    CHAPTER 1

    INTRODUCTION

    1

  • 7/27/2019 Protection of Turbogenerator

    2/50

    1.1 INTRODUCTION TO VSP

    Visakhapatnam steel plant, the first coal based steel plant in India is located, 16km

    South West city of Destiny i.e. Visakhapatnam. Bestowed with modern technologies, VSP has

    an installed capacity of 3 million tons per annum of liquid steel and 2.656 million tones of

    saleable steel. At VSP there is emphasis on total automation, seamless integration and efficient

    up gradation, which result in wide range of long and structural products to meet stringent

    demands of discerning customers within India and abroad.VSP products meet exactly

    international quality standards such as JIS, DIN, BIS, BS etc.

    VSP is certified to all the three international standards of quality. ISO- 9001 for Quality

    management, ISO-14001 for Environmental Management system and OHSAS-18001 for

    Occupational health and safety. The certificates covers quality systems of all operational

    maintenance service units besides purchase systems, training and marketing functions spreading

    over four regional marketing offices & 22 stock yards located all over country.

    VSP by successfully installing and operating efficiently RS.460 crores worth of

    pollution control and Environment control equipments and converting the barren landscape by

    planting more than 3 million plants has a made the Steel Plant , Steel Township and surrounding

    areas into heaven of lush greenery. This has made Steel Township a greener, cleaner and coolerplace, which can boost of 3 to 4c lesser temperature even in the peak summer compared to

    Visakhapatnam city.

    VSP exports Quality Pig Iron and Steel products to Sri Lanka, Myanmar, Nepal, Middle

    East, and USA. RINL-VSP has awarded STAR TRADING HIUSE status during 1997-2000.

    Having established a total manpower of about 16,613 VSP has envisaged a labour productivity

    of 265 tonnes per man year of Liquid Steel which is the best in the country and comparable with

    international levels.

    2

  • 7/27/2019 Protection of Turbogenerator

    3/50

    1.2 INTRODUCTION TO THERMAL POWER PLANT

    Thermal power plant (TPP) is the captive power plant in VSP. The average power

    demand at all units of VSP when operating in full capacity will be 221MW. The captive power

    generation capacity of 270 MW is sufficient to meet all plant needs in normal operating time.

    The objective of TPP is to supply uninterrupted essential power.

    In case of partial outage of power generation capacity due to break down, shutdown or

    other reasons, the shortfall of power is available from APSEB grid. The agreement with APSEB

    provides for exporting of surplus power to APSEB. The TPP can only generate 247.5MW of

    power; rest of the power is generated by Back Pressure Turbines and Gas Expansion turbines

    located at other departments in the VSP.

    TPP has 3 Turbo Generators of each 60mw and 1 Turbo Generator of 67.5MW. The

    Generators are air cooled and the turbines have Electro Hydraulic Turbine Governing System.

    Central admission of steam is used to reduce axial thrust. TPP also meets the air blast

    requirements of Blast Furnaces through 3 Turbo Blowers.

    TPP has 5 Boilers each of CAPACITY -330 Tons/ Hr, PRESSURE- 101 ata and

    TEMPERATURE - 540o

    C. The fuel used in boilers is composed of Pulverized coal, Blast

    Furnace gas, Coke-oven gas, Furnace oil. Oil is generally used to create initial and quick

    ignition. The calorific values and the composition of fuel used in the boilers are shown in below

    table.

    3

    Sl. No Name of the fuel Percentage of fuel Calorific value

    1 Blast furnace gas(BFG) 23% 800 kcal/nm3

    2 Coke-Oven Gas(COG) 30% 4425 kcal/nm3

    3 Furnace Oil 0.07% 10000 kcal/kg

    4 Coal 46.8% 3200-4500 kcal/kg

  • 7/27/2019 Protection of Turbogenerator

    4/50

    Table no: 1

    The entire plant is configured as 5 electrical load blocks (LBSS 1-5) and step-down

    substations are provided in each block with 220kv transformers to step-down to 33/11/6.6Kv for

    further distribution.

    4

  • 7/27/2019 Protection of Turbogenerator

    5/50

    CHAPTER 2

    INTRODUCTION TO PROTECTION

    5

  • 7/27/2019 Protection of Turbogenerator

    6/50

    2.1 POWER SYSTEM PROTECTION:

    The word 'protection' is generally used to describe the whole concept of protecting a

    power system. Power system protection is the process of making the production, transmission,

    and consumption of electrical energy as safe as possible from the effects of failures and events

    that place the power system at risk. The function of protective equipment is not the preventive

    one its name would imply, in that it takes action only after a fault has occurred: it is the

    ambulance at the foot of the cliff rather than the fence at the top. The special equipment

    adopted to detect such possible faults is referred to as protectiveequipment or protective relay and the system that uses such equipment is

    termed as protection system

    2.2 NECESSITY OF PROTECTION:

    It is fair to say that without discriminative protection it would be impossible to operate a

    modern power system. The protection is needed to remove as speedily as possible any element

    of the power system in which a fault has developed. So long as the fault remains connected, the

    whole system may be in jeopardy from three main effects of the fault, namely:

    It is likely to cause the individual generators in a power station, or groups of

    generators in different stations, to lose synchronism and fall out of step with

    consequent splitting of the system;

    A risk of damage to the affected plant; and

    A risk of damage to healthy plant.

    There is another effect, not necessarily dangerous to the system, but important from the

    consumers' viewpoint, namely, a risk of synchronous motors in large industrial premises falling

    6

  • 7/27/2019 Protection of Turbogenerator

    7/50

    out of step and tripping out; with the serious consequences that entails loss of production and

    interruption of vital processes.

    It is the function of the protective equipment, in association with the circuit breakers, to

    avert these effects. This is wholly true of large H.V. networks, or transmission systems. In the

    lower-voltage distribution systems, the primary function of protection is to maintain continuity

    of supply. This, in effect, is achieved incidentally transmission systems if the protection

    operates correctly to avert the effects mentioned above; indeed it must be so, because the

    ultimate aim is to provide 100percent continuity of supply.

    Obviously this aim cannot be achieved by the protection alone. In addition the power

    system and the distribution networks must be so designed that there are duplicate or multiple

    outlets from power sources to load centers (adequate generation may be taken for granted), and

    at least two sources of supply (feeders) to each distributing station. There are certain

    conventional ways of ensuring alternative supplies, as we shall see, but if full advantage is to be

    taken of their provision (always a costly matter) the protection must be highly selective in its

    functioning. For this it must possess the quality known as discrimination, by virtue of which it

    is able to select and to disconnect only the faulty element in the power system, leaving all others

    in normal operation so far as that may be possible. With a few exceptions the detection and

    tripping of a faulty circuit is a very simple matter; the art and skill lie in selecting the faulty one,

    bearing in mind that many circuits generators, transformers, feeders are usually affected, and in

    much the same way by a given fault, this accounts for the multiplicity of relay types and

    systems in use.

    2.3 BASIC REQUIRMENTS OF PROTECTION:

    A protection apparatus has three main functions/duties:

    Safeguard the entire system to maintain continuity of supply

    Minimize damage and repair costs where it senses fault

    Ensure safety of personnel.

    7

  • 7/27/2019 Protection of Turbogenerator

    8/50

    These requirements are necessary, firstly for early detection and localization of faults,

    and Secondly for prompt removal of faulty equipment from service.

    In order to carry out the above duties, protection must have the following qualities:

    Speed

    Selectivity

    Sensitivity

    Reliability

    Simplicity

    Economy

    2.3.1 Speed:

    Protective relaying should disconnect a faulty element as quickly as possible. This is

    desirable for many reasons.

    Improves power system stability. Decreases the amount of damage incurred.

    Reduces annoyance to electric power consumers and decreases total outage time

    for power consumers.

    Decreases the likelihood of development of one type of fault into other more

    severe type.

    Permits use of rapid reclosure of circuit breakers to restore service to customers.

    To decrease the time taken to disconnect the faulty element of the system, high speed

    protection should be operated in conjunction with high speed circuit breakers. The time interval

    within which a faulty system is disconnected from the system is called clearing time which is

    the sum of operating time of the protective relaying and breaker interrupting time.

    8

  • 7/27/2019 Protection of Turbogenerator

    9/50

    Modern high-speed protective relaying has operating time 0.02 to 0.04 sec. and CBS

    have interrupting time 0.05 to 0.06 sec. Hence clearing time may be about 0.07 to 0.10 sec.

    2.3.2 Selectivity:

    It is ability of the protective systems to determine the point at which the fault occurs and

    select the nearest of circuit breaker tripping of which will lead to clearing of fault with

    minimum or no damage to the system. In fact, opening of any other breaker to clear the fault

    will lead to greater part of the system being isolated.

    Therefore every time a fault occurs, only those breakers which are nearest to the fault

    should be opened. This gives us an idea about dividing the power system into protective zones

    which can be adequately protected with minimum part of the system isolated. Any failure

    occurring within a given zone will cause the opening of all breakers within that zone. The

    system can be divided into the following protective zones.

    Generator or generator transformer units.

    Transformers

    Bus bars

    Transmission lines

    Distribution circuits

    2.3.3 Sensivity:

    It is the capability of the relaying to operate reliably under the actual conditions that

    produce the least operating tendency. It is desirable to have the protection as sensitive as

    possible in order that it shall operate for low values of actuating quantity.

    2.3.4 Reliability:

    9

  • 7/27/2019 Protection of Turbogenerator

    10/50

    The protection relaying must be ready to function reliable and correct in operation at all

    times under any kind of fault and abnormal conditions of the power system for which it has

    been designed.

    2.3.5 Simplicity:

    Simplicity of construction and good quality of the relay, correctness of design and

    installation qualified maintenance and supervision etc. are the main factors which influence

    protective reliability. As a rule, the simple the protective scheme and the lesser the no. of

    relays, circuits and contacts it contains, the greater will be its reliability.

    2.3.6 Economy:

    As with all good engineering design economics play a major role. Too much protection

    is as bad as to little and the relay engineer must strike a sensible with due regard to practical

    situation considered

    2.4 BASIC COMPONENTS OF PROTECTION:

    Protection of any distribution system is a function of many elements .Following are the

    main components of protection.

    Relays

    Instrument Transformers

    Circuit breakers

    Tripping Batteries

    2.4.1 Relays:

    10

  • 7/27/2019 Protection of Turbogenerator

    11/50

    A relay is a device which makes a measurement or receives a controlling signal in

    consequence of which it makes sudden pre-determined changes in one or more electrical

    circuits. A protective relay is a relay which responds to abnormal conditions in an electrical

    power system, to control a circuit-breaker so as to isolate the faulty section of the system, with

    the minimum interruption to service.

    Functions of Protective Relaying

    The function of protective relaying is to cause the prompt removal from service of any

    element of the power system. When it suffers a short circuit, or when it starts to operate in any

    abnormal manner that might cause damage or otherwise interfere with the effective operation of

    the rest of the system. The relaying equipment is aided in this task by circuit breakers that are

    capable of disconnecting the faulty element when they are called up to do so by the relaying

    equipment.

    Circuit breaker is generally located so that each generator, transformer, bus,

    transmission line etc. can be completely disconnected from the rest of the system. Fusing is

    employed where protective relays and circuit breakers are not economically justifiable.Although the principal function of protective relaying is to mitigate the effects of short circuits

    other abnormal operating condition arise that also require service of protective relaying.

    A secondary function of a protective relaying is to provide indication to the location and

    type of failure. Such data not only assist in expediting repair but also, by comparison with

    human observation and automatic oscillograph records, they provide means of analyzing the

    effectiveness of the fault prevention and mitigation features including the protective relaying

    itself.

    CLASSIFICATION OF PROTECTIVE RELAYS:

    Protective relays can be broadly classified into three types

    11

  • 7/27/2019 Protection of Turbogenerator

    12/50

    Electromagnetic relay

    Static relay

    Micro processor based relay

    Electromagnetic:

    An Electromagnetic relay has one or more coils, movable elements, contact system etc.

    The operation of such relay on whether operating torque / force are greater than the restraining

    torque / force. When the actuating quantity exceeds a certain predetermined value, an operating

    torque is developed which is applied on the moving part. This causes the moving part to travel

    and to finally close a contact to energize the trip coil of the circuit breaker. Electromagnetic

    relays include attracted armature, moving coil, and induction disc and cup type relays.

    Static Relays:

    Static relays contain electronic circuitry, which may include transistor, ICs, Diodes, and

    Logic Gates etc. There is compactor circuit in the relay, which compares two or more currents

    or voltages and gives an output, which is applied to either a slave relay or a thyristor circuit.

    The slave relay is an electromagnetic relay, which finally closes a contact. A static relay

    containing a slave relay is a semi static relay. The electromagnetic relay used as a slave relay

    provides a number of output contacts at low cost. A relay using a thyristor circuit is a wholly a

    static relay. Static relay possess the advantage of having low burden on the CT and PT fast

    operation, absence of mechanical inertia and contact trouble, long life and less maintenance.

    Microprocessor Based Relays:

    12

  • 7/27/2019 Protection of Turbogenerator

    13/50

    Microprocessor based relays are the latest development. With the developments in VLSI

    technology, sophisticated and fast microprocessors are coming up. The main features, which

    have encouraged the design and development of microprocessor based, protective relays, are

    their economy, compactness, reliability, flexibility and improved performance over

    conventional relays. A number of relaying characteristics such as over current, directional,

    impedance, reactance, mho, quadrilateral, elliptical etc. can be obtained using the same

    interface. Using a multiplexer, a microprocessor can get the desired signals to obtain particular

    relaying characteristics.

    Different programs are used to obtain different relaying characteristics using the same

    interfacing circuitry, Microprocessor based protective schemes have attractive compactness in

    addition to flexibility.

    2.4.2 INSTRUMENT TRANSFORMERS:

    The voltage transformers and current transformers continuously measure the voltage

    and current of an electrical system and are responsible to give feedback signals to the relays to

    enable them to detect abnormal conditions. The values of actual currents in modern distribution

    systems varies from a few amperes in households, small industrial/commercial houses, etc. to

    thousands of amperes in power-intensive plants, national grids, etc., which also depend on the

    operating voltages. Similarly, the voltages in electrical systems vary from few hundreds of volts

    to many kilo volts. However, it is impossible to have monitoring relays designed and

    manufactured for each and every distribution system and to match the innumerable voltages and

    currents being present. Hence the voltage transformers and current transformers are used which

    enable same types of relays to be used in all types of distribution systems ensuring the selection

    and cost of relays to be within manageable ranges.

    The main tasks of instrument transformers are:

    To transform currents or voltages from usually a high value to a value easy to handle for

    relays and instruments.

    13

  • 7/27/2019 Protection of Turbogenerator

    14/50

    To insulate the relays, metering and instruments from the primary high-voltage

    system

    To provide possibilities of standardizing the relays and instruments, etc. to a few rated

    currents and voltages.

    Instrument transformers are special versions of transformers in respect of measurement of

    current and voltages. The theories for instrument transformers are the same as those for

    transformers in general.

    Basic theory of operation:

    The transformer is one of the high efficient devices in electrical distribution systems,

    which are used to convert the generated voltages to convenient voltages for the purpose of

    transmission and consumption. A transformer comprises of two windings viz., primary and

    secondary coupled through a common magnetic core. When the primary winding is connected

    to a source and the secondary circuit is left open, the transformer acts as an inductor with

    minimum current being drawn from the source. At the same time, a voltage will be produced in

    the secondary open-circuit winding due to the magnetic coupling. When a load is connected

    across the secondary terminals, the current will start flowing in the secondary, which will be

    decided by the load impedance and the open-circuit secondary voltage. A proportionate current

    is drawn in the primary winding depending upon the turns ratio between primary and

    secondary. This principle of transformer operation is used in transfer of voltage and current in a

    circuit to the required values for the purpose of standardization.

    A voltage transformer is an open-circuited transformer whose primary winding is

    connected across the main electrical system voltage being monitored. A convenient

    proportionate voltage is generated in the secondary for monitoring. The most common voltage

    produced by voltage transformers is 100120 V (as per local country standards) for primary

    voltages from 380 V to 800 kV or more. However, the current transformer is having its primary

    winding directly connected in series with the main circuit carrying the full operating current of

    the system. An equivalent current is produced in its secondary, which is made to flow through

    14

  • 7/27/2019 Protection of Turbogenerator

    15/50

    the relay coil to get the equivalent measure of the main system current. The standard currents

    are invariably 1 A and 5 A universally.

    Voltage transformers

    There are basically, two types of voltage transformers used for protection equipment.

    Electromagnetic type (commonly referred to as a VT)

    Capacitor type (referred to as a CVT).

    Electromagnetic type

    The electromagnetic type is a step down transformer whose primary

    (HV) and secondary (LV) windings are connected as below.

    Fig 1: Electromagnetic Relay

    The number of turns in a winding is directly proportional to the open-circuit

    voltage being measured or produced across it. The above diagram is a single-phase VT. In

    the three-phase system it is necessary to use three VTs at one per phase and they being

    connected in star or delta depending on the method of connection of the main power

    source being monitored. This type of electromagnetic transformers are used in voltage

    15

  • 7/27/2019 Protection of Turbogenerator

    16/50

    circuits up to 110/132 kV. For still higher voltages, it is common to adopt the second type

    namely the capacitor voltage transformer (CVT).

    Capacitor Voltage Transformer

    The basic connection adopted in this type is here the primary portion consists of

    capacitors connected in series to split the primary voltage to convenient values. The

    magnetic voltage transformer is similar to a power transformer and differs only so far as a

    different emphasis is placed on cooling, insulating and mechanical aspects. The primary

    winding has larger number of turns and is connected across the line voltage; either phase-

    to-phase or phase-to-neutral. The secondary has lesser turns however, the volts per turn

    on both primary and secondary remains same.

    .

    Fig 2: Capacitor Voltage Transformer

    The capacitor VT is more commonly used on extra high-voltage (EHV) networks. The

    capacitors also allow the injection of a high-frequency signals onto the power line conductors to

    provide end-to-end communications between substations for distance relays,

    telemetry/supervisory and voice communications. Hence, in EHV national grid networks of

    utilities, the CVTs are commonly used for both protection and communication purposes

    16

  • 7/27/2019 Protection of Turbogenerator

    17/50

    Current Transformers:

    All current transformers used in protection are basically similar in construction to

    Standard transformers in that they consist of magnetically coupled primary and secondary

    windings, wound on a common iron core, the primary winding being connected in series with

    the network unlike voltage transformers. They must therefore withstand the networks short-

    circuit current.

    There are two types of current transformers:

    1 Wound primary type

    2 Bar primary type.

    The wound primary is used for the smaller currents, but it can only be applied on low fault level

    installations due to thermal limitations as well as structural requirements due to high magnetic

    forces for currents greater than 100 A.

    Fig 3: Wound primary type CT

    The bar primary type is used as. If the secondary winding is evenly distributed aroundthe complete iron core, its leakage reactance is eliminated Protection CTs are most frequently of

    the bar primary, toroidal core with evenly distributed secondary winding type construction.

    17

  • 7/27/2019 Protection of Turbogenerator

    18/50

    Fig 4: Bar Primary Type CT

    2.4.3 CIRCUIT BREAKERS:

    Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used

    in combination to detect and isolate faults. Circuit breakers are the main making and breaking

    devices in an electrical circuit to allow or disallow flow of power from source to the load. These

    carry the load currents continuously and are expected to be switched ON with loads (making

    capacity). These should also be capable of breaking a live circuit under normal switching OFF

    conditions as well as under fault conditions carrying the expected fault current until completely

    isolating the fault side (rupturing/breaking capacity). Under fault conditions, the breakers

    should be able to open by instructions from monitoring devices like relays. The relay contactsare used in the making and breaking control circuits of a circuit breaker, to prevent breakers

    getting closed or to trip breaker under fault conditions as well as for some other interlocks.

    Protective Relay-Circuit Breaker Combination:

    The protective relay detects and evaluates the fault and determines when the circuit

    should be opened. The circuit breaker functions under control of the relay, to open the circuit

    when required. A closed circuit breaker has sufficient energy to open its contacts stored in oneform or another (generally a charged spring). When a protective relay signals to open the

    circuit, the store energy is released causing the circuit breaker to open. Except in special cases

    where the protective relays are mounted on the breaker, the connection between the relay and

    18

  • 7/27/2019 Protection of Turbogenerator

    19/50

    circuit breaker is by hard wiring. From the protection point of view, the important parts of the

    circuit breaker are the trip coil, latching mechanism, main contacts and auxiliary contacts. The

    roles played by these components in the tripping process and the following step by step

    procedure take place while isolating a fault (the time intervals between each event will be in the

    order of a few electrical cycles i.e. milliseconds):

    Fig 5: Protective Relay-Circuit Breaker Combination

    The relay receives information, which it analyzes, and determines that the circuit

    breaker is unlatched and opens its main contacts under the control of the tripping spring.

    The trip coil is deenergized by opening of the circuit breaker auxiliary contacts.

    Circuit breakers are normally fitted with a number of auxiliary contacts, which are used

    in a variety of ways in control and protection circuits (e.g. to energize lamps on a remotepanel to indicate whether the breaker is open or closed) circuit should be opened.

    19

  • 7/27/2019 Protection of Turbogenerator

    20/50

    Relay closes its contacts energizing the trip coil of the circuit breaker.

    2.4.4 TRIPPING BATTERIES:

    The operation of monitoring devices like relays and the tripping mechanisms of breakers

    require independent power source, which does not vary with the main source being monitored.

    Batteries provide this power and hence they form an important role in protection circuits. The

    relay/circuit breaker combination depends entirely on the tripping battery for successful

    operation. Without this, relays and breakers will not operate, becoming solid, making their

    capital investment very useless and the performance of the whole network unacceptable. It is

    therefore necessary to ensure that batteries and chargers are regularly inspected and maintainedat the highest possible level of efficiency at all times to enable correct operation of relays at the

    correct time.

    2.5 TYPES OF PROTECTIONS:

    Very Frequently, for attaining higher reliability, speeded-up action and improvements in

    operating flexibility of protection schemes, the separate elements of a power system, in addition

    to main or primary protection, are provided with a back-up and auxiliary protection.

    2.5.1 Main Protection:

    The main protection is the first line of defence and ensures quick-acting and selective

    clearing of faults within the boundary of circuit section or element it protects. Main protection

    as rule is provided for each section as an electrical installation.

    2.5.2 Back-up Protection:

    Back-up protection is the name given to protection which backs up the main protectionwhenever the later fails in operation, is cut out for repairs etc. It is the second line of defence

    which functions to isolate a faulty section of the system in case of the main function fails to

    20

  • 7/27/2019 Protection of Turbogenerator

    21/50

    function properly. The failure of the main protection may be due to any of the following

    reasons:

    The dc supply to tripping circuit fails.

    The current or voltage supply to relay fails.

    The circuit breaker fails to operate.

    The main protective relay fails

    Back-up protection may be provided either on same circuit breakers which would be

    normally opened by main protection or, still better, if the second line of protection makes use of

    different circuit breakers. Back-up protection usually for economic reasons not as fast as

    discriminative as the main protection.

    2.5.3 Auxiliary Protection:

    Auxiliary protection is employed in separate cases to accelerate the main protection

    operation during faults within the protected zone and also protect what is termed the dead zone

    of the main protection scheme.

    21

  • 7/27/2019 Protection of Turbogenerator

    22/50

    CHAPTER -3

    INTRODUCTION TO TURBO GENERATOR

    PROTECTION

    22

  • 7/27/2019 Protection of Turbogenerator

    23/50

    3.1 NECESSITY OF GENERATOR PROTECTIONS

    In order to generate power and transmit it to customers million of rupees must be

    spending on power system equipment. This equipment is designed to work under specified

    normal conditions however a short circuit may occur due to failure of insulation caused by:

    Over voltage due to switching

    Over voltage due to the direct and indirect lightning strokes

    Bridging of conductors by birds

    Breakdown of insulation due to decrease of its dielectric strength

    Mechanical damage to the equipment

    In modern power system it is necessary to eliminate faults to a large degree by careful

    system design. Careful insulation coordination, correct operation and maintenance, it is not

    obviously possible to ensure cent percent reliability and therefore the possibility of faults must

    be accepted.

    3.2 Generator Faults:

    Different types of faults that can occur within a generator can be classified as follows:

    Stator faults

    23

  • 7/27/2019 Protection of Turbogenerator

    24/50

    Rotor faults

    External faults

    3.2.1 Stator Faults:

    Stator faults involve the main current carrying conductors and must therefore be cleared

    quickly from the power system by a complete shutdown of the generator. They may be faults to

    earth, between phases or between turns of a phase, singly or in combination. The great danger

    from all faults is the possibility of damage to the laminations of the stator core and stator

    windings due to the heat generated at the point of fault. If the damage so caused is other than

    superficial, the stator would have to be dismantled, the damaged laminations and windings

    replaced and the stator rebuilt, all of which is a lengthy and costly process. Limitation of

    generator stator earth-fault current by means of resistance earthing is normal practice and

    serves, among other things, to minimize core burning.

    Phase-to-phase faults and interturn faults are both less common than earth faults. It is

    relatively easy to provide protection for phase-to-phase faults, but interturn faults are, on the

    other hand more difficult to detect and protection is not usually provided. Generally speaking,

    interturn faults quickly involve contact with earth via the stator core and are then tripped by

    stator earth-fault protection.

    3.2.2 Rotor Faults:

    Rotor faults may be either to earth or between turns and may be caused by the severe

    mechanical and thermal stresses acting upon the winding insulation; these are aggravated by a

    variable load cycle. The field system is not normally connected to earth so that a single earth

    fault does not give rise to any fault current. However, a second fault to earth would short circuit

    part of the field winding and thereby produce an asymmetrical field system, and unbalancedforces on the rotor. Such forces will cause excess pressure on bearings and shaft distortion, if

    not quickly removed. Under the general heading of rotor faults can be included loss of

    excitation. This may be caused by an open circuit in the main field winding or a failure

    24

  • 7/27/2019 Protection of Turbogenerator

    25/50

    elsewhere in the excitation system. Loss of excitation in a generator connected to a large

    interconnected power system results in a loss of synchronism and slightly increased generator

    speed, since the power input to the machine is unchanged. The machine behaves as an induction

    generator drawing its exciting current from the remainder of the system in the form of wattless

    current whose magnitude approximates to that of the full load rating of the machine. This may

    cause overheating of the stator winding and increased rotor losses due to the currents induced in

    the rotor body and damper winding. This condition should not be allowed to persist indefinitely

    and corrective action either to restore the field, or to off-load and shut down the machine should

    be taken. With generator outputs above half rated load, pole-slipping caused by weak field

    condition, would cause severe voltage variations which may, in turn, cause operation of the

    under voltage protection on the boiler auxiliaries. The resultant operation of 'loss of boiler

    protection would then shut down the generator unit. Other generators connected to the same bus

    bar may also be caused to 'swing' and system instability would result. Pole slipping may also

    result from insufficiently fast clearance of a system fault and require the tripping of the unit.

    3.2.3 Mechanical Condition:

    The mechanical conditions requiring consideration are over speed due to sudden loss of

    load, loss of drive due to prime mover failure and loss of condenser vacuum. The problem of

    over speed limitation, particularly in relation to sudden load changes, is considered later. With

    modem large units it is essential to anticipate over speed and take corrective action. Mechanical

    over speed devices which operation the steam stop valves are invariably fitted. In the event of

    failure of the prime mover, a generator will continue to run synchronously drawing power from

    the system. This can sometimes lead to a dangerous mechanical condition if allowed to persist,

    although the condition is immediately obvious to the attendant. Sets having an internal

    combustion prime mover must be protected against engine failure, where, if the alternator

    continues to motor serious engine damage may result.

    3.3 EXTERNAL FAULTS:

    25

  • 7/27/2019 Protection of Turbogenerator

    26/50

    Turbo alternators must be protected against the effects ofsustained external faults, for ex

    ample faults on lines or bus bars which are notcleared by the appropriate protection. The main

    condition of interest is that of an unsymmetrical fault producing negative phase sequence

    currents in the stator winding. The effect of these currents is to produce a field rotating in

    opposite sense to the d.c field system producing a flux which cuts the rotor at twice the

    rotational frequency thereby inducing double frequency currents in the field system and the

    rotor body. These currents produce severe rotor heating and modern machines have a limited

    negative phase sequence current capability. Automatic tripping is therefore required for the

    higher negative phase sequence current conditions. This capability limit applies to all modem

    hydrogen-cooled machines and many air-cooled machines, but some of the older air-cooled

    machines are designed to withstand full negative sequence currents continuously. In large

    modern alternators, particularly those employing direct cooling of the stator and rotor

    conductors, the temperature rise caused by abnormally high stator currents is more rapid than in

    the less highly rated machines and the capability limit is therefore lower.

    In the event of fault the circulating relay contact is closed and the trip coils TC1, TC2

    and TC3 are energized. The trip coil TC1 opens the main C.B while the trip coil TC3 opens the

    neutral circuit breaker. The trip coil TC2 opens the upper contacts, shorts the lower contacts so

    as to short circuit the field winding through resistor R. Thus the energy of the generator is

    dissipated in the resistor R.

    3.4 NAME PLATE DETALS OF TURBO GENERATOR USED IN TPP

    Rating - 60 MW

    Power factor - 0.8

    KVA - 75000STATOR Voltage - 11000 Volts

    Current - 3639 Amps

    ROTOR Voltage - 300 Volts

    26

  • 7/27/2019 Protection of Turbogenerator

    27/50

    Current - 596 Amps

    Frequency - 50 HZ

    No. of phases - 3

    Cooling system - Air

    Type of Insulation - Class B

    Connection - Star

    3.5 THE FOLLOWING ARE THE MAIN PROTECTION SCHEMES

    ADOPTED FOR GENERATOR

    1. Generator Differential Protection

    2. Stator Inter Turn Protection

    3. Reverse Power Protection

    4. Automatic Field suppression

    5. Local Breaker Backup Protection

    6. Stator Earth fault Protection

    7. Negative Sequence Protection

    8. Rotor earth Fault Protection

    9. Over Flux Protection

    10. Over Voltage Protection

    11. Stator Frame Over Heating Protection

    12. Abnormal Frequency Protection

    13. Loss of Field Protection

    14. Pole Slipping Protection

    15. Over Speed Protection

    27

  • 7/27/2019 Protection of Turbogenerator

    28/50

    16. Protection Against Vibrations

    17. Bearing Over Heating Protection

    18. Protection Against Motoring

    .

    CHAPTER 4

    PROTECTION SCHEMES I

    28

  • 7/27/2019 Protection of Turbogenerator

    29/50

    4.1 GENERATOR DIFFERENTIAL PROTECTION:

    This is the most common system employed for protection of stator windings against

    earth faults and phase to phase makes use of circulating current principle. In this scheme of

    protection currents at the two ends of protected sections are compared. Under normal operating

    conditions these currents are equal but may differ in the occurrence of fault in the protected

    system. The difference of currents under faulty conditions is made to flow through the relay

    operating coil. The relay then closes its contacts and makes the circuit breaker to trip and thus

    isolates the protected section from the system. Such a protection system is called a Merz-Price

    circulating current system. This protective scheme is very effective for earth faults and faults

    between phases.

    29

  • 7/27/2019 Protection of Turbogenerator

    30/50

    Fig 6: Generator Differential Protection

    The schematic arrangement of differential protection scheme is shown in fig: There

    are two sets of identical CTs each set is mounted on either side of stator phase windings. The

    secondaries of these CTs are connected in star, the neutral point being connected to current

    transformer common neutral and the outer ends of each of the three pilot wires. The fault setting

    required from the differential protection is determined by the value of the neutral earthing

    resistor and also by the amount of winding to be protected.

    Under normal healthy conditions, the currents at both ends of each winding will be

    equal, emfs induced in secondaries of CTs will be equal and so no current will flow through the

    operating coils of relays. When an earth fault or phase to phase fault occurs, this condition no

    longer holds good and the differential current flowing through the relay operating coil makes

    the circuit breaker to trip.

    4.2 STATOR INTERTURN FAULT PROTECTION:

    The differential current protection described in Section 4.1 cannot detect interturn faults

    which remain clear of earth, since there is a balance of the currents entering and leaving the

    winding despite the presence of a large current circulating the shorted turns. Interturn faults are

    not normally protected against because of the technical difficulty of so doing. If interturn faults

    30

  • 7/27/2019 Protection of Turbogenerator

    31/50

    occur in the stator slots, they quickly develop into faults to earth and are cleared by the stator

    earth fault protection. There is, however, the possibility that they may occur at the winding ends

    and so cause extensive damage to the generator before the fault evolves to one detectable by

    other protection. The primaries of CTs are inserted in these parallel paths and secondaries are

    cross connected. When there is no fault currents flowing through the two parallel paths of the

    stator winding will be equal and therefore no current will flow through the relay operating coil.

    But during inter-turn fault in the phase winding, the currents flowing through the two parallel

    paths will be different and a current proportional to the difference of two currents will flow

    through the relay operating coil which will close the trip circuit and isolate the machine from

    the power system. This kind of protection is extremely sensitive.

    Fig 7: Stator Interturn Fault Protection

    4.3 REVERSE POWER PROTECTION:

    31

  • 7/27/2019 Protection of Turbogenerator

    32/50

    Motoring of a generator will occur when turbine output is reduced such that it develops

    less than no-load losses while the generator is still on-line, the generator will operate as a

    synchronous motor and driving the turbine. The generator will not be harmed by synchronous

    motoring and a steam turbine can be harmed through overheating during synchronous motoring

    if continued long enough. The motoring of the turbine output can be detected by reverse power

    protection relay which is powered by both C.T and P.Ts. To avoid false tripping due to power

    swings a time delay is incorporated before tripping signal is generated. If the unit trips on

    reverse power protection, the input power to the turbine is increased as quickly as possible.

    Even after two to three attempts, if the machine trips on the same protection; probably the

    governor of turbine is faulty. The condition is informed to maintenance staff for rectification.

    4.4 AUTOMATIC FIELD SUPPRESSION:

    In the event of fault on the turbo generator winding even if the generator C.B is tripped,

    the fault continues to be fed as long as long as excitation will exist because emf is induced in

    the generator itself. For the quick removal of fault during emergency, it is necessary to

    disconnect the field simultaneously with the disconnection of the generator. Thus it is

    absolutely necessary to disconnect the magnetic field in the shortest possible interval of time.

    Hence it is to be ensured that all the protection system not only trips the generator circuitbreaker but also trips the automatic field discharge switch. The field discharge switch is an

    automatic control unit designed to remove voltage from the generator after its isolation from the

    system.

    32

  • 7/27/2019 Protection of Turbogenerator

    33/50

    Fig 8: Automatic Field Suppression

    4.5 LOCAL BREAKER BACK UP PROTECTION:

    For most of the faults, the generator breaker involves tripping the generator from the

    system. Failure of the breaker to open probably results in loss of protection & other problems

    such as motoring action or single phasing if one or two poles of the generator breaker fail to

    open due to mechanical failure in breaker mechanism, the result can be a single phasing

    &negative phase sequence currents induced on the rotor. The LBB protection is energized when

    the breaker trip is initiated after a suitable time interval if conformation of the breaker tripping

    from 3poles is not received .the energized tripping signal from local breaker back up protection

    will trip all 220kv generator breakers and all 220kv feeder breakers through bus bar protection.

    4.6 STATOR EARTH FAULT PROTECTION:

    Normally the generator stator neutral operates at a potential close to ground. If a faulty

    phase winding connected to ground, the normal low neutral voltage could rise as high as line-to-

    neutral voltage depending on the fault location. Although a single ground fault will not

    necessarily cause immediate damage, the presence of one increases the probability of a second.

    A second fault even if detected by differential relay, may cause serious damage.

    The usual method of detection fault is by measuring the voltage across the secondary of

    neutral grounding transformer (NGT). In the voltage-operated type, a standard induction

    33

  • 7/27/2019 Protection of Turbogenerator

    34/50

    disk type overvoltage relay is used. It is also to be noted that the relay is connected across the

    secondary winding of the transformer and the relay shall be suitably rated for the higher

    continuous operating voltage. Further, the relay is to be insensitive for third harmonic current.

    The generator neutral, the overvoltage element will not pick up because the voltage level

    will be below the voltage element pickup level. In order to cover 100% of the stator windings,

    two over lapping zones to detect stator ground faults in a high impedance grounded

    generator system, the two zones are put together cover 100% stator winding for earth

    faults. A fundamental frequency neutral over voltage relay covers about 0-95% of the

    stator zonal winding for all faults except those near the neutral.

    Fig 9: Stator Earth Fault Protection

    Another third harmonic neutral under voltage relay covers remaining 96-100% of

    the stator zone 2 winding on neutral side. a small amount of third harmonic voltage will be

    produced by most generators at their neutral and terminals. Normally they would be higher at

    34

  • 7/27/2019 Protection of Turbogenerator

    35/50

    full load. If a fault develops near the neutral, the third harmonic neutral voltage will approach

    zero and the terminal voltage will increase. Use of a third harmonic under voltage at the neutral

    it will pick up for a fault at the neutral.

    `

    CHAPTER 5

    PROTECTION SCHEMES II

    35

  • 7/27/2019 Protection of Turbogenerator

    36/50

    5.1 NEGATIVE SEQUENCE OR CURRENT UNBALANCE PROTECTION:

    When the machine delivering the equal currents in three phases, no unbalance are

    negative phase sequence current is produced as the vector sum of these currents is zero, when

    the generator is supplying an unbalanced load to a system, a negative phase sequence current is

    imposed on the generator. The system unbalance is due to opening of lines, breaker failures are

    system faults. The negative sequence current in the stator winding creates a magnetic flux wave

    in the air gap which rotates in the opposite direction to that of rotor synchronous speed. This

    flux induces currents in the rotor body, wedges, retaining rings at twice the line frequency.

    Heating occurs in these areas and the resulting temperatures depend upon the level and duration

    of the unbalanced currents. Under these conditions it is possible to reach temperatures at which

    the rotor material no longer contains the centrifugal forces imposed on them resulting in serious

    damage to the turbine generator set. Any machine as per design data will permit some level

    negative sequence currents for continuous period.

    An alarm will annunciate at annunciation panel it negative sequence currents exceed a

    normal level. Reduce the MVAR power on the machine if necessary load also and keep the

    machine for some time till the alarm vanishes at annunciation panel. If the machine trips on the

    negative sequence protection never take the machine into the service until the temperature onthe rotor parts settle down its lower value. Resynchronize the machine to the grid after

    considerable time under grid and feeder parameters all within limits. If the unit trips again on

    36

  • 7/27/2019 Protection of Turbogenerator

    37/50

    the same protection the machine is stopped after consideration time so as to cool down the rotor

    parts and inform to the maintenance staff for through examination of the system.

    A specialized relay to detect the circulating currents called a negative sequence current relay

    (since the induced currents are called negative sequence currents) is used to detect the phase

    imbalance with the generator during the unbalancing fault conditions.

    A negative sequence relay provides protection to generators and rotors against

    unbalanced loading that may result from the phase to phase faults the equipment consists of

    network energized from three CTs and a single pole relay having an inverse time characteristic

    Fig 10: Negative Sequence or Current Unbalance Protection

    The equipment consists of network energized from three C.Ts and an single pole relay

    having an inverse time characteristic connected across the network. The network consists of

    four impedances Z1, Z2, Z3, and Z4 of equal magnitude connected in a bridge formation. Z1,

    37

  • 7/27/2019 Protection of Turbogenerator

    38/50

    Z2 are non inductive resistances while Z3, Z4 are composed of both resistance and reactance.

    The values of Z2, Z4 are so adjusted that the currents flowing in these lag behind those in

    impedances Z1, Z2 by 60degrees. Resolving Ir, Ib there components IZ1, IZ3 and IZ2, IZ4 we

    find that the actual current flowing in the relay is Iy. Thus the relay is operated under the

    influence of Iy.

    5.2 ROTOR EARTH FAULT PROTECTION:

    Any rotor field winding of the generator is electrically isolated from the ground.

    Therefore the existence of one ground fault in the field winding will usually not damage

    the rotor.

    However the presence of two or more ground faults in the winding will cause magnetic

    and thermal imbalance plus localized heating and damage to the rotor metallic parts. The

    rotor earth fault may be caused due to insulation failure of winding or inter-turn fault

    followed by localized heat.

    38

  • 7/27/2019 Protection of Turbogenerator

    39/50

    Fig 11: Rotor Earth Fault Protection

    The field circuit of our generator comprises the rotor winding, the armature of the

    exciter, field circuit breaker and connecting cables. This total system is an isolated one and if an

    earth fault occurs, rotor winding turns will get short circuited which decreases the field circuit

    resistance and increases the current flowing through it. This current over heats the rotor winding

    and the exciter supplying it, causes further destruction at the points of faults and may lead to

    burning of the rotor insulation. The protection scheme consists of a high resistance connected

    across the rotor circuit and its mid point is grounded through a sensitive relay

    5.3 OVER FLUX OR OVER EXCITATION PROTECTION:

    This problem may occur in turbo generators that are connected to the grid if they

    experience generating voltage regulation problems. It may also occur for units during startup or

    resynchronizing following a trip. Over excitation in these instances may be result of equipment

    problems or operating errors in AVR.

    Moderate over fluxing (105-110%) increases core loss resulting in increase of core

    temperatures due to hysteresis and a eddy currents loss long term operation at elevated

    temperatures can short term the life of the stator insulation severe over fluxing can break down

    the insulation followed by rapid local core melting.

    A specialized volts/hertz (Per unit voltage divided by per unit frequency commonly

    called volts/hertz) relay is used to detect this condition, and will trip the generator if excessive

    volts/hertz conditions are detected.

    5.4 OVER VOLTAGE PROTECTION:

    Generator voltage is at present value under normal operating conditions as selected by

    operator in AVR. If it parts from preset value, may be due to AVR mal functioning or due to

    increase in prime-mover speed due to sudden loss of loss of load. Severe over voltage can cause

    over fluxing and winding insulation failure.

    39

  • 7/27/2019 Protection of Turbogenerator

    40/50

    The over voltage protection is provided with an over voltage relay which has two

    units one instantaneous relay set for pick up at about 130-150% of rated voltage and the

    another IDMT relay set for pick up at about 110% of rated voltage . These relays are

    energised from a PT. If an over voltage persists the generator main circuit breaker and

    the exciter field breaker will be tripped. If the generator trips for over voltage then raise

    the generator voltage slowly with manual mode in AVR. And keep generator voltage within the

    limits of normal voltage. If it is unable to control the generator voltage, the field breakers are

    tripped and informed to the maintenance staff of the AVR.

    5.5 STATOR FRAME OVER HEATING PROTECTION:

    For the protection of the turbo generator against any possible fire accident twelve fire

    detector relays are provided on either side of the stator winding. These relays have a set of

    normally open contacts. The set of contacts will close when the temperature surrounding the

    fire relay exceeds 80O C. The other relay set of contacts close when the temperature exceeds

    100O C. These contacts are wired to CO2 fire extinguishing system.

    CO2 gets discharged due to any of the following causes maintained below:

    Contact of the 100O C fire detector closed.

    Generator restricted earth fault relay operates.

    Generator differential relay operates.

    CO2 discharge system activated from turbo generator control test or manual to

    the box or push button located near the generator.

    All the above cases will actuate CO2 release mechanism and CO2 gas will be flooded

    into the generator air ducts.

    5.6 ABNORMAL FREQUENCY PROTECTION:

    40

  • 7/27/2019 Protection of Turbogenerator

    41/50

    For a generator connected to a system, abnormal frequency operation is a result of

    a severe system disturbance. The generator can tolerate moderate over frequency

    operation provided voltage is within an acceptable limits. The machine operated at higher

    speeds at which the rotor material no longer contain the centrifugal forces imposed on

    them resulting in serious damage to the turbine-generator set. The abnormal over

    frequency on the machine may be due to improper speed control adjustment or

    disoperation of the speed controller or severe grid disturbance or sudden load thrown off.

    If the unit trips due to abnormal frequency protection then change the governor speed until

    machine reaches full speed. Even after 2to3 attempts the machine is running at lower speed,

    probably the governor of the turbine is faulty. Inform to maintenance staff for rectification of

    the same.

    41

  • 7/27/2019 Protection of Turbogenerator

    42/50

    CHAPTER 6

    PROTECTION SCHEMES III

    42

  • 7/27/2019 Protection of Turbogenerator

    43/50

    6.1 LOSS OF FIELD OR LOSS OF EXCITATION PROTECTION:

    This fault is caused due to open circuit of field, short circuit of field, accidental

    tripping of field breaker, poor brush contact. This may also occur due to AVR failure.When the turbo generator is with excitation and connected to the grid, it generates

    reactive power along with active power to the grid. Loss of field or loss of excitation

    results in loss of synchronism between rotor flux & stator flux. The synchronous machine

    operates as an induction machine at higher speed and draws reactive power from the grid.

    This will result in the flow of slip frequency currents in the rotor body as well as severe

    torque oscillations in the rotor shaft. As the rotor is not designed to sustain such currents

    or to withstand the high alternating torques which results in rotor overheating, coupling

    slippage and even rotor failure.

    If the generator is not disconnected immediately when it loses excitation wide

    spread instability may very quickly develop and major system shutdown may occur.

    When loss of excitation alarm annunciates at annunciation panel, the machine may

    probably be running with less excitation at leading MVAR power. Increase the excitation

    on the machine until it reaches on lagging MVAR power. The machine trips on the same

    protection along with alarm resynchronize the machine and try to stabilize at required

    MVAR power. If not possible, trip the machine immediately and inform to the

    maintenance staff for thorough checking of the Automatic Voltage Regulator (AVR) and

    its associated parts.

    43

  • 7/27/2019 Protection of Turbogenerator

    44/50

    Many protection schemes are employed to protect the turbo generators from loss of

    field. The protection scheme used in TPP is the method generally adopted for the modern turbo

    generators. As modern large generators may be required to operate with very low values of

    excitation, when a generator loses synchronism, the quantity which changes most is its

    impedance as measured at the stator terminals.

    Loss of field will cause the terminal voltage of the generator to begin to fall, while the

    current begins to increase. The apparent impedance of the machine will therefore be seen to

    decrease and its power factor to change. The mho relay is placed which is designed to detect the

    change of impedance from the normal load value may therefore be used to provide protection

    against asynchronous operation resulting from the loss of excitation.

    Fig 12: Loss of Field or Loss of Excitation Protection

    6.2 POLE SLIP PROTECTION:

    A generator may lose synchronising with power system without failure of excitation

    system, because of severe fault disturbance or operation at a high load with leading power

    factor and hence a relatively weak field. A system power shock may make a generator rotor

    44

  • 7/27/2019 Protection of Turbogenerator

    45/50

    oscillate. Oscillation will create severe vibrations in machine and subsequent damage of

    machine bearings.

    Incase the angular displacement of rotor exceeds the stable limit; the rotor will slip a

    pole pitch. During this time machine should be isolated from the system. When a generator

    loses synchronism, the resulting high current peaks & off frequency operation may cause

    winding stresses, pulsation torques and mechanical resonances that have the potential danger to

    turbine generator.

    Fig 13: Pole Slip Protection

    6.3OVER SPEED PROTECTION:

    The turbo generator is fitted with over speed limiting gear designed to detect sudden loss

    of load and to close emergency valves immediately, to limit the magnitude of the temporary

    45

  • 7/27/2019 Protection of Turbogenerator

    46/50

    speed rise. In a typical scheme this is achieved by monitoring the electrical output of the

    generator using a watt metric relay. This relay will detect a sudden loss of output and operate

    instantaneously to close its contacts. A second relay monitors the steam input to the turbines at a

    chosen stage and the contacts are held dosed when the steam pressure is in the full load region.

    A sudden loss of load will give instantaneous operation of the output relay but the steam input

    relay does not operate immediately because steam is being admitted to and expanding in the

    turbine. Under this condition the emergency valve solenoids are energised giving instantaneous

    control of steam admission. The emergency valves remain closed until falling pressure or

    restoration of load restores the machines to normal control. The action of this equipment is

    clearly much faster than that obtainable from the governing system which requires an actual

    overspeed to produce a response and take corrective action. It is for this reason that overspeed

    limiting equipment of the type described is often installed where reheat turbines are used,

    because the long steam pipes of relatively large bore interconnecting each reheater and the

    reheat sections of the associated boiler plant present special problems due to the large volume of

    steam entrained. The overspeed limiting equipment then operates additionally into the

    interceptor emergency stop valves associated with each interceptor steam chest to give

    instantaneous control of the steam entering the turbine at all stages. In the ultimate, over

    speeding of the machine beyond the safe limit (10%) will cause operation of the overspeed

    bolts, and shut the stop valves.

    6.4 PROTECTION AGAINST VIBRATIONS:

    Rotor earth fault protection and negative sequence protection of a generator

    against unbalanced loads, described in topics 4.4 and 5.2 respectively to prevent or reduce

    vibration under those circumstances. A vibration detector may be mounted on one of the

    bearing pedestals in the case of a horizontal shaft generating set, or on the upper guide-

    bearing in case of a vertical shaft generating set. It may be set to trip the machine or

    initiate an alarm when the radial deflections of certain duration exceed a per-determined

    value.

    46

  • 7/27/2019 Protection of Turbogenerator

    47/50

    6.5BEARING OVER HEATING PROTECTION:

    Bearing over heating can be detected by a relay actuated by a thermometer-type

    bulb inserted in a hole in the bearing, or by a resistance-temperature-detector relay, such

    as used for stator over heating protection, with the detector embedded in the bearing. In

    case lubricating oil is circulated through the bearing under pressure, the oil temperature

    may be monitored if the system has provision for giving an alarm if the oil circulation is

    stopped.

    Such protection is provided for all unattended generators where the size or

    importance of the generator warrants it. Such protection for attended generators is

    generally limited only to sound an alarm.

    6.6PROTECTION AGAINST MOTORING:

    In the event of prime-mover failure the generator continues to rotate as a synchronous

    motor drawing electrical power from the system and driving the prime -mover . The motoring

    operation the machine is also known as inverted operation. This operation is not desirable, as

    firstly the machine ceases generation and no purpose is served by its motoring operation.

    The machine faults such as failure of bearings or lubricating troubles etc, are protected

    by special indicating instruments/protective devices which may stop the prime-mover

    automatically but such faults cannot be detected on the electrical side. However the inverted

    operation of the machine can be protected by employing reverse power relay.

    During the motoring operation of a generator the power flows from the bus-bars to the

    machine and the conditions in the three phases are balanced. Hence single element directional

    powers relay (reverse power relay) sensing the direction of power flow in any one phase is

    sufficient. Intentional time lag is provided to prevent operation by synchronous surges and

    power oscillations following system disturbances

    47

  • 7/27/2019 Protection of Turbogenerator

    48/50

    CONCLUSION

    A generator is the most important and most costly equipmenent in a power system. It is

    subjected to more number of troubles than any other equipment. The basic function of

    protection applied to generators is therefore to reduce the outage period to a minimum by rapid

    discriminative clearance of faults. While selecting the scheme for generator protection, the

    protection of complete unit and the stability of the system due to disturbance, in a generator

    should be considered in addition to protection of the generator itself.

    In our industry oriented mini project we have learned the importance of generator

    protection and studied various protection schemes employed for a 60MW Turbo Generator

    installed in thermal power plant (captive power plant in Visakhapatnam steel plant).

    48

  • 7/27/2019 Protection of Turbogenerator

    49/50

    BIBLOGRAPHY

    [1] A COURSE IN ELETRICAL POWER J.B.Gupta.

    [2] ELETRICAL POWERD.r. S.l.Uppal.

    [3] POWER SYSTEM PROTECTION AND SWITCH GEARBadri Ram and

    Vishwakarma.

    [4] PRINCIPLES OF POWER SYSTEMV.K.Mehta.

    [5]ELECTRIC POWER SYSTEM- A CONCEPTUAL INTRODUCTION-Alexandra von Meir, IEEE Press.

    [6]PROTECTION OF GENERATORS, TRANSFORMERS, GENERATOR-TRANSFORMER UNITS AND TRANSFORMER FEEDERS- J.Rushton,

    revised by K.G.M.Mewes.

    [7] A TEXT BOOK OF POWER SYSTEM ENGINEERING M.L.Soni, P.V.Gupta,U.S.Bhatnagar.

    [8] POWER SYSTEMS HAND BOOK- Leonard l.Grisbby.

    [9] INDUSTRIAL POWER SYSTEMS- Shoiab Khan.

    49

  • 7/27/2019 Protection of Turbogenerator

    50/50

    [10] THE ART AND SCIENCE OF PROTECTIVE RELAYING-C.Russell Mansion.