971 Elmore Drive PO Box 115250 Gainesville, FL 32611-5250 (352) 392-1331 Fax 352-392-8837
The Foundation for The Gator Nation An Equal Opportunity Institution
Office of the Vice President and Chief Financial Officer Procurement Services https://procurement.ufl.edu/
March 27, 2020
ADDENDUM NUMBER 4 ON INVITATION TO BID ITB20KO-136
TITLE: IFAS Demonstration Pavilion – Live Oak, FL
Mandatory pre-bid meeting was held March 17, 2020 at 10:00AM at the site. Bid opening is scheduled for April 9, 2020 at 3:00PM.
This addendum shall be considered part of the Contract Documents for the above-mentioned project as though it had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original Contract documents, this addendum shall govern and take precedence. Bidders are hereby notified that they shall acknowledge receipt of the addendum.
This addendum consists of:
• Change to Section 00100 – INSTRUCTION TO BIDDERS, 1.4 BID FORM, Item F• Responses to contractor questions and requests for clarification• One (1) page of drawing C-210 referenced in Q12/A12 of responses to contractor questions and
requests for clarification• Eight (8) pages of drawings referenced in Q16/A16 of responses to contractor questions and requests
for clarification• Five (5) pages of Engineer’s Addendum dated March 24, 2020• Fenetex representative contact information: Craig Scott, [email protected], 904-437-5168 (office),
904-612-6762 (mobile)
Karen Olitsky Procurement Agent III
PLEASE ACKNOWLEDGE RECEIPT OF THIS ADDENDUM 4 AND RETURN WITH YOUR BID. FAILURE TO ACKNOWLEDGE THIS ADDENDUM COULD CONSTITUTE REJECTION OF YOUR BID.
VENDOR NAME
VENDOR ADDRESS
SIGNATURE
Change to Section 00100 – INSTRUCTION TO BIDDERS, 1.4 BID FORM, Item F.
Due to the current COVID‐19 pandemic situation, the University of Florida will be accepting proposal submissions by email for this solicitation.
An email submission must be made in lieu of paper copies. These emails will not be opened prior to the published deadline of April 9, 2020 at 3pm. Any submissions received after this time will not be accepted.
Submissions should be sent to [email protected]
Copied to [email protected]
To ensure all submissions are received and avoid potential email delays, please do not wait until the deadline to submit your proposals. The proposal submission format should follow that as outlined in the original ITB document, Section 00100 – INSTRUCTION TO BIDDERS, 1.4 BID FORM, and include the Invitation to Bid Construction Acknowledgment Form, Section 00310 Bid Form (REVISED) and list of subcontractors as described in SECTION 00430 – SUBCONTRACTOR LISTING.
Responses to Contractor Questions and Requests for Clarification
Q1. What is the budget estimate for this project?
A1. $200,000
Q2. The specifications call for FRP panels. None are shown on the drawings, please clarify where these panels need to be installed.
A2. Disregard references to the FRP panels. None are in scope.
Q3. Specification Section 09960 FRP panels are not in TOC. Please clarify.
A3. Disregard references to the FRP panels. None are in scope.
Q4. The specifications call out for fire extinguishers and AED’s. Both are not shown on drawings, please clarify if they are needed on this project.
A4. Reference LS1.0. Three (3) fire extinguishers are indicated. Spec 10520 calls for one (1) AED. Owner to supply and Owner to install.
Q5. Section 10520 subsection 2.C "automatic external defibrillators" states "include the addition of one or more AED 's, with the cabinet(s) specified, furnished, and installed by the project and the device(s) themselves purchased by the project and installed by UF EH&S. Consult with the EH&S during design regarding type/size, quantity, and location(s)." Please clarify this scope of work.
A5. Reference LS1.0. Three (3) fire extinguishers are indicated. Spec 10520 calls for one (1) AED. Owner to supply and Owner to install.
Q6. Specification Section 16305 ceiling fans is not on the table of contents, but the specification is in the spec book. On drawing A4. 0 it states "Fans" not in contract. Please clarify this scope of work.
A6. The Owner will furnish and install the specified ceiling fan. The contractor is responsible for the electrical serving the fan and fan junction box suitable for the specified fan.
Q7. The drawings indicate widths that span up to approximately 25ft between columns. Fenetex has advised that Clear Vinyl Roll up curtains are typically installed no wider than about 13ft before they need intermediate columns. Is it the intent to add columns to support the roll up curtains?
A7. No. The curtains will not be clear vinyl but a Retractable Insect Screen.
Q8. Please confirm if the base bid columns are to be standard PEMB columns.
A8. Confirmed.
Q9. Please confirm that ALT 3 will only be taken if ALT 2 is accepted. There is no detail shown for screen curtain track connection to standard PEMB columns (Base Bid).
A9. Confirmed.
Q10. Who is responsible for removing the existing utility poles?
A10. The owner will coordinate the removal of the pole, and the installation of the pad mounted transformer. The contractor is responsible for the installation of the conduit from the meter to the transformer and the coordination with the local utility (Suwannee Valley Electric Coop) for the installation of the conductors from the transformer to the meter can. The contractor should contact Suwannee Valley Electric Cooperative to discuss the transformer and underground connection so that they comply with their policies.
Q11. Please confirm if the local utility company will be providing the transformer and underground connection to the new transformer.
A11. Confirmed. Contractor to install conduit from building to transformer. Utility will provide and pull conductors form the meter to the transformer.
Q12. Please clarify what items from the civil plan are in Lot 1 vs Lot 2.
A12. Reference attached plan C‐210 clarifying this item.
Q13. Given the outside condition of the electric water cooler, it is assumed that it should have freeze protection and be heavy duty. Please confirm and provide water specification.
A13. Freeze protection is not required.
Q14. There is not currently a grassing/sod specification. Please clarify sod type & proposed seed type.
A14. Bahia sod and seed shall be used at disturbed soils and stormwater basins for Lot 2. Seeding and Sod in Lot 1 is not in contract.
Q15. On sheet T0.0, the 3D plan shows landscaping. There are not any landscape & irrigation drawings. Please clarify scope if any.
A15. Landscaping is not in scope.
Q16. Addendum #2, Attachment A, contained revised technical specifications and drawings. Drawing T0.0, LSJ.0, A1.0, A1.2, A2.0, A2.1, A4.0 & A7.0 will not print to scale. These files are sized different. Can new files to scale be distributed?
A16. Yes. Reference attached architectural pdfs.
Q17. Will structural drawings be available before time of bid?
A17. Structural drawings for the metal building will not be available prior to the bid. Structural design for the slab will be provided by structural engineer once the metal building manufacturer provides the reactions. This will all be after award of contact.
Q18. Will the GC be responsible for the testing and inspections of this project?
A18. Yes.
Q19. Specification Section 00811 subsection 1.2 calls for Davis Bacon wages. Please confirm if this applies to this project.
A19. Does not apply to this project.
Q20. Specification Section 01014, 1.7, Personnel Screening. What are the costs associated with the universities screening policy? Please advise.
A20. Personnel Screening is not required at this UF IFAS facility.
Q21. Are there permitting costs associated with UF’s building permits? If so, will the contractor be responsible for paying the building permit?
A21. Yes. See permit fee schedule in the link below: http://www.ehs.ufl.edu/programs/buildcode/codes/fees/ Contractor is responsible for permitting costs.
Q22. Does specification Section 01352 LEED Requirements pertain to this project?
A22. No.
Q23. What are the liquidated damages on this project?
A23. No liquidated damages on this project.
Q24. Are barriers required during construction per Section 01530?
A24. No.
Q25. Will a University of Florida exterior building sign be included in this project? Shown in specifications, but none on drawings.
A25. Owner will furnish and install sign.
OHEOHE
OHEOHE
OHEOHE
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
O
H
E
PU
E
P
U
E
P
U
E
P
U
E
P
U
E
P
U
E
PU
E
P
U
E
UGE
U
G
E
U
G
E
U
G
E
U
G
E
U
G
E
UG
E
UG
E
P
U
E
P
U
E
P
U
E
P
U
E
P
U
E
PU
E
P
U
E
PU
E
S
TO
R
M
S
T
O
R
M
S
TO
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
ST
OR
M
ST
OR
M
ST
OR
M
ST
OR
M
ST
OR
M
ST
OR
M
ST
OR
M
ST
OR
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
IL
T
S
IL
T
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
UGE
UGE
U
G
E
U
G
E
UGE UGE UGE UGE UGE
T
x
1
P
S
TO
R
M
S
TO
R
M
S
TO
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
T
O
R
M
S
IL
T
S
IL
T
S
IL
T
S
IL
T
S
IL
T
S
IL
T
S
IL
T
SIL
T
S
IL
T
S
IL
T
S
I
L
T
S
I
L
T
S
IL
T
SILT
SIL
T
S
I
L
T
S
I
L
T
SIL
T
SIL
T
SIL
T
SIL
T
SIL
T
SIL
T
SIL
T
SIL
T
SIL
T
SILT
SILT
SILT
SILT
SILT
S
IL
T
S
IL
T
S
I
L
T
S
I
L
T
S
I
L
T
S
I
L
T
S
I
L
T
S
ILT
S
ILT
S
ILT
S
ILT
S
ILT
S
I
L
T
S
I
L
T
S
I
L
T
S
I
L
T
S
I
L
T
S
ILT
S
ILT
S
ILT
S
ILT
S
ILT
162.70
162.79
162.90
162.00
162.64
162.82
162.72
162.92
162.84
163.04
162.89
163.09
163.32
163.30
163.21
162.42
163.02
162.99
162.67
162.32
162.55
162.02
163.12
162.93
163.17
163.17
163.17
163.17
163.17
163.17
163.07
163.07
163.23
163.23
162.83
162.76
163.14
163.01
0
.
3
%
1
.
7
%
1.9%
1
.
6
%
3.5%
3
.
5
%
1
.
1
%
1
.
5
%
1
.
4
%
0
.
8
%
1
.
0
%
2
.9
%
2
.
6
%
2
.3
%
0
.
8
%
1
.
1
%
1
.1
%
1
.2
%
3.4%
5
.
0
%
2
.8
%
ST-2 MANHOLE
RIM=162.54
NW 157.91 15"
E 157.91 15"
ST-3 MANHOLE
RIM=162.37
W 158.29 15"
NW 158.58 6"
SE 158.29 15"
ST-4 TYPE C
RIM=162.02
NW 159.08 15"
N 159.37 8"
E 159.08 15"
ST-5 TYPE C
RIM=162.00
SE 159.50 15"
STCO-1 CLEANOUT
RIM=162.94
S 159.81 8"
15" H
D
P
E
160'
@
0.35%
6
"
P
V
C
8
4
'
@
0
.
5
0
%
15"
HD
PE
225'
@ 0
.35%
1
5
"
H
D
P
E
1
0
7
'
@
0
.
3
5
%
1
5
"
H
D
P
E
1
1
8
'
@
0
.
3
5
%
86'
8" HDPE
@ 0.50%
RESTORE LIMEROCK
AFTER PIPE INSTALL
RESTORE LIMEROCK
AFTER PIPE INSTALL
4
" P
V
C
R
O
O
F
D
R
A
IN
4
" P
V
C
R
O
O
F
D
R
A
IN
4
" P
V
C
R
O
O
F
D
R
A
IN
6
" P
V
C
R
O
O
F
D
R
A
IN
6
" P
V
C
R
O
O
F
D
R
A
IN
9
.2
1
'
10'
CONDUIT AND TX
SEE ELECTRICAL
PLANS FOR
DETAILS
EXISTING ELECTRIC EASEMENT
163
1
6
3
1
6
3
1
6
3
162.13
162.42
163.50
1
.0
%
0
.9
%
0
.9
%
1
.2
%
UF IFAS
LIVE OAK
PAVILLION
ENGINEER OF RECORD :
CHRISTOPHER A. GMUER
FL PE # 71599
2020-03-03
CLIE
NT
:
IF
AS
F
AC
ILIT
IE
S P
LA
NN
IN
G
& O
PE
RA
TIO
NS
DE
SIG
N :
C.M
. G
RIG
GS
, E
I
QU
ALIT
Y C
ON
TR
OL :
C.A
. G
MU
ER
, P
E
WM
D A
PP
#
TB
D
GE
ng P
RO
JE
CT
#
19-0031
PE
RM
IT
TIN
G / D
ES
IG
N R
EV
IS
IO
NS
:
2020-01-09 C
ON
CE
PT
P
LA
N T
O IF
AS
2020-02-25 IN
IT
IA
L P
ER
MIT
TIN
G
2020-02-28 R
EV
IS
ED
A
DD
A
LT
ER
NA
TE
S F
OR
B
ID
2020-03-03 100%
P
LA
NS
F
OR
B
ID
PR
IC
IN
G :
BID
DIN
G
CO
NS
TR
UC
TIO
N :
BID
DIN
G
FILE
: 19-0031-C
-200 G
RA
DE
.D
WG
| LA
ST
S
AV
ED
: 2020-03-03 12:02:29 P
M | P
LO
T S
CA
LE
: 1:1| | P
LO
TT
ED
: 2020-03-03 12:07:12 P
M | U
SE
R: cagm
uer
FL C
A # 31533
gm
uereng.com
(352) 281-4928
2603 N
W 13th S
T, B
ox 314
Gainesville, F
L 32609
C-210
PAVING,
GRADING, &
DRAINAGE
PLAN
TYPICAL DOWNSPOUT
TO ROOF DRAIN DETAIL
NOT TO SCALE
6" E
XP
OS
ED
RIS
ER
RECTANGULAR DOWNSPOUT TO
CIRCULAR PIPE ADAPTER OR
OTHER ADAPTER AS NEEDED TO
MATCH DOWNSPOUT PIPE - TYP
FLOW DIRECTION
Feet
0 20 40
Lot 1: Pavilion, Covered Walk, Sidewalk, H/C Parking (including 5’ outside the perimeter with final grading) Lot 2: Everything Else (Pavement, Pipes, etc.)
DRAWING SHEET INDEXSHEET # CIVIL PLANS SEE TOC ON C.000 Current
RevisionCurrent
Date
TITLET0.0 COVER SHEET
LIFE SAFETYLS1.0 PROPOSED - LIFE SAFETY - OVERALL
ARCHITECTURAL PLANSA1.0 PROPOSED - PLAN - OVERALLA1.2 PROPOSED - ROOF PLAN
ARCHITECTURAL EXTERIOR ELEVATIONSA2.0 PROPOSED - ELEVATIONS - EXTERIORA2.1 PROPOSED - ELEVATIONS - EXTERIOR
ARCHITECTURAL BUILDING SECTIONSA4.0 PROPOSED - SECTIONS - BUILDING
ARCHITECTUAL DETAILSA7.0 PROPOSED - DETAILS
PLUMBINGP0.1 PLUMBING LEGEND, NOTES & ABBREVIATIONSP1.1 PLUMBING FLOOR PLAN
ELECTRICALE0.1 ELECTRICAL LEGEND, CODES &
ABBREVIATIONSE1.1 ELECTRICAL FLOOR PLAN - POWERE1.2 ELECTRICAL CEILING PLAN - LIGHTINGE1.3 ELECTRICAL ROOF PLAN
STRUCTURALS1 FOUNDATION PLAN
PROJECT LOCATION
AT
FORUF PLANNING, DESIGN & CONSTRUCTION
UF/IFAS 20038 NORTH FLORIDAREC - LIVE OAK AGRICULTURE
DEMONSTRATION BUILDING
LIVE OAK, FL
PROJECT/ SITE ADDRESS
OCCUPANCY TYPE - FBC: ASSEMBLY - GROUP A-3OCCUPANCY TYPE - NFPA: ASSEMBLYNUMBER OF STORIES: 1 ABOVE GRADENUMBER OF BUILDINGS: 1AUTHORITIES HAVING JURISDICTION: UF EH&S
PROJECT NAME: UF/IFAS 20038 NORTH FLORIDA REC - LIVE OAKAGRICULTURE DEMONSTRATION BUILDING
LIVE OAK, FL
1. DRAWINGS ARE DIAGRAMATIC TO CONVEY EXISTING/NEW CONDITIONS. CONTRACTOR SHALL INSPECT AND VERIFY THE SCOPE OF WORK. ANY ADDITIONAL WORK NOT SPECIFICALLY NOTED ON THE DRAWINGS BUT YET ARE APPARENT TO FIELD INSPECTION SHALL BE CONSIDERED AS PART OF THIS CONTRACT. CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR VERIFYING ALL EXISTING CONDITIONS.2. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.3. NO INSTRUCTION, REVISIONS, ADDITIONS, DELETIONS, SPECIFICATIONS OR DETAILS OTHER THAN THE INFORMATION CONTAINED HEREIN BEFORE SHALL GOVERN THE PROJECT UNLESS THEY ARE IN WRITING AND APPROVED BY THE ARCHITECT, OWNER AND CONTRACTOR IN THE FORM OF A CHANGE ORDER.4. GC, VENDORS & SUB-CONTRACTORS SHALL REFER TO ALL DRAWINGS, PROJECT MANUAL AND PWE SHEETS (WHEN APPLICABLE) OF CONTRACT DOCUMENTS AND COMPLY WITH ALL PROVISIONS THEREIN. IF THERE IS A DESCREPANCY BETWEEN CONTRACT DOCUMENTS, EXISTING CONDITIONS AND VENDOR SUPPLIED WATER TREATMENT DOCUMENTS, GC TO VERIFY AND COORDINATE PRIOR TO INSTALLATION OF ANY SLEAVING.5. ALL MATERIALS SHALL BE INSTALLED IN ACCORDANCE W/ MANUFACTURER'S INSTRUCTIONS. IT IS GENERAL CONTRACTOR'S RESPONSIBILITY TO VERIFY AND APPROVE ALL DIMENSIONS OF EQUIPMENT AND MATERIAL WITH SUPPLIERS PRIOR TO ORDERING AND / OR INSTALLATION OF ALL PRODUCTS.6. RFI'S - SUBMIT ALL QUESTIONS ON RFI DOCUMENT PROVIDED IN BID DOCUMENTS WITH DATE OF REQUEST. ARCHITECT WILL PROVIDE RESPONSE AS QUICKLY AS PRACTICAL.7. UPON GENERAL CONTRACTOR APPROVAL, ALL SUBMITTALS ARE TO BE SENT FROM THE SUBCONTRACTOR TO THE GENERAL CONTRACTOR FOR REVIEW AND SUBMISSION TO THE ARCHITECT; THE SUBCONTRACTOR IS TO FLAG ANY SUBSTITUTIONS. THE FULL SUBMITTAL PACKAGE IS TO BE SENT ELECTRONICALLY IN PDF FORMAT ON EITHER CD, FTP WEBSITE FOR DOWNLOAD, OR DROP BOX TO THE ARCHITECT WITHIN TWO WEEKS OF AWARD. ALL SUBMITTALS ARE TO BE REVIEWED BY GC PRIOR TO SUBMISSION TO THE ARCHITECT. ALL NON-REVIEWED SUBMITTALS WILL BE REJECTED. THE ARCHITECT WILL SUBMIT TO THE PROJECT MANAGER COPIES OF ALL REJECTED SUBMITTALS AND APPROVED SUBSTITUTIONS. ALL APPROVED SUBMITTALS AND CUT-SHEETS ARE TO BE MADE AVAILABLE PERMANENTLY ON THE JOB SITE FOR FUTURE REFERENCE DURING CONSTRUCTION MEETINGS. TIMELINESS OF SUBMITTALS IS OF EXTREME IMPORTANCE DUE TO PROJECT SCHEDULE. LATE SUBMITTALS WILL BE BACKCHARGED FROM THE SCHEDULE OF VALUES.ANY REVIEWS AFTER THIRD WEEK SHALL BE BORNE BY GENERAL CONTRACTOR @ A RATE OF $200 PER SUBMITTAL.8. PROJECT MAY INCLUDE MISCELLANIOUS STANDARD DETAILS. GC IS TO REVIEW ALL TO VERIFY ALL ARE APPLICABLE. SOME DETAILS MAY BE MIRRORED FOR THIS PROJECT COORDINATE W/ FLOOR PLAN.9. SEE PROJECT MANUAL SECTION 01100 FOR ALTERNATES (WHEN APPLICABLE).10. SEE PROJECT MANUAL SECTION 01021 FOR ALLOWANCES (WHEN APPLICABLE).11. SEE LS SERIES DRAWINGS FOR CODE DATA & LIFE SAFETY INFORMATION.12. SEE SHEET A0.0.1 FOR ALL REQUIRED ADA & FIXTURE HEIGHTS.13. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND ALL SUBCONTRACTORS TO VISIT THE JOBSITE AND FAMILIARIZE THEMSELVES WITH ALL EXISTING CONDITIONS IN THE FIELD. ANY DISCREPANCIES BETWEEN EXISTING FIELD CONDITIONS AND THE CONSTRUCTION DOCUMENTS ARE TO BE BROUGHT TO ARCHITECT'S ATTENTION IMMEDIATELY PRIOR TO BIDS BEING DUE. OWNER WILL PROVIDE DIRECTION TO GENERAL CONTRACTOR FOR BIDDING PURPOSES TO ASSURE APPROPRIATE SCOPE IS INCLUDED WITHIN BID.14. CONTRACTOR IS TO COORDINATE WITH TENANTS, LANDLORDS AND/OR SURROUNDING TENANTS/LANDOWNERS WHEN PERFORMING ANY WORK. THERE SHALL NOT BE ANY DISRUPTION OF SERVICES FOR THE SURROUNDING TENANTS/LANDOWNERS DURING THE CONSTRUCTION / RELOCATION AND/OR EXPANSION AND/OR RENOVATION OF THE FACILITY.
GENERAL NOTES
MEP ENGINEERS
MITCHELL GULLEDGE ENGINEERSCRAIG GULLEDGE352-745-3991
CGULLEDGE ([email protected])
210 SW 4th AvenueGainesville, FL 32601
CONSULTANTS
PROJECT SCOPE
PROJECT INFORMATION
SITE VICINITY MAP
3D PLAN
PROPOSED
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
20 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
T0.0COVER SHEET
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
RE V
ISIO
NS
UF BLDG # 8325
DEMONSTRATION PAVILION: BASE BID: A 60’ X 75’ PRE-ENGINEERED, GALVANIZED METAL BUILDING WITH NON-TAPERED COLUMNS ON 25’ WIDE BAYS. TYPE II CONSTRUCTION, UNSPRINKLERED WITH A GROUP A-3 ASSEMBLY OCCUPANCY. THE EAVES WILL BE 12’ HIGH WITH SIDE PANELS DOWN TO 10’ ON ALL FOUR SIDES. THE GALVALUME FINISH ROOF WILL HAVE A 3:12 PITCH WITH A 2’ OVERHANG ON ALL 3 SIDES, AND A 10’ WIDE SHED ROOF ON THE NORTH SIDE. GUTTERS ON THE NORTH AND SOUTH SIDES WILL BE ROUTED TO AN UNDERGROUND DRAINAGE SYSTEM VIA DOWNSPOUTS ON ALL 8 SIDE COLUMNS. THE SLAB WILL BE 4” THICK, DESIGNED FOR PEDESTRIAN USE, WITH A SMOOTH TROWEL FINISH, AND BE SLOPED TO DRAIN. COLUMN BASES WILL BE ELEVATED RELATIVE TO THE SLAB. FOUNDATION DESIGN WILL BE BASED UPON BUILDING MANUFACTURER-PROVIDED REACTIONS.THE SIDE WALLS WILL BE R-PANELS WITH A 20-YEAR PAINTED FINISH OF OYSTER GREY WITH DARK GREEN TRIM. THE BUILDING WILL HAVE A 10’ WIDE COVERED CONCRETE WALK ON THE NORTH SIDE. THE WALK WILL CONNECT THE BUILDING TO THE PARKING.
NEW ELECTRICAL SERVICE, WITH POWER AND JUNCTION BOXES AT EACH COLUMN FOR THE ROLL-DOWN CURTAINS, POWER FOR THE CEILING FAN AND LIGHTING.
COVERED WALKWAY: PRE-ENGINEERED ALUMINUM CANOPY WITH LIGHTING OVER THE CONCRETE WALK CONNECTING THE MAIN ASSEMBLY BUILDING WITH THE PAVILION.
RELATED WORK: PLUMBING AND ELECTRICAL FOR AN ACCESSIBLE, HI-LOW WATER FOUNTAIN ON THE WEST EXTERIOR FACE OF THE MAIN ASSEMBLY BUILDING.SITE WORK FOR ACCESSIBLE ROUTE TO ADJACENT RESTROOMS AND TO PARKING, PAVING AND DRAINAGE
ALTERNATES:#1: IN LIEU OF STANDARD METAL BUILDING COLUMNS, PROVIDE RECTANGULAR OR SQUARE COLUMNS ALONG THE NORTH SIDE OF THE COVERED WALK.#2: IN LIEU OF BARE GALVANIZED COLUMNS, WRAP THE BUILDING COLUMNS WITH FRAME AND STONE VENEER.#3: IN LIEU OF OPEN BAYS, PROVIDE ROLL-DOWN, CLEAR WEATHER CURTAINS EQUIVALENT TO FENETEX
PLUMBING FIXTUERS:ACCESSIBLE RESTROOM FIXTURES ARE ON SITE IN THE ADJACENT BUILDINGS 8239 & 8312. DURING DEMONSTRATION EVENTS, THEOCCUPANTS OF THESE BUILFING WILL BE AT THE DEMOSTRATION BUILDING.ADDITIONAL ACCESSIBLE RESTROOMS WILL BE BROUGHT ON SITE FOR THE LARGER EVENTS THAT MAY OCCUR.
OCCUPANT LOAD: 292
STRUCTURAL ENGINEER
WAYLAND STRUCTURAL ENGINEER (WSE)GREG WAYLAND352-331-0727
2801 SW 81ST STREETGAINESVILLE, FL 32608
CIVIL ENGINEER
GMUER ENGINERRING(352)-281-4928
GMUERENG.COM
643
A
1
B
C
6"
6"
1'-2"
74'-0" 59'-0
"
F.E.C.
F.E.C.
OPEN YARD
OPEN YARD
OPEN YARD
OPEN YARD
NOTE: ALL FOUR SIDES ARE OPEN
DASHED LINE INDICATES PROPOSED WEATHEWR CURTAINS ALONG PERIMETER
EXIT EXITOPEN COVERED WALKWAY
EXISTING MAIN ASSEMBLY BL
NO WEATHER CURTAINS ARE PROPOSED @ EXITS
E
D
PANEL FEC
LIFE SAFETY SYMBOL LEGEND
EMERGENCY LIGHT FIXTURES ON LIFE SAFETY PANEL
CEILING MOUNTED EXIT LIGHT FIXTURE
CEILING MOUNTED EXIT LIGHT FIXTURE w/ EMERGENCY BATTERY INVERTER
FIRE EXTINGUISHER FEC
(LS1.00)
LIGHTING
GENERAL NOTES - LIFE SAFETY - OVERALLEgress from building will be possible from all sides when the weather curtains are not lowered.The two Exits shown on the north side will remain open for accessible egress at all times.See Electrical for emergency and exit lightingUse of building will include demonstrations of agricultural equipment and techniques, with exhibition booths similar to those in trade fairs. Table and chair arrangements may also be used.
TRUE
OCCUPANT LOAD BREAKDOWNA - ASSEMBLY = (1 PERSON / 15 SF)
B - BUSINESS = (1 PERSON / 100 SF)
S - ACC/SUPPLY = 0 (1 PERSON / 300 SF)
TOTAL OCCUPANCY LOAD = 292
0
292
FIRE ALARM, EXTINGUISHERS, EXITS1. FOR EXIT SIGNS AND EMERGENCY LIGHTS, SEE ELECTRICAL PLAN
INTERIOR WALLS = 0
EXTERIOR WALLS = 0
INTERIOR ROOMS = 0
EXTERIOR ROOMS = 0
BELOW ROOF ROOMS = 0
GFA (NFPA) =
AREA LEASABLE (BOMA) =
AREA BUILDING (IBC)= 4,366
TOTAL AREA BREAKDOWN
LONGEST PATH TO EXIT:LONGEST RUN = 69 FEETT1017.2: EXIT ACCESS TRAVEL DISTANCE - 200' W/O SPRINKLER SYSTEM (MOST RESTRICTIVE).
SCALE: 1/8" = 1'-0"LS1.0
PROPOSED - LIFESAFETY - OVERALL1
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
16 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
LS1.0PROPOSED - LIFE
SAFETY -OVERALL
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
RE V
ISIO
NS
* ALL SYMBOLS SHOWN MAY NOT BE ON PLAN
643
A
1
B
C
A2.0
2
A2.0 1
A2.11
A2.1
2
26'-0" 25'-0" 26'-0"
61'-4
"
20'-8
"20
'-0"
20'-8
"
77'-0"
10'-8
"
EXISTING MEETING FACILITY
PROPOSED WATER BOTTLE FILLER
0'-0" @ EACH COLUMN-0'-4"
0'-0" @ CENTER OF SLAB
SLO
PE 1:
90SL
OPE
1:90
2A7.0
_______
1A4.0
_______
2A4.0
_______
10'-0" 20'-0"
8'-0
"
EXISTING PARKING PEDESTRIAN ACCESS TO RESTROOMS AND DRIVEWAY TO BE RECONFIGURED. SEE CIVIL DRAWINGS FOR CLARIFICATION
8'-0" 8'-0"
NO TRACK ON INSIDE FACE OF THESE TWO COLUMNS
NO TRACK ON INSIDE FACE OF THESE TWO COLUMNS
ALTERNATE: PROVIDE 4 RECTANGULAR OR SQUARE COLUMNS ALONG THE NORTH SIDE OF THE WALKWAY
8'X44' LONG ALUMINUM WALKWAY COVER
LOCATE THE ALUMINUM WALKWAY COVER SO THE THE CANOPY PROJECTS BELOW THE OVERHANGS OF BOTH BUILDINGS
PROPOSED ELECTRICAL - SEE CIVIL AND ELECTRIC SHEETS
PROPOSED DEMONSTRATION PAVILION
PROPOSED COVERED WALKWAY
PORTAL FRAME WRAP IN METAL STUD, SHEATHING, S.A.F.F & STONE TO MATCH OTHER COLUMNS BOTTOM OF BEAM @ 10'-6"
PORTAL FRAME WRAP IN METAL STUD, SHEATHING, S.A.F.F & STONE TO MATCH OTHER COLUMNS BOTTOM OF BEAM @ 10'-6"
PROVIDE DOWNSPOUTS @ EACH COLUMN
PROVIDE DOWNSPOUTS @ EACH COLUMN
PROVIDE DOWNSPOUTS @ EACH COLUMN
PROVIDE DOWNSPOUTS @ EACH COLUMN
61'-4
"
25'-0" 25'-0" 25'-0"
E
8"
D
SLOPE 1:90 SLOPE 1:90
1: 48
MAX
1: 48
MAX
163.17'
EDGES,
163-50'
TOP/SLAB
PLUMBING FIXTURE CALCULATIONBuilding 8312 contains 1,382 sf of office space (Group B) and 1,560 s.f of Storage (Group S-2)Occupant Load: 1,382/100 = 14 persons + 1,560/300 = 6. 20 OCCUPANTS TOTAL
FIXTURE: WC LAV DRINKING FOUNTAIN SERVICE SINK
REQUIRED: 1 1 1 1 (REQUIRED FOR STORAGE USE)PROVIDED: 5 3 0 0 (SHOWER PROVIDED)
Building 8329 has an area and occupant load as noted below
The Proposed Building as an enclosed Assembly area of 4,366 s.f. OCCUPANT LOAD: 4,366/15 = 291 PERSONS; 291/2 = 146 MALE & 146 FEMALE MALE FEMALE FIXTURE: WC LAV WC LAV DRINKING FOUNTAIN SERVICE SINKREQUIRED: 2 1 3 1 1 1
PROVIDED: SEE FIXTURE COUNT FOR BUILDINGS 8312 & 8329
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.
352.
377.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
10 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
A1.0PROPOSED - PLAN
- OVERALL
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
SCALE: 3/32" = 1'-0"A1.0
PROPOSED - PLAN - OVERALL1
REV
ISIO
NS
TRUE
ELEC. PNL.
643
A
1
B
C
A2.0
2
A2.0 1
A2.11
A2.1
2
1A4.0
_______
2A4.0
_______
2A7.0
_______
80'-4"
3" /
1'-0"
3" /
1'-0"
3" /
1'-0"
8'X44' CANOPY ROOF
PROVIDE DOWNSPOUTS @ EACH COLUMN
PROVIDE DOWNSPOUTS @ EACH COLUMN
3A7.0
_______
E
D
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
11 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
A1.2PROPOSED - ROOF
PLAN
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
SCALE: 1/8" = 1'-0"A1.2
PROPOSED - PLAN - ROOF1
WALKWAY ROOF
DEMONSTRATION PAVILION ROOF
CONTINUOUS RIDGE VENT
RE V
ISIO
NS
TRUE
FIRST FLOOR0"
A B C
3" / 1'-0"3" / 1'-0"
10'-8"
3" / 1'-0"
AWNING8'-0"
8'-8"10'-0"
ALUMINUM WALKWAY CANOPY
EAVE HT.12'-6"
10'-4 1/2"
PROVIDE GUTTER
ED
FIRST FLOOR0"
6431 2A4.0
_______2A4.1
_______
AWNING8'-0"
3" /
1'-0"
3" /
1'-0"
2A7.0
_______
GALVANIZED STEEL COLUMN WALKWAY COLUMNS IN FORGROUND
STONE WRAPPED METAL BUILDING COLUMNS IN BACKGROUND
ALUMINUM CANOPY
EAVE HT.12'-6"
3A7.0
_______
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
12 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
A2.0PROPOSED -
ELEVATIONS -EXTERIOR
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
SCALE: 1/4" = 1'-0"A2.0
ELEVATION #11
SCALE: 1/4" = 1'-0"A2.0
ELEVATION #22
WALKWAY ROOF
CANOPY STRUCTURE TO MAIN BUILDING
RE V
ISIO
NS
FIRST FLOOR0"
Level 10"
ABC1
A4.0_______
AWNING8'-0"
3" / 1'-0"
3" / 1'-0"
3" / 1'-0"
10'-0"
EAVE HT.12'-6"10'-4 1/2"
8'-8"
PROVIDE GUTTER & DOWNSPOUTS
E D
ADJACENT BUILDING ON EAST SIDE
FIRST FLOOR0"
Level 10"
6 4 3 12A4.0
_______ 2A4.1
_______
3" /
1'-0"
3" /
1'-0"
2A7.0
_______
DOWNSPOUTS TO TIE TO U/G STORM WATER SYSTEM - SEE CIVIL
12'-0"
10'-0"
12'-6" EAVE HT.12'-6"
3A7.0
_______
ADJACENTBUILDING ON NORTH SIDE
F.E.C.F.E.C.3'-8"
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
14 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
A2.1PROPOSED -
ELEVATIONS -EXTERIOR
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
SCALE: 1/4" = 1'-0"A2.1
ELEVATION #31
SCALE: 1/4" = 1'-0"A2.1
ELEVATION #42
REV
ISIO
NS
GENERAL NOTES - SECTIONS - BUILDING
FIRST FLOOR0"
B.O. SIDE WALLS10'-0"
EAVE HT13'-0"
6431
3" /
1'-0"
EAVE HT.12'-6"
PROVIDE POWER TO JUNCTION BOX FOR FAN
FAN - NOT IN CONTRACT
3'-8"F.E.C.F.E.C.
FIRST FLOOR0"
B.O. SIDE WALLS10'-0"
EAVE HT13'-0"
A B C
3" / 1'-0"
3" / 1'-0"
3" / 1'-0"
GALVALUME ROOF
GUTTER & DOWNSPOUT
PAINTED SIDE WALL
ALT. #2: STONE VENEER ON FRAMING OVER METAL BUILDING COLUMNS, TYP.
TRACK FOR FUTURE WEATHER CURTAINS
CEILING FAN - BY OWNER - SEE MECHANICAL ALT #1: RECTANGULAR OR SQUARE TUBE STEEL COLUMNS. HOT DIPPED GALVANIZED
12'-6" EAVE HT.12'-6"
ED
DOWNSPOUTSEE CIVIL
DOWNSPOUTSEE CIVIL
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
15 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
A4.0PROPOSED -SECTIONS -BUILDING
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
SCALE: 1/4" = 1'-0"A4.0
SECTION #11
SCALE: 1/4" = 1'-0"A4.0
SECTION #22
REV
ISIO
NS
Z-FLASHING
EXTEND METAL SIDING 9" MIN. BELOW Z-GIRT TO CONCEAL HOUSING
8" Z GIRT
P.T. BLOCKING AS REQ'D
SCREEN MOTOR HOUSING (ALT. #3)
J
JUNCTION BOX FOR SCREEN MOTOR
10'-0"
BOTTOM OF METAL
9"
10'-0"
TOP OF STONE
SEAL ALL VOIDS BETWEEN COLUMNS & TOP OF FRAMING
GALVANIZED METAL CAP FLASHING
ALT. #2 STONE VENEER ON WEATHER BARRIER ON EXTERIOR GRADE SHEATHING ON GALV. METAL STUDS
10'-9"
ALIGN W/ BLDG FRAMING
±8"
DOUBLE 4" METAL STUD
ALT. #2 STONE VENEER ON WEATHER BARRIER ON EXTERIOR GRADE SHEATHING ALL 4 SIDES
4" METAL STUDS
EXTERIOR GRADE SHEATHING
FOOTING - SEE STRUCTURAL
SLOPE TO DRAIN
BOTTOM SECTION1/2
" TOP OF FOUNDATION
COLUMN BEARING
BACKER ROD & SEALANT
CONT. FLEXIBLE FLASHING OVER3-1/2" CONT. METAL FLASHING W/ HEMMED EDGE
CONCRETE PEDISTAL @ EACH COLUMN SIZE OF PEDISTAL W/ COLUMN SIZES & FRAMING
CONTINUOUS SEALANT
-0'-4"
RECEPTACLE - GFCI. SEE ELECT.
4" METAL STUDS 3 SIDES
WRAP BLDG COLUMN & FRAMING ALL 4 SIDES W/ STONE ON EXTERIOR GRADE SHEATHING ON METAL STUDS
PLAN
TRACK FOR SCREEN CURTAIN (ALT. #3)
12 GA, 6"X2.5" GALVANIZED STEEL CHANNEL
BACKER ROD & SEALANT BOTH SIDES
BACKER ROD & SEALANT BOTH SIDES
BLOCKING AS REQ'D FOR MOUNTING TRACK
12 GA, 6"X2.5" GALVANIZED STEEL CHANNEL
ADIROLFF O
E T AT S
R EG I S T ERED
ARCH
ITECT
AR
0014
129J .
NAELcM
DRA W HO
R
CHECKED BY:DRAWN BY:DATE:
SHEET
P.35
2.37
8.44
00F.3
52.3
77.5
378
1628
NW
6TH
STR
EET
GAIN
ESVI
LLE
FL 3
2609
ARCH
ITEC
TS &
PLA
NNER
SFL
CER
TIFI
CATE
SVM
SKIN
NER
VIG
NOL
A M
cLEA
N, I
NC.
FOR
ALL
REPO
RTS,
PLA
NS, S
PECI
FICA
TION
S, C
OMPU
TER
FILE
S, F
IELD
DAT
A, N
OTES
& O
THER
DOC
UMEN
TS &
INST
RUM
ENTS
PRE
PARE
D BY
THE
DES
IGN
PROF
ESSI
ONAL
AS
INST
RUM
ENTS
OF
SERV
ICE
SHAL
L RE
MAI
N TH
E PR
OPER
TY O
F TH
E DE
SIGN
PRO
FESS
IONA
L. T
HE D
ESIG
N PR
OFES
SION
AL S
HALL
RET
AIN
ALL
COM
MON
LAW
, STA
TUTO
RY &
OTH
ER R
ESER
VED
RIGH
TS, I
NCLU
DING
THE
COP
YRIG
HT T
HERE
TO. U
SE O
F TH
ESE
DOCU
MEN
TS F
OR A
NY P
URPO
SE O
RPR
OJEC
T OT
HER
THAN
THE
PRO
JECT
WHI
CH IS
SUB
JECT
OF
THE
AGRE
EMEN
T IS
UNL
AWFU
L.
AA34
78PR
OJEC
T Ho
war
d M
cLea
n Jr
AR
0014
129
HJM
3/11
/20
20 2
:39:
15 P
MB
IM 3
60:/
/014
60-3
0 -
IFA
S PA
VIL
ION
LIV
E O
AK
/014
60-1
4 U
F-IF
AS
REN
DER
ING
PA
VIL
LIO
N (1
0_1
0_2
019
)NEW
EST
.rvt
03/12/2020
A7.0PROPOSED -
DETAILS
UF/I
FAS
2003
8 N
ORTH
FLO
RIDA
REC
-LIV
E OA
K AG
RICU
LTUR
EDE
MON
STRA
TION
BUI
LDIN
G
UF
PLA
NN
ING
, DES
IGN
&C
ON
ST
RU
CT
ION LIVE
OK,
FL
3206
0
DESI
GN P
HA
SE:
PERM
IT D
OCU
MEN
TS
JER
1460-30
RE V
ISIO
NS
SCALE: 3" = 1'-0"A7.0
SECTION @ TOP OF COLUMNS1
SCALE: 3" = 1'-0"A7.0
PROPOSED - COLUMN SECTION BOTTOM SECTION2
SCALE: 3" = 1'-0"A7.0
PROPOSED - COLUMN SECTION PLAN3
Mitchell Gulledge Engineering, Inc.
210 SW 4th Avenue
Gainesville, FL 32601
352.745.3991
www.mitchellgulledge.com
Andrew Mitchell, PE, CxA, LEED AP BD+C
Craig Gulledge, PE, CxA, LEED AP BD+C
March 24, 2020
Howard McLean Skinner Vignola McLean, Inc. 1628 NW 6th Street Gainesville, FL 32609
Re: Addendum IFAS Live Oak Pavilion MG Project Number: 19096
Dear Howard:
Please issue the following as an addendum.
1. SPECIFICATIONS:a. Section 00 00 00 TABLE OF CONTENTS: Replace section in its entirety with the attached section
indicating deleted section 26 41 00.b. Delete Section 26 41 00 LIGHTNING PROTECTION in its entirety.
2. DRAWINGS:a. Sheet E0.1 – ELECTRICAL LEGEND, CODES, & ABBREVIATIONS: Replace sheet in its entirety with
the attached 24”x36” sheet dated March 24, 2020.b. Sheet E1.2 – ELECTRICAL CEILING PLAN – LIGHTING: Replace sheet in its entirety with the
attached 24”x36” sheet dated March 24, 2020.c. Delete Sheet E1.3 – ELECTRICAL ROOF PLAN in its entirety.
Sincerely,
Craig Gulledge, PE, CxA, LEED AP BD+C Principal
Attachments
Mitchell Gulledge Engineering, Inc. MG Project Number: 19096 00 00 00 TABLE OF CONTENTS
Page 1 of 2 100% Construction Documents
TABLE OF CONTENTS
22 00 00 PLUMBING GENERAL 22 05 01 PLUMBING CODES AND STANDARDS 22 05 02 PLUMBING RELATED WORK 22 05 23 PLUMBING VALVES 22 10 00 PIPES AND FITTINGS 22 11 13 POTABLE WATER SYSTEM 22 13 16 SOIL WASTE AND VENT SYSTEM 22 24 00 TESTING, CLEANING, AND STERILIZATION OF PIPING SYSTEMS 26 00 00 ELECTRICAL GENERAL 26 05 01 ELECTRICAL CODES AND STANDARDS 26 05 02 ELECTRICAL RELATED WORK 26 05 26 GROUNDING AND BONDING 26 05 31 WIRES AND CABLES 26 05 33 RACEWAYS 26 05 34 BOXES AND FITTINGS 26 05 53 ELECTRICAL IDENTIFICATION 26 05 90 ELECTRICAL EXCAVATION AND BACKFILL 26 24 20 PANELBOARDS 26 27 26 GENERAL WIRING DEVICES 26 28 16 HEAVY DUTY SAFETY SWITCHES 26 41 00 LIGHTNING PROTECTION
26 56 00 EXTERIOR LIGHTING
Mitchell Gulledge Engineering, Inc. MG Project Number: 19096 00 00 00 TABLE OF CONTENTS
Page 2 of 2 100% Construction Documents
THIS PAGE LEFT INTENTIONALLY BLANK
NEC ELECTRICAL LOAD CALCULATION: PANEL 2PA (240Y/120V 1Ø 3W)
LOAD DESCRIPTION PER UNIT LOAD UNITSCONNECTED
LOADSADJUSTMENT
FACTORNEC 220 CALC
LOADNOTES
HIGH VOLUME LOW VELOCITY FANS 7200.0 VA ea 1 7.2 kVA 1.25 9.0 kVA
LIGHTING 73 VA ea 16 1.168 kVA 1.25 1.46 kVA
LIGHTING 29 VA ea 4 0.116 kVA 1.25 0.145 kVA
LIGHTING 41 VA ea 2 0.082 kVA 1.25 0.103 kVA
EWC 600 VA ea 1 0.6 kVA 1.00 0.6 kVA
RECEPTACLES 180 VA ea 12 2.16 kVA 1.00 2.16 kVA
TOTALS (kVA) 11.326 kVA 13.468 kVA
TOTALS (A) 47.19 A 56.11 A
TELECOMMUNICATIONS:
ROUGH-IN-ONLY TO. 18" AFF UNO. PROVIDE 1"C TO ABOVE ACCESSIBLE CEILING.
ABBREVIATIONS AC ABOVE COUNTERACS (ELECTRONIC) ACCESS CONTROL SYSTEMAWG AMERICAN WIRE GAUGEBOD BASIS OF DESIGNC CONDUITCAM CAMERACB CIRCUIT BREAKERCFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFOI CONTRACTOR FURNISHED, OWNER INSTALLEDCKT CIRCUITCMS COMBINATION MOTOR STARTERCO CARBON MONOXIDEDIV DIVISIONECB ENCLOSED CIRCUIT BREAKEREOR ENGINEER OF RECORDEWC ELECTRIC WATER COOLEREX EXISTING TO REMAINFSS FUSED SAFETY SWITCHG GROUND, GROUND FAULT CIRCUIT INTERRUPTERGCB GFCI CIRCUIT BREAKERLTG LIGHTINGLTS LIGHTSMCC MOTOR CONTROL CENTERNAC NOTIFICATION APPLIANCE CIRCUITOFCI OWNER FURNISHED, CONTRACTOR INSTALLEDOFOI OWNER FURNISHED, OWNER INSTALLEDPBD PANELBOARDPQM POWER QUALITY METERSPD SURGE PROTECTION DEVICESLC SIGNALING LINE CIRCUITSS SAFETY SWITCHSWBD SWITCHBOARDTBD TO BE DETERMINEDTCR TELECOMMUNICATIONS ROOMTO TELECOMMUNICATIONS OUTLETTYP TYPICALUF UNIVERSITY OF FLORIDAUFL UNIVERSITY OF FLORIDAUNO UNLESS NOTED OTHERWISEVFD VARIABLE FREQUENCY DRIVEWAO WORK AREA OUTLETWAP WIRELESS ACCESS POINTWP WEATHER PROOF / WEATHER RESISTANTWR WEATHER PROOF / WEATHER RESISTANTWRT WITH RESPECT TO
TELECOMMUNICATIONS SUBSCRIPTS:
CAM CAMERA TO.WAP WIRELESS ACCESS POINT TO.AC ABOVE COUNTER
POWER EQUIPMENT AND CONNECTIONS:
A-1
2P1A
GENERAL SUBSCRIPTS (APPLY TO ALL CATEGORIES):
FED FROM GFCI TYPE CIRCUIT BREAKER.GCB
INDICATES HEIGHT OF FIXTURE, RECEPTACLE, BOX, CABINET, ETC. HEIGHT IS TO CENTERLINE UNLESS OTHERWISE INDICATED.
72"
EXISTING TO REMAINEX
WEATHERPROOF INSTALLATION, WITH APPROPRIATELY LISTED OR INDICATED PRODUCTS.WP
ELECTRICAL EQUIPMENT TAG.
ELECTRICAL HOME RUN TO PANELBOARD. UNDERLINED LABEL INDICATES PANELBOARD NAME AND CIRCUIT NUMBER. UNLESS INDICATED OTHERWISE, DEFAULT WIRING IS #12 & #12G. PROVIDE CONDUCTORS AS NEEDED FOR INDICATED SWITCHED LEGS, ZONES, ETC. SEE ELECTRICAL EQUIPMENT SCHEDULE FOR SPECIFIC CIRCUIT SIZING.
CODES AND STANDARDS ALL PROJECT WORK SHALL BE GOVERNED BY AND ADHERE TO THE FOLLOWING CODES AND STANDARDS.
1. FLORIDA BUILDING CODE - SIXTH EDITION (2017)2. FLORIDA BUILDING CODE - SIXTH EDITION (2017) - ENERGY CONSERVATION3. FLORIDA FIRE PREVENTION CODE - SIXTH EDITION (2017)
A. FIRE CODE (NFPA 1 - 2015 FLORIDA EDITION)B. LIFE SAFETY CODE (NFPA 101 - 2015 FLORIDA EDITION)
4. NATIONAL ELECTRIC CODE (2014 NFPA 70).5. UNDERWRITERS' LABORATORIES (UL)6. AMERICAN NATIONAL STANDARDS INSTITUTION (ANSI)7. AMERICAN SOCIETY OF TESTING MATERIALS (ASTM)8. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)9. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)10. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)11. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA)12. AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS (ASHRAE)13. SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)14. ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)15. TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)16. ELECTRONICS INDUSTRY ALLIANCE (EIA)
SAFETY SWITCH. MOUNT AS INDICATED. 60" TO TOP UNO.
FUSED SAFETY SWITCH. MOUNT AS INDICATED. 60" TO TOP UNO.
PANELBOARD.
RECEPTACLE:
DUPLEX RECEPTACLE. 18" AFF UNO.
ABOVE COUNTER DUPLEX RECEPTACLE. 46" AFF UNO. COORDINATE WITH COUNTER, BACKSPLASH, ETC.
DUPLEX RECEPTACLE FACE DOWN IN CEILING.
RECEPTACLE SUBSCRIPTS:
LIGHTING CONTROLS:
LIGHTING CONTROLS SUBSCRIPTS:
2 2-POLE TOGGLE SWITCH.3 3-WAY TOGGLE SWITCH.4 4-WAY TOGGLE SWITCH.a,b LOWERCASE LETTERS INDICATE SWITCHING/DIMMING ZONES.
TOGGLE SWITCH. 46" AFF UNO.
SPECIAL PURPOSE RECEPTACLE. 18" AFF UNO. COORDINATE WITH EQUIPMENT.
PC
LC
TC
120/277V 20A PHOTOCELL. BOD: INTERMATIC EK4236S.
120/277V LIGHTING CONTACTOR. BOD: ENCLOSED SQUARE D CLASS 8903 WITH HOA SWITCH.
120/277V ASTRONOMICAL TIME CLOCK. BOD: INTERMATIC ET1125CR.
LIGHT FIXTURES SUBSCRIPTS:
a,b LOWERCASE LETTERS INDICATE SWITCHING/DIMMING ZONES.24/7 LIGHT NOT SWITCHED BY OCCUPANCY SENSORS OR SWITCHES.EM PARTIAL SHADING OR 'EM' SUBSCRIPT INDICATES EMERGENCY FIXTURE. SEE LIGHT FIXTURE SCHEDULE.
LIGHT FIXTURES:
LIGHT FIXTURES SHALL BE AS INDICATED IN LIGHT FIXTURE SCHEDULE. SEE LIGHT FIXTURE SCHEDULE.
E ELECTRICAL CONNECTION TO EQUIPMENT. SEE ELECTRICAL EQUIPMENT SCHEDULE.
J JUNCTION BOX.
111AH
ANNOTATIONS:
ELECTRICAL SHEET NOTE.
MECHANICAL EQUIPMENT TAG.
1
DEMOLITION SHEET NOTE.1
LEGEND
G GFCI-TYPE RECEPTACLE.GCB GFCI-TYPE POWER FROM BRANCH CIRCUIT BREAKER.EWC NON-GFCI RECEPTACLE ON GFCI CIRCUIT BREAKER. COORDINATE HEIGHT WITH EQUIPMENT.WP WEATHER RESISTANT WIRING DEVICE. WP RECEPTACLES SHALL BE GFCI TYPE WITH IN-USE COVERS.6-30R NEMA RECEPTACLE TYPE.
CEILING MOUNT TO ROUGH-IN.
GENERAL DEMOLITION NOTES 1. ALL CIRCUITS AND SYSTEMS OUTSIDE OF THE PROJECT AREA ARE TO REMAIN IN SERVICE AT ALL
TIMES THROUGHOUT THE WORK. COORDINATE ANY NECESSARY OUTAGES WITH OWNER PRIOR TO PROCEEDING.
2. DEMOLISH ALL FIXTURES AND CIRCUITS AS INDICATED. DEMOLISH ALL ASSOCIATED WIRES, RACEWAY, AND BOXES. MAINTAIN FUNCTIONALITY OF ALL REMAINING FIXTURES AND EQUIPMENT.
3. DEMOLISH ANY SYSTEMS AND APPURTENANCES DISCOVERED WITHIN WALLS BEING DEMOLISHED. WHERE THESE SYSTEMS SERVE AREAS OUTSIDE OF THE PROJECT AREA, COORDINATE WITH OWNER, ARCHITECT, AND ENGINEER TO MAINTAIN EXISTING FUNCTIONALITY IN A WAY COMPATIBLE WITH THIS PROJECT.
1
AHU-OAPANEL P1
EXAMPLE PANELBOARD/SWITCHBOARD LABEL EXAMPLE MECHANICAL EQUIPMENT DISCONNECT LABEL
PROVIDE ENGRAVED PLASTIC TAG WITH 1/4" HIGH LETTERS.NORMAL POWER: BLACK LETTERS ON WHITE BACKGROUND.STANDBY POWER: WHITE LETTERS ON RED BACKGROUND.
DIMENSIONS SHOWN ARE MINIMUM.
208Y/120VFROM XFMR TPA
FROM MDP1"
3"
1"
3"
4L-1
2P 12
LABEL WIRING DEVICE CIRCUITS WITH PERMANENT MARKER. LETTERING SHALL
BE LEGIBLE 1/4" PRINT. LOCATE LABEL WHERE NOT VISIBLE AFTER
INSTALLATION OF COVER PLATE.
SWITCH WITHCOVERPLATE REMOVED
RECEPTACLE WITHCOVERPLATE REMOVED
CONVERT TO FMC FOR FINAL 48" TO 72". LFMC WHERE WET, DAMP, OR OTHERWISE
AT RISK. SEE SPECIFICATION.
BENDS, ELBOWS, PULLBOXES, ETC AS REQUIRED
INTERIOR ABOVE 72" AFF: EMTINTERIOR BELOW 72" AFF: RGSEXTERIOR: RGS
MOTORIZEDEQUIPMENT
SAFETY SWITCH BY DIV 26
NOTE: ROUTE EXTERIOR CONNECTIONS TO EQUIPMENT BELOW GRADE IF SAFETY SWITCH IS MORE THAN 12" FROM EQUIPMENT. MAKE WET AND DAMP LOCATION CONNECTIONS TO BOTTOM OF ENCLOSURES WHEREVER POSSIBLE.
OVERRIDE CAPABILITY MAY BE INTEGRAL TO TC.
L
N
H
O
A
TC PC
LOAD
NEU
GND
2PA
PROVIDE #4/0 CU TO ALL METALLIC WATER PIPES, CONCRETE ENCASED ELECTRODE, LIGHTNING PROTECTION, AND BUILDING STRUCTURE. PROVIDE #4/0 CU TO TWO 20' CU GROUND RODS. ARRANGE GROUND RODS WITH 10' SIDES. SEE GROUND FLOOR PLAN.
PROVIDE NEW METER SOCKET PER UTILITY STANDARDS FOR SELF
CONTAINED CL200 METER.
NEW UTILITY COMPANY PAD-MOUNT TRANSFORMER. COORDINATE
CONNECTIONS WITH UTILITY. FAULT CALCULATIONS ARE BASED ON 167kVA
TRANSFORMER WITH 4%IZ. PROVIDE PAD PER UTILITY REQUIREMENTS.
100/2
REMOVE EXISTING POLE AND POLE MOUNT
TRANSFORMER .
NEW UNDERGROUND ELECTRIC. COORDINATE WITH UTILITY
SCA: 8.09kAIC
FLOOR
EWC
INSTALL NON-GFCI RECEPTACLE CONCEALED BEHIND WATER COOLER ACCESS PANEL. COORDINATE WITH WATER COOLER TEMPLATE. EWC RECEPTACLE SHALL BE ON GFCI CIRCUIT BREAKER. WR WHERE IN EXTERIOR LOCATION.
NEU
GND
NEU
GND
SINGLE LINE DIAGRAM LEGEND
PANELBOARD
CIRCUIT BREAKER
TRANSFORMER
METER
LINETYPE LEGENDDEMOLISH
EXISTING TO REMAIN
NEW WORK
CHECKED BY:DRAWN BY:DATE:
SHEET
P.3
52
.378
.44
00
F.3
52
.377
.53
7816
28
NW
6T
H S
TR
EE
TG
AIN
ES
VIL
LE F
L 3
26
09
AR
CH
ITE
CT
S &
PL
AN
NE
RS
FL C
ER
TIF
ICA
TE
SVM
SK
INN
ER
VIG
NO
LA
Mc
LE
AN
, IN
C.
FOR
AL
L R
EP
OR
TS
, PL
AN
S, S
PE
CIF
ICA
TIO
NS
, CO
MP
UT
ER
FIL
ES
, FIE
LD
DA
TA
, NO
TE
S &
OT
HE
R D
OC
UM
EN
TS
& I
NS
TR
UM
EN
TS
PR
EP
AR
ED
BY
TH
E D
ES
IGN
PR
OF
ES
SIO
NA
L A
S I
NS
TR
UM
EN
TS
OF
SE
RV
ICE
SH
AL
L R
EM
AIN
TH
E P
RO
PE
RT
Y O
F T
HE
DE
SIG
N P
RO
FE
SS
ION
AL
. TH
E D
ES
IGN
PR
OF
ES
SIO
NA
L S
HA
LL
RE
TA
IN A
LL
CO
MM
ON
LA
W, S
TA
TU
TO
RY
& O
TH
ER
RE
SE
RV
ED
RIG
HT
S, I
NC
LU
DIN
G T
HE
CO
PY
RIG
HT
TH
ER
ET
O. U
SE
OF
TH
ES
E D
OC
UM
EN
TS
FO
R A
NY
PU
RP
OS
E O
RP
RO
JE
CT
OT
HE
R T
HA
N T
HE
PR
OJ
EC
T W
HIC
H I
S S
UB
JE
CT
OF
TH
E A
GR
EE
ME
NT
IS
UN
LA
WF
UL
.
AA
34
78
PR
OJE
CT
LO
CA
TIO
N:
Mitchell Gulledge Engineering, Inc.
210 SW 4th Avenue
Gainesville, FL 32601FL License EB-31501 p.352.745.3991
www.mitchellgulledge.com MG#19096
3/
24
/2
02
0 1
0:3
6:4
9 A
MB
IM 3
60
://0
14
60
-30
- I
FA
S P
AV
ILIO
N L
IVE
OA
K/M
G19
09
6_I
FA
S L
ive
Oa
k P
av
ilio
n_2
02
0.r
vt
03/02/2020
E0.1ELECTRICAL
LEGEND, CODES, &ABBREVIATIONS
UF
/IF
AS
20
03
8 N
OR
TH
FL
OR
IDA
RE
C -
LIV
E O
AK
AG
RIC
UL
TU
RE
DE
MO
NS
TR
AT
ION
BU
ILD
ING
UF
PL
AN
NIN
G, D
ES
IGN
&C
ON
ST
RU
CT
ION LIV
E O
K, F
L 3
20
60
DE
SIG
N P
HA
SE
: 10
0%
CD
S
BNF
1460-30
APM
And
rew
P. M
cCad
din
PE
-83
318
NOT TO SCALE2
ELECTRICAL EQUIPMENT LABELING DETAILNOT TO SCALE
1ELECTRICAL WIRING DEVICE LABEL DETAIL
NOT TO SCALE4
MOTORIZED EQUIPMENT CONNECTION DETAIL
NOT TO SCALE5
SINGLE-CIRCUIT EXTERIOR LIGHTING CONTROL DIAGRAM
NOT TO SCALE6
ELECTRICAL SINGLE LINE DIAGRAM
NOT TO SCALE3
EWC RECEPTACLE DETAIL
RE
VIS
ION
S
1A
DD
10
3/2
4/2
020
PC
TC
WP
,f,3
WP,f,3
WP
,a,3
643
A
1
B
C
E
D
4VPL 4VPL
4VPL
4VPL
4VPL4VPL4VPL
4VPL
a,EM
a
a,EM b d,EM
a b,EM c
d,EM
c d
2
E1.2
FLD
FLD
FLD
FLD
e
e
e
e
BOL BOL
2PA-14
f f
4VPL
b
4VPL
d
4VPL
c
4VPL
b
4VPL
c
4VPL
4VPL
4VPL
PROVIDE 4"x4"x72" PRESSURE TREATED WOOD POST BURIED 24" FOR SWITCH MOUNTING.
SHEET NOTES PROVDE WEATHERPROOF SWITCHES FOR ZONES a-e.1
1
XEBXEB
A B C
MOUNT TO PURLINS - TYPICAL.
4VPL
4VPL
4VPL
4VPL
CHECKED BY:DRAWN BY:DATE:
SHEET
P.3
52
.378
.44
00
F.3
52
.377
.53
7816
28
NW
6T
H S
TR
EE
TG
AIN
ES
VIL
LE F
L 3
26
09
AR
CH
ITE
CT
S &
PL
AN
NE
RS
FL C
ER
TIF
ICA
TE
SVM
SK
INN
ER
VIG
NO
LA
Mc
LE
AN
, IN
C.
FOR
AL
L R
EP
OR
TS
, PL
AN
S, S
PE
CIF
ICA
TIO
NS
, CO
MP
UT
ER
FIL
ES
, FIE
LD
DA
TA
, NO
TE
S &
OT
HE
R D
OC
UM
EN
TS
& I
NS
TR
UM
EN
TS
PR
EP
AR
ED
BY
TH
E D
ES
IGN
PR
OF
ES
SIO
NA
L A
S I
NS
TR
UM
EN
TS
OF
SE
RV
ICE
SH
AL
L R
EM
AIN
TH
E P
RO
PE
RT
Y O
F T
HE
DE
SIG
N P
RO
FE
SS
ION
AL
. TH
E D
ES
IGN
PR
OF
ES
SIO
NA
L S
HA
LL
RE
TA
IN A
LL
CO
MM
ON
LA
W, S
TA
TU
TO
RY
& O
TH
ER
RE
SE
RV
ED
RIG
HT
S, I
NC
LU
DIN
G T
HE
CO
PY
RIG
HT
TH
ER
ET
O. U
SE
OF
TH
ES
E D
OC
UM
EN
TS
FO
R A
NY
PU
RP
OS
E O
RP
RO
JE
CT
OT
HE
R T
HA
N T
HE
PR
OJ
EC
T W
HIC
H I
S S
UB
JE
CT
OF
TH
E A
GR
EE
ME
NT
IS
UN
LA
WF
UL
.
AA
34
78
PR
OJE
CT
LO
CA
TIO
N:
Mitchell Gulledge Engineering, Inc.
210 SW 4th Avenue
Gainesville, FL 32601FL License EB-31501 p.352.745.3991
www.mitchellgulledge.com MG#19096
3/
24
/2
02
0 1
0:3
6:5
1 A
MB
IM 3
60
://0
14
60
-30
- I
FA
S P
AV
ILIO
N L
IVE
OA
K/M
G19
09
6_I
FA
S L
ive
Oa
k P
av
ilio
n_2
02
0.r
vt
03/02/2020
E1.2ELECTRICAL
CEILING PLAN -LIGHTING
UF
/IF
AS
20
03
8 N
OR
TH
FL
OR
IDA
RE
C -
LIV
E O
AK
AG
RIC
UL
TU
RE
DE
MO
NS
TR
AT
ION
BU
ILD
ING
UF
PL
AN
NIN
G, D
ES
IGN
&C
ON
ST
RU
CT
ION LIV
E O
K, F
L 3
20
60
DE
SIG
N P
HA
SE
: 10
0%
CD
S
BNF
1460-30
APM
And
rew
P. M
cCad
din
PE
-83
318
N 1/8" = 1'-0"
ELECTRICAL CEILING PLAN - LIGHTING
LIGHT FIXTURE SCHEDULETYPE DESCRIPTION BASIS OF DESIGN LIGHT SOURCE INITIAL LUMENS COLOR TEMPERATURE WATTAGE VOLTAGE MOUNTING NOTES
4VPL 4' VAPORTIGHT LED WRAP H.E. WILLIAMS 96-4-L62/840-PCFR-DRV-UNV LED 6200 lm 4000 K 73 VA 120 V MOUNT TO PURLINS MOUNT TO STRUCTURE.
BOL LED BOLLARD WITH EMERGENCY BATTERY GARDCO PBL-36-14L-800-NW-G2-3-EBP-120-F1-FINISH LED 3198 lm 4000 K 41 VA 120 V POLE IN GROUND COORDINATE FINISH WITH ARCHITECT. PROVIDE EMERGENCY BATTERY WITH FIXTURE. BATTERY SHALL BE RATED FOR 4°F.
FLD LED EXTERIOR FLOOD LIGHT WALL MOUNT PHILLIPS GARDCO CSFS-16-530-NW-G1-YK-A33-120-BK WITH BP-(F) LED 3025 lm 4000 K 29 VA 120 V WALL AT 9' PROVIDE BP-(F) SURFACE MOUNT BASE PLATE.
XEB EDGE LIT LED EXIT SIGN BEGHELLI FTZ-SA-LG-IH LED 2 VA 120 V WET LOCATION & RATED FOR 0 DEGREES FAHRENHEIT
NOTES:1. SUBMIT ALTERNATES TO A/E FOR CONSIDERATION A MINIMUM OF 10 BUSINESS DAYS PRIOR TO BID. SUBMIT FIXTURE "CUT SHEET", INDICATING ALL INTENDED RATINGS AND OPTIONS.2. A/E WILL REVIEW ALTERNATES TO DETERMINE IF THEY ARE FUNCTIONALLY, AESTHETICALLY, AND STRUCTURALLY EQUAL. A/E RESERVE THE RIGHT TO REJECT ANY FIXTURES WHICH ARE NOT DEEMED EQUAL TO THE BASIS OF DESIGN.3. ALTERNATES REJECTED BY A/E SHALL NOT RESULT IN ADDITIONAL CHARGES TO THE OWNER.4. FIXTURES HALF SHADED OR MARKED 'EM' ON THE PLANS SHALL BE PROVIDED WITH BODINE BATTERIES PROVIDING AT LEAST 700lm OUTPUT FOR AT LEAST 90 MINUTES.
N 1/4" = 1'-0"
EAST ELEVATION
RE
VIS
ION
S
1A
DD
10
3/2
4/2
020
1