    REPORT TO CLARIF TO CESC

    THE SIMLATION ARIABLES AND CONCEPTS

    SED IN CMI OFFER 13.10.0021 (PSST)

    1/09/2010

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    2/14

    INDE

    1. DEFINITIONS:............................................................... 3

    2. PSST DATA............................................................... 6

    3. DIAGRAM OF FLES OF ENERG ............................... 7

    4. PERFORMANCE RATIO: C ............................. 9

    ANNE: PSST SIMLATION: 1.05 M

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    3/14

    1.

    B PSST (

    PSST ):

    I . I:

    I ( )

    (/2). T ()

    (/2)

    G H : (/2/)

    T '

    . G H I (GHI)

    . T

    D N I (DNI)

    D H I (DIF).

    I :

    I .

    N S

    N = GS / GI. I

    IAM

    T ( IAM, "I A M")

    P ' ,

    .

    ( PSS)FIAM = 1 (1/ 1), = ,

    = PSST P 0.05.

    E :

    I

    IAM.

    E STC

    T STC

    STC.

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    4/14

    I

    I 1000 /2 (STC).T P "E .

    I". I

    .

    T

    T . I

    '

    .

    O

    T ( R I )

    . T

    R

    M

    I P '

    . , P

    .

    N, ""

    , . M

    ,

    , .

    M

    L ""

    I/ .

    STC: S T C

    I . STC :

    1. ( ),

    . T 1 . . (1,000 /2)

    2.

    ( ). T 1.5.

    3. . STC

    25 C.

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    5/14

    N O C T (NOCT): T

    P 800 /2 , 20C

    1 . NOCT

    .

    MPP: :

    P (I)

    () . T

    , /I O' L. A P

    ,

    (MPP) ,

    (/I = /I)

    P R

    T , E C (JRC/I),

    () ,

    "" STC

    (I G ).

    T PR (S, P , , , )

    ( ). "S "

    , //,

    ,

    .

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    6/14

    2.

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    7/14

    3.

    N: T .

    ) 1 2

    G H I (/2/)

    GH = 1,905.8 /2/

    FT= +7.3% ( )

    (T=20)

    I (/2/)

    (T=20)

    GI= 2,045.7 /2/

    N = 2 %

    IAM = 2,8 %

    "E"

    IAM (/2/)

    GE = 1,947.7 /2/

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    8/14

    ) 1,05

    "E" (/)

    GE = G2 GE = 8,217 1,947.7 = 16,004,251 /

    G2 = A

    GE = 16,004,251 /

    = 12.8 %

    G (/)

    2,054,231 /

    I L = 3.6 %

    T L = 9.2 %

    A S = 0.5 %

    M Q L = 3.2 %

    M L = 2.2 %

    O L = 2 %

    G (/)

    1,658,828 /

    I = 2.8 %

    A E I O (/)1,612,294 /

    N S P (/(K))

    = EI/PP = 1,612,294 / 1,048 = 1,538

    = 1,538 /(K)

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    9/14

    4.

    R I E = GI /() STC

    N S P = EOI /()

    /

    = GI ( 3.) = 2,045.7

    = ( 3.) = 1,538

    PR = 75.2 %

    ( 1 2 1 )

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    10/14

    ANNE:

    PSST SIMLATION: 1.05 M

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    11/14

    Page 1/402/09/10PVSYST V4.37

    Grid-Connected System: Simulation parameters

    Project : Gajner

    Geographical Site Gajner Country India

    Situation Latitude 27.9N Longitude 73.0ETime defined as Legal Time Time zone UT+6 Altitude 232 m

    Albedo 0.20

    Meteo data : Gajner , synthetic hourly data

    Simulation variant : Gajner Policristalino 1,05 MWp

    Simulation date 02/09/10 11h35

    Simulation parameters

    Collector Plane Orientation Tilt 20 Azimuth 0

    Horizon Free Horizon

    Near Shadings according to module

    PV Array Characteristics

    PV module Si-poly Model XL24195Manufacturer XL TELECOM & ENERGY LIMITED

    Number of PV modules In series 24 modules In parallel 224 stringsTotal number of PV modules Nb. modules 5376 Unit Nom. Power 195 WpArray global power Nominal (STC) 1048 kWp At operating cond. 945 kWp (50C)Array operating characteristics (50C) U mpp 574 V I m pp 1648 ATotal area Module area 8217 m

    PV Array loss factorsHeat Loss Factor ko (const) 29.0 W/mK kv (wind) 0.0 W/mK / m/s

    => Nominal Oper. Coll. Temp. (800 W/m, Tamb=20C, wind 1 m/s) NOCT 45 CWiring Ohmic Loss Global array res. 11.4 mOhm Loss Fraction 3.0 % at STCSerie Diode Loss Voltage Drop 0.7 V Loss Fraction 0.1 % at STCArray Soiling Losses Loss Fraction 0.5 %Module Quality Loss Loss Fraction 3.0 %Module Mismatch Losses Loss Fraction 2.0 % at MPPIncidence effect, ASHRAE parametrization IAM = 1-bo (1/cos i - 1) bo Parameter 0.05

    System Parameter System type Grid-Connected System

    Inverter Model JEMA IF 1000KWManufacturer Data sheetInverter Characteristics Operating Voltage 410-850 V Unit Nom. Power 1000 kW AC

    User's needs : Unlimited load (grid)

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    12/14

    Page 2/402/09/10PVSYST V4.37

    Grid-Connected System: Near shading definition

    Project : Gajner

    Simulation variant : Gajner Policristalino 1,05 MWp

    Main system parameters System type Grid-ConnectedNear Shadings according to modulePV Field Orientation tilt 20 azimuth 0PV modules Model XL24195 Pnom 195 WpPV Array Nb. of modules 5376 Pnom total 1048 kWpInverter Model JEMA IF 1000KW Pnom 1000 kW acUser's needs Unlimited load (grid)

    Perspective of the PV-field and surrounding shading scene

    West South

    Zenith

    East

    Iso-shadings diagram

    -120 -90 -60 -30 0 30 60 90 120Azim uth []

    0

    15

    30

    45

    60

    75

    90

    Sunheight[]

    Gajner: 1,1MW 8.5 m_xltelenergy

    Beam shading factor (according to module) : Iso-shadings curves

    1: 22 june

    2: 22 may - 23 july3: 20 apr - 23 aug4: 20 mar - 23 sep5: 21 feb - 23 oct6: 19 jan - 22 nov7: 22 december

    7h

    8h

    9h

    10h

    11h

    12h

    13h

    14h

    15h

    16h

    17h

    18h

    19h

    1

    2

    3

    4

    5

    6

    7

    Behindthe plane

    Behindthe plane

    Shading loss: 1 %Shading loss: 5 %

    Shading loss: 10 %Shading loss: 20 %Shading loss: 40 %

    Attenuation for diffuse: 0.969and albedo: 0.292

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    13/14

    Page 3/402/09/10PVSYST V4.37

    Grid-Connected System: Main results

    Project : Gajner

    Simulation variant : Gajner Policristalino 1,05 MWp

    Main system parameters System type Grid-ConnectedNear Shadings according to modulePV Field Orientation tilt 20 azimuth 0PV modules Model XL24195 Pnom 195 WpPV Array Nb. of modules 5376 Pnom total 1048 kWpInverter Model JEMA IF 1000KW Pnom 1000 kW acUser's needs Unlimited load (grid)

    Main simulation resultsSystem Production Produced Energy 1612 MWh/year Specific 1538 kWh/kWp/year

    Performance Ratio PR 75.2 %

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec0

    1

    2

    3

    4

    5

    6

    7

    8

    NormalizedEnergy[kWh/kWp/day]

    Normalized productions (per installed kWp): Nominal power 1048 kWp

    Yf : Produced useful energy (inverter output) 4.21 kWh/kW p/dayLs : System Loss (inverter, ...) 0.12 kWh/kWp/dayLc : Collection Loss (PV-array losses) 1.27 kWh/kWp/day

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec0.0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    PerformanceRatioPR

    Performance Ratio PR

    PR : Performance Ratio (Yf / Yr) : 0.752

    Gajner Policristalino 1,05 MWp

    Balances and main results

    GlobHor T Amb GlobInc GlobEff EArray EOutInv EffArrR EffSysR

    kWh/m C kWh/m kWh/m kWh kWh % %

    January 113.1 14.70 146.5 137.7 123325 119874 10.24 9.96

    February 128.5 17.40 154.4 147.1 129413 125824 10.20 9.92March 167.4 23.50 183.7 176.0 151505 147328 10.04 9.76

    April 195.0 28.30 199.0 190.9 160241 155864 9.80 9.53

    May 216.1 31.30 206.7 197.8 163345 158792 9.62 9.35

    June 206.7 31.10 192.3 183.6 151842 147581 9.61 9.34

    July 185.7 29.50 176.3 167.6 140049 136087 9.67 9.39

    August 174.2 28.50 172.7 164.6 138000 134088 9.73 9.45

    September 161.1 28.30 170.4 162.9 136379 132533 9.74 9.47

    October 138.6 26.20 158.9 151.4 128964 125343 9.88 9.60

    November 114.3 21.40 144.8 137.2 118890 115591 9.99 9.72

    December 105.1 16.70 140.1 131.0 116621 113390 10.13 9.85

    Year 1905.8 24.77 2045.7 1947.7 1658576 1612294 9.87 9.59

    Legends: GlobHor Horizontal global irradiat ion

    T Amb Ambient Temperature

    GlobInc Global incident in coll. plane

    GlobEff Effective Global, corr. for IAM and shadings

    EArray Effective energy at the output of the array

    EOutInv Available Energy at Inverter Output

    EffArrR Effic. Eout array / rough area

    EffSysR Effic. Eout system / rough area

  • 8/10/2019 Report to CESC on Variables and Concepts of PVSYST

    14/14

    Page 4/402/09/10PVSYST V4.37

    Grid-Connected System: Loss diagram

    Project : Gajner

    Simulation variant : Gajner Policristalino 1,05 MWp

    Main system parameters System type Grid-ConnectedNear Shadings according to modulePV Field Orientation tilt 20 azimuth 0PV modules Model XL24195 Pnom 195 WpPV Array Nb. of modules 5376 Pnom total 1048 kWpInverter Model JEMA IF 1000KW Pnom 1000 kW acUser's needs Unlimited load (grid)

    Loss diagram over the whole year

    Horizontal global irradiation1906 kWh/m

    +7.3% Global incident in coll. plane

    -2.0% Near Shading Factor on global

    -2.8% IAM factor on global

    Effective irradiance on collectors1948 kWh/m * 8217 m coll.

    efficiency at STC = 12.8% PV conversion

    efficiency at STC = 12.8%2054231 kWh

    -3.6% PV loss due to irradiance level

    -9.2% PV loss due to temperature

    -0.5% Array Soiling loss

    -3.2% Module quality loss

    -2.2% Module array mismatch loss-2.0% Ohmic wiring loss

    Array virtual energy at MPP1658828 kWh

    -2.8% Inverter Loss during operation (efficiency)

    0.0% Inverter Loss over nominal inv. power

    -0.0% Inverter Loss due to power threshold

    0.0% Inverter Loss over nominal inv. voltage

    -0.0% Inverter Loss due to voltage threshold

    Available Energy at Inverter Output1612294 kWh