equipment at hps
TRANSCRIPT
-
7/31/2019 Equipment at HPS
1/60
Electro-mechanical Equipment
in Hydro Power Station
-
7/31/2019 Equipment at HPS
2/60
Main Electro-Mechanical Equipments
Turbine MIV (Spherical Valve)/Butterfly Valve Governing System
Mechanical Auxiliaries like Cooling water system, drainage
dewatering system, Fire fighting system HVAC etc. Generator Electrical Auxiliaries like Bus Duct, LT/HT switchgears, DC
battery system, earthing, cabling, Station/Auxiliary Transformer etc. Generator Transformers
Switchyard and Pot head yard XLPE Cables/Tie line Control and Instrumentation Systems( SCADA)
-
7/31/2019 Equipment at HPS
3/60
Hydraulic Turbines
Hydraulic Turbines
Impulse Turbine Reaction Turbine
Pelton Turbine Francis Turbine
Propeller Turbine
Kaplan Turbine
Bulb Turbine
Deriaz Turbine
-
7/31/2019 Equipment at HPS
4/60
Types of Hydraulic Turbines
Reaction Turbines Derive power from pressure drop across turbine
Totally immersed in water
Angular & linear motion converted to shaft power Propeller, Francis, and Kaplan turbines
Impulse Turbines Convert kinetic energy of water jet hitting buckets
No pressure drop across turbines
Pelton, Turgo, and crossflow turbines
-
7/31/2019 Equipment at HPS
5/60
Pelton Turbine
-
7/31/2019 Equipment at HPS
6/60
PELTON ARRANGEMENT
-
7/31/2019 Equipment at HPS
7/60
Francis Turbine
Runner
Spiral CasingSectional View
-
7/31/2019 Equipment at HPS
8/60
Kaplan Turbine
-
7/31/2019 Equipment at HPS
9/60
Deriaz Turbine
-
7/31/2019 Equipment at HPS
10/60
Spiral case and wicket gates/Nozzles- to direct and control the
water entering the turbine runner. The spiral case is a steel-linedconduit connected to the penstock or intake conduit, and itdistributes flow uniformly into the turbine. Wicket gates areadjustable vanes that surround the turbine runner entrances andthey control the area available for water to enter the turbine.
-
7/31/2019 Equipment at HPS
11/60
SELECTION CRITERIA FOR TYPE OF HYDROTURBINE
Depends mainly on:
Head availableSpecific Speed
Impulse Turbine :- Pelton Wheel turbine for Head>300m
Reaction Turbine:- Francis Turbine for Head 30m to 400mKaplan Turbine for Head 10m to 60m
Bulb/Tubular Turbine Head 3 to 30m
In the overlapping zone of head more detailed analysis is required fromtechno-economic considerations.
-
7/31/2019 Equipment at HPS
12/60
Overlapping Regionbetween Francis
and Pelton Turbine
TapovanVishnugad,Head-494,
Francis Sp.Speed-78
LoharinagPala. Head-438, FrancisSp. Speed-
85.3
LoharinagPala. Head-438, PeltonSp. Speed-
56
TapovanVishnugad,Head-494,Pelton Sp.Speed-54.6
Figure 1: Selection of
turbines; Head vs
Specific Speed (Ns)
(Source:IS:12837:1989)
-
7/31/2019 Equipment at HPS
13/60
Turbines of NTPC Projects
PROJECT TYPE OF TURBINE
Koldam(4X200 MW) Francis
Loharinag Pala(4X150 MW) Pelton
Tapovan Vishnugad(4X130 MW) Pelton
Lata-Tapovan(3X57 MW) Francis
Rammam Pelton
-
7/31/2019 Equipment at HPS
14/60
Main Inlet Valve
Main inlet valves at the inlet of the turbine areinstalled to isolate the flow in case ofmaintenance and emergency .
Spherical ValveGenerally used as Main Inlet Valve for high headinstallation in case of the Pelton type of turbine (In LNP&TVN)
Butterfly valveGenerally used as Main Inlet Valve for medium headinstallation in case of the Francis type of turbine (InKoldam) and as Penstock valve (e.g. LNP& TVN)
-
7/31/2019 Equipment at HPS
15/60
Cross-section of Power house -LNP
-
7/31/2019 Equipment at HPS
16/60
L-section of Power house -LNP
-
7/31/2019 Equipment at HPS
17/60
MIV floor drawing -LNP
-
7/31/2019 Equipment at HPS
18/60
Governing System
It regulates the speed and the output of the Turbine-Generatorunits by controlling the position of the wicket gates (in Francis)and Nozzles (in Pelton) to adjust the water flow through theturbine.
The hydraulic turbine governor is equipment to control the guidevanes/ nozzles by detecting the turbine speed and the opening ofthe guide vane/nozzles in order to keep the turbine speed stableor to regulate its output.
Accordingly the controllability of the power station and the quality
of the electric power depends upon the performance of thegovernor.
It operates the Deflector (in Pelton) in case of sudden loadrejection to divert the water jet.
-
7/31/2019 Equipment at HPS
19/60
Contd
Main components of the Governor systemOil Pressure UnitPressure accumulatorElectro-Hydro actuatorPressurizing system
Air Pressure (40-70Kg/cm2) Nitrogen pressure (100 Kg/cm2 and above)
High pressure systems are compact as compared to the Lowpressure system.
Due to space constraints in case of underground Power house,generally high pressure system is used .KoldamAir pressure systemLNP&TVN- Nitrogen/Air High Pressure System
-
7/31/2019 Equipment at HPS
20/60
Schematic diagram of Governor
-
7/31/2019 Equipment at HPS
21/60
DEFLECTOR SERVOMOTOR
-
7/31/2019 Equipment at HPS
22/60
LINKAGE ARRANGEMENT OF
DEFLECTOR SERVOMOTOR
-
7/31/2019 Equipment at HPS
23/60
NOZZLE SERVOMOTOR
-
7/31/2019 Equipment at HPS
24/60
OIL PRESSURE UNIT
-
7/31/2019 Equipment at HPS
25/60
Mechanical Auxiliaries
Cranes
Cooling Water System & General water system
Fire Fighting system
Air conditioning and Ventilation System Drainage and dewatering system
-
7/31/2019 Equipment at HPS
26/60
Cranes
Cranes used in the hydro-power house Power house crane
Transformer house crane (in case of underground PH)
Butterfly valve house crane
Capacity of the PH crane is decided by heaviest
equipment (Generally Generator Rotor) to be lifted bythe crane.
When the weight of the heaviest equipment is veryhigh then 2 PH cranes are used in the tandem
PH Crane is one of the most important equipmentbecause it plays a major role in the erection of theequipments.
-
7/31/2019 Equipment at HPS
27/60
TF and BF valve House crane
TF hall crane is used for the erection andmaintenance of the GIS equipments.
BF valve house crane is used for the
erection and maintenance of the Butterflyvalve.
-
7/31/2019 Equipment at HPS
28/60
Cooling Water System
Water is used to cool the various equipments like Generator air cooler
Thrust bearing
Guide bearing/Shaft seal
Generator transformer
Due to heavy silt content in river water closed loopcooling system is adopted and circulating water is
cooled in Plate heat exchanger (PHE).
Koldam, LNP &TVN- closed loop cooling system.
-
7/31/2019 Equipment at HPS
29/60
Schematic diagram of CWS-LNP
-
7/31/2019 Equipment at HPS
30/60
COOLING WATER SYSTEM
-
7/31/2019 Equipment at HPS
31/60
COOLING WATER PUMPS
-
7/31/2019 Equipment at HPS
32/60
COOLING WATER FILTERS
-
7/31/2019 Equipment at HPS
33/60
Air conditioning and ventilation
system Air conditioning units (For control room , Shift
engineer room and conference room )
Ventilation Supply and Exhaust air fans Supply and return air ducts
Air Handling Units
-
7/31/2019 Equipment at HPS
34/60
Air conditioning and ventilation system- LNP
-
7/31/2019 Equipment at HPS
35/60
Fire Protection system
Fire alarm and Detection system Bymeans of Smoke detector, heat detector
Protection system
Water based Hydrant system
Medium velocity spray system
High velocity spray system
Inert gas clean agent system
Portable fire extinguisher
-
7/31/2019 Equipment at HPS
36/60
Generator
Convert the mechanical power produced by theturbine into the electrical power.
Major Components- Shaft : coupled with turbine shaft and rotates synchronously.
Rotor :series of large electromagnets that spins inside Stator.
Stator : a tightly-wound coil of copper wire around rotor.
Excitation system: sends an DC current to the rotor.
As the turbine blades turn, so do a series of magnetsinside the generator, Giant magnets (i.e. rotor) rotatepast copper coils (i.e. Stator), producing alternatingcurrent (AC).
-
7/31/2019 Equipment at HPS
37/60
A cross- sectional view of Hydroturbine-Generator Unit
-
7/31/2019 Equipment at HPS
38/60
Generator parameters Output capacity in KVA Rated speed
Rated Voltage Power factor Insulation system Reactive power capability Short Circuit Ratio (SCR) Inertia constant/Fly Wheel Effect Generator efficiency
Bearing arrangement Cooling system Excitation system
Bearing arrangement Umbrella type- Thrust bearing is placed below the rotor, a guide bearing
surrounds it . Mostly used for higher diameter and lower speed.
Semi-Umbrella type - Thrust bearing is placed below the rotor and guidebearing is installed above the rotor.
Suspended type - combined thrust bearing and guide bearing on topbracket above the rotor
-
7/31/2019 Equipment at HPS
39/60
Cooling system of Generator
Air cooling is used for large hydro generators
Cooling of the machine should be as uniformas possible.
Cooling is achieved by forced air cooling bynatural fan action of the rotor or withsupplementary motor operated cooling fans
In our design, cooling is achieved by axial fanfitted on rotor.
-
7/31/2019 Equipment at HPS
40/60
EXCITATION SYSTEM
STATIC EXCITATION SYSTEMStatic, potential source rectifier exciters are generally used for medium to large generators.They are also used for smaller generating sets, partly owing to the free choice of locationand the reduced length of the set and because of the fast-acting response to networktransients. Static potential source rectifier exciters derive the necessary electrical powerdirectly from the terminals of the generator. They consist of a power transformer, thethyristor control element, the electronic regulator and the de-excitation unit.
BRUSHLESS EXCITATION SYSTEMThe essential components of a brushless exciter system are the ac exciter machine withits rectifier bridge and the electronic regulator. Power for the voltage regulator can beprovided by a permanent magnet generator or via a transformer from the generatorterminals. The brushless exciter consists of a salient-pole synchronous generator with athree-phase winding in the rotor and a dc exciter winding in the stator. It is mounted on thegenerator shaft. At the non-driving end of the rotor is the diode carrier ring with six silicondiodes in a bridge connection.
-
7/31/2019 Equipment at HPS
41/60
Transformers
A transformer is an electrical device that takeselectricity of one voltage and changes it into another
voltage.
Type of TF used in hydro power plant Generator Transformer- It takes the low voltage Supply from the
Generator and converts it into High voltage to be transmitted to the Grid.
Unit auxiliary Transformer- It takes the supply from the generatoroutput and converts it to low voltage for the auxiliary consumption of the unit.
Station Transformer - Used to feed the equipments which are common
for the station.
-
7/31/2019 Equipment at HPS
42/60
Electrical Single Line Diagram
-
7/31/2019 Equipment at HPS
43/60
Classification based on Cooling arrangementof TF Air cooled
Water cooled
Koldam LNP
TVN
-
7/31/2019 Equipment at HPS
44/60
Switchyard
It is an interface between generating Unit andGrid.Used to evacuate the generated power to grid.
Elements of Switchyard: Bus bar Insulators
Circuit Breakers (SF6, Vacuum, Air, Gas etc.) Isolators Current Transformer (CT) Capacitive Voltage Transformer (CVT) Surge Arrestor Lightning Protection System Wave Trap
-
7/31/2019 Equipment at HPS
45/60
Types of Switchyard
SURFACE
low cost, Large space requirement, In case of steepslope Stepping of the area Under ground Due to space constrain GIS (Gas insulated
switchyard ), Small area requirement.
Factor affecting selection of type of AIS and
GIS Space Terrain Cost
Koldam Over ground
LNP - GIS TVN - GIS
-
7/31/2019 Equipment at HPS
46/60
GIS Insulating Medium SF6 Low space requirement due to reduction in clearances Unaffected by climatic conditions such as rains etc. No corona losses SF6 has excellent properties to be used as an insulating medium,
very high dielectric strength, chemically inert, non-inflammable, non
poisonous Costly equipments Online monitoring of pressure of SF6 gas is required Main features: pressure of SF6 gas selected from 5-40 bar
depending upon the requirements Bare conductors run inside metallic enclosures surrounded by
pressurized sf6 gas All CTs, circuit breakers, PTs etc are inside the metal clad
enclosures GIS will be used first time in NTPC in Loharinag pala and Tapovan
Vishnugad HEPP
GAS INSULATED
-
7/31/2019 Equipment at HPS
47/60
SWITCHGEAR
-
7/31/2019 Equipment at HPS
48/60
XLPE Cable
XLPE STANDS FOR Cross linked polyethyleneinsulated power cable (XLPE cable)
XLPE cable is used as interconnecting circuitbetween GIS and transmission lines through
overhead pothead yard.
XLPE cables are generally used because thedistance between GIS and pothead yard is moreand through a Cable ventilation tunnel.
400 KV XLPE cables are used for first time in NTPCin Loharinag Pala and Tapovan Vishnugad HEPP
-
7/31/2019 Equipment at HPS
49/60
XLPE CABLES..
-
7/31/2019 Equipment at HPS
50/60
Electrical Auxiliaries
BUSDUCT
DC supply system
Grounding system
Illumination
-
7/31/2019 Equipment at HPS
51/60
BUS DUCTS AND UCBs
-
7/31/2019 Equipment at HPS
52/60
BUS DUCT
Bus ducts
-
7/31/2019 Equipment at HPS
53/60
Bus ducts
-
7/31/2019 Equipment at HPS
54/60
DC supply system
D.C. Supply distribution systems typicallycontains:-
Batteries
Battery Chargers
Distribution Boards
-
7/31/2019 Equipment at HPS
55/60
D.C. Batteries Batteries are required at most of the hydro-electric stations for control alarm
annunciation, protection, communication, emergency lighting and solenoidoperated valves and field flashing requirements of generating units. Ingeneral, lead acid batteries are widely used. The standard voltage rating forthe batteries used are 110 V or 220 V depending on the DC load of thepower station.
Batteries are generally designed with 10% design margin and 25% of agingfactor. Small and medium hydro plant one battery set (110 V) with twobattery chargers and for large hydro stations, two battery sets (220 V each)and one 48 V battery set with two (2) chargers for each battery are generally
recommended. Minimum load requirement on D.C. system is generator fieldflash load for one unit and emergency lighting.
Battery Chargers The battery charger having rectifiers with thyristors are usually used for
charging the battery system. The charging is generally in float charging i.e.the batteries are kept in float charging condition in the normal operation. In
case of commissioning of the batteries and otherwise the boost charger isused to charge the boost batteries.
G di S
-
7/31/2019 Equipment at HPS
56/60
Grounding System
Separate groundmat, if feasible, be provided for power house, switchyard,remote structures such as control buildings, communication buildings,
spillway gate structures, storage buildings, etc.
Power House Grounding System be designed to provide a maximum 1.0ohm resistance to ground.
If the control, computer and communication rooms are located in electrically
noisy areas (e.g. VFC drives(in case pumped staorage), high voltage GISequipment etc), a "High-frequency signal reference ground grid beneath afalse floor shall be considered, to provide a noise-free, low impedenceground to the equipment.
Switchyard grounding electrode systems should be designed to provide amaximum of 1.0 ohm resistance to ground. The switchyard mat shouldextend 1.5 - 2.0 mts. outside the switchyard fencing.
Touch and Step potentials limit be maintained to an acceptable value.
Ill i i
-
7/31/2019 Equipment at HPS
57/60
Illumination
General indoor and outdoor lighting and receptacle are served by 3-, 4 wire
A.C. system. Transformers and panels are located so as to optimize wiring andto limit voltage drops to acceptable values.
Fluorescent lamps are most used in interior spaces
High-density Discharge (HD)
Sodium vapour lighting fixtures are preferred for outdoor lighting such as
switchyards, spillways and dams, parking areas etc. Automatic switching viaphoto electric cells can be adopted for outdoor lighting to optimize powerconsumption.
Metal-halide fixtures are used for certain indoor areas such as erection bay,generator hall, machine shop, turbine pit and other "high-bay" areas whereproper color redention is needed and long-life is essential.
Emergency lighting is deployed in the event that normal A.C. power distribution
system fails. The emergency requirement are at first met from the dieselgenerator sets and when all alternatives of A.C. supply fail, battery poweredemergency fixtures provide the minimum requirement of lighting. The batteryshould have sufficient capacity to provide 4 hours uninterrupted illuminationindependently.
-
7/31/2019 Equipment at HPS
58/60
C&I COMPONENTS IN A TYPICAL
HYDRO STATION
1. MAIN PLANT CONTROL & INSTRUMENTATION SYSTEM
TURBINE, GENERATOR & AUXILIARIES
COOLING WATER SYSTEM
DRAINAGE & DEWATERING SYSTEM
FLOOD DETECTION SYSTEM
2. SWITCHYARD SCADA AND SUBSTATION AUTOMATION SYSTEM
3. DAM /RESERVOIR INSTRUMENTATION4. SPILLWAY INSTRUMENTATION
C S S C
-
7/31/2019 Equipment at HPS
59/60
CONTROL SYSTEM AUTOMATION HIERARCHY
1. LOCAL
2. UCB
- DRIVE
- SUB GROUP
- GROUP
3. Station
- SUB GROUP
- GROUP
- STATION
4. REMOTE (FUTURE)
- GROUP
- STATION
-
7/31/2019 Equipment at HPS
60/60
THANK YOU