www.electroind.com Communication and User Interface • Standard 10/100BaseT Ethernet Port • Expandable Serial Ports (Dual RS485 Ports) • Modbus, Modbus TCP, DNP 3.0 Level 2 • 8 Simultaneous Connections via Ethernet • Optional Second Ethernet Port • Vivid 256 Color Display • Optional 100BaseT Fiber Port • Data Download Speed 20 Times Faster Than Existing Technology New Generation Transient Recording Power Quality 10MHz Transient Recorder (166,000 Samples per Cycle) 8 Channel Waveform Recorder Voltage Surge, Sag and Transient Recording Current Fault Signatures and Analysis 1 Gigabyte Memory – Highly Extensive Recording Capability Transient Recorder and Power Meter With Advanced Power Quality and Communication Electro Industries/GaugeTech The Leader in Power Monitoring and Control

Upload: vukien

Post on 16-May-2018

218 views

Category:

Documents


2 download

TRANSCRIPT

ww

w.e

lec

tro

ind

.co

m

Communication and User Interface • Standard 10/100BaseT Ethernet Port

• Expandable Serial Ports (Dual RS485 Ports)

• Modbus, Modbus TCP, DNP 3.0 Level 2

• 8 Simultaneous Connections via Ethernet

• Optional Second Ethernet Port

• Vivid 256 Color Display

• Optional 100BaseT Fiber Port

• Data Download Speed 20 Times Faster Than Existing Technology

New Generation Transient Recording Power Quality • 10MHz Transient Recorder (166,000 Samples per Cycle)

• 8 Channel Waveform Recorder

• Voltage Surge, Sag and Transient Recording

• Current Fault Signatures and Analysis

• 1 Gigabyte Memory – Highly Extensive Recording Capability

Transient Recorder and Power Meter With Advanced Power Quality and Communication

Electro Industries/GaugeTech The Leader in Power Monitoring and Control

IntroductionFrom today’s utility giants or Fortune 100 companies, to local

electrical municipals, an effective energy management and power

monitoring program is critical to success. The Nexus® 1500 meter

is the most advanced monitoring product on the market today,

providing you with the total picture of energy usage and power

quality from any metered point in a power distribution network,

allowing you to make power related decisions quickly

and effectively.

• TechnologyspecificallydesignedforUtilitiesandIndustry

• RealTimepowerqualitymonitoringandanalysisidentifies PQ and reliability events quickly

• Managepeakdemandelectricalpowerusage

• ReportdataquicklyandreliablyusingEthernetorserialcommunications

• Advancedtransientanalysisforcriticalpowersystems

• AlsotheperfectsolutionforCircuitBreakerorTransformermonitoring

The Perfect Monitoring Choice for Critical Applications• UtilityTransmissionLineSubstations

• PowerGeneration

• HighlyCriticalIndustrials

• Hospitals/Medical

High Performance Revenue Metering Features• ExtensiveLoadProfiling:log virtually unlimited historical

trending.

• SystemEvents(AntiTampering):the unit provides extensive usage information for detection of unauthorized access. The unit records:

• Resets • Programmingchanges • PasswordAccessChanges • Timechanges • PowerUp/Down • Changeoffirmware

• TransformerLossandLineLossCompensation: for both iron and copper and total substation losses.

• LoadAggregation/UniversalMetering: pulse inputs can be used to aggregate or accumulate different loads; utility products, such as gas and water can also be accumulated.

• TimeofUseCapability: bi-directional consumption and demand; 20 year calendar.

• Max/MinIntegrationandRecording: time-stamped max and min values for all measured readings.

• CoincidentalReadings: identify number of capacitors needed, peak inefficiencies, etc.

• PasswordProtectionPreventsUnauthorizedTampering:Userprogrammablepasswords.

• PredictedDemand: The meter uses rate of change to predict the peak demand of the next demand interval. Perfect for proactive load shedding.

Extremely Advanced Technology For Critical Monitoring

Billing Data and System Reliability Monitoring

Accu-Measure™ Auto-Calibrating Measurement TechnologyEIG’spatentedAccu-Measure™Auto-calibrationtechnology

allows a field-mounted metering device to achieve precision

accuracy and maintain the accuracy over temperature

andtime.ThistechniqueisuniquetoEIGandconsistsof

precise measurement technology and high precision internal

reference standards.

Accu-Measure™ Technology features:

• 8IndependentHigh-Powered16-BitA/DConverters.

• DualInternalReferencesforperiodicAuto-calibration.

• Internaltemperaturesensortosensedeviationsininstrument temperature.

• Designedtoallowforrepeatableandconsistentenergymeasurement results.

Benefits of Auto-Calibrating Technology:

• Improvesaccuracyovertemperature.

• Improvesrepeatabilty,reducingmetersettlingtime.

• Improveslong-termstability.

• ReliesonprecisioninternalDCreferencestomaintainaccuracy.

V-Switch™ TechnologyTheNexus®1500meterisequippedwithEIG’sexclusiveV-Switch™

technology, which enables meter upgrades in the field without

removingthemeterfromservice.Nexus®1500V-Switch™keys

include:

• V1:StandardNexus®1500meterwith128Megmemory + 512 samples per cycle

• V2:V1+1Gigtotalmemory+1024samplespercycle

• V3:V2+10MHzTransientRecording

PARAMETER

Voltage (L-N)

Voltage (L-L)

Current

Frequency

KW @ Unity PF

KW @ .5 PF

KVA

VAR

PF

Harmonic Magnitudes

KW/Hours

KVA/Hours

KVAR/Hours

200 MSEC*

0.1%

0.1%

0.1%

0.03 Hz

0.1%

0.1%

0.1%

0.1%

0.1%

N/A

N/A

N/A

N/A

1 SECOND*

0.05%

0.05%

0.025%

0.01 Hz

0.06%

0.1%

0.08%

0.08%

0.08%

0.2%

0.04%

0.08%

0.08%

DISPLAYRESOLUTION

5 Digit

5 Digit

5 Digit

00.001 Hz

5 Digit

5 Digit

5 Digit

5 Digit

3 Digit

3 Digit

16 Digit

16 Digit

16 Digit

* Note: Readings are in percent of reading where applicable (more accurate standard), not in percent of full scale (less accurate standard).

2

High Resolution Transient Sensing Power Quality Recorder

Detailed Power Quality Analysis and Waveform RecordingEIG’sNexus®1500meterisoneoftheindustry’spremierfault

and voltage disturbance recorders. This instrument captures a

comprehensive picture history of voltage reliability and power

quality events within mass memory for detailed and extensive

forensic engineering analysis.

• 16BitWaveformandFaultRecorder:

• Recordupto1024samplespercycleconsistingoftransientcapturesatover166,000samplespercycle.

• Voltageandcurrentrecordingwithpreandpost-eventanalysis.

• Faultrecordingoffers8timesfullscalecapturecapability.

• 16bitA/Dconverterprovidesprecisewaveformresolution.

• Bothhardwareandsoftwaretriggersavailable.

• Viewharmonicmagnitudesto512thorderforeachvoltage and current channel.

• Realtimeharmonicmagnitudesareresolvedtothe128thorder.

• PercentTHDandK-Factorarecalculated.

• Conductpowerqualityanalysisatthehighendoftheharmonic magnitude spectrum.

• High-SpeedStatusInputTriggers:

• Waveformsarerecordedattimeofstatuschange.

• Inputchangeandwaveformrecordingaretime-stampedto a 1msec resolution.

• EN61000-4-15FlickerMeter:

• EN61000-4-15FlickerMeter.

• FlickercompliantwithEN61000-4-15standard.

• Operatesonboth220Volt/50Hzand120Volt/60Hzvoltages throughout standard test points.

3

Multi-channelWaveformRecorder

• Subcycle10MHzTransientRecorder(V3Option):

Transients often cause intermittent, expensive periods of downtime. The subcycle transient recorder allows you to:

• Recordsubcycletransientsat10MHzresolution.

• Monitorswitchingnoisefromcapacitors,statictransferswitches,SCRs,andotherdevicesthatnegativelyimpact power quality.

• Thisfeatureisessentialforcriticalapplicationssuchas hospitals, wafer-fabs plants, data centers and other highly power quality sensitive applications.

• IndependentITIC/CBEMALogPlotting:

• Quicklyviewtotalsurges,sags,andaveragedurationintheindependentITIC/CBEMAlog.

• PhasorAnalysis:

• Themonitorreadsaphaseangleanalysisbetweenthevoltage and current channels, allowing you to analyze efficiency and system integrity.

EN61000-4-15FlickerCompliance

Sub-cycleTransientswith10MHzPickupFrequency

4

Multiple Programmable Memory Logs

1 Gigabyte Extensive Onboard Mass Memory Securely Records All Data

Virtually unlimited Historical trending logs

The Nexus® 1500 meter is equipped with vast amounts of memory. Ausercanpartitionthismemoryforlogstoragebysettingupboththenumberoflogsandthenumberofparametersperlog.Upto8historicallogscanbecreatedwithupto128parametersperlog.Withsuchextensivememory,themetercanlogforyears.

out of limit logThe unit offers an independent out of limit log. This allows a user to download out of limit information to obtain a sequence of events for anyoccurrence.Utilizingthe1msecclockresolution,thelogscanbecombined with different metered points throughout a distribution system to provide an accurate system-wide depiction of a power disturbance.

eVent-triggered WaVeform recording log The Nexus® 1500 meter records waveforms with a resolution of up to 1024samplespercycle.Theamountofwaveformrecordingisbasedonthe amount of memory installed.

The unit records the waveform when a value goes out of limit and when thevaluereturnstonormal.Allinformationistime-stampedtothenearest1msec.The8onboardHigh-SpeedInputscanbetiedtothewaveformrecording.Recordwhenabreakertrippedascomparedtowhentherelayactivated. This is very useful for fault and breaker integrity analysis.

The unit can be programmed to take more than one recording every time an event occurs. Thousands of cycles can be recorded per event.

itic/cBema log TheNexus®1500meterstoresaseparateCBEMAlogthatrecordsmagnitude and duration of voltage and current surges and sags for every powerqualityevent.ThisallowstheusertoconductrealtimeCBEMAanalysiswithoutdownloadingallstoredwaveforms.TheseparateCBEMAlog also allows the unit to provide a more comprehensive picture of power quality over time.

system eVents log The Nexus® 1500 meter logs extensive usage information for detection of unauthorized access. The unit records:

•Resets

•Programmingchanges

•PasswordAccessChanges

•TimeChanges

•PowerUp/PowerDown

•ChangeofFirmware

ExtensiveMemoryReadsDataIndefinitely

input status logThis log allows the user to record when the internal inputs change status.

uploadaBle flasH memoryThe Nexus® 1500 meter utilizes uploadable flash memory technologyonallprocessorsandDSPslocatedintheunit.This insures that the unit can be upgraded without removing it from service.

set limit controlThe Nexus® 1500 power monitor provides programmable setpoints for user settings. This feature allows a user to configure the meter to be used as a control device for many applications such as:

•CapacitorControl

•LoadShedding

•AutomaticTransferSchemes

•TransformerMonitoring&Control

•RedundantProtection(NotdesignedforPrimary Over-CurrentProtection)

•ManyOtherControlFunctions

WaVeform / transient logsThe 1500 can log waveform, utilizing its programmable memory for all surges, sags and transients within the scope of what it sees. Thousands of events can be logged with resolutionupto1024samplespercycleandtransientsat10MHzresolution.

custom allocataBle memory structureAusercancustomdefinelogsizeswithinthemeter.Thusthe full memory can be allocated specifically to the desired function.WithEIGtechnology,themetercanbeconfiguredoptimally for your application.

ITIC/CBEMATrending

OutofLimitLogExtensiveHistoricalTrending

ConfigurableMemoryAllocationTable

Robust Communication and Output Features

On-Board Communication for Every Application

Standard Communications:

• 100BaseTEthernetRJ45Port

• ANSIOpticalPort

• FrontcoverUSBport

Optional RS485 and Second Ethernet Port:

• Twoidenticalbuilt-inserialports:Upto115Kbaud.

• StandardprotocolsincludeModbusRTU/ASCIIandDNP3.0Level2.

• Alsoavailable,secondEthernetport,eitherRJ45orFiberOptic.

8 Built-In Digital High-Speed Status Inputs:

• Inputsautomaticallysensewhetherthecircuitisexternallywetted.

• Ifexternallywetted,inputupto300VDCisaccepted.

• Ifinternallywetted,themetersuppliesthenecessaryvoltageforthe control application.

Sync. Check-Aux. Volt Input —High-speed Vaux input can be used for:

• Neutraltoground.

• Voltagereadings.

• Synchronizingschemes.

• Obtainingthefrequency,magnitude,andphaseangleonbothsides of a switch, or between generator and bus voltage.

Industry Leading DNP 3.0 Level 2 Plus —complies with all DNP

Level 1 and Level 2 certification requirements, plus:

• Upto136measurements(64BinaryInputs,8BinaryCounters,64AnalogInputs)canbemappedtoDNPstaticpointsinthecustomizableDNPPointmap.

• Upto16relaysand8resetscanbecontrolledthoughDNP.

• Report-by-exceptionprocessing(DNPEvents)deadbandscanbe set on a per-point basis.

• 250availableevents,ofcombinationsoffourevents(BinaryInput Change,FrozenCounter,CounterChange,AnalogChange).

• AvailableFreezecommands:Freeze,Freeze/No-Ack,FreezewithTime,FreezewithTime/No-Ack.

• FreezewithTimecommandenablesthemetertohaveinternaltimedrivenFrozenCounterandFrozencountereventdata.

•Thirdpartycertificationisavailable.

•Newprogrammablesecondaryscaleallowsuserstomaximize16bit analog input resolution precisely around the desired parameters providingenhancedresolutiontoSCADA.

ExpandablE Output MOdulEs

Expandable Displays and Outputs

Rapid Response™ Ethernet:• RapidResponse™10/100BaseTEthernetallowsfor8

simultaneousconnectionsofEthernetModbusTCPprotocol.OnesocketforDNP3.0protocolisalsoavailable.RapidResponse™technologyinsuresthatthe Nexus® meter is optimized to download data as quickly as possible.

•UtilizinganovelModbusTCPapproach,themeterwilldownload up to 20 times faster than existing Nexus® 125XSeriesmeters.Nolongwaittimetoretrievedata.

Analog Transducer Signal Outputs:

• 1mAON4/1mAON8:4or8AnalogOutputs,0-1mA,self-powered, scalable, bidirectional.

• 20mAON4/20mAON8:4or8AnalogOutputs,4-20mA,self-powered, scalable.

Wiring:CommonMode.

Accuracy:0.1%ofFullScale.

Calibration:Self-calibrating.

Scaling: Programmable.

Ordering:Upto4AnalogOutputmodulesforeach Nexus®1500meter.Morethan2 ModulesrequiresanexternalPower Supply,Model#PSIO.

Digital Dry Contact Relay Outputs:

• 4RO1:4RelayOutputs,5amps,125AC/DC, FormC–LatchingRelays.

• Ordering:Upto4modulescanbeused.

Digital Solid State Pulse Outputs:

• 4PO1:4SolidStatePulseOutputs, FormAorCKYZpulses.

• MaximumPulseSpeed:20pulsespersecond.

• Ordering:Upto4modulescanbeused.

Output Module Accessories:

• PSIO:Additionalpowersupplyforupto4Outputmodules.Neededwhenusing3ormoredisplaysand/orOutputmodules.SeemanualforspecificVAallotments.

• MBIO:MountingbracketforOutputmodules.Mustbeordered with output module.

5

Superfast Download Speed — 20X Faster Means Easier To Use

2RS485Ports(Optional)

ColorLCD

ANSI

OpticalPort

4Voltage

Inputs

4CurrentInputs

IRIG-BInput

8High-SpeedStatusInputs

OnboardEthernet

TCP/ IPConnection

RevenueLock

HighSpeed

USBPort 2Infrared

AccuracyTestPulses

p60n tOuch scrEEn lcd display

p40nMultifunctiOn lEd display

NEW

2ndEthernetPort (Optional)

6

Dimensional Drawings

Wiring Diagrams

7

Vibrant Color LCD Touch Screen Display

A Truly Beautiful InterfaceTheNexus®1500meterfeaturesanLCDcolor

display with touch screen capability. The display

uses bright TFT glass with a high temperature

andlonglifeLEDbacklight.LEDissuperiorto

CCFLsolutionsduetobettertemperatureand

half-lifespecifications.Screendisplaysinclude:

•Real-timeviewing(voltage,current, power,demand)

•Accumulatedenergyandtimeofuse readings

•Flickerreadings

•Alarms

•Phasoranalysis

•Harmonicspectrumanalysis,and waveforms

•Realtimetrending

•Logstatus

•Configurationsettings

InputVoltageRange

• (5-347)VAC, Phase to Neutral

• (10-600)VAC, Phase to Phase

VoltageInputWithstandCapability

• Voltage Inputs isolated to 2500VDC Meets ANSI C37.90.1 (Surge Withstand Capability)

InputCurrentRange

• 5 Amp Inputs 4x continuous programmable to any CT range

• Fault Current recording to 80 amps peak secondary based on 5 Amp full scale

CurrentInputWithstandCapability

• 100 Amps for 10 Seconds

• 300 Amps for 1 Second

Burden

• Voltage Inputs: 0.072VA/Phase Max at 600 Volts, 0.003VA Max at 120 Volts

• Current Inputs: 0.02VA/Phase Max at 20 Amps

Isolation

All inputs to outputs are isolated to 2500 Volts.

TemperatureRating

• Operating Temperature: (-20 to +70)°C

• Humidity: Up to 95% RH Non-condensing

SensingMethod

• Up to 1024 Samples per Cycle (Programmable)

• Voltage Transient: 10MHz

• 16 Bit A/D Resolution – Multiple Converters

• Utilizes patented Accu-measure™ Technology

• True RMS

AccuracyRating

• This unit complies with and exceeds ANSI C12.20 and IEC687 accuracy requirements.

UpdateTime

• 1 Second — Revenue Accurate Readings

• 200 msec — High Speed Readings

ControlPowerRequirements

• (Suffix -D2): (90–265)VAC, (100-370)VDC

• Burden: 25VA Max

FrequencyRange

• 45Hz–69.9Hz

CommunicationFormat

• Programmable parity and stop bits

• Communication Protocols: Modbus TCP/IP, ASCII/RTU, DNP 3.0

• ANSI Optical Port

• USB 1.1/2.0 Virtual COM Port

• RJ45 Ethernet Port – 10/100BaseT

• 2 RS485 Ports (optional)

Shipping

Total shipping weight: approx. 5 lbs (2.3 kgs)

Shipping container dimensions: 16" x 13" x 11" (40.64cm x 33.02cm x 27.94cm)

Compliance

• ANSI C12.20 Class 0.2 and IEC687 (Accuracy)

• ANSI C62.41 (Surge)

• ANSI/IEEE C37.90.1 – Surge Withstand

• IEC 1000-4-2 – ESD

• IEC 1000-4-3 – Radiated Immunity

• IEC 1000-4-4 – Fast Transient

• IEC 1000-4-5 – Surge Immunity

• IEC 868 – Flicker Meter

• IEC 61000-4-15 – Flicker Meter

• CE Marked

• UL and cUL Listed

Specifications

OUTPUTMODULES

1mAON4 4AnalogOutputs,0–1mA

1mAON8 8AnalogOutputs,0–1mA

20mAON4 4AnalogOutputs,4–20mA

20mAON8 8AnalogOutputs,4–20mA

4RO1 4RelayOutputs

4PO1 4SolidStatePulseOutputs

PSIO PowerSupplyforAdditional Outputmodules

MBIO OutputMountingBracket (mustbeorderedwith purchaseofmodule)

ViVid cOlOr display

1800 Shames Drive, Westbury, NY 11590 1-877-EIMETER (1- 877-346-3837) Email: [email protected] Tel: 516-334-0870 Website: www.electroind.com

Electro Industries/GaugeTechThe Leader in Power Monitoring and Control

To order a Nexus® 1500 meter:1. Fill out the options you want in the order chart shown below. Listaccessoriesseparately.

2. SpecifyCommunicatorEXT3.0.

3. EIGcanalsoprovidecurrentandpotential transformers.

E15

4705

090

508

B

Ordering Information

Accessory Options

Ordering Specifications

OptionNumbers: -

-

-

-

-

-Example:

-

-

Nexus®BaseMeter

Nexus®1500

Nexus® 1500 Meter

ControlPower

D2

115AC(100-240)VAC

D2Universal

(90-265)VAC@50/60Hz or (100-370)VDC

FrequencyRange

60 Hz

60 Hz

50 Hz

VirtualSwitch

V2

V1Standard Nexus® 1500 meter with 128 Meg memory / 512 samples per cycle

V2V1 + 1 Gig memory /

1024 samples per cycle

V3V2 + 10 MHz

Transient Recording

-

-

-

-

-

-485P

X No Option

485P2 RS485 and

4 Pulse Outputs

I/OSlot2

NTFO

X No Option

NTFOSecond Network Card:

Combined RJ45 / Fiber Optic

(ST Terminated)

X No Option

6RO16 Relay Outputs

I/OSlot3

6RO1

X No Option

6RO16 Relay Outputs

I/OSlot4

6RO1

SOFTWARECOMEXT3.1C CommunicatorEXT3.0 forWindows®

Single-ComputerLicense (OneSite)

COMEXT3.MC CommunicatorEXT3.0 forWindows® Multiple-ComputerLicense (OneSite)

OUTPUTMODULES

1mAON4 4AnalogOutputs,0–1mA

1mAON8 8AnalogOutputs,0–1mA

20mAON4 4AnalogOutputs,4–20mA

20mAON8 8AnalogOutputs,4–20mA

4RO1 4RelayOutputs

4PO1 4SolidStatePulseOutputs

PSIO PowerSupplyforAdditional Outputmodules

MBIO OutputMountingBracket (mustbeorderedwith purchaseofmodule)

EXTERNALDISPLAYS

P60N GraphicalLCD Touch-ScreenDisplay

P40N Multi-FunctionLEDDisplay

CommunicationExpansion/Slot1