    Transformers :

    Principle, Types andConstructional Details.

    R. K. Mishra

    Director & Head of Institute

    NPTINER, Guwahati.

  • 7/30/2019 RKM D HOI Transformer Mod

    2/67

    Layout of Switchyard showing locations

    of different Transformers in a TPS :

    2

  • 7/30/2019 RKM D HOI Transformer Mod

    3/67

    3

    Transformer :

    Static Apparatus

    Core Type (small size)

    Shell Type (large size)

    1 Transformer

    3 Transformer(either 3 Nos. of 1 Transformer or,single unit 3 Transformer)

  • 7/30/2019 RKM D HOI Transformer Mod

    4/67

    4

    Advantages of single unit 3

    Transformer :

    Greater efficiency

    Smaller size

    Less cost compared with a Bank

    having equal kVA capacity of three1 Transformer

  • 7/30/2019 RKM D HOI Transformer Mod

    5/67

    5

    Advantages of three 1 units :

    Greater availability with a singlestandby.

    Ease of maintenance.

    Ease of manufacture, transportationand erection.

  • 7/30/2019 RKM D HOI Transformer Mod

    6/67

    6

    Symbols :

  • 7/30/2019 RKM D HOI Transformer Mod

    7/67

    7

    Symbols (contd.) :

  • 7/30/2019 RKM D HOI Transformer Mod

    8/67

    8

    Name Plate Details :

    (1). IS standard IS:2026:1962 etc.(2). Manufacturers Name.

    (3). Serial No.(4). Rated kVA.

    (5). Frequency.

    (6). Number of phases.

    (7). Rated voltage on noload(HV/LV).

  • 7/30/2019 RKM D HOI Transformer Mod

    9/67

    9

    Name Plate Details (contd.) :

    (08). Rated current (HV/LV).

    (09). Impedance voltage in %.

    (10). Winding connection vector diagram.

    (11). Type of cooling.

    (12). Weight of core assembly andwinding in Kgs.

  • 7/30/2019 RKM D HOI Transformer Mod

    10/67

    10

    Name Plate Details (contd.) :

    (13). Total quantity and weight of

    insulating liquid.

    (14). Weight of complete transformer.(15). Temperature rise in oil.

    (16). Year of manufacture.

    (17). Customer reference.

  • 7/30/2019 RKM D HOI Transformer Mod

    11/67

    11

    Core type transformer :

  • 7/30/2019 RKM D HOI Transformer Mod

    12/67

    Core Type Transformer (contd.) :

    12

    http://www.leonardo-energy.org/files/root/Images/2007/UI39.preview.JPG
  • 7/30/2019 RKM D HOI Transformer Mod

    13/67

    Core Type Transformer (contd.) :

    13

  • 7/30/2019 RKM D HOI Transformer Mod

    14/67

    Core Type 3 Transformer :

    14

  • 7/30/2019 RKM D HOI Transformer Mod

    15/67

    Core Type 3 Transformer (contd.) :

    15

  • 7/30/2019 RKM D HOI Transformer Mod

    16/67

    Shell Type Transformer :

    16

  • 7/30/2019 RKM D HOI Transformer Mod

    17/67

    Shell Type Transformer (contd.):

    17

  • 7/30/2019 RKM D HOI Transformer Mod

    18/67

    Shell Type Transformer (contd.):

    18

  • 7/30/2019 RKM D HOI Transformer Mod

    19/67

    Shell Type Transformer (contd.) :

    19

  • 7/30/2019 RKM D HOI Transformer Mod

    20/67

    Shell Type 3 Transformer :

    20

  • 7/30/2019 RKM D HOI Transformer Mod

    21/67

    Core and Shell Type Transformer :

    21

  • 7/30/2019 RKM D HOI Transformer Mod

    22/67

    22

    Types of Transformer :

    (1). As per construction :

    (a) Core type transformer

    (b) Shell type transformer

    (2). As per voltage :

    (a) Stepup transformer(b) Stepdown transformer

    (c) Auto transformer

  • 7/30/2019 RKM D HOI Transformer Mod

    23/67

    23

    Types of Transformer (contd.) :

    (3). As per phase :

    (a) 1 Transformer(b) 3 Transformer

    bank of 3 Nos. of 1Transformer

    single unit 3Transformer

  • 7/30/2019 RKM D HOI Transformer Mod

    24/67

    24

    Types of Transformer (contd.) :

    (4). As per application :

    (a) Power Transformer

    (b) Distribution Transformer

    (c) Isolation Transformer

  • 7/30/2019 RKM D HOI Transformer Mod

    25/67

    25

    Types of Transformer (contd.) :

    (5). As per winding :

    (a) Single winding transformer

    (b) Two winding transformer

    (c) Three winding transformer

  • 7/30/2019 RKM D HOI Transformer Mod

    26/67

    26

    Tertiary Winding :

    (1). Reduces triple harmonic contents

    of output voltage thereby

    stabilizes potential of neutral

    point.

    (2). Suppresses 3rd harmonic current

    which causes communicationinterference.

  • 7/30/2019 RKM D HOI Transformer Mod

    27/67

    27

    Tertiary Winding (contd.):

    (3). Permits the transformation of

    unbalanced 3 load.

    (4). Reduces system zero sequence

    impedance for effective

    grounding.

    (5). Supplies additional auxiliary load.

  • 7/30/2019 RKM D HOI Transformer Mod

    28/67

    28

    Differences between Power Transformer

    and Distribution Transformer :

    Power Transformer Distribution Transformer

    01.

    Single 3 unitor, three 1units, / and/, 3wire.

    01.Single 3 unit,/, 4wire.

    02. Capacity : MVA 02. Capacity : kVA

  • 7/30/2019 RKM D HOI Transformer Mod

    29/67

    29

    Differences between Power Transformer

    and Distribution Transformer (contd.) :

    Power Transformer Distribution Transformer

    03.voltage rating :220 kV/11 kV or,higher as 400 kV

    03.

    voltage rating :

    11 kV/415 V,(HV : 33 kV also),415 V/230 V etc.

    04.Flux density :

    1.5 to 1.7 Wb m

    2

    04.Flux density :

    1.7 Wb m

    2

    05. Load : on full load 05.Load : part of dayon noload, partload.

  • 7/30/2019 RKM D HOI Transformer Mod

    30/67

    30

    Differences between Power Transformer

    and Distribution Transformer (contd.):

    Power Transformer Distribution Transformer

    06.Ratio of iron lossto copper loss =1:1

    06.Ratio of iron lossto copper loss =1:3

    07.% impedance =6% to 18%

    07.% impedance =4% to 5%

  • 7/30/2019 RKM D HOI Transformer Mod

    31/67

    31

    Differences between Power Transformer

    and Distribution Transformer (contd.) :

    Power Transformer Distribution Transformer

    08.

    Cooling : forcedair, forced oil,forced water,self oil cooled.

    08.Cooling :self oil cooled.

    09.Regulation :6% to 10 %

    09.Regulation : 4%to 9%

  • 7/30/2019 RKM D HOI Transformer Mod

    32/67

    32

    Distribution Transformer Ratings :

    kVA ratings : 63 kVA, 100 kVA,

    25 kVA, 40 kVA etc.

    Voltage ratings : 6.6 kV/415 V,

    11 kV/415 V

    Tappings : 2.5%, 5.0%

  • 7/30/2019 RKM D HOI Transformer Mod

    33/67

    33

    Transformer Specifications :

    (1). kVA rating

    (2). Rated Voltage

    (3). No. of phases(4). Rated Frequency

    (5). Connections

    (6). Tappings

  • 7/30/2019 RKM D HOI Transformer Mod

    34/67

    34

    Transformer Connections :

    3 connections

    (a) connection : schematic diagram

  • 7/30/2019 RKM D HOI Transformer Mod

    35/67

    35

    Transformer Connections (contd.) :

    3 connections

    (a) connection : features :

    0 phase shift.

    Economic for small HV Transformer,because No. of turns per phase andamount of insulation is minimum asVph = VL/(3). So, conductors are of

    large cross section. Less expensive and mechanically

    strong winding.

  • 7/30/2019 RKM D HOI Transformer Mod

    36/67

    36

    Transformer Connections (contd.) :

    3 connections

    (b) connection : schematic diagram

  • 7/30/2019 RKM D HOI Transformer Mod

    37/67

    37

    Transformer Connections (contd.) :

    3 connections

    (b) connection : features :

    0 phase shift. Economic for large, LV Transformer

    in which insulation problem is noturgent.

    Vph = VL

  • 7/30/2019 RKM D HOI Transformer Mod

    38/67

    38

    Transformer Connections (contd.) :

    3 connections

    (c) connection : features :

    +30 phase shift.

    Main use at sub-station end wherevoltage is to be stepped down.

    Ratio between primary line voltage

    and secondary line voltage is= 3:1

  • 7/30/2019 RKM D HOI Transformer Mod

    39/67

    39

    Transformer Connections (contd.) :

    3 connections

    (d) connection : features :

    30 phase shift.

    Main use at the beginning oftransmission system where voltageis to be stepped up.

    Ratio between primary line voltageand secondary line voltage is= 1:3

  • 7/30/2019 RKM D HOI Transformer Mod

    40/67

    40

    Transformer Connections (contd.) :

    3 connections

    (e) Open or, Vconnection :

    (schematic diagram)

  • 7/30/2019 RKM D HOI Transformer Mod

    41/67

    41

    Transformer Connections (contd.) :

    3 connections

    (e) Open or, Vconnection : features

    one of the Transformers of a bank is out and 3 supply isconnected.

    Voltage output = 58% of

    Power output = 86.6% of

  • 7/30/2019 RKM D HOI Transformer Mod

    42/67

    42

    Transformer Connections (contd.) :

    3 connections

    (f) Scottconnection or, TT connection :

    One of the Transformers has centretaps both on primary and secondarywindings and known as MainTransformer, other one has tapping

    at 0.866 and known as TeaserTransformer.

  • 7/30/2019 RKM D HOI Transformer Mod

    43/67

    43

    Transformer Connections (contd.) :

    3 connections

    (f) Scottconnection or, TT connection :

    (schematic diagram)

  • 7/30/2019 RKM D HOI Transformer Mod

    44/67

    44

    Impedance Voltage :

    It is the voltage required to be applied at ratedfrequency between line terminals of a 3 winding or,between terminals of a 1 winding to cause the ratedcurrent to flow into these terminals when the terminals ofthe other windings are shorted. It is measured as % ofrated voltage of former winding.

  • 7/30/2019 RKM D HOI Transformer Mod

    45/67

    45

    Vector Group :

    1st symbol HV winding connection

    2nd symbol LV winding connection

    3rd symbol phase displacement

    1 1 Oclock 302 11 Oclock +303 6 Oclock 1804 12 Oclock 0

  • 7/30/2019 RKM D HOI Transformer Mod

    46/67

    46

    Vector Table :

    (a) 0 phase shift :

    yo

    Ddo

    Dzo

    Zdo

  • 7/30/2019 RKM D HOI Transformer Mod

    47/67

    47

    Vector Table :

    (b) 30 phase shift (Lag) :

    Dy1 yd1

    yz1

    zy1

  • 7/30/2019 RKM D HOI Transformer Mod

    48/67

    48

    Vector Table :

    (c) +30 phase shift (Lead) :

    Dy11 Yd11

    Yz11

    Zy11

  • 7/30/2019 RKM D HOI Transformer Mod

    49/67

    49

    Vector Table :

    (d) 180 phase shift :

    Yy6

    Dd6 Dz6

    Zd6

  • 7/30/2019 RKM D HOI Transformer Mod

    50/67

    50

    Construction :

    (01). Core(02). Windings(03). Tap Changers(04). Tanks

    (05). Bushings(06). Auxiliary Equipment(07). Cooling System(08). Insulating Oil(09). Conservator Tank

    (10). Breather(11). Radiators(12). Buchholz Relay

  • 7/30/2019 RKM D HOI Transformer Mod

    51/67

    51

    Construction (contd.) :

    (1). Core :

    laminated, thickness : 0.28 mm to 0.30 mm,

    CRGO,

    3% silicon iron.

  • 7/30/2019 RKM D HOI Transformer Mod

    52/67

    52

    Construction (contd.) :

    (2). Winding :

    type : spiral, helical, or, disc type. selection depends on

    current rating

    short circuit strength

    temperature rise

    overload condition impedance

    voltage surge strength

  • 7/30/2019 RKM D HOI Transformer Mod

    53/67

    53

    Construction (contd.) :

    (3). Tap Changers :

    OFFLoad type and ONLoad type. In generating stations mainly OFFLoad

    types are used as voltage regulation isdone by AVR. Power Transformers in receiving stations

    are having ONLoad type. In Power Stations, station service

    transformers have ONLoad type. Tappings are provided on HV side.

  • 7/30/2019 RKM D HOI Transformer Mod

    54/67

    54

    Construction (contd.) :

    (4). Tank :

    Body is made up of rolled steel

    plate. Conservator tank is cylindrical and

    permits free expansion of oil w.r.t.temperature.

    Oil Gauge is provided to indicate theoil level.

  • 7/30/2019 RKM D HOI Transformer Mod

    55/67

    55

    Construction (contd.) :

    (5). Breather :

    Air is drawn into conservator

    through a vent which has moisturetrap (silica gel).

    Blue dry &

    Pink moisture.

  • 7/30/2019 RKM D HOI Transformer Mod

    56/67

    56

    Construction (contd.):

    (6). Bushings :

    connected to HV lines.

    moulded high quality glazedporcelain insulator with conductorthrough its centre (up to 33 kV).

    HV oil filled condenser patterngraded resin bonded paper.

  • 7/30/2019 RKM D HOI Transformer Mod

    57/67

    57

    Construction (contd.) :

    (7). Cooling Systems :

    ON or, OA type oil immersed natural cooling.

    FOW or, OFW type oil immersed forced oil cooled withforced water cooled.

    AA or, AN type

    dry type self cooled (below 15 kV). AFAAB type dry type forced. AA/AFA & AN/AB type.

  • 7/30/2019 RKM D HOI Transformer Mod

    58/67

    58

    Parallel Operation :

    (1). Primary windings of Transformers

    suitable for supply system

    voltage and frequency.

    (2). Transformers should be properlyconnected with regard to

    polarity.

    (3). Voltage ratings of both primaries and

    secondaries should be identical (sametransformation ratio).

  • 7/30/2019 RKM D HOI Transformer Mod

    59/67

    59

    Parallel Operation (contd.):

    (4). Percentage impedance should be same,

    i.e., (I1Zo1/V1)x100 = (I2Zo2/V2)x100.

    (5). Voltage ratio must refer to terminal

    voltage of primary and secondary

    (not ratio of No. of turns per phase).

    (6). Phase displacement between primary

    and secondary voltages must be same.(7). Phase sequence must be same.

  • 7/30/2019 RKM D HOI Transformer Mod

    60/67

    60

    Parallel Operation (contd.):

    (8). Examples :

    can be operated in parallel with

    (with same transformation ratio possible). can be operated in parallel with (with same transformation ratio possible).

    or, can not be paralled with

    or, . and can be paralled by certain

    shiftings.

  • 7/30/2019 RKM D HOI Transformer Mod

    61/67

    61

    Transformers in 210 MW Thermal

    Power Station :

    (1). Main Unit stepup Transformer :

    also known as

    GeneratorTransformer (GT). voltage rating : 15.75 kV / 220 kV.

    capacity : 250 MVA

    tapchanger : OFFLoad type.

  • 7/30/2019 RKM D HOI Transformer Mod

    62/67

    62

    Transformers in 210 MW Thermal

    Power Station (contd.):

    (2).Unit Auxiliary Transformer (UAT) :

    stepdown type.

    voltage rating : 15.75 kV / 6.6 kV.

    capacity : 10,000 kVA

    tapchanger : ONLoad type,

    2 Nos.

  • 7/30/2019 RKM D HOI Transformer Mod

    63/67

    63

    Transformers in 210 MW Thermal

    Power Station (contd.):

    (3). Station Auxiliary Transformer

    (SAT) :

    stepdown type. voltage rating : 220 kV / 6.6 kV.

    capacity : 16,000 kVA.

    tapchanger : ONLoad type,2 Nos.

    T f i 210 MW Th l

  • 7/30/2019 RKM D HOI Transformer Mod

    64/67

    64

    Transformers in 210 MW Thermal

    Power Station (contd.):

    (4). Transformers for LT supply :

    Cooling Tower two transformers each of 1000 kVA.

    Electrostatic Precipitator one transformer of 1600 kVA.

    Standby one transformer of 1600 kVA.

    Lighting one transformer of 1000 kVA.

  • 7/30/2019 RKM D HOI Transformer Mod

    65/67

    65

    Generator Transformer (GT) :

    250 MVA, 3, 50 Hz. Cooling OFWF. HV at NoLoad 230 kV. LV at NoLoad 15.75 kV. HV line current 627.55 Amp

    LV line current 9164.29 Amp Temperature rise of oil 50 C Temperature rise of winding 60 C Connection Nd11 Impedance voltage 12.77%

    Weight of core and winding 140265 kg Weight of oil 43380 kg (49860 Litre) Total weight 216980 kg

  • 7/30/2019 RKM D HOI Transformer Mod

    66/67

    66

    Unit Auxiliary Transformer (UAT) :

    15 MVA / 25 MVA, 3, 50 Hz. Cooling ONAN / ONAF HV at NoLoad 15.75 kV LV at NoLoad 7 kV HV line current 917.5 Amp

    LV line current 2064.4 Amp Temperature rise of oil 50 C Temperature rise of winding 55 C Connection Dyn1 Percentage impedance 10.08, 10.22 and 10.38 Weight of core and winding 18300 kg

    Weight of oil 7440 kg (7800 Litre) Total weight 37500 kg

  • 7/30/2019 RKM D HOI Transformer Mod

    67/67

    Station Transformer (ST) :

    25 MVA / 40 MVA, 3, 50 Hz. Cooling ONAN / ONAF HV at NoLoad 220 kV LV at NoLoad 7 kV or, 11 kV Connection Nyn0d1 Percentage impedance 15.21, 17.32 and

    20.53 Weight of core and winding 36000 kg

    Weight of oil 27500 kg (31600 Litre) Total weight 88000 kg