delay protection) default setting IR=1.0In, t R = 480s7.2. I sd (short delay protection) default setting Isd=8IR , tsd = 0.4s (NO, OFF means inverse switch, original setting is OFF)7.3. I i (instantaneous protection) default setting I i = 10 I n7.4. I g (ground fault protection) default setting I g = 0.8 I n, tg = 0.4s8. Fault indicator: Lighting when fault occurs.

Electronic Controller

3SW68-M

In= A

0.6

1.00.9

0.50.40.30.2

0.80.7

1.0

0.70.60.50.4 1.0

0.950.9

0.850.8

OFF

OFF

0.6

0.80.75

0.50.40.30.2

0.70.65

OFF

10864

321.5

1215

432

1512108

OFF

6

1

90604530 480

360240180120

15

0.10.2

0.40.30.20.1

0.30.4

2I t OFFON @8IR

@1.5 IR

Isd

Ii

Ig

tR

tsd

tg

In

In

In

IR

IR

0.6

1.00.9

0.50.40.30.2

0.80.7

1.0

ESCESC

0.70.60.50.4 1.0

0.950.9

0.850.8

OFF

OFF

0.6

0.80.75

0.50.40.30.2

0.70.65

OFF

10864

321.5

1215

432

1512108

OFF

6

1

90604530 480

360240180120

15

0.10.2

0.40.30.20.1

0.30.4

2I t OFFON @8IR

@1.5 IR

Isd

Ii

Ig

tR S

tsd S

tg(S)

In

In

In

IR

IR

4000

2

4

6

8

3

5

7

1

ESCESC

Operation

Page 11: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-11www.sassin.com

Power Distribution Electrics

ESCESC

In= A

Electronic Controller

3SW68 H-

RESET

Warn/Alarm

Healthy

BUS

IR

Is

I sd

I i

I g

4000

2

3

4

1

5

6

7

8

H type Intelligent controller panel(3SW68-2500、4000、6300)

1 Mechanical RESET buttonIt pops up after tripping. Manual reset is required.2. Indication of intelligent controller model3. LCD display4. Indication of rated current (In)5. Software RESET button6. Status indicator area7. Characteristic curve and protection reason indicator8. Function key area

.

Page 12: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-12 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Intelligent controller protection characteristics

SW68-L and 68-M3 3SW

OFF (Set by user) Setting current adjustment range IR(A)

tR(S) at 7.2IR

tR(S) at 2IR

1.05IR

≤2h action

2h no action

0.4xIn 0.45 0.5 0.55 0.6 0.7 0.8 0.9 1.0xIn xIn xIn xIn xIn xIn xIn xIn

15 30 60 120 240 480 Note: 30,60,120,240 for 3SW68-L(1600)

8.4 16.9 33.7 67.5 135 270

0.65 1.3 2.6 5.2 10.4 20.8

60 Note: 30 min for 3SW68-L(1600)

When 1>8IR

When 1>8IR

Inverse characteristic (set by user) I²tsd(s)(according to requirements set by the user) I²tsd(s)

0.1 0.2 0.3 0.4

0.06 0.14 0.23 0.35

As per characteristic curves

OFF 1.5xIR 2xIR 2.5xIR 3xIR 4xIR 5xIR 6xIR 8xIR 10xIR 12xIR 20xIR

Note: (3,4,6,8,10,12,15)In for 3SW68-L(1600)

OFF 0.2xIn 0.3xIn 0.4xIn 0.5xIn 0.6xIn 0.7xIn 0.8xIn 0.9xIn 1.0xIn

(Note: (0.2~0.8)In for 3SW68-L(1600)

0.1 0.2 0.3 0.4

0.06 0.14 0.23 0.35

Inverse time characteristics

1.3 1.25IR( IR for generator protection))

tR(S) at 1.5IR

Thermal memory time setting(min)

Returnable time (s)

Earth fault settings ( ±10%)accuracy

Setting current adjustment range Ig(A)

Overload alarm setting (accuracy ±10%)

Overload alarm currentDelay time tm (s)

Inverse time characteristics

0.5tR

when Im>IR

Setting current adjustment range Isd(A)

Definite characteristic (set by user) tsd(s) (according to requirements set by the user) tsd(s)

Instantaneous short-circuit setting (accuracy of ±10%)

Setting current adjustment range Ii(A)

Definite time characteristics ( set by user) tg(s)

Returnable time (s)

Inverse time characteristics (set by user) I²tsd(s)

OFF 1.5xIR 2xIR 2.5xIR 3xIR 4xIR 5xIR 6xIR 8xIR 10xIR 12xIR 20xIR Note:(3~10)IR for 3SW68-L(1600)

Overload long-time delay settings (accuracy ±10% based on tR(s) at 1.5IR)

Short-circuit short-time delay settings (accuracy ±10% based on tR(s) at 1.5IR when I<8IR)

As per characteristic curves

Page 13: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-13www.sassin.com

Power Distribution Electrics

3SW68-H

Setting current adjustment range Isd (A) ±10% accuracy

Short circuit short definite time Isd(A)

Setting delay time tsd(s)±15% accuracy

1/10tR (tR(s)when 1.5IR as a benchmark)

0.1 0.2 0.3 0.4 0.06 0.14 0.23 0.35

Instantaneous short-circuit ISetting current adjustment range Ig(A)±10% accuracy

Ground protection type T WSetting current adjustment range Ig(A)±10% accuracySetting delay time tg(s) ±15% accuracy 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

0.06 0.14 0.23 0.35 resetting ratio is 0.85

Current imbalancealarm/trip/off selectabe

alarm/trip/off selectabe

(When the three-phase current imbalance is greater than 1.1 times the set value,the protection action will be done.

(When the three-phase current imbalance is greater than 1.1 times the set value,the protection action will be done.

Required current protection

Setting range of value of start protection required(0.2~1)xInSetting range of protection action time required 15~1500s

Under voltage protection

Load monitoring (power based)

Over voltage protection

Alarm/trip selectable(When the three-phase current imbalance is greater than 1.1 times the set value,the protection action will be done; the return character will be lower than 0.9 setting value.

Made 1/mode 2/OFF selectableMeasurementFrequencyPower

Electric energy

Current DemandPower DemandHarmonic Self-test function

DI/DO FunctionZone selective interlocking featureTest function

40~65HzActive power: -32768kW~32768kWReactive power: -32768kar~32768karApparent power: 0kVA~65535kVAActive energy: 0~4294967295kWhReactive energy: 0~4294967295kWhApparent energy: 0~4294967295kWhCurrent real-time measurementsPower real-time measurementsCurrrent:3~31harmonicVoltage:3~31harmonicThe EEPROM fault, setting parameters lost, AD sampling error, RAM or ROM error, error messages and alarm signalsProvide digital input and output (AC250V 5A resistive or DC110V 0.5A resistive)Short circuit interlock and ground interlockTest release: Long-time delay, short-time delay ,instantaneous ,ground

ON/OFF selectable

1.05IR

1.30R(Generator protection 1.25IR)

Delay time

Inverse time characteristics

Thermal memory time setting

Setting current adjustment range Isd ±10% accuracy

8.4 16.9 33.8 67.5 135 2700.94 1.88 3.75 7.50 15 300.65 1.3 2.6 5.2 10.4 20.8

Instantaneous 10 20 30 45 60 120 180

Set by the user as needed, tR(s)when 1.5IR as a benchmark,10% accuracy)(0.4~1.0)xIn (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)

ON/OFF selectable(1.5~15)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)

ON/OFF selectable(1.5~15)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)

ON/OFF selectable(1.0~20)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)

ON/OFF selectable(0.2~1.0)xIR (Inm≤2500A step length 1A ;Inm>2500A,step length 2A)

Setting current adjustment range IR(A)

15 30 60 120 240 480

Alarm/trip selectable(When the current imbalance is greater than 1.1 times the set value,the protection action will be done; the return character will be lower than 0.9 setting value.

Overload long-time delay settings

≤2h action2h no action

tR(S) at 7.2IR

tR(S) at 2IRtR(S) at 1.5IR

tR(S) at 6.0IR

Short-circuit short-time delay settings

Returnable time (s)

Returnable time (s)

Page 14: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-14 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Current protection characteristics for intelligent controller

Monitor and controlling setting(R)

setting(lc1)

setting(lc1)

2l tswitch off2l tinput

t

0 I

Short-circuit short-time delay definite time (I²t OFF)

Overload long-time delay current setting IROverload long-time delay time setting tR

Short- circuit short-time delay current setting Isd Short-circuit short-time delay inverse time (I²t ON) Short-circuit short-time delay time setting tsd nstantaneous setting IiShort-circuit i

Long delay, short delay, instantaneous protection features

I

t

Characteristics curve

Earth fault current setting Ig

Earth fault delay time setting tg

Earth fault protection features

t

I

Page 15: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-15www.sassin.com

Power Distribution Electrics

Protection characteristics of intelligent controller 3SW68-H

Characteristics curve of overload protection

00801 02 03 05 081 1 5 2 3 5 8 10

10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

Ig earth fault protection current setting value tg fault protection time setting valueearth

0.4s0.3s0.2s0.1s

Ir4=0.2ln-1.01ln

t (s)

x ln

Earth fault protection characteristic curve

Isd

Ir3

Ir3

t (s)10000

5000

2000

1000

500

200

100

50

20

10

5

2

1

0.5

0.2

0.1

0.05

0.02

0.8 1 1.5 2 3 5 8 10 15 20

× IR

Ir1=0.4-1 X In

tL=15StL=30StL=60StL=120StL=240StL=480S

Ir2=1-15 x In

t

ts=0.3S

ts=0.2S

ts=0.1S

s=0.4S

kA30 60 90 100 120 150 200

Ir1: Overload long-delay setting Ir2: Short-circuit short-delay current settingIr3: Overload long-delay time settingTl: Instantaneous short-circuit current settingTs: Short-circuit short-delay time setting

Page 16: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-16 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Kinds of characteristic overview ( rate curve: C8)

Fast inverse time lag C8

trip

tim

e (s

ecs)

* Ir (setting value of long time delay)

standard inverse time lag C8 fast inverse time lag C8express inverse time lag C8 express inverse time lag(M) C8

high voltage fuse compatibility C8 2I t C1

0.01

0.1

1

10

100

1000

1 10

Express inverse time lag C8

* Ir (setting value of long time delay)

0.1

1

10

100

1000

1 10

* Ir (setting value of long time delay)

0.1

1

10

100

1000

10000

1 10

trip

tim

e (s

ecs)

trip

tim

e (s

ecs)

* Ir (setting value of long time delay)

0.1

1

10

100

1000

10000

1 10

trip

tim

e (s

ecs)

Standard inverse time lag C8

Page 17: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-17www.sassin.com

Power Distribution Electrics

The meaning of terminals

SB1

SB2SB3

S1~S7DW

XT

TA

FUFQ

QY

DT

M

SASAL

Q1~Q8Q9~Q14

Abbreviation MeaningClosing button (self-providedby user)Shunt button (self-provided byuser)Under-voltage button(self-provided by user)Indicator (self-provided by user)Circuit breaker

Secondary wiring circuit

Current mutual transformer

Fuse (self-provided by user)Shunt releaseUnder-voltage releaseUnder-voltage delay release with time delay Closed coil

Motor operating mechanism

Limit switch of motorContact for malfunction tripping indicatorAuxiliary contacts 4NO+4NCContacts for drawer 3-position indicator

Abbreviation Abbreviation Meaning Meaning

Connection diagram for the secondary circuit of the L-type intelligent controller

1 2 3 4

5 6 8 10 12 14 16 18 20 22 24 26

SB1 E

SB2 E

SB3 E

XT

DW

TA

AC220V/DC110-220V

DC24V

FU

M

SA

28

58 61 6446 49 52 5537 39 41 437 9 11 13 15 17 19 21 23 2527 29 31 33 35

30 32 34 36 38 40 42 44 45 47 48 50 51 53 54 56 57 59 60 62 63 65 66

Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13Q14

DT F Q/QY

P

FU

L N PE

12 13 14 15 16 17 18 19

S5 S6 S7S2 S3 S4S1

PE N

SAL

FU

- +

Electronic controller Auxiliary contact for user

Fault indicator Storage indicator Closing indictor Tripping indicator

Control power supply

Breaker body

ST Power modules TV

Shuntrelease

Closingelectromagnet

Contracteletromanet

Under-voltagerelease Drawer three-position indication

Electronic controller

Maincircuit

#1, #2: Input terminal of auxiliary power supply; #1 is the positive pole.P: Protective ground terminal to connect the side plate of the breaker.#3, #4, #5: SDE malfunction tripping output contacts (#4 is the common terminal); contact capacity: AC380V 16A#13, #14, #19, #20, #21: #19 is the output common terminal; #20 is output contact No.1 (D01) for self-diagnosis function; #21 is output contact No.2 (D02) for malfunction tripping function; #13 is output contact No.3 (D03) for overload warning function; #14 is output contact No.4 (D04) for grounding alarm function.#25, #26: To connect external current transformer (For 3P+N only)Note:1)It is necessary to select power supply unit when DC control power is applied. Connect the DC control power to power supply unit, where the output contacts have already been connected before delivery.2)Normally it is not necessary to select power supply unit when AC control power is applied; just simply connect the power supply to the terminal #1 and #2. In case you require power supply unit, please make the connection according to the wiring diagram. The output contacts of the unit have already been connected before delivery.3)Drawer 3-position indicator is an optional device for users.4)The connections marked in the dotted lines are to be made by the users.5)The conditions that the controller outputs self-diagnosis signal:a.Controller internal temperature ≥80℃b.Chip works abnormallyc.Controller loses power6)Different power supplies can be connected when the control voltages of DT, F and Q/QY are not same.7)A pushbutton with normal open contact can be installed in series between the terminal #42 and power supply for manually controlling pre-storage.8)SB2 can be connected in parallel to relay contacts for remote tripping.9)Additional accessories need to be self-provided by users.

Page 18: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-18 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

1 2 5 6 7 8 9 10 13 15 16 29 30

3 4 17 18 19 20 21 22 23 24

12

25

A (+) B (-)

L1~L4

P1~P3

ZT100

DW

ZCT

A,B,C

N

A (+) B (-)

D01 D02

D03 OR DI2 D04 OR DI1

P 11 14

282726

DC24V

Un U1 U2 U3

Power input

Auxiliary contacts synchronous with the circuit breaker

Communication ground wire Communication

port

Add N-phase input in 3P + N

3SW68-1600 Intelligent controllerLinear signal coil

Power mutual inductor Add mutual inductor input in ground or leakage

Voltage measurement signal input

Center ground lug

Programmable input / Output contacts

To the power line side

Figure: input and output interfaces of 3SW68-1600 type M, H

Connection port of 3SW68-1600(type M、H)

1 2

6 8 10 12 14 16 18 20 22 24 26

SB1 E

SB2 E

SB3 E

XT

DW

TA

AC220V/DC110-220V

DC24V

FU

M

SA

28

58 61 6446 49 52 5537 39 41 4311 13 15 17 19 21 23 25 27 29 31 33 35

30 32 34 36 38 40 42 44 45 47 48 50 51 53 54 56 57 59 60 62 63 65 66

Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13Q14

DT F Q/QY

P

FU

L N PE

12 13 14 15 16 17 18 19

S5 S6 S7S4S1

PE N

SAL

FU

- +

5 7 9

3 4

S3S2

Contract electromagnet

Under-voltagerelease Auxiliary contact for user Drawer 3-position indicator

Control power supply

Electronic controllerBreaker body

Main circuit Electronic controller Closing

electromagnet Shunt release

Fault indicator Storage instruction Closing instruction Tripping indication

ST Power modules TV

Note: Short 3 and 4 when no external currenttransformer needs to beconnected

Connection diagram for secondary circuit of the M , H-type intelligent controller

Qa Qb Qc Qd

Page 19: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-19www.sassin.com

Power Distribution Electrics

SB1SB2SB3

S1~S7DWXT

TAFUFQ

QYDT

MSA

SAL

Q1~Q8Q9~Q14

Meaning Abbreviation Meaning Meaning

TN

Qa , QbQc , Qd

Motor operating mechanism Limit switch of MotorContact for malfunction tripping indicatorContacts for closing indicatorContacts for tripping indicatorAuxiliary contacts 4NO+4NCContacts for drawer 3-position indicator

Current mutual transformerFuse (self-provided by user)Shunt releaseUnder-voltage releaseUnder-voltage delay release with time delay Closed coil

AbbreviationAbbreviationClosing button (self-provided by user)Shunt button (self-provided by user)Under-voltage button(self-provided by user)Indicator (self-provided by user)Circuit breakerSecondary wiring circuitResidual current transformer (can be supplied upon user’s request)

The meaning of terminalsPower supply input#1, #2: DC24V #1: positive pole #2: negative pole; P: Protective ground terminal to connect the side plate of the breaker.External current transformer inputTerminals #3, #4 are for external current transformer input.The terminals are to be connected to the output terminals of external current transformer ZT100 when the grounding method is type T.The terminals are to be connected to the output terminals of external rectangular current transformer ZCT1 when the grounding method is type W.Auxiliary contacts for malfunction trippingTerminals #5, #6, #7 are the contacts for malfunction tripping indicator. Contact capacity: AC380V 2A; DC250V 0.3AAuxiliary contacts synchronous with circuit breakerTerminals #8, #9, #10, #11, #12, #14 are two sets of auxiliary contacts synchronous with circuit breaker. Contact capacity: AC380V 1A; DC250V 0.15ACommunication output#15, #16: Communication interface output. The output methods of three communication protocols are the same. #15 and #16 are blank when with communication function.#13: Communication shielding groundProgrammable I/O interfaceTerminals #17~#24 are blank when signal unit is not selected. (DO: DC11V 0.5A, AC250V 5A; DI: DC11V~13V AC110V~250V)When the signal unit is type S1: (4DO mode)#17, #18: Programmable output contact No.1 (DO1)#19, #20: Programmable output contact No.2 (DO2)#21, #22: Programmable output contact No.3 (DO3)#23, #24: Programmable output contact No.4 (DO4)When the signal unit is type S2: (3DO+1DI mode)#17, #18: Programmable output contact No.1 (DO1)#19, #20: Programmable output contact No.2 (DO2)#21, #22: Programmable output contact No.3 (DO3)#23, #24: Programmable switching input No.1 (DI1)When the signal unit is type S3: (3DO+1DI mode)#17, #18: Programmable output contact No.1 (DO1)#19, #20: Programmable output contact No.2 (DO2)

#21, #22: Programmable switching input No.1 (DI1)#23, #24: Programmable switching input No.2 (DI2)Voltage signal inputTerminals #25~#28 are the input terminal of voltage signal. Please pay attention that the connection sequence must be right and they must be connected to the line side of the power supply. The terminals are blank if no additional functions are selected.Terminals #29~#30 are to be connected to signal input of neutral line with an external current transformer when grounding method is 3P+N.Note:1) It is necessary to select power supply unit when DC control power is applied. Connect the DC control power to power supply unit, where the output contacts have already been connected before delivery.2) Normally it is not necessary to select power supply unit when AC control power is applied; just simply connect the power supply to the terminal #1 and #2. In case you require power supply unit, please make the connection according to the wiring diagram. The output contacts of the unit have already been connected before delivery.3) Drawer 3-position indicator is an optional device for users.4) The connections marked in the dotted lines are to be made by the users.5) The conditions that the controller outputs self-diagnosis signal:a. Controller internal temperature ≥80℃b. Chip works abnormallyc. Controller loses power6) Different power supplies can be connected when the control voltages of DT, F and Q/QY are not same.7) A pushbutton with normal open contact can be installed in series between the terminal #42 and power supply for manually controlling pre-storage.8) SB2 can be connected in parallel to relay contacts for remote tripping.9) Additional accessories need to be self-provided by users.

Page 20: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-20 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Secondary circuit wiring diagram equipped with Intelligent controller (3SW68-2500、4000、6300)

Main circuit

Position indication

Control unitUnder

voltageElectric

switch onElectric

switch offElectric energy storage

Ready-for-close

Remote

resetAuxiliary sw

itch

ConnectionTest

Separation

Fault tripping

Switch on

Switch off

Ready-for-charging

Circuit breakerPow

er source

Draw-out base communication

module

Power module output

Six line program-mable extended output module

Ready-for-close

Auxiliary switch

Intelligent controller

Auxiliary open mode

Four groups convertible contactFour pieces of normally-open and four pieces of normally-closed contacts

Six-group convertible contactSix pieces of normally-open and six pieces of normally-closed contacts

picture 1Perm

utation and combination of external term

inal picture 2

Permutation and com

bination of internal terminal

picture 3

Page 21: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-21www.sassin.com

Power Distribution Electrics

Explanation of terminal block:1#、2#: Auxiliary power input 1# is“+” 2# is“-”if it is direct current3#、4#、5#、6#: A、B、C、N three-phase voltage input terminal are used for voltage indication (optional)7#、8#、9#:Fault trip indication signal output10#、11#、12#:Switch on indication signal output 13#、14#、15#:Switch off indication signal output16#、17#:Programmable output 1(optional)18#、19#:Programmable output 2(optional)20#、21#:ZS1 signal output,20# connects“+”,21# connects“-”(optional)22#、23#:ZS1signal output,22# connects“-”,23# connects“+”(optional)24#、25#、26#:Intelligent controller communication terminal,24# connects with SH Shielding layer, 25# connects A,26# connects B, but connects with the draw-out-base communication module input if there is a draw-out-base communication module,24# connects S',25# connects A',26# connects B'(optional)27#、28#:Added earth current or current leakage type transformer input(optional)29#、30#:External neutral current transformer input (optional)31#、32#、33#:Under voltage(or time delayed)release power input, 33# is empty terminal(optional)34#、35#、36#:Closing electromagnet power input,36# is empty terminal37#、38#、39#:Shunt release power input,39# is empty terminal40#、41#、42#:Energy storage electrically operated power input and energy storage ready signal output.43#、44#、45#:Open ready signal output(optional)46#、47#、48#: Remote reset power input, 48# is empty terminal (optional)49#、50#、51#:Programmable extended output,49# connects A,50# connects B, 51# is empty terminal(optional)52#、53#、54#:Empty terminal(Spare)55#~58#:Auxiliary switch for connecting terminal output

Explanation of symbol

Under-voltage button (Self-provided by user)Closing button (Self-provided by user)Shunt button (Self-provided by user) Remote reset button (Self-provided by user)Shunt releaseRemote control closed relay (Self-provided by user)Remote control trip relay (Self-provided by user)

SB1SB2SB3SB4

FJ1 J2

Under-voltage (or time delayed) releaseClosing electromagnetElectric motor operating mechanismElectric motor limit switchTerminal blockFuse

QX M SAXT Fu

Abbreviation Meaning Abbreviation Meaning

A1~A6: Three position signal output(optional)B1~B6: Empty terminal(Spare)T1~T4: Three position signal input(optional)S、A、B:Communication output(optional)

Illustration1.The corresponding circuit breakers in the diagram are switched off and no energy stored. The controller indicates no fault2.The dotted line part shall be connected by user, the picture is for reference only.3. 1#, 2# terminal power source must be prepared when the main loop current is 0.4 In. The DC24V、AC230VAC or 400V power can be connected depending on controller power type. The power then connects with DC 110VD and C220V after converted by power module.4. Q, X, F, M connects different control power sources depending on respective voltage specifications. Please note X, F are short-time duty components, the electrified time should not exceed 4 seconds.5.37# terminal directly connects power source (see the picture) (automatic pre-energy storage). It can also connect power source after serially connecting the normally open button (Manual pre-energy storage).6.The three position signal sampling from the draw-out base communication module should be processed by optical coupling isolation.7. The outdoor terminal which fixed on the drawing frame of breaker, wiring connection is according to picture 2; the terminal which fixed in internal breaker, wiring connection is according to picture 3.

Page 22: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Selection and ordering data

200 3P4P

400 3P4P

630 3P4P

800 3P4P

1000 3P4P

1250 3P4P

1600 3P4P

Number ofpoles Type code Order code Type code Order code

Fixed type Drawer type

L type controller

In(A)

Frame A3SW68-1600 Horizontal terminal connection

Vertical terminal connection200 3P

4P400 3P

4P630 3P

4P800 3P

4P1000 3P

4P1250 3P

4P1600 3P

4PHorizontal terminal connection

200

400

630

800

1000

1250

1600

3P4P3P4P3P4P3P4P3P4P3P4P3P4P

W68AF 3LH200NW68AF 4LH200NW68AF 3LH400NW68AF 4LH400NW68AF 3LH630NW68AF 4LH630NW68AF 3LH800NW68AF 4LH800NW68AF 3LH1000NW68AF 4LH1000NW68AF 3LH1250NW68AF 4LH1250NW68AF 3LH1600NW68AF 4LH1600N

2805728058280592806028061280622806328064280652806628067280682806928070

W68AD 3LH200NW68AD 4LH200NW68AD 3LH400NW68AD 4LH400NW68AD 3LH630NW68AD 4LH630NW68AD 3LH800NW68AD 4LH800NW68AD 3LH1000NW68AD 4LH1000NW68AD 3LH1250NW68AD 4LH1250NW68AD 3LH1600NW68AD 4LH1600N

2809928100281012810228103281042810528106281072810828109281102811128112

3W68AF 3LV200N4W68AF 4LV200N3W68AF 3LV400N4W68AF 4LV400N3W68AF 3LV630N4W68AF 4LV630N3W68AF 3LV800N4W68AF 4LV800N3W68AF 3LV1000N4W68AF 4LV1000N3W68AF 3LV1250N4W68AF 4LV1250N3W68AF 3LV1600N4W68AF 4LV1600N

2807128072280732807428075280762807728078280792808028081280822808328084

W68AD 3LV200NW68AD 4LV200NW68AD 3LV400NW68AD 4LV400NW68AD 3LV630NW68AD 4LV630NW68AD 3LV800NW68AD 4LV800NW68AD 3LV1000NW68AD 4LV1000NW68AD 3LV1250NW68AD 4LV1250NW68AD 3LV1600NW68AD 4LV1600N

2811328114281152811628117281182811928120281212812228123281242812528126

N type65kA

H type65kA W68AF 3LH200H

W68AF 4LH200HW68AF 3LH400HW68AF 4LH400HW68AF 3LH630HW68AF 4LH630HW68AF 3LH800HW68AF 4LH800HW68AF 3LH1000HW68AF 4LH1000HW68AF 3LH1250HW68AF 4LH1250HW68AF 3LH1600HW68AF 4LH1600H

W68AD 3LH200HW68AD 4LH200HW68AD 3LH400HW68AD 4LH400HW68AD 3LH630HW68AD 4LH630HW68AD 3LH800HW68AD 4LH800HW68AD 3LH1000HW68AD 4LH1000HW68AD 3LH1250HW68AD 4LH1250HW68AD 3LH1600HW68AD 4LH1600H

2814128142281432814428145281462814728148281492815028151281522815328154

2818328184281852818628187281882818928190281912819228193281942819528196

Rated current

Air Circuit BreakersSeries 3SW68

1-22 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Page 23: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

200

400

630

800

1000

1250

1600

Type code Order code Type code Order codeFixed type Drawer type

In(A)3P4P3P4P3P4P3P4P3P4P3P4P3P4P

Vertical terminal connection

200

400

630

800

1000

1250

1600

3P4P3P4P3P4P3P4P3P4P3P4P3P4P

M type controllerHorizontal terminal connection

H type65kA

W68AF 3LV200HW68AF 4LV200HW68AF 3LV400HW68AF 4LV400HW68AF 3LV630HW68AF 4LV630HW68AF 3LV800HW68AF 4LV800HW68AF 3LV1000HW68AF 4LV1000HW68AF 3LV1250HW68AF 4LV1250HW68AF 3LV1600HW68AF 4LV1600H

2815528156281572815828159281602816128162281632816428165281662816728168

W68AD 3LV200HW68AD 4LV200HW68AD 3LV400HW68AD 4LV400HW68AD 3LV630HW68AD 4LV630HW68AD 3LV800HW68AD 4LV800HW68AD 3LV1000HW68AD 4LV1000HW68AD 3LV1250HW68AD 4LV1250HW68AD 3LV1600HW68AD 4LV1600H

2819728198281992820028201282022820328204282052820628207282082820928210

N type65kA W68AF 3MH200N

W68AF 4MH200NW68AF 3MH400NW68AF 4MH400NW68AF 3MH630NW68AF 4MH630NW68AF 3MH800NW68AF 4MH800NW68AF 3MH1000NW68AF 4MH1000NW68AF 3MH1250NW68AF 4MH1250NW68AF 3MH1600NW68AF 4MH1600N

2822528226282272822828229282302823128232282332823428235282362823728238

W68AD 3MH200NW68AD 4MH200NW68AD 3MH400NW68AD 4MH400NW68AD 3MH630NW68AD 4MH630NW68AD 3MH800NW68AD 4MH800NW68AD 3MH1000NW68AD 4MH1000NW68AD 3MH1250NW68AD 4MH1250NW68AD 3MH1600NW68AD 4MH1600N

2826728268282692827028271282722827328274282752827628277282782827928280

Vertical terminal connection200 3P

4P400 3P

4P630 3P

4P800 3P

4P1000 3P

4P1250 3P

4P1600 3P

4P

W68AF 3MV200NW68AF 4MV200NW68AF 3MV400NW68AF 4MV400NW68AF 3MV630NW68AF 4MV630NW68AF 3MV800NW68AF 4MV800NW68AF 3MV1000NW68AF 4MV1000NW68AF 3MV1250NW68AF 4MV1250NW68AF 3MV1600NW68AF 4MV1600N

2823928240282412824228243282442824528246282472824828249282502825128252

W68AD 3MV200NW68AD 4MV200NW68AD 3MV400NW68AD 4MV400NW68AD 3MV630NW68AD 4MV630NW68AD 3MV800NW68AD 4MV800NW68AD 3MV1000NW68AD 4MV1000NW68AD 3MV1250NW68AD 4MV1250NW68AD 3MV1600NW68AD 4MV1600N

2828128282282832828428285282862828728288282892829028291282922829328294

Rated current Number ofpoles

L type controllerFrame A3SW68-1600

Air Circuit BreakersSeries 3SW68

1-23www.sassin.com

Power Distribution Electrics

Page 24: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

200 3P4P

400 3P4P

630 3P4P

800 3P4P

1000 3P4P

1250 3P4P

1600 3P4P

Type code Order code Type code Order codeFixed type Drawer type

M type controller

In(A)

Frame A3SW68-1600 Horizontal terminal connection

Vertical terminal connection200 3P

4P400 3P

4P630 3P

4P800 3P

4P1000 3P

4P1250 3P

4P1600 3P

4P

H type65kA

W68AF 3MH200HW68AF 4MH200HW68AF 3MH400HW68AF 4MH400HW68AF 3MH630HW68AF 4MH630HW68AF 3MH800HW68AF 4MH800HW68AF 3MH1000HW68AF 4MH1000HW68AF 3MH1250HW68AF 4MH1250HW68AF 3MH1600HW68AF 4MH1600H

2830928310283112831228313283142831528316283172831828319283202832128322

W68AD 3MH200HW68AD 4MH200HW68AD 3MH400HW68AD 4MH400HW68AD 3MH630HW68AD 4MH630HW68AD 3MH800HW68AD 4MH800HW68AD 3MH1000HW68AD 4MH1000HW68AD 3MH1250HW68AD 4MH1250HW68AD 3MH1600HW68AD 4MH1600H

2835128352283532835428355283562835728358283592836028361283622836328364

W68AF 3MV200HW68AF 4MV200HW68AF 3MV400HW68AF 4MV400HW68AF 3MV630HW68AF 4MV630HW68AF 3MV800HW68AF 4MV800HW68AF 3MV1000HW68AF 4MV1000HW68AF 3MV1250HW68AF 4MV1250HW68AF 3MV1600HW68AF 4MV1600H

2832328324283252832628327283282832928330283312833228333283342833528336

W68AD 3MV200HW68AD 4MV200HW68AD 3MV400HW68AD 4MV400HW68AD 3MV630HW68AD 4MV630HW68AD 3MV800HW68AD 4MV800HW68AD 3MV1000HW68AD 4MV1000HW68AD 3MV1250HW68AD 4MV1250HW68AD 3MV1600HW68AD 4MV1600H

2836528366283672836828369283702837128372283732837428375283762837728378

200 3P4P

400 3P4P

630 3P4P

800 3P4P

1000 3P4P

1250 3P4P

1600 3P4P

H type controllerHorizontal terminal connectionN type

65kA W68AF 3HH200NW68AF 4HH200NW68AF 3HH400NW68AF 4HH400NW68AF 3HH630NW68AF 4HH630NW68AF 3HH800NW68AF 4HH800NW68AF 3HH1000NW68AF 4HH1000NW68AF 3HH1250NW68AF 4HH1250NW68AF 3HH1600NW68AF 4HH1600N

2839328394283952839628397283982839928400284012840228403284042840528406

W68AD 3HH200NW68AD 4HH200NW68AD 3HH400NW68AD 4HH400NW68AD 3HH630NW68AD 4HH630NW68AD 3HH800NW68AD 4HH800NW68AD 3HH1000NW68AD 4HH1000NW68AD 3HH1250NW68AD 4HH1250NW68AD 3HH1600NW68AD 4HH1600N

2843528436284372843828439284402844128442284432844428445284462844728448

Rated current Number ofpoles

Air Circuit BreakersSeries 3SW68

1-24 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Page 25: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Type code Order code Type code Order codeFixed type Drawer type

W68AF 3HV200NW68AF 4HV200NW68AF 3HV400NW68AF 4HV400NW68AF 3HV630NW68AF 4HV630NW68AF 3HV800NW68AF 4HV800NW68AF 3HV1000NW68AF 4HV1000NW68AF 3HV1250NW68AF 4HV1250NW68AF 3HV1600NW68AF 4HV1600N

2840728408284092841028411284122841328414284152841628417284182841928420

W68AD 3HV200NW68AD 4HV200NW68AD 3HV400NW68AD 4HV400NW68AD 3HV630NW68AD 4HV630NW68AD 3HV800NW68AD 4HV800NW68AD 3HV1000NW68AD 4HV1000NW68AD 3HV1250NW68AD 4HV1250NW68AD 3HV1600NW68AD 4HV1600N

2844928450284512845228453284542845528456284572845828459284602846128462

W68AF 3HH200HW68AF 4HH200HW68AF 3HH400HW68AF 4HH400HW68AF 3HH630HW68AF 4HH630HW68AF 3HH800HW68AF 4HH800HW68AF 3HH1000HW68AF 4HH1000HW68AF 3HH1250HW68AF 4HH1250HW68AF 3HH1600HW68AF 4HH1600H

2847728478284792848028481284822848328484284852848628487284882848928490

W68AD 3HH200HW68AD 4HH200HW68AD 3HH400HW68AD 4HH400HW68AD 3HH630HW68AD 4HH630HW68AD 3HH800HW68AD 4HH800HW68AD 3HH1000HW68AD 4HH1000HW68AD 3HH1250HW68AD 4HH1250HW68AD 3HH1600HW68AD 4HH1600H

2851928520285212852228523285242852528526285272852828529285302853128532

W68AF 3HV200HW68AF 4HV200HW68AF 3HV400HW68AF 4HV400HW68AF 3HV630HW68AF 4HV630HW68AF 3HV800HW68AF 4HV800HW68AF 3HV1000HW68AF 4HV1000HW68AF 3HV1250HW68AF 4HV1250HW68AF 3HV1600HW68AF 4HV1600H

2849128492284932849428495284962849728498284992850028501285022850328504

W68AD 3HV200HW68AD 4HV200HW68AD 3HV400HW68AD 4HV400HW68AD 3HV630HW68AD 4HV630HW68AD 3HV800HW68AD 4HV800HW68AD 3HV1000HW68AD 4HV1000HW68AD 3HV1250HW68AD 4HV1250HW68AD 3HV1600HW68AD 4HV1600H

2853328534285352853628537285382853928540285412854228543285442854528546

H type controllerFrame A3SW68-1600

200

400

630

800

1000

1250

1600

In(A)3P4P3P4P3P4P3P4P3P4P3P4P3P4P

Vertical terminal connection

200

400

630

800

1000

1250

1600

3P4P3P4P3P4P3P4P3P4P3P4P3P4P

Horizontal terminal connectionH type65kA

Vertical terminal connection200 3P

4P400 3P

4P630 3P

4P800 3P

4P1000 3P

4P1250 3P

4P1600 3P

4P

Rated current Number ofpoles

Air Circuit BreakersSeries 3SW68

1-25www.sassin.com

Power Distribution Electrics

Page 26: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

L type controllerFrame B3SW68-2500

1250 3P4P

1600 3P4P

2000 3P4P

2500 3P4P

Type codeIn(A)

Horizontal terminal connection

Vertical terminal connection1250 3P

4P1600 3P

4P2000 3P

4P2500 3P

4P

1250

1600

2000

2500

3P4P3P4P3P4P3P4P

Horizontal terminal connection

Vertical terminal connection1250 3P

4P1600 3P

4P2000 3P

4P2500 3P

4P

1250

1600

2000

2500

3P4P3P4P3P4P3P4P

M type controllerHorizontal terminal connection

N type65kA

H type85kA

W68BF 3LH1250NW68BF 4LH1250NW68BF 3LH1600NW68BF 4LH1600NW68BF 3LH2000NW68BF 4LH2000NW68BF 3LH2500NW68BF 4LH2500N

W68BF 3LV1250NW68BF 4LV1250NW68BF 3LV1600NW68BF 4LV1600NW68BF 3LV2000NW68BF 4LV2000NW68BF 3LV2500NW68BF 4LV2500N

W68BF 3LH1250HW68BF 4LH1250HW68BF 3LH1600HW68BF 4LH1600HW68BF 3LH2000HW68BF 4LH2000HW68BF 3LH2500HW68BF 4LH2500H

W68BF 3LV1250HW68BF 4LV1250HW68BF 3LV1600HW68BF 4LV1600HW68BF 3LV2000HW68BF 4LV2000HW68BF 3LV2500HW68BF 4LV2500H

N type65kA W68BF 3MH1250N

W68BF 4MH1250NW68BF 3MH1600NW68BF 4MH1600NW68BF 3MH2000NW68BF 4MH2000NW68BF 3MH2500NW68BF 4MH2500N

Rated current Number ofpoles Order code Type code Order Code

Fixed type Drawer type

2856128562285632856428565285662856728568

W68BD 3LH1250NW68BD 4LH1250NW68BD 3LH1600NW68BD 4LH1600NW68BD 3LH2000NW68BD 4LH2000NW68BD 3LH2500NW68BD 4LH2500N

2857728578285792858028581285822858328584

2856928570285712857228573285742857528576

W68BD 3LV1250NW68BD 4LV1250NW68BD 3LV1600NW68BD 4LV1600NW68BD 3LV2000NW68BD 4LV2000NW68BD 3LV2500NW68BD 4LV2500N

2858528586285872858828589285902859128592

2859328594285952859628597285982859928600

W68BD 3LH1250HW68BD 4LH1250HW68BD 3LH1600HW68BD 4LH1600HW68BD 3LH2000HW68BD 4LH2000HW68BD 3LH2500HW68BD 4LH2500H

2860928610286112861228613286142861528616

2860128602286032860428605286062860728608

W68BD 3LV1250HW68BD 4LV1250HW68BD 3LV1600HW68BD 4LV1600HW68BD 3LV2000HW68BD 4LV2000HW68BD 3LV2500HW68BD 4LV2500H

1821418215182161821718218182191822018221

1822218223182241822518226182271822818229

W68BD 3MH1250NW68BD 4MH1250NW68BD 3MH1600NW68BD 4MH1600NW68BD 3MH2000NW68BD 4MH2000NW68BD 3MH2500NW68BD 4MH2500N

1823818239182401824118242182431824418245

Air Circuit BreakersSeries 3SW68

1-26 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Page 27: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

1250

1600

2000

2500

Type code Order code Type Code Order CodeFixed type Drawer type

In(A)3P4P3P4P3P4P3P4P

Frame B3SW68-2500

Mtype controllerVertical terminal connection

W68BF 3MV1250NW68BF 4MV1250NW68BF 3MV1600NW68BF 4MV1600NW68BF 3MV2000NW68BF 4MV2000NW68BF 3MV2500NW68BF 4MV2500N

1823018231182321823318234182351823618237

W68BD 3MV1250NW68BD 4MV1250NW68BD 3MV1600NW68BD 4MV1600NW68BD 3MV2000NW68BD 4MV2000NW68BD 3MV2500NW68BD 4MV2500N

1824618247182481824918250182511825218253

1250

1600

2000

2500

3P4P3P4P3P4P3P4P

H type85kA W68BF 3MH1250H

W68BF 4MH1250HW68BF 3MH1600HW68BF 4MH1600HW68BF 3MH2000HW68BF 4MH2000HW68BF 3MH2500HW68BF 4MH2500H

1825418255182561825718258182591826018261

Horizontal terminal connectionW68BD 3MH1250HW68BD 4MH1250HW68BD 3MH1600HW68BD 4MH1600HW68BD 3MH2000HW68BD 4MH2000HW68BD 3MH2500HW68BD 4MH2500H

1827018271182721827318274182751827618277

1250

1600

2000

2500

3P4P3P4P3P4P3P4P

Vertical terminal connectionW68BF 3MV1250HW68BF 4MV1250HW68BF 3MV1600HW68BF 4MV1600HW68BF 3MV2000HW68BF 4MV2000HW68BF 3MV2500HW68BF 4MV2500H

1826218263182641826518266182671826818269

W68BD 3MV1250HW68BD 4MV1250HW68BD 3MV1600HW68BD 4MV1600HW68BD 3MV2000HW68BD 4MV2000HW68BD 3MV2500HW68BD 4MV2500H

1827818279182801828118282182831828418285

1250

1600

2000

2500

3P4P3P4P3P4P3P4P

H type controller

Vertical terminal connection1250

1600

2000

2500

3P4P3P4P3P4P3P4P

Horizontal terminal connectionN type65kA W68BF 3HH1250N

W68BF 4HH1250NW68BF 3HH1600NW68BF 4HH1600NW68BF 3HH2000NW68BF 4HH2000NW68BF 3HH2500NW68BF 4HH2500N

1828618287182881828918290182911829218293

W68BD 3HH1250NW68BD 4HH1250NW68BD 3HH1600NW68BD 4HH1600NW68BD 3HH2000NW68BD 4HH2000NW68BD 3HH2500NW68BD 4HH2500N

1830218303183041830518306183071830818309

W68BF 3HV1250NW68BF 4HV1250NW68BF 3HV1600NW68BF 4HV1600NW68BF 3HV2000NW68BF 4HV2000NW68BF 3HV2500NW68BF 4HV2500N

1829418295182961829718298182991830018301

W68BD 3HV1250NW68BD 4HV1250NW68BD 3HV1600NW68BD 4HV1600NW68BD 3HV2000NW68BD 4HV2000NW68BD 3HV2500NW68BD 4HV2500N

1831018311183121831318314183151831618317

N type65kA Rated current Number of

poles

Air Circuit BreakersSeries 3SW68

1-27www.sassin.com

Power Distribution Electrics

Page 28: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

2000

2500

3200

4000

3P4P3P4P3P4P3P4P

L type controllerHorizontal terminal connection

Vertical terminal connection2000 3P

4P2500 3P

4P3200 3P

4P4000 3P

4P

1250

1600

2000

2500

Type code Order code Type code Order codeFixed type Drawer type

In(A)3P4P3P4P3P4P3P4P

H type controller

1250

1600

2000

2500

3P4P3P4P3P4P3P4P

Horizontal terminal connectionH type85kA

W68BF 3HH1250HW68BF 4HH1250HW68BF 3HH1600HW68BF 4HH1600HW68BF 3HH2000HW68BF 4HH2000HW68BF 3HH2500HW68BF 4HH2500H

1831818319183201832118322183231832418325

W68BD 3HH1250HW68BD 4HH1250HW68BD 3HH1600HW68BD 4HH1600HW68BD 3HH2000HW68BD 4HH2000HW68BD 3HH2500HW68BD 4HH2500H

1833418335183361833718338183391834018341

W68BF 3HV1250HW68BF 4HV1250HW68BF 3HV1600HW68BF 4HV1600HW68BF 3HV2000HW68BF 4HV2000HW68BF 3HV2500HW68BF 4HV2500H

1832618327183281832918330183311833218333

W68BD 3HV1250HW68BD 4HV1250HW68BD 3HV1600HW68BD 4HV1600HW68BD 3HV2000HW68BD 4HV2000HW68BD 3HV2500HW68BD 4HV2500H

1834218343183441834518346183471834818349

Frame B3SW68-2500

N type85kA 18350

18351183521835318354183551835618357

W68CD 3LH2000NW68CD 4LH2000NW68CD 3LH2500NW68CD 4LH2500NW68CD 3LH3200NW68CD 4LH3200NW68CD 3LH4000NW68CD 4LH4000N

1836618367183681836918370183711837218373

1835818359183601836118362183631836418365

W68CD 3LV2000NW68CD 4LV2000NW68CD 3LV2500NW68CD 4LV2500NW68CD 3LV3200NW68CD 4LV3200NW68CD 3LV4000NW68CD 4LV4000N

1837418375183761837718378183791838018381

2000 3P4P

2500 3P4P

3200 3P4P

4000 3P4P

Horizontal terminal connectionH type100kA 18382

18383183841838518386183871838818389

W68CD 3LH2000HW68CD 4LH2000HW68CD 3LH2500HW68CD 4LH2500HW68CD 3LH3200HW68CD 4LH3200HW68CD 3LH4000HW68CD 4LH4000H

1839818399184001840118402184031840418405

W68CF 3LH2000NW68CF 4LH2000NW68CF 3LH2500NW68CF 4LH2500NW68CF 3LH3200NW68CF 4LH3200NW68CF 3LH4000NW68CF 4LH4000N

W68CF 3LV2000NW68CF 4LV2000NW68CF 3LV2500NW68CF 4LV2500NW68CF 3LV3200NW68CF 4LV3200NW68CF 3LV4000NW68CF 4LV4000N

W68CF 3LH2000HW68CF 4LH2000HW68CF 3LH2500HW68CF 4LH2500HW68CF 3LH3200HW68CF 4LH3200HW68CF 3LH4000HW68CF 4LH4000H

Rated current

Vertical terminal connection

2000

2500

3200

4000

3P4P3P4P3P4P3P4P

Vertical terminal connection1839018391183921839318394183951839618397

W68CD 3LV2000HW68CD 4LV2000HW68CD 3LV2500HW68CD 4LV2500HW68CD 3LV3200HW68CD 4LV3200HW68CD 3LV4000HW68CD 4LV4000H

1840618407184081840918410184111841218413

W68CF 3LV2000HW68CF 4LV2000HW68CF 3LV2500HW68CF 4LV2500HW68CF 3LV3200HW68CF 4LV3200HW68CF 3LV4000HW68CF 4LV4000H

Frame C3SW68-4000

Number ofpoles

Air Circuit BreakersSeries 3SW68

1-28 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Page 29: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

L type controllerFrame C3SW68-4000

1842218423184241842518426184271842818429

W68CD 3LV2000SW68CD 4LV2000SW68CD 3LV2500SW68CD 4LV2500SW68CD 3LV3200SW68CD 4LV3200SW68CD 3LV4000SW68CD 4LV4000S

2000 3P4P

2500 3P4P

3200 3P4P

4000 3P4P

W68CF 3LH2000SW68CF 4LH2000SW68CF 3LH2500SW68CF 4LH2500SW68CF 3LH3200SW68CF 4LH3200SW68CF 3LH4000SW68CF 4LH4000S

1841418415184161841718418184191842018421

1843018431184321843318434184351843618437

W68CD 3LH2000SW68CD 4LH2000SW68CD 3LH2500SW68CD 4LH2500SW68CD 3LH3200SW68CD 4LH3200SW68CD 3LH4000SW68CD 4LH4000S

2000 3P4P

2500 3P4P

3200 3P4P

4000 3P4P

W68CF 3LV2000SW68CF 4LV2000SW68CF 3LV2500SW68CF 4LV2500SW68CF 3LV3200SW68CF 4LV3200SW68CF 3LV4000SW68CF 4LV4000S

1843818439184401844118442184431844418445

S type120kA

2000

2500

3200

4000

3P4P3P4P3P4P3P4P

M type controllerHorizontal terminal connection

Vertical terminal connection2000 3P

4P2500 3P

4P3200 3P

4P4000 3P

4P

N type85kA W68CF 3MH2000N

W68CF 4MH2000NW68CF 3MH2500NW68CF 4MH2500NW68CF 3MH3200NW68CF 4MH3200NW68CF 3MH4000NW68CF 4MH4000N

1844618447184481844918450184511845218453

W68CD 3MH2000NW68CD 4MH2000NW68CD 3MH2500NW68CD 4MH2500NW68CD 3MH3200NW68CD 4MH3200NW68CD 3MH4000NW68CD 4MH4000N

1846218463184641846518466184671846818469

W68CF 3MV2000NW68CF 4MV2000NW68CF 3MV2500NW68CF 4MV2500NW68CF 3MV3200NW68CF 4MV3200NW68CF 3MV4000NW68CF 4MV4000N

1845418455184561845718458184591846018461

W68CD 3MV2000NW68CD 4MV2000NW68CD 3MV2500NW68CD 4MV2500NW68CD 3MV3200NW68CD 4MV3200NW68CD 3MV4000NW68CD 4MV4000N

1847018471184721847318474184751847618477

Vertical terminal connection

2000

2500

3200

4000

3P4P3P4P3P4P3P4P

Horizontal terminal connection

Vertical terminal connection2000 3P

4P2500 3P

4P3200 3P

4P4000 3P

4P

H type100kA W68CF 3MH2000H

W68CF 4MH2000HW68CF 3MH2500HW68CF 4MH2500HW68CF 3MH3200HW68CF 4MH3200HW68CF 3MH4000HW68CF 4MH4000H

1847818479184801848118482184831848418485

W68CD 3MH2000HW68CD 4MH2000HW68CD 3MH2500HW68CD 4MH2500HW68CD 3MH3200HW68CD 4MH3200HW68CD 3MH4000HW68CD 4MH4000H

1849418495184961849718498184991850018501

W68CF 3MV2000HW68CF 4MV2000HW68CF 3MV2500HW68CF 4MV2500HW68CF 3MV3200HW68CF 4MV3200HW68CF 3MV4000HW68CF 4MV4000H

W68CD 3MV2000HW68CD 4MV2000HW68CD 3MV2500HW68CD 4MV2500HW68CD 3MV3200HW68CD 4MV3200HW68CD 3MV4000HW68CD 4MV4000H

1848618487184881848918490184911849218493

3206932070320713207232073320743207532076

Type code Order code Type code Order codeFixed type Drawer type

In(A)Rated current Number of

poles

Horizontal terminal connection

Air Circuit BreakersSeries 3SW68

1-29www.sassin.com

Power Distribution Electrics

Page 30: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Frame C3SW68-4000

M type controller

2000 3P4P

2500 3P4P

3200 3P4P

4000 3P4P

Type code Order code Type code Order codeFixed type Drawer type

In(A)

Horizontal terminal connectionS type120kA

W68CF 3MH2000SW68CF 4MH2000SW68CF 3MH2500SW68CF 4MH2500SW68CF 3MH3200SW68CF 4MH3200SW68CF 3MH4000SW68CF 4MH4000S

W68CD 3MH2000SW68CD 4MH2000SW68CD 3MH2500SW68CD 4MH2500SW68CD 3MH3200SW68CD 4MH3200SW68CD 3MH4000SW68CD 4MH4000S

3207732078320793208032081320823208332084

3209332094320953209632097320983209932100

Vertical terminal connection2000 3P

4P2500 3P

4P3200 3P

4P4000 3P

4P

W68CF 3MV2000SW68CF 4MV2000SW68CF 3MV2500SW68CF 4MV2500SW68CF 3MV3200SW68CF 4MV3200SW68CF 3MV4000SW68CF 4MV4000S

W68CD 3MV2000SW68CD 4MV2000SW68CD 3MV2500SW68CD 4MV2500SW68CD 3MV3200SW68CD 4MV3200SW68CD 3MV4000SW68CD 4MV4000S

3208532086320873208832089320903209132092

3210132102321033210432105321063210732108

2000

2500

3200

4000

3P4P3P4P3P4P3P4P

H type controllerHorizontal terminal connectionN type

85kA W68CF 3HH2000NW68CF 4HH2000NW68CF 3HH2500NW68CF 4HH2500NW68CF 3HH3200NW68CF 4HH3200NW68CF 3HH4000NW68CF 4HH4000N

W68CD 3HH2000NW68CD 4HH2000NW68CD 3HH2500NW68CD 4HH2500NW68CD 3HH3200NW68CD 4HH3200NW68CD 3HH4000NW68CD 4HH4000N

3210932110321113211232113321143211532116

3212532126321273212832129321303213132132

Rated current

2000

2500

3200

4000

3P4P3P4P3P4P3P4P

Horizontal terminal connection

Vertical terminal connection

2000 3P4P

2500 3P4P

3200 3P4P

4000 3P4P

Vertical terminal connection2000 3P

4P2500 3P

4P3200 3P

4P4000 3P

4P

H type100kA

W68CF 3HV2000NW68CF 4HV2000NW68CF 3HV2500NW68CF 4HV2500NW68CF 3HV3200NW68CF 4HV3200NW68CF 3HV4000NW68CF 4HV4000N

W68CD 3HV2000NW68CD 4HV2000NW68CD 3HV2500NW68CD 4HV2500NW68CD 3HV3200NW68CD 4HV3200NW68CD 3HV4000NW68CD 4HV4000N

3211732118321193212032121321223212332124

3213332134321353213632137321383213932140

W68CF 3HH2000HW68CF 4HH2000HW68CF 3HH2500HW68CF 4HH2500HW68CF 3HH3200HW68CF 4HH3200HW68CF 3HH4000HW68CF 4HH4000H

W68CD 3HH2000HW68CD 4HH2000HW68CD 3HH2500HW68CD 4HH2500HW68CD 3HH3200HW68CD 4HH3200HW68CD 3HH4000HW68CD 4HH4000H

3214132142321433214432145321463214732148

3215732158321593216032161321623216332164

W68CF 3HV2000HW68CF 4HV2000HW68CF 3HV2500HW68CF 4HV2500HW68CF 3HV3200HW68CF 4HV3200HW68CF 3HV4000HW68CF 4HV4000H

W68CD 3HV2000HW68CD 4HV2000HW68CD 3HV2500HW68CD 4HV2500HW68CD 3HV3200HW68CD 4HV3200HW68CD 3HV4000HW68CD 4HV4000H

3214932150321513215232153321543215532156

3216532166321673216832169321703217132172

Number ofpoles

Air Circuit BreakersSeries 3SW68

1-30 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Page 31: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Frame C3SW68-4000

H type controllerHorizontal terminal connection

2000

2500

3200

4000

Type code Order code Type code Order codeFixed type Drawer type

In(A)3P4P3P4P3P4P3P4P

Vertical terminal connection2000 3P

4P2500 3P

4P3200 3P

4P4000 3P

4P

S type120kA

W68CF 3HH2000SW68CF 4HH2000SW68CF 3HH2500SW68CF 4HH2500SW68CF 3HH3200SW68CF 4HH3200SW68CF 3HH4000SW68CF 4HH4000S

W68CD 3HH2000SW68CD 4HH2000SW68CD 3HH2500SW68CD 4HH2500SW68CD 3HH3200SW68CD 4HH3200SW68CD 3HH4000SW68CD 4HH4000S

3217332174321753217632177321783217932180

3218932190321913219232193321943219532196

W68CF 3HV2000SW68CF 4HV2000SW68CF 3HV2500SW68CF 4HV2500SW68CF 3HV3200SW68CF 4HV3200SW68CF 3HV4000SW68CF 4HV4000S

W68CD 3HV2000SW68CD 4HV2000SW68CD 3HV2500SW68CD 4HV2500SW68CD 3HV3200SW68CD 4HV3200SW68CD 3HV4000SW68CD 4HV4000S

3218132182321833218432185321863218732188

3219732198321993220032201322023220332204

Rated current

4000

5000

6300

3P4P3P4P3P4P

Frame D3SW68-6300

L type ControllerHorizontal terminal connection

Vertical terminal connection4000 3P

4P5000 3P

4P6300 3P

4P

N type100kA W68DF 3LH4000N

W68DF 4LH4000NW68DF 3LH5000NW68DF 4LH5000NW68DF 3LH6300NW68DF 4LH6300N

W68DD 3LH4000NW68DD 4LH4000NW68DD 3LH5000NW68DD 4LH5000NW68DD 3LH6300NW68DD 4LH6300N

322053220632207322083220932210

322173221832219322203222132222

W68DF 3LV4000NW68DF 4LV4000NW68DF 3LV5000NW68DF 4LV5000NW68DF 3LV6300NW68DF 4LV6300N

W68DD 3LV4000NW68DD 4LV4000NW68DD 3LV5000NW68DD 4LV5000NW68DD 3LV6300NW68DD 4LV6300N

322113221232213322143221532216

322233222432225322263222732228

4000

5000

6300

3P4P3P4P3P4P

Horizontal terminal connection

4000 3P4P

5000 3P4P

6300 3P4P

H type120kA W68DF 3LH4000H

W68DF 4LH4000HW68DF 3LH5000HW68DF 4LH5000HW68DF 3LH6300HW68DF 4LH6300H

W68DD 3LH4000HW68DD 4LH4000HW68DD 3LH5000HW68DD 4LH5000HW68DD 3LH6300HW68DD 4LH6300H

322293223032231322323223332234

322413224232243322443224532246

W68DF 3LV4000HW68DF 4LV4000HW68DF 3LV5000HW68DF 4LV5000HW68DF 3LV6300HW68DF 4LV6300H

W68DD 3LV4000HW68DD 4LV4000HW68DD 3LV5000HW68DD 4LV5000HW68DD 3LV6300HW68DD 4LV6300H

322353223632237322383223932240

322473224832249322503225132252

4000

5000

6300

3P4P3P4P3P4P

Horizontal terminal connectionS type150kA W68DF 3LH4000S

W68DF 4LH4000SW68DF 3LH5000SW68DF 4LH5000SW68DF 3LH6300SW68DF 4LH6300S

W68DD 3LH4000SW68DD 4LH4000SW68DD 3LH5000SW68DD 4LH5000SW68DD 3LH6300SW68DD 4LH6300S

322533225432255322563225732258

322653226632267322683226932270

Vertical terminal connection

Number ofpoles

Air Circuit BreakersSeries 3SW68

1-31www.sassin.com

Power Distribution Electrics

Page 32: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Frame D3SW68-6300

L type ControllerS type150kA

4000 3P4P

5000 3P4P

6300 3P4P

Type code Order code Type code Order codeFixed type Drawer type

In(A)W68DF 3LV4000SW68DF 4LV4000SW68DF 3LV5000SW68DF 4LV5000SW68DF 3LV6300SW68DF 4LV6300S

W68DD 3LV4000SW68DD 4LV4000SW68DD 3LV5000SW68DD 4LV5000SW68DD 3LV6300SW68DD 4LV6300S

322593226032261322623226332264

322713227232273322743227532276

Rated current Vertical terminal connection

4000

5000

6300

3P4P3P4P3P4P

M type ControllerHorizontal terminal connection

4000 3P4P

5000 3P4P

6300 3P4P

N type100kA

4000

5000

6300

3P4P3P4P3P4P

Horizontal terminal connection

4000 3P4P

5000 3P4P

6300 3P4P

H type120kA

W68DF 3LV4000HW68DF 4LV4000HW68DF 3LV5000HW68DF 4LV5000HW68DF 3LV6300HW68DF 4LV6300H

W68DD 3LV4000HW68DD 4LV4000HW68DD 3LV5000HW68DD 4LV5000HW68DD 3LV6300HW68DD 4LV6300H

4000

5000

6300

3P4P3P4P3P4P

Horizontal terminal connection

4000 3P4P

5000 3P4P

6300 3P4P

S type150kA

W68DF 3MH4000NW68DF 4MH4000NW68DF 3MH5000NW68DF 4MH5000NW68DF 3MH6300NW68DF 4MH6300N

W68DD 3MH4000NW68DD 4MH4000NW68DD 3MH5000NW68DD 4MH5000NW68DD 3MH6300NW68DD 4MH6300N

322773227832279322803228132282

322893229032291322923229332294

W68DF 3MV4000NW68DF 4MV4000NW68DF 3MV5000NW68DF 4MV5000NW68DF 3MV6300NW68DF 4MV6300N

W68DD 3MV4000NW68DD 4MV4000NW68DD 3MV5000NW68DD 4MV5000NW68DD 3MV6300NW68DD 4MV6300N

322833228432285322863228732288

322953229632297322983229932300

W68DF 3MH4000HW68DF 4MH4000HW68DF 3MH5000HW68DF 4MH5000HW68DF 3MH6300HW68DF 4MH6300H

W68DD 3MH4000HW68DD 4MH4000HW68DD 3MH5000HW68DD 4MH5000HW68DD 3MH6300HW68DD 4MH6300H

323013230232303323043230532306

323133231432315323163231732318

323073230832309323103231132312

323193232032321323223232332324

W68DF 3MH4000SW68DF 4MH4000SW68DF 3MH5000SW68DF 4MH5000SW68DF 3MH6300SW68DF 4MH6300S

W68DD 3MH4000SW68DD 4MH4000SW68DD 3MH5000SW68DD 4MH5000SW68DD 3MH6300SW68DD 4MH6300S

323253232632327323283232932330

323373233832339323403234132342

W68DF 3MV4000SW68DF 4MV4000SW68DF 3MV5000SW68DF 4MV5000SW68DF 3MV6300SW68DF 4MV6300S

W68DD 3MV4000SW68DD 4MV4000SW68DD 3MV5000SW68DD 4MV5000SW68DD 3MV6300SW68DD 4MV6300S

323313233232333323343233532336

323433234432345323463234732348

Vertical terminal connection

Vertical terminal connection

Vertical terminal connection

Number ofpoles

Air Circuit BreakersSeries 3SW68

1-32 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Page 33: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

4000

5000

6300

Type code Order code Type code Order codeFixed type Drawer type

In(A)3P4P3P4P3P4P

Frame D3SW68-6300

H type controllerHorizontal terminal connection

Vertical terminal connection4000 3P

4P5000 3P

4P6300 3P

4P

N type100kA

W68DF 3HV4000NW68DF 4HV4000NW68DF 3HV5000NW68DF 4HV5000NW68DF 3HV6300NW68DF 4HV6300N

W68DD 3HV4000NW68DD 4HV4000NW68DD 3HV5000NW68DD 4HV5000NW68DD 3HV6300NW68DD 4HV6300N

323553235632357323583235932360

323673236832369323703237132372

4000

5000

6300

3P4P3P4P3P4P

Horizontal terminal connection

4000 3P4P

5000 3P4P

6300 3P4P

H type120kA

4000

5000

6300

3P4P3P4P3P4P

Horizontal terminal connection

4000 3P4P

5000 3P4P

6300 3P4P

S type150kA W68DF 3HH4000S

W68DF 4HH4000SW68DF 3HH5000SW68DF 4HH5000SW68DF 3HH6300SW68DF 4HH6300S

W68DD 3HH4000SW68DD 4HH4000SW68DD 3HH5000SW68DD 4HH5000SW68DD 3HH6300SW68DD 4HH6300S

324093241032411324123241332414

W68DF 3HH4000NW68DF 4HH4000NW68DF 3HH5000NW68DF 4HH5000NW68DF 3HH6300NW68DF 4HH6300N

W68DD 3HH4000NW68DD 4HH4000NW68DD 3HH5000NW68DD 4HH5000NW68DD 3HH6300NW68DD 4HH6300N

323493235032351323523235332354

323613236232363323643236532366

W68DF 3HH4000HW68DF 4HH4000HW68DF 3HH5000HW68DF 4HH5000HW68DF 3HH6300HW68DF 4HH6300H

W68DD 3HH4000HW68DD 4HH4000HW68DD 3HH5000HW68DD 4HH5000HW68DD 3HH6300HW68DD 4HH6300H

323733237432375323763237732378

323853238632387323883238932390

W68DF 3HV4000HW68DF 4HV4000HW68DF 3HV5000HW68DF 4HV5000HW68DF 3HV6300HW68DF 4HV6300H

W68DD 3HV4000HW68DD 4HV4000HW68DD 3HV5000HW68DD 4HV5000HW68DD 3HV6300HW68DD 4HV6300H

323793238032381323823238332384

323913239232393323943239532396

W68DF 3HV4000SW68DF 4HV4000SW68DF 3HV5000SW68DF 4HV5000SW68DF 3HV6300SW68DF 4HV6300S

W68DD 3HV4000SW68DD 4HV4000SW68DD 3HV5000SW68DD 4HV5000SW68DD 3HV6300SW68DD 4HV6300S

324033240432405324063240732408

324153241632417324183241932420

323973239832399324003240132402

Rated current

Vertical terminal connection

Vertical terminal connection

Number ofpoles

Air Circuit BreakersSeries 3SW68

1-33www.sassin.com

Power Distribution Electrics

Page 34: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-34 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Electric operation mechanismIt is used for breaker motor for energy storage and automatic energy-restoringNormal standard configuring accessories are as below

Accessories

Rated voltage (V) Conventional thermal current Ith(A)

Rated control capacity

AC230415250

10830VA

DC 75W

Rated control power voltage Ue(v)Tripping voltage (V)Reliable switch-on voltage(V)Reliable switch-off voltage(V)Power consumptionDelay time of under-voltage delayed release (s)

AC400, AC230(0.35~0.7)Ue(0.85~1.1)Ue≤0.35Ue12VA0.5, 1, 2, 3

Rated control power voltage Us(v)Tripping voltage(V)Power consumptionStorage time (s)

AC400, AC230, DC220, DC110(0.85~1.1)Us80VA, 80W<5

Closing electromagnet After charging is finished, the closing electromagnet can break the circuit breaker by remote controlNormal configuring accessories

Rated control power source voltage Us(v)Tripping voltage(V)Closing time (ms)

AC400, AC230, DC220, DC110(0.85~1.1)Us<70

Rated control power source voltage Us(v)Tripping voltage (V)Break time (ms)

AC400, AC230, DC220, DC110(0.7~1.1)Us<30

Shunt releaseTo break the circuit breaker by remote controlNormally deployed accessories

Under-voltage releaseThe under-voltage release consists of release coil and control units.The under-voltage release works in two ways: instantaneous operation and delayed operation.Operational accessory

Note: If the delay time of under-voltage delayed release is above 3 second, it is the special specification

Auxiliary contactStandard configuration we provided to client is four convertible contacts. The six convertible contacts, four normally open, four normally closed contacts or six normally open, normally closed contacts are also available for special applications

Page 35: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-35www.sassin.com

Power Distribution Electrics

Outline and installation dimensions

74

Ø11 15

51

50 25

150

51

72

4xØ6.5

29795

297

276265230

35

364

353

8xØ3.5

317

352

70 70

a

4470 70

25Ø11

Installation dimensions of door Vertical terminal Horizontal terminal

Button of breaker

Centerof breaker

Centerof door

Vertical terminal Horizontal terminal248

351

145

282

74

Rated current a(mm)200-630A800-1000A1250-1600A

51015

3SW68-1600/3P Drawer type

Page 36: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-36 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

(3SW68-1600)4P Drawer type

70 70 70

a

70 70 7050

25

Ø11 15

35

276265230

35

317

352

7

364

353

8xØ3.5

Button of breaker

Centerof breaker

Centerof door

Installation dimensions of door Vertical terminal Horizontal terminal

Ø11 15

297

4xØ6.5

297

95 74

51

150

7251

50 25

150

318

351

74 215

352

Vertical terminal Horizontal terminal

Rated current a(mm)200-630A800-1000A1250-1600A

51015

Page 37: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-37www.sassin.com

Power Distribution Electrics

Rated current a(mm)200-630A800-1000A1250-1600A

51015

Installation dimensions of door Vertical terminal Horizontal terminal

Vertical terminal Horizontal terminal

70 70

50

25

Ø1115

70 70

a

276265230

8xØ3.5

Button of breaker

Centerof doorCenter

of breaker

330

319

283

320

237

254

Ø11 15

15

150

52

50100 90

194

194

16

R

52

60 52

150

4xØ7

(3SW68-1600)3P Fixed type

Page 38: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-38 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

Rated current a(mm)200-630A800-1000A1250-1600A

51015

Ø11 15

1515

050

5260 52

150

4xØ7100 90

194

194

52

320

324

Installation dimensions of door Vertical terminal Horizontal terminal

Vertical terminal Horizontal terminal

276265230

8xØ3.5

330

319

283

Centerof door

Centerof breaker

Button of breaker

35

70

a

70 70 70 70 7050

25

Ø11

15

(3SW68-1600)4P Fixed type

Page 39: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-39www.sassin.com

Power Distribution Electrics

3P N

3P N

304.

579

3P NOn the board before the next level of inlet and outletLevel on the outlet plate forward

On the board before the next vertical inlet and outlet

77 77

5-Φ11 5-Φ1138.5 38.5

25 25 25 25

30

25 13.552

90.5

1552 82

1552 82

25 13.552

102

Used as the center extended busbar of the horizontal, front board inlet and outlet wire combination of a 3-pole circuit breaker

Used as the extended busbar in the left or right of the horizontal, front board inlet and outlet wire combination of a 3-pole circuit breaker

Used as the extended busbar in the left or right of the horizontal, front board inlet and outlet wire combination of a 4-pole circuit breaker

Note: Use the busbar to connect the screws; Class M10 is of 8.8 torque: and 50 Nm should be used with the contact washer.

244.

5

3P N

3P N

5025 Φ11

1542

015

15.5

130

130

244.

5

Special wiring 3SW68-1600 (Darwer type)

Forward outlet plate

Forward under the outlet plate on the vertical

7738.5

25 25

30

8252

30

25 25

77

2552

13.5

38.55-Φ11

1552 82

25 13.552

15

5-Φ11

Used as the extended busbar center-left or right of the horizontal,front board inlet and outlet wire combination of a 4-pole circuit breaker, and also available as that of the vertical inlet and outlet wire combination of 3 or 4-pole circuit breaker

Extended busbar size of the breaker

Page 40: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-40 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

(3SW68-2500) Fixed type

Rated Current (In)

Mounting hole

4P 3P

420(P)325(P)

347(3P)367(3P)422(4P)462(4P)

403

4-Ø8

Mounting hole center

Vertical wiring

Horizontal wiring

A

N 3P

95 78.595 95

95 95 95 78.5

7030

1530

Φ10

1530

H

135

56.5

1250A 1600A 2000A 2500A 15mm 15mm 20mm 20mmFemale cable(H)

Vertical wiring

Mounting hole center

Chamber door

70 30

Φ10

30.5 170 98308.5

366

248

A

Horizontal wiring

Chamber door248

H

135

56.5

30.5 170308.5

98

366

A

Mounting hole center

Page 41: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-41www.sassin.com

Power Distribution Electrics

(3SW68-2500) Fixed type

4P 3P

70

Φ10

A

30

126

135

107.5 175 100380

455

Chamber door

135

56.5

H

A

107.5 175 100

390455

Mounting hole center

47 position

Chamber door

247(3P)347(3P)369(4P)442(4P)

4-Ø8

450

Mounting hole

3P

95

95

7030

1530

Φ10

A

N

95 95

95 95

1530

H42

Horizontal wiring

Mounting hole center

Vertical wiring

Horizontal wiring

Vertical wiring

Rated Current (In) Female cable(H)1250A 1600A 2000A 2500A 15mm 15mm 20mm 20mm

47 position

Page 42: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-42 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

3P

7030

1530

A

N

2000~2500A

3200~4000A

Ø13

126 126 126 94

136 141(3P)136(4P)

141(3P)136(4P)

79

10050Ø13

5025

2000~2500A

3200~4000A

126 126 126

126 126 126

94

94

3015

3010

5025

403

4P 3P544(4P)418(3P)

440(3P)460(3P)566(4P)586(4P)

248AA

3200~4000A 2000~2500A

30.5 170 98308.5366

40356

.513

530

1010 20

135

56.5

248AA3200~4000A 2000~2500A

30.5 170 98308.5366

56.5

135

Ø13

70 30

403

71.5

135

100

50

Ø13

(3SW68-4000) Fixed type

Horizontal wiring

Vertical wiring

Mounting hole center

Chamber door

Chamber door

Mounting hole center

Vertical wiring

Horizontal wiring Mounting hole center

4-Ø8Mounting hole

Page 43: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-43www.sassin.com

Power Distribution Electrics

(3SW68-4000) Darwer type

450

4P 3P

325(3P)440(3P)540(4P)566(4P)

57.5

63

2000~2500A 126 126 126 36.5(P)31(4P)

3015

126 126 126 36.5(P)31(4P)

5025

3200~4000A

3200~4000A

2000~2500A

136 141(3P)136(4P)

141(3P)136(4P)

21.5(3P)16(4P)100

50

5025

Ø13

Ø13

126 126 12636.5(P)31(4P)

3P

A

N

3015

Horizontal wiring

Horizontal wiring

Vertical wiring

107.5 175 100390455

126

135

70 30

Ø13

2000~2500AA

Vertical wiring Chamber door

Mounting hole center

47 position

2000~2500A

126

135

107.5 175 100390455

A

Chamber door

Mounting hole center

47 position

Mounting hole center 3200~4000A

126

135

10

30

492

10

141

135

100

50Ø13

492

A A3200~4000A

Horizontal wiring Vertical wiring

Page 44: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-44 www.sassin.com

Pow

er D

istr

ibut

ion

Elec

tric

s

4P 3P

4P 3P

225115

(2.5)

255

307.

5

Installation base of circuit breaker

Mounting hole centerline The center line of door openings

8-Ø5

260

100

286

Mounting hole centerline

Mounting hole centerline The center line of door openings

290

351

115240

(2.5)

8-Ø5

Mounting hole centerline

270

110

322

Door openings

Door openings

(3SW68-1600) Fixed type

(3SW68-1600) Darwer type

Installation base of circuit breaker

Page 45: Power Distribution Electrics - Sassin...Air Circuit Breakers Series 3SW68 1-5 Power Distribution Electrics D 6300 3,4 N H S 4000 5000 6300 50/60 400,690 1000 12 100%In Rated ultimate

Air Circuit BreakersSeries 3SW68

1-45www.sassin.com

Power Distribution Electrics

(3SW68-4000)Fixed type

4P 3P

355 (42.5)220

13.5

285

8-Ø4

393

317

4P 3P

355 (42.5)162.5(3P)157(4P)

4518

281

393

19 7315

315

3

11-Ø4

44.5

(3SW68-4000)Darwere type

Mounting hole centerline The center line of door openings

Installation base of circuit breaker

Mounting hole centerline

Door openings

Door openings

Mounting hole centerline

Mounting hole centerline The center line of door openings

Installation base of circuit breaker