electrak lightrak system guide - legrand uk & ireland · · 2015-10-29lightrak / system guide...
TRANSCRIPT
LIGHTRAK / SYSTEM GUIDEINCLUDING BUSCOM
Lightrak®...KNX lighting
control system
P O W E R E D B Y S P E C I A L I S T S
LTK_Bro_Covers v1.indd 1 29/08/2012 12:21
Electrak®
... the specialist in power
distribution throughout the workplaceElectrak, part of the Legrand Group in the UK, is a leading manufacturer of power distribution and lighting control solutions. Its power track, fl oor boxes and grommets, desk modules and lighting control ranges are installed in high specifi cation offi ces around the world.
LTK_Bro_002_003 v1.indd 2 29/08/2012 12:14
LEGRAND IN THE UK - POWERED BY SPECIALISTS In the UK Legrand has developed a customer focused
structure which harnesses the power of its market
leading specialist brands to deliver innovative,
integrated solutions for every phase of construction.
Legrand is the global specialist in electrical
and digital building infrastructures. Innovation
is the driving force behind its development.
With an increasing investment in research
and development (circa 5% of sales) and more
than 4,000 active patents, the Legrand Group
is focused on maintaining a high rate of new
product launches that present innovative
solutions to the market.
SUSTAINABLE DEVELOPMENTFrom design through to manufacturing,
the Legrand Group selects materials and
processes that respect people and
the environment.
• Effi cient and environmentally aware product design
• Product functions that help to avoid energy waste
• Management of manufacturing and logistics sites
• Integration of environmental concerns and ISO 14001
procedures at the Group’s global sites.*
* 84% of sites are ISO 14001:2004 accredited including all UK sites.
CONTENTS
Buscom trunking 4
Lightrak system - features 6
Adapting to changing buildings 8
Integration with KNX and DALI 10
Lightrak sensors 12
System support service 14
Case studies 15
ORDERING INFORMATION
System components, lighting
control units, sub-cabling 16
Standard switching devices 17
Sub-bus addressable devices 18
Buscom trunking 24 - 37
TECHNICAL INFORMATION
Lightrak 19 - 23
Buscom trunking 38 - 43
LTK_Bro_002_003 v1.indd 3 29/08/2012 12:14
• Power and communications within a single
trunking system
• Suitable for use with any lighting control protocol,
including: KNX, LonWorks and DALI
• Modular, lexible system which is quick and simple
to install and adapt
• Reduced potential points of failure in comparison
with traditional wiring installations
04
Buscom trunking...a unique power and data backbone Buscom is at the heart of Electrak’s lighting control solutions... distributing both
power and communications within a single busbar trunking system, it provides a
lexible and simple alternative to traditional wiring installations.
THE HEART OF YOUR LIGHTING CONTROL SYSTEM Installing a matrix of Buscom trunking in the ceiling void creates an accessible power and
communications backbone throughout a building. The backbone can be tapped into at any point to
facilitate instant connection to power and control circuits.
Buscom incorporates a shielded twisted pair communications bus inside each length and tap-off,
and is suitable for use with any lighting control protocol, including: KNX, LonWorks and DALI.
MODULAR. FLEXIBLE. SIMPLE. Trunking lengths simply push it together, saving time and money on installation. With cable
terminations only required for power and control circuits in the feed unit, Buscom delivers a plug
and play solution that allows for future lighting layout changes to be made quickly and eficiently,
whilst drastically reducing the potential points of failure in comparison with traditional wiring
methods.
LTK_Bro_004_005 v1.indd 4 29/08/2012 12:15
05
INTELLIGENCE IN THE PANEL INTELLIGENCE IN THE BUSBAR INTELLIGENCE IN THE LCU
energy saving
ENERGY SAVING
As with all Electrak solutions, Buscom is a modular system designed to be quick and simple to install, reducing man hours and energy usage on site.
Lighting control modules
located in a central cabinet are
connected to the Buscom system
via communication circuits that
terminate in the feed unit. Control
signals are then distributed
along the trunking run and made
available at any tap-off outlet.
Integrating lighting control
technology into the Buscom feed
unit is particularly effective for
DALI control. Each trunking run
converts to an individual DALI
network into which luminaires can
tap-in at any point.
Lighting control units (LCUs)
are mounted onto and plugged
into Buscom trunking, providing
a hub into which multiples of
luminaires and switching devices
are plugged. Buscom’s integrated
communication bus provides the
backbone which networks all
control devices together.
Buscom adds a new dimension to lighting busbar that extends the unquestionable
plug and play advantages from the power circuit to the control circuit. This unique
system for distributing lighting control signals delivers unrivalled fl exibility,
regardless of the location of the intelligence...
LTK_Bro_004_005 v1.indd 5 29/08/2012 12:15
SNAP ON... PLUG IN
Lightrak lighting control units
(LCUs) simply snap on and plug into
Electrak’s Buscom trunking and
are easily unplugged, moved and
reprogrammed to accommodate
future lighting layout changes.
06
MULTI-GANG SWITCHES
1, 2, 4 and 8 gang options connect via CAT. 5 cable and RJ 45 plugs
PRESENCE OR ABSENCE DETECTION
Saves energy and ensures that lighting is only on when needed
TIMED EVENT CONTROLLER
Programmable touch screen units optimise energy saving
EMERGENCY TEST
Traditional key switch to enable testing of self-contained emergency luminaires
SCENE SETTING SWITCH
Multiple lighting scenarios are memorised and retrieved at the touch of a button
Lightrak®...fully addressable lighting control
Designed to work in harmony with
Electrak’s Buscom trunking, Lightrak’s
lighting control system offers high end
sophistication with unbeatable
lexibility and speed of installation.
LTK_Bro_006_007 v1.indd 6 29/08/2012 12:16
Lighting levels are adjusted in relation to the natural daylight contribution.
Sensors initiate dimming, saving energy and delivering a constant luminance at the desk.
Optimise energy savings in cellular ofices and meeting rooms. The occupant chooses when the lights are on; the system ensures they are switched off when the space is vacated.
Two way DALI communication facilitates feedback from DALI emergency inverters onto the KNX bus.
Monitoring and reporting software can be easily integrated with KNX.
A comprehensive range of control devices is available: PIR / ultrasonic sensors - wireless reconiguration of sensor parameters - scene setting - remote control - time scheduling - traditional switching and emergency key switch.
Analogue and DSI dimming through to full DALI control in addressable mode.
Networked over a KNX backbone that can be integrated onto IP or BMS systems.
A full KNX network can support in excess of 64,000 KNX devices.
Each output of every lighting control unit (LCU) is individually controllable.
Lightrak offers full building-wide control for even the largest of projects.
SOPHISTICATED TECHNOLOGY
DALI EMERGENCY FEEDBACK
DAYLIGHT LINKING
FULLY ADDRESSABLE
WIDE RANGING CONTROL
ABSENCE DETECTION
07
• Fast, easy installation. Snap on / plug in
• Fully addressable and PC reconigurable
• Analogue, DSI and DALI control
• Comprehensive range of energy saving switching, sensing and scheduling devices available
• Seamless connectivity with KNX devices from close to 300 manufacturers
• Interface with other building control systems via the open KNX protocol
• Two way communication with DALI, facilitating control and feedback
• Traditional emergency lighting test functions
• Comprehensive design and commissioning service
LTK_Bro_006_007 v1.indd 7 29/08/2012 12:17
08
At the Category A stage of an ofice it-out the lighting requirements of the inal tenant are not known.
With Lightrak, developers are able to install a cost-effective lighting control solution that is adequate for the client attraction phase, but can be upgraded to meet the needs of the incoming tenant with a minimum level of investment in time and labour.
The ability to adapt with the building thr
LTK_Bro_008_009 v3.indd 8 30/08/2012 16:19
09
With a matrix of Buscom trunking installed, a Lightrak installation provides a future proof solution where lighting schemes can be completely reconigured without the need to run or terminate any additional cables. Lighting control units are simply unplugged, moved and reprogrammed; additional devices and control units can also be added to extend the capability of any installation.
o adapt with the building throughout its life
LTK_Bro_008_009 v3.indd 9 30/08/2012 16:19
energy saving
ENERGY SAVING
10
Lightrak®...seamless integration with your technology of choice
The Lightrak system operates over a KNX backbone. This
enables all control devices connected to the system to
communicate with each other, and facilitates seamless
interoperability with any KNX certifi ed product.
KNX PROTOCOL SYSTEMSKNX is the worldwide standard for all applications
in home and building control, ranging from lighting
and shutter control to security, HVAC, metering and
energy management. With close to 300 members and
approximately 7000 certifi ed product ranges, the KNX
Association holds partnership agreements with over
30,000 installer companies in over 100 countries.
All products bearing the KNX logo are certifi ed in order
to guarantee system compatibility, interworking and
interoperability and are commissioned via a single,
manufacturer independent design and commissioning tool.
KNX IS APPROVED AS:
• European Standard (CENELEC EN 50090 and
CEN EN 13321-1)
• International Standard (ISO/IEC 14543-3)
For more information about KNX, visit: www.knx.org
Lighting accounts for up to 40% of a commercial building’s electricity use.(Lighting Industry Federation)
Lighting controls can provide energy savings of 30% to 55%.
LEFT: KNX was used as the underlying technology at
Terminal 5, Heathrow... possibly the largest lighting
control installation in Europe
LTK_Bro_010_011 v1.indd 10 29/08/2012 12:18
DELIVERING DALI EMERGENCY FEEDBACK The DALI lighting control unit (LCU) incorporates a
KNX to DALI interface that enables full DALI control in
addressable mode, and also facilitates the feedback from
the DALI network back onto the KNX bus.
Utilising widely available KNX gateways, this DALI
feedback can then be fed into building management
systems (BMS) or other monitoring and reporting software,
allowing emergency lighting test data to be logged and
alarms raised should essential maintenance be required.
DALI FEATURE IMAGE
11
For more information about DALI, visit: www.dali-ag.org
DALI: DIGITAL LIGHTING CONTROL DALI (Digital Addressable Lighting Interface) is a protocol
dedicated purely to lighting control, as set out in the
technical standard IEC 62386. Each unit in a DALI network
has its own address, allowing direct communication with
each individual itting.
TECHNICAL FEATURES The information low with DALI is bi-directional. Rather
than only giving commands about the light level from the
control system to the itting, DALI also enables information
feedback on the condition of the ittings.
The itting can transmit information related to:
• whether the light is switched on or off
• the preset light level
• the ballast condition
Therefore DALI is ideal for use with building automation
systems where remote supervising and service reports are
required.
LTK_Bro_010_011 v1.indd 11 29/08/2012 12:18
energy saving
ENERGY SAVING
EVEN GREATER SAVINGSIndependent research shows that the
added control available through using
absence detection can provide an
additional 10% energy saving over and
above the signifi cant savings already
offered by presence detection.
The simple way to instant energy savingsCombining lighting management sensors with traditional light switches puts users in complete control. Lights can be manually switched on and off or, if users forget to switch off lights, the sensors will do so automatically.
Users feel in complete control by turning on lights using a traditional switch, typically located by the door
The sensor will automatically switch off lights to save energy when available light is suffi cient (although lights can still be switched on if preferred)*
The sensor will automatically switch on lights when movement is detected and available light is insuffi cient*
When leaving the room, lights can be manually turned off using a switch. If lights are not turned off, the occupancy sensor will do so automatically
IN DARKNESS
IN BRIGHT LIGHT
IN NORMAL
LIGHT
IN WEAK LIGHT
* Lux levels can be set according to user preferences
12
Lighting controls are eligible for 100% Enhanced Capital Allowance under the Carbon Trust administered scheme.
LTK_Bro_012_013 v2.indd 12 30/08/2012 09:51
THE RIGHT TECHNOLOGY FOR EVERY ENVIRONMENTLegrand lighting management
solutions are available in three
different technologies to provide
effective occupancy detection in
different environments... all of which
can be controlled and commissioned
remotely at the touch of a button.
For small, enclosed spaces
PIR sensors detect occupancy
using the heat difference between
people and the ambient space.
For large spaces and open
areas Ultrasonic sensors
transmit sound waves throughout an
area and measure the speed at which
they come back.
For spaces with low or
infrequent movement from
occupants Dual technology, as the
name suggests, combines both
infra-red and ultrasonic detection.
REMOTE CONFIGURATORS FOR INSTANT PROGRAMMING OF EACH SENSOR
Sensors can be quickly and easily re-confi gured at the touch of a button,
and without the need to ever remove the sensors from the ceiling... putting
users in complete control and reducing health and safety risks.
• Advanced commissioning tool with LCD display
- Precise digital programming
- Instant visibility of individual sensor settings
- PIR / ultrasonic priority preferences for dual technology sensors
• Basic commissioning tool
- Pre-programmed settings
Save time. Save money. And, of course, save energy.
13
LTK_Bro_012_013 v2.indd 13 30/08/2012 09:22
Legrand...supporting you from initial design
through installation and beyond
DEDICATED DESIGN TEAM Lighting control units can either be supplied
unprogrammed for third party system integration,
or complete with a full in-house project design and
commissioning service.
Our experienced team provides support at all stages
of a project, from the outline brief through to inal site
commissioning.
Sales engineers work with designers at the early stages
of a project to recommend optimum Buscom layouts
and lighting control options. This service is backed by a
specialist support team who are on hand to work with
clients to complete detailed design schemes and provide
full support through the installation phase.
BESPOKE SOLUTIONS Every project is unique and sets its own challenges.
Our bespoke product development service enables us to
provide solutions to these challenges, and has delivered
tailor-made lighting control installations in a wide range
of building developments, including: Terminal 5, Heathrow,
London Underground, Canary Wharf and Central Bank
of Kuwait.
14
LTK_Bro_014_015 v1.indd 14 29/08/2012 12:19
LIGHTRAK PROJECTS
• Royal Bank of Scotland – Delhi, India
• Fidelity Investments – Delhi, India
• Cyprus Postal Service – Nicosia, Cyprus
• 2 x ITTL Showrooms – Nicosia, Cyprus
• Barclays Bank – Pane, India
• UKPS – Liverpool, England
• Lloyds TSB Bank – Old Broad Street,
London, England
• Bridgewater Place, Mixed use
Development – Leeds, England
• Lloyds TSB Card Contact Centre -
Petriies, Scotland
• Gray’s School of Art - Robert Gordon
University, Aberdeen, Scotland
• Rolls Royce - Glasgow, Scotland
• Liverpool School of Tropical Medicine
Ofice and Labs – University of Liverpool,
England
• Quorum Business Park, Ofice
Development (16 Buildings) - Newcastle
upon Tyne, England
• Mann Island, Ofice Development –
Liverpool, England
• Rotherham Civic Quarters, Local
Government Ofices - Rotherham,
England
• First Street Manchester, Manchester City
Council - England
• Velocity Buildings, Ofice Development -
Brooklands, Surrey, England
• Broadgate West, Ofice Development –
London, England
• Abbey Gardens, Ofice Development -
Reading, England
• HSE – Dublin, Ireland
• KPMG – Manchester, England
• KPMG – Watford, England
• Rackspace Data Centre – Slough,
England
• Translational Research Building –
Newcastle University, England
• Shadon House Care Facility –
Gateshead, England
TRUSTED THOUGHOUT THE UK AND ACROSS THE WORLD
15
LTK_Bro_014_015 v1.indd 15 29/08/2012 12:20
Lightrak® KNX lighting control systemsystem components, lighting control units (LCUs) and sub-cabling to luminaires
16
Pack Cat. Nos. Sub-cabling to luminaires
Plugs only
1 FFE080 6 pole rewirable plug (male)
Pre-wired plugs and leads (5 m LSOH)
1 FFE085 With 6 pole male plug to free end – 5 core
1 FFE095 With 6 pole male plug to free end – 6 core
1 FFE115 With 6 pole male plug to 6P female plug – 6 core
1 FFE135 With 6 pole male plug to 4P female plug – 4 core
1 FFE120 With 6 pole male plug to free end – 3 core no dimming
1 FFE125 With 6 pole male plug to free end – 4 core no dimming
Pack Cat. Nos. System components
1 FFA001 Statutory warning plaque
1 FFA004 Timed event controller (flush)
1 FFA006 Timed event controller (surface)
1 FFA008 Powered line coupler
1 FFA010 Buscom mounting power supply unit
1 FFA012 Line power supply
1 FFA014 KNX signal cable – 100 m
1 FFA016 USB to KNX interface
Lighting control units (LCUs) – 9 outputs (fully addressable)
Analogue dimming (1-10 V)
1 FFD054 Buscom mounting (standard buscom)
1 FFD054B1 L1 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD054B2 L2 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD054B3 L3 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD055 Rewirable surface mounting
Digital dimming (DSI)
1 FFD056 Buscom mounting (standard buscom)
1 FFD056B1 L1 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD056B2 L2 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD056B3 L3 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD057 Rewirable surface mounting
DALI (digital addressable lighting interface)
1 FFD060 Buscom mounting (standard buscom)
1 FFD060B1 L1 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD060B2 L2 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD060B3 L3 Key ‘B’ buscom mounting (3 phase buscom)
1 FFD061 Rewirable surface mounting
Dimensions and technical information (p. 19-23)
Proprietory lighting control system to work alongside Electrak’s 25 and 40 A buscom trunking with integral communications busOffers high speed installation and unrivaled flexibility for future reconfiguration. PC configurable, covers all lighting control requirements Based on the KNX open protocol and compatible with 1-10 V, DSI and DALI lighting installations Designed and manufactured in the UK from robust galvanised steel
Powered line coupler
FFA008
Timed event controller
FFA004
Feed unit
See p. 28-29
Lighting control unit
FFD060
Luminaire sub cabling
FFE115
Buscom mounting power supply unit
FFA010
- - -/-
- -
NEW
LTK_Bro_016_017 v4.indd 16 22/08/2012 15:31
Lightrak® KNX lighting control systemstandard switching devices
17
Dimensions and technical information (p. 19-23)
Pack Cat. Nos. CAT 5 cabling to switching devices
1 FFF205 5 m CAT 5 lead – plug to plug
1 FFF210 10 m CAT 5 lead – plug to plug
Standard switching devices connect into the system via simple CAT 5 cabling either straight into a lighting control unit or into a multi-gang switch interface. The inputs of the control units are addressable and can be commissioned to control any output or group of outputs throughout the entire KNX network. Future layout changes can be accommodated easily as all control units are plug and play and can be re-commissioned through KNX ETS software
Pack Cat. Nos. Standard presence detector
Plug into lighting control unit 1 FFC047 Presence detector
Switches
Switches for 1 gang back box
Plug into lighting control unit (see p. 16) 1 FFB030 1 gang switch
1 FFB032 1 gang key switch
1 FFB033 1 gang key switch – surface (including back box)
1 FFB034 2 gang switch
Switches for 2 gang back box
Plug into multi-gang switch interface (Cat. No. FFB020)
1 FFB022-2 2 gang switch
1 FFB022-3 3 gang switch
1 FFB022-4 4 gang switch
Switches for 2 x 2 gang back box
Plug into multi-gang switch interface (Cat. No. FFB020)
1 FFB024-5 5 gang switch
1 FFB024-6 6 gang switch
1 FFB024-7 7 gang switch
1 FFB024-8 8 gang switch
Multi-gang switch interface
1 FFB020 Buscom mounted multi-gang switch interface
Back boxes
1 FFB036 1 gang
1 FFB026 2 gang
1 FFB028 2 x 2 gang
4 gang switch
FFB022-4
Multi-gang
switch interface
FFB020
Presence detector
FFC047
1 gang switch
FFB030
1 gang key switch
FFB032
- - -/-
- -
- -
-/- -
-
Lighting control unit
See p. 16
LTK_Bro_016_017 v4.indd 17 22/08/2012 15:32
Lightrak® KNX lighting control system sub-bus addressable devices
18
Technical information (p. 21)
Addressable sensing and switching devices can be connected in series on a sub-bus Each sub-bus connects onto the KNX network via a sub-bus to KNX interface unit The addressable sensors offer a higher level of capability and functionality :• Factory set to presence mode, absence mode activated by commissioning tool• Factory pre-set light level threshold 500 lux for false ceiling, 300 lux for surface mounting / flush mounting detectors• Factory pre-set time delay 15 minutes• Precise adjustment on-site via commissioning toolDevices can be commissioned to control any output or group of outputs throughout the entire KNX network. Future layout changes can be accommodated easily as all devices can be re-commissioned through KNX ETS software
Pack Cat. Nos. Sub-bus to KNX interface unit
1 FFC020 Buscom mounting interface unit
Sub-bus sensors – commissioning tool
1 FFC021 Digital hand-held commissioning tool
Sub-bus sensors – ceiling mounting
Connect into interface unit (Cat. No. FFC020) With absence and presence modes Includes 5 m connection lead
PIR sensor
Detection field 45 m2 – Ø 8 mOptimum distance between detectors : 6 m
1 FFC050 PIR ceiling mounting switch sensor 360° 1 FFC051 Surface mounting box for FFC050
Combined PIR and ultrasonic sensor
Detection field 90 m2 – Ø 11 mOptimum distance between detectors : 10 m
1 FFC052 PIR and ultrasonic ceiling mounting sensor 360° 1 FFC053 Surface mounting box for FFC052
Sub-bus sensors – wall mounting
Connect into interface unit (Cat. No. FFC020) With absence and presence modes
Includes 10 m connection lead
PIR sensor
Maximum range 8 m – IP 42 1 FFC054 PIR wall mounting sensor 180°
Combined PIR and ultrasonic sensor
Maximum range 11 m – IP 42 1 FFC055 PIR and ultrasonic wall mounting sensor 180°
IP 55 sensor
Maximum range 15 m – IP 55 1 FFC056 PIR wall mounting sensor 270°
Pack Cat. Nos. Sub-bus sensor – for corridors
Connects into interface unit (Cat. No. FFC020) With absence and presence modes
Includes 10 m connection lead Maximum range 30 m – IP 42 1 FFC057 PIR sensor 140°
IR remote control
For sub-bus sensors (client use) 1 FFC058 On / off – dimming controller
Other sub-bus devices
Light measurement cell
Connects into interface unit (Cat. No. FFC020) Includes 5 m lead
1 FFC059 Photocell light level sensor
Sub-bus switches
Connect into interface unit (Cat. No. FFC020) Includes 10 m connection lead
Complete with brushed stainless steel plate, yolk and magnesium rockers
1 FFC030 2 gang 2 way sub-bus switch 1 FFC033 4 scenario sub-bus switch
Sub-bus accessories
1 FFC022 Sub-bus cable – 100 m 1 FFC023 RJ45 doubler unit to extend sub-bus 1 FFC024 Sub-bus to RJ45 connector
FFC052
FFC050 FFC059 FFC023 FFC024
FFC055
FFC058
FFC020
FFC021
NEW
Available 2013
LTK_Bro_018 v4.indd 18 22/08/2012 15:37
19
Lightrak® KNX lighting control systemtechnical information
n KNX technical specification
Each line coupler can support 64 bus devices (lighting control units, multi-gang switch interface units, bus interface units etc)A maximum of 15 line couplers may be linked with a main bus line together to form an area; therefore an area can support up to 960 devicesThe system may be further expanded with the addition of a backbone bus line which would allow the linking together of 15 main bus lines via 15 line couplers, therefore any single system could support 14 400 devicesBy utilising additional line couplers this total can exceed 64 000 devices (for additional information, please contact us on +44 (0) 845 600 6266)
Within any KNX bus line the following cable lengths are permitted :• Power supply unit to bus device 350 m maximum• Bus device to bus device 700 m maximum• Total bus line length 1 000 m maximum• Minimum distance between 2 power supply units on one line is 200 m(1)
n Powered line coupler FFA008
Connections
• 230 V± : screw connection block• Primary line : screw connection block• Secondary line : screw connection block
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 358 mm, width 200 mm, depth 75 mm• Weight : approximately 2·750 kg
Technical specifications
Supply voltage : 230V± 50/60HzProtection (supply) : 13 A BS 1362 fused spurInternal protection : 6·3 A fuse to IEC127-2Primary line load : 15 mWSecondary line load : 200 mWSecondary output voltage : 30Vdc +/- 2 VSecondary output current : 630 mAEMC complies with : EN 50090-2-2 : 1997, EN 55022BClimatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n Buscom trunking mounted power supply unit FFA010
Connections
• 230 V± : Electrak integrated tap-off• Bus : Electrak integrated tap-off
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 330 mm, width 110 mm, height 60 mm
9 mm bracket clearance from busbar trunking• Weight : approximately 1·90 kg
Technical specifications
Supply voltage : 230 V± 50/60 HzProtection (supply) : 13 A BS 1362 fuse fitted in tap-offInternal protection : 6·3 A fuse to IEC 127-2Secondary output voltage : 30 Vdc +/- 2 VSecondary output current : 640 mATap-off ASTA approved : BS EN 60439-2 : 2000EMC complies with : EN 50090-2-2 :1997, EN 55022BClimatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n Line power supply FFA012
Connections
• 230 V± : screw connection block• Bus : screw connection block
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 358 mm, width 110 mm, depth 75 mm• Weight : approximately 1·95 kg
Technical specifications
Supply voltage : 230 V± 50/60HzProtection (supply) : 13 A BS 362 fused spurInternal protection : 6·3 A fuse to IEC 127-2Secondary output voltage : 30 Vdc +/- 2 VSecondary output current : 640 mAEMC complies with : EN 50090-2-2 : 1997, EN 55022BClimatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
(1) Electrak manufacture a buscom trunking mounted power supply unit for this application, Cat. No. FFA010 see p. 16 All dimensions (mm) are nominal
LTK_Bro_019_023 v4.indd 19 23/08/2012 13:55
20
n Lighting control unit – analogue dimming Cat. Nos.FFD054/FFD055
Connections
• 4 RJ45 inputs : CAT 5 providing switching input• 9 GST/6 providing 230 V± to luminairesL1 Switched live brownE Earth green / yellowN Neutral blueL2 Maintained live black2 Dimming common white3 Dimming red
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking• Weight : approximately 1·75 kg
Technical specifications
Supply voltage : 230 V± 50/60HzMaximum load : 10 A BS 1362 fuse fitted in tap-offMaximum power : 2 300 VABus voltage : 30 Vdc +/- 2 VTap-off ASTA approved : BS EN 60439-2 : 2000EMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n Lighting control unit – DSI dimming Cat. Nos. FFD056/FFD057
Connections
• 4 RJ45 inputs : CAT 5 providing switching input• 9 GST/6 providing 230 V± to luminairesL1 Switched live brownE Earth green / yellowN Neutral blueL2 Maintained live black2 Dimming common white3 Dimming red
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking• Weight : approximately 1·75 kg
Technical specifications
Supply voltage : 230 V± 50/60 HzMaximum load : 10 A BS 1362 fuse fitted in tap-offMaximum power : 2 300 VABus voltage : 30 Vdc +/- 2 VTap-off ASTA approved : BS EN 60439-2 : 2000EMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n Lighting control unit – DALI Cat. Nos. FFD060/FFD061
Connections
• 4 RJ45 inputs : CAT 5 providing switching input• 9 GST/6 providing 230 V± to luminairesL1 Switched live brownE Earth green / yellowN Neutral blue2 DALI3 DALI
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking• Weight : approximately 1·75 kg
Technical specifications
Supply voltage : 230 V± 50/60 HzMaximum load : 10 AMaximum power : 2 300 VAKNX bus voltage : 30 Vdc +/- 2 VTap-off ASTA approved : BS EN 60439-2 : 2000EMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4x
n 4 gang switch Cat. No. FFB022-4
Physical specifications
• Housing : steel back box 132 mm x 72 mm minimum 48 mm deep• Dimensions : length 125 mm, width 64 mm, height 41 mm• Weight : approximately 0·668 kg
Technical specifications
Supply voltage : 9 VdcEMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n 8 gang switch Cat. No. FFB024-8
Physical specifications
• Housing : steel back box 136 mm x 136 mm minimum 52 mm deep• Dimensions : length 127 mm, width 122 mm, height 41 mm• Weight : approximately 1·30 kg
Technical specifications
Supply voltage : 9 VdcEMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n Multi-gang switch interface Cat. No. FFB020
Connections
• 230 V± : Electrak integrated tap-off• Bus : Electrak integrated tap-off• Switch : CAT 5 lead (RJ45 to RJ45)
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 126 mm, width 102 mm, height 46 mm plus
9 mm mounting bracket• Weight : approximately 0·66 kg
Technical specifications
Supply voltage : 230 V± 50/60 HzProtection : 3 A BS 1362 fuse fitted in tap-offNominal load : 24 mAMaximum bus load : 12 mATap-off ASTA approved : BS EN 60439-2 : 2000EMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
n Lighting control unit – dimensions
Lightrak® KNX lighting control systemtechnical information
All dimensions (mm) are nominal
Cat. Nos. FFD054, FFD056, FFD060
LTK_Bro_019_023 v4.indd 20 22/08/2012 16:06
21
Lightrak® KNX lighting control system sub-bus sensors technical information
n Wall mounting
Wall mounting sensors are supplied with mounting base Simply ix base to the wall, connect wires to the automatic wiring block and ix sensor to base
n Ceiling mounting
All sub-bus sensors have built-in bracket systems that enable ceiling mounting. Most sensors are suitable for standard EU boxes (Ø 65). This is important for applications where the ceiling is unavailable for sensor installation. Only one Cat. No. is required for two ways of mounting
Cat.No FFC021
This commissioning tool enables a very precise commissioning of your sensors :- Time: from 0 seconds to 60 min- Lux: from 1 lux to 1 275 lux- Detection mode : presence, presence walkthrough, absence modes- PIR and US detection sensibility : low, medium, high, very high- Provides access to advanced functions such as calibration, alarms, choice of mode of detection (initial detection, maintain detection, retrigger), daylight function - Allows downloading, saving and duplication of sensor parameters
Hand-held commissioning tool can be used to adjust settings :
n Settings
Most sensors feature Smart Factory Set technology. Adjustments are typically not needed after installationIf adjustments need to be made (due to last minute changes in furniture or ixture placement), sensitivity and time delays should match the activity levels of the monitored spaces
Presence mode
Walkthrough mode
Absence mode
3'
n Sub-bus to KNX interface unit FFC020
Connections
• Bus : Electrak integrated tap-off connecting 230 V± and KNX bus
Physical specifications
• Housing : galvanised steel, natural finish• Dimensions : length 125 mm, width 154 mm, height 72 mm plus 9 mm
mounting bracket
Technical specifications
Supply voltage : 230 V± 50/60 HzProtection : 3 A BS 1362 fuse fitted in tap-offTap-off ASTA approved : BS EN 60439-2 : 2000EMC complies with : EN 50090-2-2 : 1997Climatic condition class : 3K4 (5ºC to 40ºC)IP rating : 4xCertification : KNX certified
LTK_Bro_019_023 v4.indd 21 23/08/2012 13:56
Layout key
n Example of ceiling layout for Lightrak KNX fully addressable system (see opposite)
n KNX system topology schematic diagram
Example of typical layout
1.15.0 (maximum)
1.5.64
Repeaterpower linecoupler
1.5.128 1.5.192(maximum)
KNX standardbus cable
Bu
s lin
e(m
ax.
64
LC
U)
KNX standard bus cable interconnectingmain line powered line coupler
AREA 2 main bus line
AREA 3 main bus line
AREA 4 main bus line
AREA 15 main bus line (maximum)
1.5.01.4.01.3.01.2.01.1 .0
AREA 1 main bus line
Bu
s lin
e(m
ax.
64
LC
U)
Backbonepoweredline coupler
1.0. –1.0.1 1.0.2 1.0.3 1.0.4 1.0.15
Backbone bus line
KNX standard bus cableinterconnecting backbonepowered line coupler
Main linepoweredline coupler
Backbonepower supply unit
Lightrak® KNX lighting control systemtypical layout and system topology
22
1/1
Electrical distribution board and power cabling
Powered line coupler and KNX cabling
Timed event controller
Buscom feed unit and lengths
Lighting control unit and reference number
Luminaires and sub-cabling
Standard presence detector and CAT 5 sub cabling
Sub-bus interface unit and sub-bus cabling
PIR bus sensor
Dual technology (PIR and ultrasonic) bus sensor
Bus switch
Bus scenario switch
LTK_Bro_019_023 v4.indd 22 23/08/2012 14:39
23
1/2
1/1
2/2
2/1
3/2
3/1
4/2
4/1
5/2
5/1
6/1 6/2
1/5
1/4
1/3
1/2
1/1
2/5
2/4
2/3
2/2
2/1
3/3
3/2
3/1
4/2
4/1
5/2
5/1
6/1 6/2
Cat A lighting layout
The left hand area fitted out to Cat B tenant layout
LTK_Bro_019_023 v4.indd 23 22/08/2012 17:47
pour exemple XXXXXXxxxxxxxxxxxxxxElectrak® buscom trunking2P, 3P, dual circuit and 3 phase systems
3 m track 0·5 m spacings
2 m track 0·5 m spacings
3 m track 1·0 m spacings
2 m track 1·0 m spacings
Single sided BBA3145C BBA2145C BBA3141C BBA2141C
Double sided BBA3245C BBA2245C BBA3241C BBA2241C
Single sided CCA3145C CCA2145C CCA3141C CCA2141C
Double sided CCA3245C CCA2245C CCA3241C CCA2241C
Single sided BBA3155C BBA2155C BBA3151C BBA2151C
Double sided BBA3255C BBA2255C BBA3251C BBA2251C
Single sided CCA3155C CCA2155C CCA3151C CCA2151C
Double sided CCA3255C CCA2255C CCA3251C CCA2251C
Single sided BBB3145C BBB2145C BBB3141C BBB2141C
Double sided BBB3245C BBB2245C BBB3241C BBB2241C
Single sided CCB3145C CCB2145C CCB3141C CCB2141C
Double sided CCB3245C CCB2245C CCB3241C CCB2241C
Single sided BBB3155C BBB2155C BBB3151C BBB2151C
Double sided BBB3255C BBB2255C BBB3251C BBB2251C
Single sided CCB3155C CCB2155C CCB3151C CCB2151C
Double sided CCB3255C CCB2255C CCB3251C CCB2251C
Single sided BBC3145C BBC2145C BBC3141C BBC2141C
Double sided BBC3245C BBC2245C BBC3241C BBC2241C
Single sided CCC3145C CCC2145C CCC3141C CCC2141C
Double sided CCC3245C CCC2245C CCC3241C CCC2241C
Single sided BBC3155C BBC2155C BBC3151C BBC2151C
Double sided BBC3255C BBC2255C BBC3251C BBC2251C
Single sided CCC3155C CCC2155C CCC3151C CCC2151C
Double sided CCC3255C CCC2255C CCC3251C CCC2251C
Single sided BBD3145C BBD2145C BBD3141C BBD2141C
Double sided BBD3245C BBD2245C BBD3241C BBD2241C
Single sided CCD3145C CCD2145C CCD3141C CCD2141C
Double sided CCD3245C CCD2245C CCD3241C CCD2241C
Single sided BBD3155C BBD2155C BBD3151C BBD2151C
Double sided BBD3255C BBD2255C BBD3251C BBD2251C
Single sided CCD3155C CCD2155C CCD3151C CCD2151C
Double sided CCD3255C CCD2255C CCD3251C CCD2251C
Electrak 302P + E system
SYSTEM IP RATING RATING
25 A
40 A
25 A
40 A
25 A
40 A
25 A
40 A
IP 54
IP 4X
IP 54
Electrak 313P + E system
24
OUTLETS
IP 4X
25 A
40 A
25 A
40 A
25 A
40 A
25 A
40 A
Electrak 32Dual circuit system
Electrak 333 phase system
IP 54
IP 4X
IP 54
IP 4X
LTK_Bro_024_025 v2.indd 24 22/08/2012 16:16
Centre feedSuspended feed
unit left handSuspended feed unit right hand
Surface feed unit left hand
Surface feed unit right hand
Suspended flexible corner
0·5 m
Suspended flexible corner
2·0 m
Surface flexible corner 0·5 m
Surface flexible corner 2·0 m
BBA44FC BBA14LFC BBA14RFC BBA34LFC BBA34RFC BBA140XC BBA142XC BBA340XC BBA342XC
– BBA24LFC BBA24RFC – – BBA240XC BBA242XC – –
CCA44FC CCA14LFC CCA14RFC CCA34LFC CCA34RFC CCA140XC CCA142XC CCA340XC CCA342XC
– CCA24LFC CCA24RFC – – CCA240XC CCA242XC – –
– BBA15LFC BBA15RFC BBA35LFC BBA35RFC BBA150XC BBA152XC BBA350XC BBA352XC
– BBA25LFC BBA25RFC – – BBA250XC BBA252XC – –
– CCA15LFC CCA15RFC CCA35LFC CCA35RFC CCA150XC CCA152XC CCA350XC CCA352XC
– CCA25LFC CCA25RFC – – CCA250XC CCA252XC – –
BBB44FC BBB14LFC BBB14RFC BBB34LFC BBB34RFC BBB140XC BBB142XC BBB340XC BBB342XC
– BBB24LFC BBB24RFC – – BBB240XC BBB242XC – –
CCB44FC CCB14LFC CCB14RFC CCB34LFC CCB34RFC CCB140XC CCB142XC CCB340XC CCB342XC
– CCB24LFC CCB24RFC – – CCB240XC CCB242XC – –
– BBB15LFC BBB15RFC BBB35LFC BBB35RFC BBB150XC BBB152XC BBB350XC BBB352XC
– BBB25LFC BBB25RFC – – BBB250XC BBB252XC – –
– CCB15LFC CCB15RFC CCB35LFC CCB35RFC CCB150XC CCB152XC CCB350XC CCB352XC
– CCB25LFC CCB25RFC – – CCB250XC CCB252XC – –
BBC44FC BBC14LFC BBC14RFC BBC34LFC BBC34RFC BBC140XC BBC142XC BBC340XC BBC342XC
– BBC24LFC BBC24RFC – – BBC240XC BBC242XC – –
CCC44FC CCC14LFC CCC14RFC CCC34LFC CCC34RFC CCC140XC CCC142XC CCC340XC CCC342XC
– CCC24LFC CCC24RFC – – CCC240XC CCC242XC – –
– BBC15LFC BBC15RFC BBC35LFC BBC35RFC BBC150XC BBC152XC BBC350XC BBC352XC
– BBC25LFC BBC25RFC – – BBC250XC BBC252XC – –
– CCC15LFC CCC15RFC CCC35LFC CCC35RFC CCC150XC CCC152XC CCC350XC CCC352XC
– CCC25LFC CCC25RFC – – CCC250XC CCC252XC – –
BBD44FC BBD14LFC BBD14RFC BBD34LFC BBD34RFC BBD140XC BBD142XC BBD340XC BBD342XC
– BBD24LFC BBD24RFC – – BBD240XC BBD242XC – –
CCD44FC CCD14LFC CCD14RFC CCD34LFC CCD34RFC CCD140XC CCD142XC CCD340XC CCD342XC
– CCD24LFC CCD24RFC – – CCD240XC CCD242XC – –
– BBD15LFC BBD15RFC BBD35LFC BBD35RFC BBD150XC BBD152XC BBD350XC BBD352XC
– BBD25LFC BBD25RFC – – BBD250XC BBD252XC – –
– CCD15LFC CCD15RFC CCD35LFC CCD35RFC CCD150XC CCD152XC CCD350XC CCD352XC
– CCD25LFC CCD25RFC – – CCD250XC CCD252XC – –
25
LTK_Bro_024_025 v2.indd 25 22/08/2012 16:16
Ele
ctr
ak
30
2P
+ E
sy
ste
mS
YS
TE
M
PH
AS
E
IP R
AT
ING
L+
N
IP 54
IP 4X
Ele
ctr
ak
31
3P
+ E
sy
ste
m
Ele
ctr
ak
32
Du
al
cir
cu
it s
ys
tem
L1
NL
1 L
2 N
IP 54
IP 4X
IP 54
IP 4X
L1
N1
L2
N2
IP 54
IP 4X
IP 54
IP 4X
L1
NL
2 N
IP 54
IP 4X
IP 54
IP 4X
L3
NP
ha
se
s
ele
cta
ble
IP 54
IP 4X
IP 54
IP 4X
L +
L +
L +
N
IP 54
IP 4X
pour exemple XXXXXXxxxxxxxxxxxxxxElectrak® buscom trunking tap-offs
Rewirable 0·8 m 2 m 3 m 5 m
With comms – DDE408FC DDE42FC DDE43FC DDE45FC
No comms DDF4F DDE408F DDE42F DDE43F DDE45F
With comms – DDE508FC DDE52FC DDE53FC DDE55FC
No comms DDF5F DDE508F DDE52F DDE53F DDE55F
With comms – DDE408FC DDE42FC DDE43FC DDE45FC
No comms DDF4F DDE408F DDE42F DDE43F DDE45F
With comms – DDE508FC DDE52FC DDE53FC DDE55FC
No comms DDF5F DDE508F DDE52F DDE53F DDE55F
With comms – DDG408FC DDG42FC DDG43FC DDG45FC
No comms DDH4F DDG408F DDG42F DDG43F DDG45F
With comms – DDG508FC DDG52FC DDG53FC DDG55FC
No comms DDH5F DDG508F DDG52F DDG53F DDG55F
With comms – DDE408FC DDE42FC DDE43FC DDE45FC
No comms DDF4F DDE408F DDE42F DDE43F DDE45F
With comms – DDE508FC DDE52FC DDE53FC DDE55FC
No comms DDF5F DDE508F DDE52F DDE53F DDE55F
With comms – DDJ408FC DDJ42FC DDJ43FC DDJ45FC
No comms DDK4F DDJ408F DDJ42F DDJ43F DDJ45F
With comms – DDJ508FC DDJ52FC DDJ53FC DDJ55FC
No comms DDK5F DDJ508F DDJ52F DDJ53F DDJ55F
With comms – DDM408L1FC DDM42L1FC DDM43L1FC DDM45L1FC
No comms DDN4L1F DDM408L1F DDM42L1F DDM43L1F DDM45L1F
With comms – DDM508L1FC DDM52L1FC DDM53L1FC DDM55L1FC
No comms DDN5L1F DDM508L1F DDM52L1F DDM53L1F DDM55L1F
With comms – DDM408L2FC DDM42L2FC DDM43L2FC DDM45L2FC
No comms DDN4L2F DDM408L2F DDM42L2F DDM43L2F DDM45L2F
With comms – DDM508L2FC DDM52L2FC DDM53L2FC DDM55L2FC
No comms DDN5L2F DDM508L2F DDM52L2F DDM53L2F DDM55L2F
With comms – DDM408L3FC DDM42L3FC DDM43L3FC DDM45L3FC
No comms DDN4L3F DDM408L3F DDM42L3F DDM43L3F DDM45L3F
With comms – DDM508L3FC DDM52L3FC DDM53L3FC DDM55L3FC
No comms DDN5L3F DDM508L3F DDM52L3F DDM53L3F DDM55L3F
With comms – – – – –
No comms DDP4SF – – – –
With comms – – – – –
No comms DDP5SF – – – –
With comms – – – – –
No comms – – – – –
With comms – – – – –
No comms – – – – –
13 A FUSED TAP-OFFS
26
Ele
ctr
ak
33
3 p
ha
se
sy
ste
m
LTK_Bro_026_027 v2.indd 26 22/08/2012 16:17
– DDE408C DDE42C DDE43C DDE45C
DDF4 DDE408 DDE42 DDE43 DDE45
– DDE508C DDE52C DDE53C DDE55C
DDF5 DDE508 DDE52 DDE53 DDE55
– DDE408C DDE42C DDE43C DDE45C
DDF4 DDE408 DDE42 DDE43 DDE45
– DDE508C DDE52C DDE53C DDE55C
DDF5 DDE508 DDE52 DDE53 DDE55
– DDG408C DDG42C DDG43C DDG45C
DDH4 DDG408 DDG42 DDG43 DDG45
– DDG508C DDG52C DDG53C DDG55C
DDH5 DDG508 DDG52 DDG53 DDG55
– DDE408C DDE42C DDE43C DDE45C
DDF4 DDE408 DDE42 DDE43 DDE45
– DDE508C DDE52C DDE53C DDE55C
DDF5 DDE508 DDE52 DDE53 DDE55
– DDJ408C DDJ42C DDJ43C DDJ45C
DDK4 DDJ408 DDJ42 DDJ43 DDJ45
– DDJ508C DDJ52C DDJ53C DDJ55C
DDK5 DDJ508 DDJ52 DDJ53 DDJ55
– DDM408L1C DDM42L1C DDM43L1C DDM45L1C
DDN4L1 DDM408L1 DDM42L1 DDM43L1 DDM45L1
– DDM508L1C DDM52L1C DDM53L1C DDM55L1C
DDN5L1 DDM508L1 DDM52L1 DDM53L1 DDM55L1
– DDM408L2C DDM42L2C DDM43L2C DDM45L2C
DDN4L2 DDM408L2 DDM42L2 DDM43L2 DDM45L2
– DDM508L2C DDM52L2C DDM53L2C DDM55L2C
DDN5L2 DDM508L2 DDM52L2 DDM53L2 DDM55L2
– DDM408L3C DDM42L3C DDM43L3C DDM45L3C
DDN4L3 DDM408L3 DDM42L3 DDM43L3 DDM45L3
– DDM508L3C DDM52L3C DDM53L3C DDM55L3C
DDN5L3 DDM508L3 DDM52L3 DDM53L3 DDM55L3
– – – – –
DDP4S – – – –
– – – – –
DDP5S – – – –
– – – – –
– DDR408 DDR42 DDR43 DDR45
– – – – –
– DDR508 DDR52 DDR53 DDR55
Rewirable 0·8 m 2 m 3 m 5 m
16 A UNFUSED TAP-OFFS
27
LTK_Bro_026_027 v2.indd 27 22/08/2012 16:17
Electrak® 30 2P + E buscom trunkingpower and communication distribution
28
Pack Cat. Nos. Flexible lengths for single sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left Length Rating Weight (m) (A) (kg)(1)
1 BBA140XC 0·5 25 2·91 1 BBA142XC 2 25 3·21 1 CCA140XC 0·5 40 2·94 1 CCA142XC 2 40 3·33
Surface mounted – right to left Length Rating Weight (m) (A) (kg)(1)
1 BBA340XC 0·5 25 2·99 1 BBA342XC 2 25 3·05 1 CCA340XC 0·5 40 3·02 1 CCA342XC 2 40 3·41
Pack Cat. Nos. Electrak 30 2 P + E + comms – single sided system
2P + E buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versions Socket outlets are colour coded white and are located on just one side of the bar
2P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBA3145C 3 6 4·47 1 BBA2145C 2 4 3·27 1 BBA3141C 3 3 4·42 1 BBA2141C 2 2 3·24 40 A 1 CCA3145C 3 6 4·57 1 CCA2145C 2 4 3·36 1 CCA3141C 3 3 4·52 1 CCA2141C 2 2 3·31
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and 2 x 16 mm Ø cable entry holes and single screw cable terminals for power and data Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops
Suspended Weight (kg)(1)
1 BBA14LFC 25 A left 1·22 1 BBA14RFC 25 A right 1·49 1 CCA14LFC 40 A left 1·27 1 CCA14RFC 40 A right 1·49
Surface mounted Weight (kg)(1)
1 BBA34LFC 25 A left 1·31 1 BBA34RFC 25 A right 1·54 1 CCA34LFC 40 A left 1·31 1 CCA34RFC 40 A right 1·54
Centre feed Weight (kg)(1)
1 BBA44FC 25 A 1·8 1 CCA44FC 40 A 1·8
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
LN
PE
C
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
CCA14LFC
CCA14RFC CCA142XC
CCA3145C
CCA2145C
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
LTK_Bro_028_029 v3.indd 28 23/08/2012 13:58
Electrak® 30 2P + E buscom trunkingpower and communication distribution
29
Pack Cat. Nos. Electrak 30 2 P + E + comms – double sided system
2P + E buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versions Socket outlets are colour coded white and are located on both sides of the bar The comms circuit is only available on one side of the bar as shown in the diagram below
2P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBA3245C 3 11 4·85 1 BBA2245C 2 7 3·52 1 BBA3241C 3 6 4·70 1 BBA2241C 2 4 3·47 40 A 1 CCA3245C 3 11 5·05 1 CCA2245C 2 7 3·65 1 CCA3241C 3 6 4·96 1 CCA2241C 2 4 3·61
Feed units for double sided system
Double sided feed units come with 2 x 25 mm Ø cable entry holes for each side of the bar, plus a further 2 x 16 mm Ø. holes for the comms side of the bar
Single screw cable terminals are provided for power and data. Supplied with end stops
Suspended Weight(kg)(1)
1 BBA24LFC 25 A left 1·29 1 BBA24RFC 25 A right 1·51 1 CCA24LFC 40 A left 1·39 1 CCA24RFC 40 A right 1·61
Flexible lengths for double sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left Length Rating Weight (m) (A) (kg)(1)
1 BBA240XC 0·5 25 3·14 1 BBA242XC 2 25 3·67 1 CCA240XC 0·5 40 3·25 1 CCA242XC 2 40 3·91
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
L
N
PE
PE
N
L
C
Pack Cat. Nos. Tap-off units with and without comms
Power only tap-offs can plug into any tap-off outlet Tap-offs with comms can only be plugged into the comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick-up L1+N, colour coded white
Length Fixed Weight (m) polarity (kg)(1)
1 DDE408C 0·8 0·2 1 DDE42C 2 0·4 1 DDE43C 3
L + N 0·5
1 DDE45C 5 0·7
13 A fused tap-off units
Pre-wired tap-off units to pick-up L1+N, supplied with BS 1362 fuse, colour coded white
Length Fixed Weight (m) polarity (kg)(1)
1 DDE408FC 0·8 0·2 1 DDE42FC 2 0·4 1 DDE43FC 3
L + N 0·5
1 DDE45FC 5 0·7
Tap-off units without comms – rewirable
16 A unfused tap-off unit
Rewirable tap-off unit to pick-up L1+N, colour coded white, can plug into any tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDF4 L + N 0·14
13 A fused tap-off unit
Rewirable tap-off unit to pick-up L1+N, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDF4F L + N 0·14
DDF4F
CCA3245C
CCA2245C
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5C = Tap-off with communications circuit
For power only, remove the C
DDE45CDDE45
LTK_Bro_028_029 v3.indd 29 22/08/2012 16:18
Electrak® 31 3P + E buscom trunkingpower and communication distribution
30
Pack Cat. Nos. Flexible lengths for single sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBB140XC 0·5 25 3·04
1 BBB142XC 2 25 3·40
1 CCB140XC 0·5 40 3·08
1 CCB142XC 2 40 3·56
Surface mounted – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBB340XC 0·5 25 2·99
1 BBB342XC 2 25 3·32
1 CCB340XC 0·5 40 3·00 1 CCB342XC 2 40 3·48
Pack Cat. Nos. Electrak 31 3P + E – single sided system
3P + E buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versions Socket outlets are colour coded white and are located on just one side of the bar
3P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBB3145C 3 6 4·62 1 BBB2145C 2 4 3·37 1 BBB3141C 3 3 4·58 1 BBB2141C 2 2 3·34 40 A 1 CCB3145C 3 6 4·77 1 CCB2145C 2 4 3·47 1 CCB3141C 3 3 4·73 1 CCB2141C 2 2 3·44
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and 2 x 16 mm Ø cable entry holes and single screw cable terminals for power and data Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops
Suspended Weight (kg)(1)
1 BBB14LFC 25 A left 1·25 1 BBB14RFC 25 A right 1·48 1 CCB14LFC 40 A left 1·33 1 CCB14RFC 40 A right 1·55
Surface mounted Weight (kg)(1)
1 BBB34LFC 25 A left 1·29 1 BBB34RFC 25 A right 1·52 1 CCB34LFC 40 A left 1·37 1 CCB34RFC 40 A right 1·59
Centre feed Weight (kg)(1)
1 BBB44FC 25 A 1·8 1 CCB44FC 40 A 1·8
Integral communication bus suitable for KNX, Lonworks, DALI, protocols etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
L 2
L1
N
PE
C
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
CCB14LFC
CCB14RFC CCB142XC
CCB3145C
CCB2145C
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
LTK_Bro_030_031 v3.indd 30 23/08/2012 14:05
Electrak® 31 3P + E buscom trunkingpower and communication distribution
31
Pack Cat. Nos. Electrak 31 3P + E – double sided system
3P + E buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versions Socket outlets are colour coded white and are located on both sides of the bar The comms circuit is only available on one side of the bar as shown in the diagram below
3P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBB3245C 3 11 5·15 1 BBB2245C 2 7 3·72 1 BBB3241C 3 6 5·06 1 BBB2241C 2 4 3·68 40 A 1 CCB3245C 3 11 5·45 1 CCB2245C 2 7 3·92 1 CCB3241C 3 6 5·36 1 CCB2241C 2 4 3·88
Feed units for double sided system
Double sided feed units come with 2 x 25 mm Ø cable entry holes for each side of the bar, plus a further 2 x 16 mm Ø. holes for the comms side of the bar. Single screw cable terminals are provided for power and data
Suspended Weight (kg)(1)
1 BBB24LFC 25 A left 1·35 1 BBB24RFC 25 A right 1·58 1 CCB24LFC 40 A left 1·49 1 CCB24RFC 40 A right 1·72
Flexible lengths for double sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left Length Rating Weight (m) (A) (kg)(1)
1 BBB240XC 0·5 25 3·45 1 BBB242XC 2 25 4·03 1 CCB240XC 0·5 40 3·53 1 CCB242XC 2 40 4·35
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos. Tap-off units with and without comms
Power only tap-offs can plug into any tap-off outlet Tap-offs with comms can only be plugged into the comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up L1, L2+N, colour coded white
Length Fixed Weight (m) polarity (kg)(1)
1 DDE408C 0·8 0·2 1 DDE42C 2 0·4 1 DDE43C 3
L + N 0·5
1 DDE45C 5 0·7
1 DDG408C 0·8 0·2 1 DDG42C 2 0·4 1 DDG43C 3
L1 + L2 + N 0·5
1 DDG45C 5 0·7
13 A fused tap-off units
Pre-wired tap-off units to pick-up L1, L2+N, supplied with BS 1362 fuse, colour coded white
Length Fixed Weight (m) polarity (kg)(1)
1 DDE408FC 0·8 0·2 1 DDE42FC 2 0·4 1 DDE43FC 3
L + N 0·5
1 DDE45FC 5 0·7
1 DDG408FC 0·8 0·2 1 DDG42FC 2 0·4 1 DDG43FC 3
L1 + L2 + N 0·5
1 DDG45FC 5 0·7
Tap-off units without comms – rewirable
16 A unfused tap-off unit
Rewirable tap-off units colour coded white, can plug into any tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDF4 L + N 0·14 1 DDH4 L1 L2 N1 0·14
13 A fused tap-off unit
Rewirable tap-off units supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDF4F L + N 0·14 1 DDH4F L1 L2 N1 0·14
L2
L1
N
PE
PE
N
L1
L2
C
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
DDH4F
CCB3245C
CCB2245C
(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5C = Tap-off with communications circuit. For power only, remove the C
DDE45DDE45C
LTK_Bro_030_031 v3.indd 31 22/08/2012 16:20
Electrak® 32 4P + E (dual circuit) buscom trunkingpower and communication distribution
32
Pack Cat. Nos. Flexible lengths for single sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBC140XC 0·5 25 3·17
1 BBC142XC 2 25 3·59
1 CCC140XC 0·5 40 3·22 1 CCC142XC 2 40 3·79
Surface mounted – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBC340XC 0·5 25 3·09
1 BBC342XC 2 25 3·51 1 CCC340XC 0·5 40 3·14 1 CCC342XC 2 40 3·71
Pack Cat. Nos. Electrak 32 4P + E (dual circuit) – single sided system
Dual circuit buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versionsSocket outlets are colour coded white and are located on just one side of the bar
4 P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBC3145C 3 6 4·77 1 BBC2145C 2 4 3·47 1 BBC3141C 3 3 4·73 1 BBC2141C 2 2 3·44 40 A 1 CCC3145C 3 6 4·97 1 CCC2145C 2 4 3·61 1 CCC3141C 3 3 4·93 1 CCC2141C 2 2 3·58
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and 2 x 16 mm Ø cable entry holes and single screw cable terminals for power and data Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops
Suspended Weight (kg)(1)
1 BBC14LFC 25 A left 1·29 1 BBC14RFC 25 A right 1·52 1 CCC14LFC 40 A left 1·38 1 CCC14RFC 40 A right 1·61
Surface mounted Weight (kg)(1)
1 BBC34LFC 25 A left 1·33 1 BBC34RFC 25 A right 1·56 1 CCC34LFC 40 A left 1·42 1 CCC34RFC 40 A right 1·65
Centre feed Weight (kg)(1)
1 BBC44FC 25 A 1·8 1 CCC44FC 40 A 1·8
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
CL2
N2
L1
N1
PE
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
CCC14LFC
CCC14RFC CCC142XC
CCC3145C
CCC2145C
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
LTK_Bro_032_033 v3.indd 32 23/08/2012 14:06
Electrak® 32 4P + E (dual circuit) buscom trunkingpower and communication distribution
33
Pack Cat. Nos. Electrak 32 4P + E (dual circuit) – double sided system
Dual circuit buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versionsSocket outlets are colour coded white and are located on both sides of the bar The comms circuit is only available on one side of the bar as shown in the diagram below
4 P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBC3245C 3 11 5·46 1 BBC2245C 2 7 3·92 1 BBC3241C 3 6 5·37 1 BBC2241C 2 4 3·88 40 A 1 CCC3245C 3 11 5·86 1 CCC2245C 2 7 4·70 1 CCC3241C 3 6 5·77 1 CCC2241C 2 4 4·15
Feed units for double sided system
Double sided feed units come with 2 x 25 mm Ø cable entry holes for each side of the bar, plus a further 2 x 16 mm Ø. holes for the comms side of the bar. Single screw cable terminals are provided for power and data Supplied with end stops
Suspended Weight (kg)(1)
1 BBC24LFC 25 A left 1·42 1 BBC24RFC 25 A right 1·64 1 CCC24LFC 40 A left 1·60 1 CCC24RFC 40 A right 1·83
Flexible lengths for double sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left Length Rating Weight (m) (A) (kg)(1)
1 BBC240XC 0·5 25 3·42 1 BBC242XC 2 25 4·52 1 CCC240XC 0·5 40 3·91 1 CCC242XC 2 40 5·32
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos. Tap-off units with and without comms
Power only tap-offs can plug into any tap-off outlet Tap-offs with comms can only be plugged into the comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up L1+N1 or L2+N2, colour coded white
Length Fixed Weight (m) polarity (kg)(1)
1 DDE408C 0·8 0·2 1 DDE42C 2 0·4 1 DDE43C 3
L1 + N1 0·5
1 DDE45C 5 0·6 1 DDJ408C 0·8 0·2 1 DDJ42C 2 0·4 1 DDJ43C 3
L2 + N2 0·5
1 DDJ45C 5 0·6
13 A fused tap-off units
Pre-wired tap-off units to pick up L1+N1 or L2+N2, supplied with BS 1362 fuse, colour coded white
Length Fixed Weight (m) polarity (kg)(1)
1 DDE408FC 0·8 0·2 1 DDE42FC 2 0·4 1 DDE43FC 3
L1 + N1 0·5
1 DDE45FC 5 0·6 1 DDJ408FC 0·8 0·2 1 DDJ42FC 2 0·4 1 DDJ43FC 3
L2 + N2 0·5
1 DDJ45FC 5 0·6
Tap-off units without comms – rewirable
16 A unfused tap-off units
Rewirable tap-off units to pick up required circuit, colour coded white, can plug into any tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDF4 L1 + N1 0·14 1 DDK4 L2 + N2 0·14
13 A fused tap-off units
Rewirable tap-off units to pick up required circuit, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDF4F L1 + N1 0·14 1 DDK4F L2 + N2 0·14
CL2
N2
L1
N1
PE
N1
L1
N2
L2
PE
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
DDK4F
CCC3245C
CCC2245C
(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5C = Tap-off with communications circuit. For power only, remove the C
DDJ45CDDJ45
LTK_Bro_032_033 v3.indd 33 22/08/2012 16:21
Electrak® 33 4P + E (3 phase) buscom trunkingpower and communication distribution
34
Pack Cat. Nos. Flexible lengths for single sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBD140XC 0·5 25 3·17 1 BBD142XC 2 25 3·59 1 CCD140XC 0·5 40 3·22 1 CCD142XC 2 40 3·79
Surface mounted – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBD340XC 0·5 25 3·09 1 BBD342XC 2 25 3·51 1 CCD340XC 0·5 40 3·14 1 CCD342XC 2 40 3·71
Pack Cat. Nos. Electrak 33 4P + E (3 phase) – single sided system
3 phase buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versionsSocket outlets are colour coded grey and are located on just one side of the bar
4 P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBD3145C 3 6 4·77 1 BBD2145C 2 4 3·47 1 BBD3141C 3 3 4·75 1 BBD2141C 2 2 3·44 40 A 1 CCD3145C 3 6 4·97 1 CCD2145C 2 4 3·61 1 CCD3141C 3 3 4·93 1 CCD2141C 2 2 3·58
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and 2 x 16 mm Ø cable entry holes and single screw cable terminals for power and data Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops
Suspended Weight (kg)(1)
1 BBD14LFC 25 A left 1·29 1 BBD14RFC 25 A right 1·52 1 CCD14LFC 40 A left 1·38 1 CCD14RFC 40 A right 1·61
Surface mounted Weight (kg)(1)
1 BBD34LFC 25 A left 1·33 1 BBD34RFC 25 A right 1·56 1 CCD34LFC 40 A left 1·42 1 CCD34RFC 40 A right 1·65
Centre feed Weight (kg)(1)
1 BBD44FC 25 A 1·80 1 CCD44FC 40 A 1·80
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
L3
L2
L1
N1
PE
C
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
CCD14LFC
CCD14RFC CCD142XC
CCD3145C
CCD2145C
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
LTK_Bro_034_036 v2.indd 34 23/08/2012 14:07
Electrak® 33 4P + E (3 phase) buscom trunkingpower and communication distribution
35
Pack Cat. Nos. Electrak 33 4P + E (3 phase) – double sided system
3 phase buscom trunking system with integral communications bus circuit available in IP 4X and IP 54 versionsSocket outlets are colour coded grey and are located on both sides of the bar The comms circuit is only available on one side of the bar as shown in the diagram below
4 P + E trunking lengths
Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets
Length Tap-off Weight 25 A (m) outlets (kg)(1)
1 BBD3245C 3 11 5·46 1 BBD2245C 2 7 3·92 1 BBD3241C 3 6 5·37 1 BBD2241C 2 4 3·88 40 A 1 CCD3245C 3 11 5·86 1 CCD2245C 2 7 4·70 1 CCD3241C 3 6 5·77 1 CCD2241C 2 4 4·15
Feed units for double sided system
Double sided feed units come with 2 x 25 mm Ø cable entry holes for each side of the bar, plus a further 2 x 16 mm Ø. holes for the comms side of the bar. Single screw cable terminals are provided for power and data
Suspended Weight (kg)(1)
1 BBD24LFC 25 A left 1·42 1 BBD24RFC 25 A right 1·64 1 CCD24LFC 40 A left 1·60 1 CCD24RFC 40 A right 1·83
Flexible lengths for double sided system
Flexible lengths can be used to change direction, change level or overcome obstructions
Suspended – right to left
Length Rating Weight (m) (A) (kg)(1)
1 BBD240XC 0·5 25 3·42 1 BBD242XC 2 25 4·52 1 CCD240XC 0·5 40 3·91 1 CCD242XC 2 40 5·32
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos. Tap-off units
Power only tap-offs can plug into any tap-off outlet of the 3 phase bar Tap-offs with comms can only be plugged into the comms side of the 3 phase bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up required circuit, colour coded grey
Length Fixed Weight (m) polarity (kg)(1)
1 DDM408L1C 0·8 0·2 1 DDM42L1C 2 0·4 1 DDM43L1C 3
L1 + N 0·5
1 DDM45L1C 5 0·6
1 DDM408L2C 0·8 0·2 1 DDM42L2C 2 0·4 1 DDM43L2C 3
L2 + N 0·5
1 DDM45L2C 5 0·6
1 DDM408L3C 0·8 0·2 1 DDM42L3C 2 0·4 1 DDM43L3C 3
L3 + N 0·5
1 DDM45L3C 5 0·6
13 A fused tap-off units
Pre-wired tap-off units to pick up required circuit, supplied with BS 1362 fuse, colour coded grey, can plug into any Electrak 33 tap-off outlet
Length Fixed Weight (m) polarity (kg)(1)
1 DDM408L1FC 0·8 0·2 1 DDM42L1FC 2 0·4 1 DDM43L1FC 3
L1 + N 0·5
1 DDM45L1FC 5 0·6
1 DDM408L2FC 0·8 0·2 1 DDM42L2FC 2 0·4 1 DDM43L2FC 3
L2 + N 0·5
1 DDM45L2FC 5 0·6
1 DDM408L3FC 0·8 0·2 1 DDM42L3FC 2 0·4 1 DDM43L3FC 3
L3 + N 0·5
1 DDM45L3FC 5 0·6
N
L1
L2
L3
L3
L2
L1
N
PE
PE
C
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
DDM408L1C DDM408L1
CCD3245C
CCD2245C
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5C = Tap-off with communications circuit. For power only, remove the C
LTK_Bro_034_036 v2.indd 35 22/08/2012 16:22
36
Electrak® 33 4P + E (3 phase) buscom trunkingpower and communication distribution
Pack Cat. Nos. Tap-off units without comms – rewirable
16 A unfused tap-off units
Rewirable tap-off units to pick up required circuit, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDN4L1 L1 + N 0·14 1 DDN4L2 L2 + N 0·14 1 DDN4L3 L3 + N 0·14
13 A fused tap-off units
Rewirable tap-off units to pick up required circuit, supplied with BS 1362 fuse, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDN4L1F L1 + N 0·14 1 DDN4L2F L2 + N 0·14 1 DDN4L3F L3 + N 0·14
Phase selectable tap-off units without comms 2P + E terminals – rewirable
16 A unfused tap-off unit
Rewirable tap-off units, phase selectable, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDP4S L + N 0·14
13 A fused tap-off unit
Rewirable tap-off units, phase selectable, supplied with BS 1362 fuse, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed Weight polarity (kg)(1)
1 DDP4SF L + N 0·14
Selection chart (p. 24-27)Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos. Tap-off units without comms –4P + E pre-wired (LSOH 5 x 1·5 mm2 cable)
16 A unfused tap-off units
Pre-wired tap-off units to pick up required circuit, colour coded grey, can plug into any Electrak 33 tap-off outlet
Length Fixed Weight (m) polarity (kg)(1)
1 DDR408 0·8 L + L + L + N 0·20 1 DDR42 2 L + L + L + N 0·36 1 DDR43 3 L + L + L + N 0·50 1 DDR45 5 L + L + L + N 0·63
DDR43DDN4L1F
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
LTK_Bro_034_036 v2.indd 36 23/08/2012 14:08
Electrak® buscom trunkingfixings and ancillary items
37
Pack Cat. Nos. Fixings
1 EEA304 Trunking 57 mm edge surface mounting fixing bracket
1 EEA308 Trunking suspended fixing bracket
1 EEA312 Trunking suspended fixing bracket c/w cable duct stirrup. Used when running cable duct on top of buscom trunking
1 EEA324 Luminaire suspension fixing bracket
1 EEA328 Luminaire 45 mm edge suspension fixing bracket (clip on)
1 EEA332 Luminaire 57 mm edge suspension fixing bracket (clip on)
1 EEB340 Open hook luminaire suspended bracket
1 EEB344 Closed ring on luminaire
1 EEC348 Cable duct 3 m long x 50 mm(w) x 13 mm(h)
1 EEC357 Joint bracket cable duct
1 EEC352 Cable duct fixing bracket
Pack Cat. Nos. Ancillary items
1 EEC356 2 m empty length for adjusting the length at the end of a run (to be cut)
1 EEC360 IP 54 outlet cover (spare or replacement)
1 EEC364 Joint sleeve is used if load is hung off trunking joint or near when joint is centre of a fixing span
1 EEC366 Left hand end stop spare
1 EEC368 Right hand end stop spare
Dimensions and technical information (p. 41)
Brackets are manufactured from robust galvanised steel, ensuring that the entire installation can be expected to stand up to all normal site conditions
EEA304
EEA308
EEA324
EEA312
EEA328 EEA332
EEB340 EEB344EEC356
EEC348
EEC360EEC352 EEC364
LTK_Bro_037 v2.indd 37 22/08/2012 16:24
Electrak® buscom trunkingtechnical information
25 A rated - max. conductor size 6 mm2
40 A rated - max. conductor size 16 mm2
Double sided trunking feed units have power cable terminals on both sides.IP 4X galvanised steel IP 54 ABS
Comms busMax. conductor size 1·5 mm2
Red + Black -
2 pole + earth + comms
n Feed units
Track lengths simply push fit together
Electrak buscom trunking can be used with Electrak’s cost effective lighting control system, Lightrak KNX, or any other systems using control protocols such as KNX, Lonworks, DALI, etc.Electrak’s overhead trunking couples high quality engineering with rigidity of design, and provides power for a variety of applications including lighting, heating and ventilation. The robust easy fix modular system permits loads to be suspended directly from the trunking using Electrak’s various fixing brackets Push fit connection keeps installation costs to a minimum
38
Direct protection by enclosure. Indirect protection by protective circuit
Electrical test data
Derating factor for Electrak 32 single sided – 0·8 –
Derating factor for Electrak 32 double sided 0·8 0·7 –
Derating factor for Electrak 33 double sided – 0·8 –
Rated operational voltage (Ue) 230/400 230/400 V±
Rated insulation voltage (Ui) 500 500 V±
Frequency (f) 50/60 50/60 Hz
Rated impulse withstand voltage 4·0 4·0 KV
Busbar resistance (R20) 3·9 2·7 mΩ/m
Resistance (R1) 4·2 3·0 mΩ/m
Impedance (Z1) 4·8 3·4 mΩ/m
Reactance (X1) 2·5 1·6 mΩ/m
Protective conductor 1·5 1·5 mΩ/m
UOM 25 A 40 A
Volt drops
Live and neutral : busbars 9·0 6·0 mV/A/m
(R1+R2) Feed unit 3·0 2·4 mV/A
Tap-off 0·8 m 22·0 22·0 mV/A
Tap-off 2·0 m 52·0 52·0 mV/A
Flexible length assembly 0·5 m 5·0 3·5 mV/A
Flexible length assembly 2 m 20·0 14·0 mV/A
UOM 25 A 40 A
Earth fault loop
Impedance : busbar 4·5 3·0 mΩ/m
Earth housing 1·5 1·5 mΩ/m
Feed unit 2·4 2·4 mΩTap-off 0·8m 23·0 23·0 mΩTap-off 2·0m 53·0 53·0 mΩFlexible length assembly 0·5 m 2·5 1·75 mV/A
Flexible length assembly 2 m 10·0 7·0 mV/A
Rated conditional short-circuit current (Icc) 16·0 16·0 KA
Rated short time withstand current (Icw) at 1 sec 0·65 1·0 KA
Rated peak short-circuit current (Ipk) 0·975 1·5 KA
Ambient temperature 35·0 35·0 ˚C
UOM 25 A 40 A
Mechanical data UOM
Number of conductors 2-10 2-10 –
Busbar conductor cross sectional area 4·0 6·0 mm2
Cable terminal capacity 6·0 16·0 mm2
Cable terminal capacity bus 1·5 1·5 mm2
Tap-off cable 16 A 1·5 1·5 mm2
Tap-off cable 13 A fused 1·5 1·5 mm2
Tap-off entry 16·0 16·0 mmØ
Feed unit entry holes power 25·0 25·0 mmØ
Feed unit entry holes bus 16·0 16·0 mmØ
IP rating (optional) 4 X (54) 4 X (54) –
25 A 40 A
n Standards
n Buscom trunking options
• L2 • L3
• L2 • N2 • L2
• L • L1 • L1 • L1
• N • N • N1 • NPE PE PE PE Communication bus
ASTA approved to BS EN 60439-2 and IEC 439-2Manufactured within an approved ISO 9001 : 2008 facilityAssessed Quality Assurance Certificate No. 10679Electrak fully complies with the requirements of BS 7671 : 2008 (IEE Wiring Regulations)
LTK_Bro_038_043 v3.indd 38 22/08/2012 16:27
Electrak® buscom trunkingtechnical data
39
Fixing distance (m) 1·5 2 2·5 3 3·5 4
Max. point load (deflection = 1/500 x span) (Kg) 20 17 13 12 9 7
Max. distributed load (deflection = 1/500 x span) (Kg) 33 28 22 20 15 12
Max. point load (deflection = 1/350 x span) (Kg) 33 24 18 16 10 9
Max. distributed load (deflection = 1/350 x span) (Kg) 55 40 30 26 16 15
Average ambient air temperature 25˚C 30˚C 35˚C 40˚C 45˚C 50˚C
Rating factor (K1) 1·1 1·05 1 0·95 0·90 0·85
Fixing distance in metres (m) 1·5 2 2·5 3 3·5 4
Max. point load (deflection = 1/500 x span) (Kg) 10 6 4·5 4 3·5 3
Max. distributed load (deflection = 1/500 x span) (Kg) 16 10 7·5 7 6 5
Max. point load (deflection = 1/350 x span) (Kg) 13 10 7 6 5 0
Max. distributed load (deflection = 1/350 x span) (Kg) 20 16 11 10 8 0
Communication control circuit
Type Bus cable (LSOH)
Construction Sheathed 0·5 mm2 copper twisted pair
Insulation - conductor Flame retardant low emission HCL
Sheath LSOH material
Rated insulation voltage (Ui) (between power circuit and bus) 500 V
Max. bus operating voltage 50 V
Max. bus operating current 0·65 A
Max. conductor resistance (@20˚C) 73·2 Ω/km
Max. mutual capacitance 100 nf/km
Material specifications
Buscom trunking housing Galvanised steel
Busbars High conductivity copper
Busbar insulator Flame retardant LSOH to BS 7211
Trunking connector / tap-off entry box / cable connector Flame retardant polycarbonate
Tap-off housing Flame retardant polycarbonate
Trunking connector blades / tap-off blades Copper
Feed unit IP 4X Galvanised steel
Feed unit IP 54 ABS
Flexible length conduit Flame retardant LSOH nylon
Feed unit terminals / earth block Brass
Brackets Galvanised steel
13 A tap-off, fuse To BS 1362, ASTA approved
DurabilityElectrak power and communications distribution systems are well designed and extremely robust. They can be expected to stand up to all normal site conditions Electrak has been short circuit strength tested by ASTA
Earth fault loop impedanceBS 7671 : 2008 IEE Wiring Regulations require accurate determination of the total earth loop impedance, which must be sufficiently low to allow the protective device to operate within the specified time, which for socket outlets is 0·4 seconds The values relevant to Electrak for calculating the earth fault loop impedance are shown in the electrical test data table, see opposite
Buscom trunking rating in ambient temperatures
For ambient temperatures other than 35˚C apply the multiplier factor K1 to the rated current
Buscom trunking mechanical loadingFor point loads and evenly distributed loads the maximum weight that can be supported is given below
Maximum loading for suspended buscom trunking
Maximum loading for surface mounted buscom trunking
Notes
1. Where trunking joints occur in the middle of the suspension span, and weight is to be suspended from that point, it is recommened to use a strenghting bracket EEC364 over the joint to stop deflection
2. If the load requirements exceed the above figures, please contact us on +44 (0) 845 600 6266 For design information and technical specification, please contact us on +44 (0) 845 600 6266 Suspension rods and fixings should be of suitable size to carry the weight of both the track and suspended load
LTK_Bro_038_043 v3.indd 39 22/08/2012 16:27
Electrak® buscom trunkingdimensions
40
n Fixing dimensions
220 195·5
195·5
500 500 500 500 500 304·5
3 000
195·5 1 000 1 000
220 500 500 500 304·5
2 000
195·5 1 000 804·5
804·5
32
45
57
209 308
517
220 209
429
57
220 32010
148
10452
52
148
220 308
828
300
57
0·5 m outlet spacings
0·5 m outlet spacings
0·5 m outlet spacings
0·5 m outlet spacings
2 x 25 Ø
2 x 25 Ø
4 x 25 Ø2 x 25 Ø
(
218
2 x 16 Ø
2 x 16 Ø
2 x 16 Ø 2 x 16 Ø
All dimensions (mm) are nominal
Buscom trunking 3 m
Buscom trunking 2 m
Feed unit – left
End stop – right
Centre feed – front view
End stop – left Surface feed unit – end view
Feed unit – right
End view both have 2 x 16 mm holes extra in comms feed
Double sided system
Single sided system
Buscom trunking End view
Suspended feed unit
LTK_Bro_038_043 v3.indd 40 22/08/2012 16:28
41
Tap-off
fuse removal
Fuse holder
96
68
136
68
107
927·5 7·5
30
57
60
7Ø 7 Ø
7 Ø
15
82 21
38
16
3
14
1
12
8·5 Ø
8·5 Ø
38 21
82
99
·7
94
·5
12
8·5 Ø
8.5 Ø22
60 35
30 6 Ø 6 Ø
70
13
78 30
39 6 Ø 6 Ø
53
·5
8·5
1277
50
95
59
3513
70
M5
70
M5
82 21
38
13
0
12
5
10
8
128·5 Ø
8·5 Ø
Cat. No. EEA304 Surface trunking fixing bracket with trunking clipped in
Cat. No. EEA308 Suspended trunking fixing bracket
Cat. No. EEA312 Suspended trunking fixing bracket cable duct stirrup
Cat. No. EEC352 Cable duct fixing bracket
Cat. No. EEA324 Luminaire suspended fixing bracket
Cat. No. EEA328 Luminaire 45 mm edge suspension fixing bracket
Cat. No. EEA332 Luminaire 57 mm edge suspension fixing bracket
Pre-wired tap-offs – 33 mm deep
Fused tap-off
Rewirable and phase selection tap-offs – 35 mm deep
Cat. No. EEB344 Closed ring hook
Cat. No. EEB340 Open hook
All dimensions (mm) are nominal
LTK_Bro_038_043 v3.indd 41 22/08/2012 16:28
Electrak® buscom trunkinginstallation
42
EEA312
EEB344EEC352 Cable duct bracket
Ensure surface is level. Screw fix through both fixing holes of surface fixing brackets to surface with No. 8 fixing screws Hook trunking into place and push fit to close
Suspended trunking fixing brackets
Calculate the distance between fixing brackets - the maximum fixing distance should not exceed 4 m. If loads are to be hung, please consult loading charts on page 39. The maximum buscom trunking weight is 2 kg/m When fixing brackets to drop rods or surfaces, see mounting details below
EEA304 57 mm Edge surface fixing bracket
Surface mounted trunking fixing brackets
2
1
Considerations before installation
Considerations before installation
Cable duct clips into bracket
When using cable duct along trunking
Electrak’s buscom trunking system comprises continuous lengths of galvanised steel trunking available in 2 m and 3 m lengths with integral connectors and regular tap-off outlets on one or both sides
Each trunking run commences with a feed unit for electrical and comms bus cable termination. The connection between the trunking, the feed unit and subsequent trunking lengths is push fit and requires no tools to terminate the connection or ensure good earthing. Each complete track run is finished with an end stop. Flexible lengths can be used to overcome obstructions or used as corners where required
The trunking system is available with IP 4X or IP 54 ingress protection, fully factory tested and ASTA approved to BS EN 60439-2 : 2008
1
2
Buscom trunking lengths
2
2
1
2
1
End stop
Left feed unit
To install - push fit parts together
To take apart - use a screwdriver to depress the locking catch
1
2
Push fit connection
Push in to release
1
n Design and installation
EEA308
LTK_Bro_038_043 v3.indd 42 22/08/2012 16:28
43
EEA324 Luminaire fixing brackets
EEA328 45 mm Edge luminaire fixing brackets (maximum load 5 kg)
EEA332 57 mm Edge luminaire fixing bracket (maximum load 5 kg)See maximum loading charts p. 39
Luminaire mounting fixing brackets : surface trunking
Luminaire mounting fixing brackets : suspended trunking
EEB344
EEA304
EEA332
EEA304
EEA332
EEB340
All dimensions (mm) are nominal
LTK_Bro_038_043 v3.indd 43 22/08/2012 16:29
Lig
htr
ak
lig
hti
ng
co
ntr
ol
gu
ide
09
/20
12
. 3
.5KHead office (UK and Ireland):
Legrand Electric LimitedGreat King Street North, Birmingham, B19 2LFTel: 0870 608 9000 Fax: 0870 608 9004Website: www.legrand.co.uk
The Legrand logo is a registered trademark of the Legrand group of companies.
Distributor:
This document is printed on sustainably sourced paper. Please recycle.
Contact details
Quotations and Technical Support: The Power Distribution Division of Legrand Electric Ltd. Great King Street North, Birmingham, B19 2LF
Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6760
E-mail: [email protected]
Customer Services: The Power Distribution Division of Legrand Electric Ltd. No. 1 Industrial Estate Medomsley Road, Consett, County Durham, DH8 6SR
Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6366
E-mail: [email protected]
Accounts: Legrand Electric Ltd. Great King Street North, Birmingham, B19 2LF
Tel: +44 (0) 870 608 9000 Fax: +44 (0) 870 608 9004
LTK_Bro_Covers v1.indd 2 29/08/2012 12:21