vaisala hvac product presentation documents/product presentations/cen-g-hva… · vaisala hvac...
TRANSCRIPT
Vaisala HVAC Product Presentation
Page © Vaisala
Technological leadershipTechnology used in Mars
curiosity rover Inhouse manufacturing in
our own cleanroom located in Vantaa Humidity and dew point
sensors CO2 sensors including light
sources, detectors and filters Barometric pressure
sensors Temperature sensors
2 B211486EN-C
Page © Vaisala
Vaisala HVAC product families80-series 90-series 110-series
Vaisala inhouse sensing technology x x x2-year warranty x x xDuct/outdoor models x xCalibration certificate x xSmart measurement modules xField adjustable x xConfigurable options x xSplashproof * xEnhanced chemical tolerance x x
* In certain models
3 B211486EN-C
Page © Vaisala
80-series
The HMW80 humidity and GMW80 carbon dioxide transmitters are cost-efficient solutions for demand-controlled ventilation Vaisala HUMICAP® and CARBOCAP®
sensor technology provides long lifetime, long-term stability and minimal lifetime cost CARBOCAP ® technology is suitable for
24/7 occupied spaces – internal reference measurement removes the need to adjust against unknown minimum values (ABC calibration)
4 B211486EN-C
Page © Vaisala
80-series Low self-heating by CARBOCAP ®
sensor The housing design allows for accurate
CO2 and temperature measurements in single device Comprehensive family of cost-efficient
variants available at short delivery times Easy installation:
– No warm-up time or calibration period required
– Loop powered versions available– Wiring in the back plate – snap-on
Sensor location
Sensor location
Vaisala GMW83DAnother brand
5 B211486EN-C
Page © Vaisala
The HMW90 humidity and GMW90 carbon dioxide transmitters are designed for the most demanding HVAC applications
Calibration certificate included Highest accuracy Digital ModBus RTU / BACNET
MSTP outputs available Field serviceable, low life cycle
cost
90-series
6 B211486EN-C
Page © Vaisala
90-series
Field serviceableModule replacement (calibration certificate
included) Calibration against handheld or calibration
gas Reduced life-cycle cost
Available in different colours
Decorative cover For best fit to architectural environment
7 B211486EN-C
Page © Vaisala
110-seriesHMDW110 series HVAC
instruments are designed for demanding applications also in washdown areas IP65 – duct, wall and outdoor mount Calibrated HUMICAP® sensors
provide ±2 %RH accuracy and long-term stability, traceable calibration certificate included 4 … 20 mA loop powered outputs
8 B211486EN-C
Page © Vaisala
110-series
Includes wall, duct and outdoor versions Outdoor version with a radiation shield
Compatible with the RDP100 remote displaySpecial sensors available for H2O2
disinfection applicationField serviceableEasy installation
9 B211486EN-C
Page © Vaisala
HUMICAP® humidity sensor
The same sensor is used in demanding industrial applications in power generation; auto industry; industrial drying; paper mills etc HUMICAP® sensor’s technical benefits:
Stability: Accurate measurements not only today, but after years of use Robustness: The sensor tolerates dust, dirt
and high humidity Selectivity: Fresh paint, cleaning fluids and
new building materials do not cause false readings or drift
10 B211486EN-C
Page © Vaisala
HUMICAP® humidity sensor
Unbeatable stability both indoors and outdoors.
Humicap180R specified stability in typical HVAC applications:
± 0.5 %RH/year
11 B211486EN-C
Page © Vaisala
CARBOCAP® CO2 sensor The CARBOCAP® carbon dioxide sensor brings
analyzer-level reliability to HVAC measurements. Dual wavelength single-beam technology guarantees the best possible stability.
CARBOCAP® sensor’s technical benefits:– Immediately correct measurements when
plugged in, no waiting for the sensor to correct offset drift
– Works also in 24/7 occupied spaces as reference measurment ar eperformed in every cycle
– Excellent stability and long lifetime with proprietary microglow lightsource
http://www.vaisala.com/en/industrialmeasurements/products/carbondioxide/Pages/default.aspx
12 B211486EN-C
Page © Vaisala
CARBOCAP® CO2 sensor
The light output from the microglow chip is much more stable over time than traditional filament lamps. This means improved CO2 measurement stability and longer sensor lifetime
Emitter
Membrane for thermal insulation
Frame
Reference and CO2 measurement is performed on every measurement cycle using an inhouse tunable filter chip. This guarantees excellent stability and low temperature dependence. 1000 ppm stability test results for 23 powered units in office conditions shown in picture with ±75 ppm 5 year total accuracy specification
Filament lamp
Largest value
smallest value25% fractileMedian75% fractileLegend:
13 B211486EN-C
Page © Vaisala
Animation of the CARBOCAP ®
operating principle
www.vaisala.com/CARBOCAP
B211486EN-C14
Page © Vaisala
Additional informationDatasheets, bid specs and price information available at
www.vaisala.com/hvac
HVAC Knowledge base for application notes, brochureshttp://www.vaisala.com/en/industrialmeasurements/applications/HVAC/Pages/default.aspx#tab=6
Contact your local sales representativehttp://www.vaisala.com/en/contact/sales/Pages/default.aspx
On-line storehttps://store.vaisala.com
15 B211486EN-C
Page © Vaisala
80-series variants
GMW84 GMW84S GMW83 GMW83A GMW83RP GMW83T GMW83D GMW83DRP GMW86P GMW86PTCO2 measuremet x x x x x x x x x xT measurement x x x x 2) x x 2) 1) 1)Humidity measurement x x4..20 mA x x x x0..10 V x x x x x x x xTraffic lights xRelay xTemperature setpoint x xDisplay
TMW82 TMW83 HMW82 HMW83 HMW88 HMW88D HMW89 HMW89DRH measurement x x x x x xHumidity parameters x x x xT measurement x x x x x x x x4..20 mA x x x x0..10 V x x x xWall mount x x x x x x x x
TMD82 TMD83 HMD82 HMD82D HMD83 HMD83D HMS82 HMS83RH measurement x x x x x xHumidity parameters x x x x x xT measurement x x x x x x x x4..20 mA x x x0..10 V x x x x xDuct mount x x x x x xOutdoor mount x x
16 B211486EN-C
1) Passive Pt10002) Passive Pt1000 and
active voltage output
Page © Vaisala
90-series variants
TMW92 TMW93 HMW92 HMW92D HMW93 HMW93D HMW95 HMW95DRH measurement x x x x x xT measurement x x x x x x x xCalculated parameters x x x x x x4..20 mA x x x0..5/10 V x x xBacnet MS/TP x xModBus RTU x xDisplay x x xRelay x x
GMW93 GMW93D GMW93R GMW93RD GMW93RA GMW94 GMW94D GMW94RD GMW95 GMW95D GMW95R GMW95RDCO2 measurement x x x x x x x x x x x xRH measurement x x x x x xT measurement x x x x x x x x x x x xCalculated parameters x x x x x x4..20 mA x x x0..5/10 V x x x x xBacnet MS/TP x x x xModBus RTU x x x xDisplay x x x x x xIndicator LED x
Configurable models TMW90, HMW90, GMW90 and GMW90R
17 B211486EN-C
Page © Vaisala
110-series variants
HMW110 HMD110 HMS110 HMW112 HMD112 HMS112RH x x x x x xT x x x x x xCalculated parameters x x x x x xWall mount x xDuct mount x xOutdoor mount x xCatalytic sensor * *Configurable outputs x x x
*) Catalytic sensor for environments with hydrogen peroxide desinfection
18 B211486EN-C