C4 A heavy duty moisture-proof disc shall be fitted between the greased flange face and the cover. The disc shall have a diameter eq uivalent t o the inside diameter of the bolt holes. 04-SAMSS-035 Para. 12.2 SAUDI ARAMCO USE ONLY WORK PERMIT REQUIRED? CONTRACTOR INSPECTION LEVEL SAUDI ARAMCO INSPECTION LEVEL ACTUAL INSPECTION DATE & TIME EC / PMCC / MCC NO. REV. NO. PURCHASE ORDER NUMBER SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER ITEM No.  ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE MH's SP ENT TRAVEL TIME QUANTITY INSP. SCHEDULED INSPECTION DATE & TIME LAYOUT DRAWING NUMBER PLANT NO. EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. CONTRACTOR / SUBCONTRACTOR Storage and Preservation of Materials of Well Head Piping SAI S-L -2084 25-May- 05 PIPING - Pipe shall not be rolled or dropped off trucks. SAES-L-450, Para. 8.6 SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARA MCO INSPE CTION CHE CKL IS SAIC NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER C3  Th e raise d fa ce po rtion of t he flan ge an d t he ri ng jo in t gr oove shall be covered with a heavy grease, (see Attachment 1). 04-SAMSS-035 Para. 12.2 C. Storage, Handling and Preservation of Valves C1 Valve end flanges shall be fitted w ith ply wood covers. The cover diameter shall be the same as the outside diameter of the flange and shall be at least 10 mm thick for valves up to NPS 10 inch and 12 mm thick for v alves NP S 12 inch and lar ger. C2  Th e co ve r shall be at t ac he d by machine bo lt s with a nut and washer fitte d on the inside of th e flange. There shall be four (4) bolts on valves up to NPS 10 inch nominal size and eight (8) bolts on valves NPS 12 inch and larger . The bolts diamet er shall not be less than ½ t he size of  the flange bolt hole. 04-SAMSS-035 Para. 12.2 04-SAMSS-035 Para. 12.2  A6 Internally coated pipe shall be handled from the outside diamet er (O.D.), only. 02-SAMSS-011, Para. 10 B1 Fittings and Flanges must be packaged in steel-banded wooden crates or secured to skids. 02-SAMSS-011, Para. 10  A7 When a length of pipe is cut from a longer joint of pipe, all vendor markings and other identifying information shall be transferred to each length of pipe. SAES-L-450, Para. 8.8  A5 Pipe stacking shall be made in a manner w hich will not damage the pipe or the coating. SAES-L-450, Para. 8.3  A. Pip e Stor age, Hand li ng an d Pres erv ati on  A2 End bevel protectors shall remain on pipes and fittings while in storage, protectors shall not damage internal or external coating. SAES-L-450, Para. 8.4  A4 Pipe handling procedure and equipm ent is approved by the Saudi Aramco PMT, and is available. SAES-L-450, Para. 8.1  A3 Slings for lifting pipe shall be nylon or similar material to prevent damage to t he pipe surface. Wire rope slings shall not be used. SAES-L-450, Para. 8.5  A1 B. Storage, Handling and Preservation of fitti ngs & Flanges B2 Fittings and Flanges must be protected from mechanical damage. Welding ends must be protected with suitable wood, plastic, or metal covers, (see Attachment 1). C5  Th e en ds of t hr ea de d an d soc ke t w el d en d va lv es sh al l be pr ot ec t ed wit h tight fitting plastic caps. 04-SAMSS-035 Para. 12.3 SAES-L-450, Para. 8.7 Page 1 of 3

Upload: philipyap

Post on 02-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

7/27/2019 SAIC-L-2084 Rev 0

http://slidepdf.com/reader/full/saic-l-2084-rev-0 1/3

C4A heavy duty moisture-proof disc shall be fitted between the greasedflange face and the cover. The disc shall have a diameter equivalent tothe inside diameter of the bolt holes.

04-SAMSS-035Para. 12.2

SAUDI ARAMCO USE ONLYWORK PERMIT REQUIR

CONTRACTOR INSPECTION LEVELSAUDI ARAMCO INSPECTION LEVEL

ACTUAL INSPECTION DATE & TIME

EC / PMCC / MCC NO.REV. NO. PURCHASE ORDER NUMBER

SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER

ITEMNo.

ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE

MH's SP ENT TRAVEL TIMEQUANTITY INSP.SCHEDULED INSPECTION DATE & TIME

LAYOUT DRAWING NUMBER

PLANT NO.EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID.

CONTRACTOR / SUBCONTRACTOR

St or ag e and Pr es er vat ion of Mat er ial s o f Wel l Head Pi pi ng SA IS-L -2084 25-May -05 PIPING -

Pipe shall not be rolled or dropped off trucks.SAES-L-450,

Para. 8.6

SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)

SAUDI ARAMCO INSPECTION CHECKLIS SAIC NUMBER DATE APPROVED QR NUMBER

PROJ ECT TITLE WBS / BI / J O NUMBER

C3 The raised face portion of the flange and the ring joint groove shall becovered with a heavy grease, (see Attachment 1).

04-SAMSS-035Para. 12.2

C. Storage, Handling and Preservation of Valves

C1

Valve end flanges shall be fitted with plywood covers. The coverdiameter shall be the same as the outside diameter of the flange andshall be at least 10 mm thick for valves up to NPS 10 inch and 12 mmthick for valves NP S 12 inch and larger.

C2

The cover shall be attached by machine bolts with a nut and washerfitted on the inside of the flange. There shall be four (4) bolts on valvesup to NPS 10 inch nominal size and eight (8) bolts on valves NPS 12

inch and larger. The bolts diameter shall not be less than ½ the size of the flange bolt hole.

04-SAMSS-035Para. 12.2

04-SAMSS-035Para. 12.2

A6Internally coated pipe shall be handled from the outside diameter (O.D.),

only.

02-SAMSS-011,Para. 10

B1 Fittings and Flanges must be packaged in steel-banded wooden cratesor secured to skids.

02-SAMSS-011,Para. 10

A7When a length of pipe is cut from a longer joint of pipe, all vendormarkings and other identifying information shall be transferred to eachlength of pipe.

SAES-L-450,Para. 8.8

A5Pipe stacking shall be made in a manner which will not damage the pipeor the coating.

SAES-L-450,Para. 8.3

A. Pipe Stor age, Hand li ng an d Pres ervation

A2End bevel protectors shall remain on pipes and fittings while in storage,protectors shall not damage internal or external coating.

SAES-L-450,Para. 8.4

A4

Pipe handling procedure and equipment is approved by the SaudiAramco PMT, and is available.

SAES-L-450,Para. 8.1

A3Slings for lifting pipe shall be nylon or similar material to prevent damageto the pipe surface. Wire rope slings shall not be used.

SAES-L-450,Para. 8.5

A1

B. Storage, Handling and Preservation of fitti ngs & Flanges

B2Fittings and Flanges must be protected from mechanical damage.Welding ends must be protected with suitable wood, plastic, or metalcovers, (see Attachment 1).

C5 The ends of threaded and socket weld end valves shall be protected withtight fitting plastic caps.

04-SAMSS-035Para. 12.3

SAES-L-450,Para. 8.7

Page 1 of 3

7/27/2019 SAIC-L-2084 Rev 0

http://slidepdf.com/reader/full/saic-l-2084-rev-0 2/3

*Person Responsible for Completion of Quality Work / Test Y =YES N =NO F =FAILED

T&I Witnessed QC Record Reviewed

Name, Sign and Date:Quality Record Approved:

Name, Organization,Initials and Date:

T&I Witnessed QC Record Reviewed

SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)

SAUDI ARAMCO INSPECTION CHECKLIS SAIC NUMBER DATE APPROVED QR NUMBER

PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR

St or ag e and Pr es er vat ion of Mat er ial s o f Wel l Head Pi pi ng SA IS-L -2084 25-May -05 PIPING -

REFERENCE DOCUMENTS:

ITEMNo.

ACCEPTANCE CRITERIA

ATTACHMENTS:1. FIGURE 1 - Flanged Valves; FIGURE 2 - Weld End Valves

Work VerifiedQC Supervisor Proponent and Others

Contractor / Thir d-Party

Work VerifiedQC Inspector

REFERENCE

3. 04-SAMSS-035, General Requirements for Valves, 31 J uly, 2001

REMARKS:

PASS FAIL N/A RE-INSP DATE

1. SAES-L-450, Construction of On-Land and Near-Shore Pipelines, 30 September, 20033. 02-SAMSS-011, Forged Steel Weld Neck Flanges for Low and Intermediate Temperature Service, 28 J anuary, 2004

PID Representative

Construction Representative*

Name, Initials and Date:Work is Complete and Ready for Inspection:

Name, Initials and Date:

Name, Initials and Date:Performed Inspection Work / Rework May Proceed

Name, Initials and Date:

Work Verified

Saudi A ramcoPMT Representative

T&I Witnessed QC Record Reviewed

Page 2 of 3

7/27/2019 SAIC-L-2084 Rev 0

http://slidepdf.com/reader/full/saic-l-2084-rev-0 3/3

At tachment 1

St or ag e and Pr es er vat ion of Mat er ial s o f Wel l Head Pi pi ng SA IS-L -2084 25-May -05 PIPING -

SAUDI ARAMCO ID/PID - 2/19/05 - REV A (Standards Cutoff - August 2004)

SAUDI ARAMCO INSPECTION CHECKLIS SAIC NUMBER DATE APPROVED QR NUMBER

Page 3 of 3